Sunteți pe pagina 1din 8

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 21, NO.

4, OCTOBER 2006 1989

A Novel Wavelet-Based Algorithm for Discrimination


of Internal Faults From Magnetizing Inrush
Currents in Power Transformers
Jawad Faiz, Senior Member, IEEE, and S. Lotfi-Fard, Student Member, IEEE

Abstract—In this paper, a new algorithm based on processing 2nd order harmonic [3]. However, the 2nd order harmonic com-
differential current is proposed for digital differential protection ponent may also be generated during internal faults in the power
of power transformers by considering different behaviors of the
transformer. This may be due to current transformer saturation
differential currents under fault and inrush current conditions.
In this method, a criterion function is defined in terms of differ- or the presence of a shunt capacitor or the distributive capaci-
ence of amplitude of wavelet coefficients over a specific frequency tance in a long extra high-voltage (EHV) transmission line to
band. The criterion function is then used for three phases, and in- which the transformer may be connected [4]. In certain cases,
ternal faults are precisely discriminated from inrush current less the magnitude of the 2nd order harmonic in an internal fault
than a quarter a cycle after the disturbance; this is one advan-
tage of the method. Another advantage of the proposed method current can be close to or greater than that present in the mag-
is that the fault detection algorithm does not depend on the selec- netizing inrush current. Moreover, 2nd order harmonic compo-
tion of thresholds. The merit of this method is demonstrated by nents in the magnetizing inrush currents tend to be relatively
simulation of different faults and switching conditions on a power small in modern large power transformers because of improve-
transformer using PSCAD/EMTDC software. Also the proposed
algorithm is tested offline using data collected from a prototype ments in the power transformer core material [5].
laboratory three-phase power transformer. The test results show To enhance the reliability of differential protection, several
that the new algorithm is very quick and accurate. methods have utilized voltage signals as well as current sig-
Index Terms—Inrush current, internal fault, power transformer, nals [6]. In [7], differential power method has been proposed
wavelet transform. to recognize fault from inrush current. The proposed method in
[8] is based on modal transform of voltage and current wave-
forms. Disadvantages of these methods include the need to use
I. INTRODUCTION voltage transformers and increased protective algorithm calcu-
lation cost. In other methods, fault conditions are recognized
T HE POWER transformer protection is of critical impor-
tance in power systems. Since minimization of frequency
and duration of unwanted outages, is very desirable, this is a
by the distortion characteristic of differential current waveform.
One of these methods operates via measuring of intervals be-
high demand imposed on power transformer protective relays; tween two successive peaks of differential current waveform
this includes the requirements of dependability associated with [9]. The operation criterion in another method is the duration
no mal-operations, security associated with no false tripping, in which differential current waveform remains near zero [10].
and operating speed associated with short fault clearing time [1]. Delayed fault detection is the disadvantage of this group of al-
One of the main concerns in protecting this particular compo- gorithms. Various methods based on processing differential cur-
nent of power systems lies in the accurate and rapid discrimina- rent harmonics have been proposed to detect internal faults of
tion of magnetizing inrush current from different internal faults power transformers. In some methods, differential current har-
currents. This is because the magnetizing inrush current, which monics are used as inputs to a trained neural network and fuzzy
occurs during the energizing the transformer, generally results logic [11], [12]. The problem associated with these methods is
in several times full load current and therefore can cause malop- the need to design neural networks or fuzzy laws, which re-
eration of the relays [2]. Such maloperation of differential relays quire a huge number of training patterns produced by simula-
can affect both the reliability and stability of the whole power tions of various cases [13]. However, these approaches might
system. need re-training for use in other power transformer systems if
Since a magnetizing inrush current generally contains a larger the transformer, for example, is changed in capacity and voltage
2nd order harmonic component than that of internal fault, con- ratings as well as iron-core constructions and winding connec-
ventional transformer protection systems are designed to re- tions. In another approach the multi-criteria aggregation tech-
strain during inrush transient phenomenon by sensing this large nique based on fuzzy logic has been employed [14]. However,
for such an approach, there are no recommended criteria for set-
Manuscript received August 25, 2005; January 15, 2006. This work was sup-
ting the internal parameters of a relay.
ported by the University of Tehran, Tehran, Iran. Paper no. TPWRD-00501– A wavelet-based signal processing technique is an effective
2005. tool for power system transient analysis and feature extraction.
The authors are with the Center of Excellence on Applied Electromagnetic Some applications of wavelet analysis in power systems include
Systems, Department of Electrical and Computer Engineering, University of
Tehran, Tehran 1439957131, Iran (e-mail: jfaiz@ut.ac.ir). analysis and detection of electromagnetic transients [15], power
Digital Object Identifier 10.1109/TPWRD.2006.877095 quality [16], data compression [17], and fault detection [18]. Re-
0885-8977/$20.00 © 2006 IEEE
1990 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 21, NO. 4, OCTOBER 2006

cently, several new protective schemes have been proposed to


deal with the foregoing problem in power transformer protection
based on wavelet transforms (WT) [19]–[21]. A wavelet-based
method has been presented in [19]. The drawback of this method
is that it requires the measurement of voltage in addition to cur-
rent that increases the cost of hardware implementation. In [20],
an algorithm has been recommended using a combination of the
WT and neural network. In this method a WT has been used as Fig. 1. Implementation of DWT.
a preprocessor and the output of the wavelet is the input of the
artificial neural network. The required algorithm training and TABLE I
other above-mentioned problems are the drawbacks of the algo- FREQUENCY LEVELS OF WAVELET FUNCTION COEFFICIENTS
rithm. In [21], a wavelet-based algorithm has been suggested.
This algorithm has not been considered the condition in which
both inrush current and internal fault present simultaneously.
This paper introduces a simple decision making method
based on the WT for discriminating internal faults from inrush
currents. This algorithm has been developed by considering
different behaviors of the differential currents under fault and
inrush current conditions. The WT technique is first applied
in order to decompose the differential current signals into a
series of wavelet components, each of which is a time-do-
main signal that covers a specific frequency band. Thus, more
distinctive signal features that represent internal faults and The WT is a powerful signal processing tool used in power
inrush currents are extracted. As a result, by quantifying the system [15]–[18]. The WT, like the STFT, allows time localiza-
extracted features, a criterion function is defined in terms of tion of different frequency components of a given signal, how-
difference of amplitude of wavelet coefficients over a specific ever with one important difference: STFT uses a fixed width
frequency band, due to the fault and inrush current. By using windowing function. As a result, both frequency and time reso-
this criterion function for three phases, the internal faults can lution of the resulting transform will be prior fixed but in the case
be accurately discriminated from inrush current less than a of the WT, the analyzing functions, which are called wavelets,
quarter a cycle after the disturbance. Another advantage of will adjust their time-widths to their frequency in such a way
the proposed method is that the fault detection algorithm does that, higher frequency wavelets will be very narrow and lower
not depend on the selection of thresholds. The merit of this frequency ones will be broader. Therefore, in contrast with the
method is demonstrated by simulation of different faults and STFT, the WT can separate transient components in the upper
switching conditions on a power transformer. For this purpose, frequency isolated in a shorter part of power frequency cycle.
a power system involving a power transformer and transmis- The ability of the WT to focus on short time intervals for
sion lines, on both sides of the transformer, is considered. To high-frequency components and long intervals for low-fre-
include effective factors on differential current components, quency components improves the analysis of signals with
the elements of this power system have been modeled using localized impulses and oscillations. For this reason, wavelet
PSCAD/EMTDC software. The proposed algorithm is also decomposition is ideal for studying transient signals and
tested offline using data collected from a prototype laboratory obtaining a much better current characterization and a more
three-phase power transformer. The test results show that the reliable discrimination [22].
new algorithm is very quick and accurate. Fig. 1 illustrates the implementation procedure of a Discrete
WT (DWT), in which S is the original signal, LPF and HPF are
II. WAVELET TRANSFORM the low-pass and high-pass filters respectively. At the first stage,
The waveforms associated with fast electromagnetic tran- an original signal is divided into two halves of the frequency
sients are typically non-periodic signals which contain both high- bandwidth, and sent to both HPF and LPF. Then the output of
frequency oscillations and localized impulses superimposed on LPF is further cut in half of the frequency bandwidth, and sent
the power frequency and its harmonics. These characteristics to the second stage; this procedure is repeated until the signal is
present a problem for traditional discrete Fourier transform decomposed to a pre-defined certain level. If the original signal
(DFT), because its use assumes a periodic signal and that the is being sampled at Fs Hz, the highest frequency that the signal
representation of a signal by the DFT is best reserved for periodic could contain, from Nyquist’s theorem, would be Fs/2 Hz. This
signals. As power system disturbances are subject to transient and frequency would be seen at the output of the high frequency
non-periodic components, the DFT alone can be an inadequate filter, which is the first detail. Thus, the band of frequencies be-
technique for signal analysis. If a signal is altered in a localized tween Fs/2 and Fs/4 would be captured in detail 1; similarly, the
time instant, the entire frequency spectrum can be affected. To re- band of frequencies between Fs/4 and Fs/8 would be captured
duce the effect of non-periodic signals on the DFT, the short-time in detail 2, and so on. The sampling frequency in this paper is
Fourier transform (STFT) is used. It assumes a local periodicity taken to be 10 kHz and Table I shows the frequency levels of the
within a continuously translated time window [22]. wavelet function coefficients.
FAIZ AND LOTFI-FARD: NOVEL WAVELET-BASED ALGORITHM FOR DISCRIMINATION OF INTERNAL FAULTS 1991

Fig. 2. Different behavior of fault and inrush current.

III. PROPOSED ALGORITHM

The new method of discriminating inrush current from in-


ternal fault is based on the different behavior of these waveforms
following the disturbance. Since the magnetizing inrush cur-
rent corresponds to the transformer core saturation, the inrush
current has a conical shape (non-sinusoidal); in other words in-
rush current at the switching time increases very slowly; as time Fig. 3. Differential current as a result of internal fault AB-G at t = 0:3 s and
frequency levels obtained from WT.
passes its slope increases. However, when a fault occurs, the dif-
ferential current has higher slope compared with the starting of
the inrush current, and its slope decreases as time passes. Fig. 2
illustrates the above-mentioned features [23]. Since these fea-
tures stem from the different nature of the currents and param-
eters of transformer and the connected power system has no
influence on it, so these features may be used as the basis of
discriminating the fault from the inrush current.
The proposed algorithm is based on two principles.
1) The differential current due to fault begins with a higher
slope and then its slope decreases. But differential current
due to inrush current begins with a low slope and then its
slope is raised.
2) A larger slope in the time domain shows that there are
higher frequencies in the frequency domain.
Based on the above principles, it is expected that following the
internal fault, the amplitude of the high frequencies at the initial
instants has a decreasing trend; it means that its value drops from
large value to a small value. This trend has been shown in Fig. 3
(D1-D5) where the differential current due to the AB-G internal
fault at and frequency levels from the WT are visible. It
is also expected that following the inrush current the amplitude
of the high frequency components at the initial time of fault has
increasing trend. It means that their amplitudes increase from Fig. 4. Differential current as a result of inrush current at t = 0:3 s and fre-
a low value to a high value. The differential current due to the quency levels obtained from WT.
inrush current at s and the resultant frequency from WT
are visible as shown in Fig. 4 (D1-D5).
The aforementioned features at frequency level D5 is clearly and Y. Based on the above explanations, in the case of inrush
visible. Fig. 5 shows the differential current waveform due to current , and in the case of internal fault . The
the fault current and inrush current at frequency level D5. In second inequality is studied for every phase and if there is such
order to introduce a criterion function for discriminating the in- inequality even in one phase, a fault exists and the trip command
rush current from the internal fault current, the amplitudes of the is issued. As shown in Fig. 6, the above Inequalities can be used
two first peaks of the differential current in D5, following the to discriminate the internal fault from the inrush current around
disturbance, are considered and called X and Y. Fig. 6 shows a quarter a cycle which is very quick. Also the suggested cri-
the absolute value of the differential current in D5 and points X terion function is simple and it prevents complicated and huge
1992 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 21, NO. 4, OCTOBER 2006

Fig. 5. (a) Inrush current and (b) internal fault current in D5.

Fig. 6. Absolute value of (a) inrush current and (b) internal fault current in D5.
Fig. 7. Flowchart of the proposed algorithm.

computations. This, of course, has a large effect on the speed of


the diagnosis trend. IV. SIMULATION RESULTS
It is noted that the characteristics mentioned which used in To obtain the required current signals for investigation of the
the diagnosis process are normally appeared over high frequen- merit of the proposed algorithm, a part of a power system con-
cies (not over low frequencies, that is, D6-D7, A7 where fre- sisting of a power transformer and relevant CTs with transmis-
quencies are lower than 156.25 Hz). As shown in Figs. 3 and 4, sion lines on the both sides of the transformer are modeled using
amplitudes of the wavelet coefficients in D5 are larger that that PSCAD/EMTDC software that is shown in Fig. 8. So the re-
of D1-D4, which enhance the precision of the obtained X and quired current signals for a digital differential protection can be
Y. This is the reason for using D5 in the proposed algorithm. provided. The proposed power system consists of a 500-MVA
A simplified flowchart of the proposed algorithm has been and 400/230-kV transformer and the distributed model for the
shown in Fig. 7; block (1) implements the calculation of the transmission lines is used. A long 400-kV line in parallel with
three-phase differential currents; the restraining currents are the transformer distorts the faulty current waveform.
only used at the stage of blocks (1) and (2) to prevent false Different cases of inrush current and fault current are simu-
tripping due to external faults, current-transformer (CT) mis- lated. Different cases of inrush current are simulated by varying
match, CT error between LV and HV sides and error caused by those major parameters that influencing the characteristics of this
tap-changer; block (2) signifies that the relay is activated if any current. These parameters are the residual core flux of single-
one of three-phase differential currents is over a setting of the phase transformers , the voltage angle of switching phase a
differential protection [24]. If the output of block 2 is “Yes”, , switching in the case of close or open secondary, the high
there is an internal fault and/or inrush current which must be or low power supply connected to transformer and knee of the
discriminated. In fact, the proposed algorithm commences core magnetic characteristic. Different cases of fault currents are
from block (3) and its aim is to discriminate internal fault from also simulated where the major factors affecting the characteris-
inrush current. Block (3) implements the WT to the differential tics of the current are considered. These factors include the type
currents; block (4) estimates X, Y, where means the X for of fault and load condition. The results of application of the pro-
phase a and means the Y for phase a and so on. Finally posed algorithm for different conditions of inrush current have
the decision is made by block (5) to discriminate internal been summarized in Table II. This table shows the values of X
faults from inrush currents. If an internal fault is detected, the and Y of different phases during shorter than a quarter a cycle
relay will issue a tripping signal; otherwise, the relay will be following waveform distortion due to different inrush current.
restrained and does not operate. The first column of the table presents the remnant fluxes in the
FAIZ AND LOTFI-FARD: NOVEL WAVELET-BASED ALGORITHM FOR DISCRIMINATION OF INTERNAL FAULTS 1993

Fig. 8. Diagram of the simulated power system.

TABLE II
VALUES OF X AND Y ( 102 ) FOLLOWING DISTURBANCE FOR DIFFERENT INRUSH CURRENTS CASES

single-phase transformer core at instant of switching as percent cases have been included and in all cases the fault have been
of the rated flux. The second column shows the voltage angle of properly diagnosed. The first and second row of this table show
phase at the instant of switching. The third column exhibits switching and fault condition in different cases respectively. In-
that the investigated differential current related to which phase. dices ij in these two rows express the ith row and jth column of
The forth and fifth columns show that at the time of inrush cur- Tables II and III. In this case it is assumed that Table II is 5
rent occurring the secondary of transformer is open or close. In 11 and Table III is 3 10 matrices. For instance, 2,4 in the first
both no-load and on-load cases, influence of stiff or weak power column of Table IV is: no-load, char.1, ,
system and also effect of flux density change of the knee of the ; and 2,3 in the second column of Table IV is: no-load,
transformer magnetic core characteristic have been studied. Flux A-G, . Tables II–IV show that in all cases the algorithm
density of the knee of characteristic 2 is larger than that of char- acts properly.
acteristic 1. The results of application of the proposed algorithm One of these cases is studied in detail. Fig. 9 shows a differen-
for internal fault conditions have been summarized in Table III. tial current due to simultaneous inrush current and fault (A-G)
Simulations have been carried out for different faults in no-load at s and WT coefficients in D5. As seen, the WT co-
and on-load of power system. In addition to the fault and inrush efficients in D5 is decreasing, and , so
currents cases, it is necessary to study the merit of the algorithm . Thus, the occurrence of the fault is detected accurately
for simultaneous fault and switching; in Table IV, four different shorter than a quarter a cycle (3.9 ms).
1994 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 21, NO. 4, OCTOBER 2006

TABLE III
VALUES OF X AND Y ( 10 2 ) FOLLOWING DISTURBANCE FOR DIFFERENT INTERNAL FAULT CASES

TABLE IV
2
VALUES OF X AND Y ( 10 ) FOLLOWING SIMULTANEOUS INRUSH
CURRENT AND INTERNAL FAULT CASES

Fig. 10. Experimental setup for differential current data collection.

supply and the transformer. The configuration of the switches


and the control circuit is shown in [21]. The collected currents
data are to be used for testing the merits of the proposed
algorithm.
The following cases are proposed.
1) Fault currents:
• secondary line-to-ground fault, onload;
• primary line-to-line fault, no load;
• primary three-phase fault, no load.
2) Magnetizing inrush current, no load.
Fig. 9. Differential current as a result of simultantanuose A-G internal fault In many cases, the transformer is no load, which provides the
and inrush current at t = 0:3 s and frequency levels obtained from WT. worst operating conditions.
Case 1) Single-phase-to-ground fault current
The single line-to-ground fault (phase c) occurred
V. OFFLINE TESTING OF ALGORITHM on the secondary side with a balanced Y-connected
The proposed algorithm is to be tested on a three-phase, load of phase connected to the secondary side. It
5-kVA, 230/550–575–600, 60-Hz, core type, -Y-connected should be noted that the primary line-to-line voltage
laboratory prototype power transformer. The experimental is set to 50 V in all investigated faults in order to
setup for collecting different types of investigated differential avoid the saturation or damage in the test equipment.
currents is shown in Fig. 10 [21]. Three identical CTs are Fig. 11 shows the three-phase differential currents
connected in Y on the primary side, and another three identical Ia, Ib, Ic, and the frequency range D5 due to Ic. As
CTs are connected in on the secondary side of the power seen , , so holds after 2.8
transformer. The differential current is measured at point Q ms of the disturbance (i.e., shorter than a quarter a
using Tektronics current probe. The differential current is sam- cycle that shows the disturbance is a fault).
pled at 10 kHz and stored using Tektronics 2212 digital storage Case 2) Line-to-line fault current
oscilloscope. Three identical triac switches and a control circuit In the case of line-to-line fault between phases B
to trigger them are used to provide a short contact between the and C, the transformer is no load, and the fault takes
FAIZ AND LOTFI-FARD: NOVEL WAVELET-BASED ALGORITHM FOR DISCRIMINATION OF INTERNAL FAULTS 1995

Fig. 11. Three-phase currents for the case of secondary onload single-phase-to-
ground fault current and the frequency range D5 due to Ic.
Fig. 13. Three-phase currents for the case of no-load primary three-phase-to-
ground fault current and the frequency range D5 due to Ib.

Fig. 12. Three-phase currents for the case of onload primary phase-to-phase
fault current and the frequency range D5 due to Ib.
Fig. 14. Three-phase currents for the case of unloaded magnetizing inrush cur-
rent and the frequency range D5 due to Ic.

place on the primary side of the transformer. Fig. 12


shows the three-phase differential currents Ia, Ib, Case 4) Unloaded Magnetizing Inrush Current
Ic and the frequency range D5 due to Ib. As seen For the case of magnetizing inrush current, the
, , so holds after 3.6 no-load transformer at a supply line voltage of 230
ms of the disturbance (i.e., shorter than a quarter of V is considered. Fig. 14 shows the three-phase dif-
a cycle that shows the disturbance is a fault). ferential currents Ia, Ib, Ic, and the frequency range
Case 3) Three-Phase-to-Ground Fault Current D5 due to Ic. As seen and ,
The three-phase fault has occurred on the primary so holds after 2.9 ms of the disturbance (i.e.,
side of the no-load power transformer. Fig. 13 shows shorter than a quarter of a cycle and this situation
the three-phase differential currents Ia, Ib, Ic, and is also the same in other phases which shows that
the frequency range D5 due to Ib. As seen, there is no fault and the maltrip is not issued).
, , so holds after 3.2 ms of These offline test results show that the proposed algorithm is
the disturbance (i.e., shorter than a quarter a cycle accurate for building a reliable differential protection scheme
that shows the occurrence of a fault). for three-phase power transformers. In addition, in all cases of
1996 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 21, NO. 4, OCTOBER 2006

tested internal faults, the fault is identified in less than a quarter [11] P. Bastard, M. Meunier, and H. Regal, “Neural network-based algo-
a cycle based on a 60-Hz supply. rithm for power transformer differential relays,” Proc. Inst. Elect. Eng.,
vol. 142, no. 4, pp. 386–392, 1995.
[12] M. C. Shin, C. W. Park, and J. H. Kim, “Fuzzy logic-based for large
power transformer protection,” IEEE Trans. Power Del., vol. 18, no. 3,
VI. CONCLUSION pp. 718–724, Jul. 2003.
In this paper, a novel algorithm for transformer differential [13] M. E. Hamehani Golshan, M. Saghaian-nejad, A. Saha, and H. Samet,
“Anew method for recognizing internal faults from inrush current con-
protection was presented. This method is based on the different ditions in digital differential protection of power transformer,” Elect.
behaviors of differential currents. A criterion function was de- Power Syst. Res., vol. 71, pp. 61–67, 2004.
fined using the difference of the amplitude of the WT over a [14] B. Kasztenny, E. Rosolowski, M. M. Saha, and B. Hillstrom, “A self-
organizing fuzzy logic based protective relay-an application to power
particular frequency spectrum due to a fault and inrush current, transformer protection,” IEEE Trans. Power Del., vol. 12, no. 3, pp.
internal fault conditions can be detected by evaluation of the 1119–1127, Jul. 1997.
criterion functions of the three phases. In addition to suitable [15] Y. Y. Hong and C. W. Wang, “Switching detection/classification using
discrete wavelet transform and self-organizing mapping network,”
accuracy, the proposed method can discriminate fault from in- IEEE Trans. Power Del., vol. 20, no. 2, pt. II, pp. 1662–1668, Apr.
rush current quickly, less than a quarter a cycle after the distur- 2005.
bance. The proposed algorithm does not require choosing any [16] P. Daponte, M. D. Penta, and G. Mercurio, “Transient meter: A
distributed measurement system for power quality monitoring,” IEEE
coefficient or threshold values. This is another advantage of the Trans. Power Del., vol. 19, no. 2, pp. 456–463, Apr. 2004.
method. The ability of the new method was demonstrated by [17] M. V. Ribeiro, J. M. T. Romano, and C. A. Duqe, “An improved
simulating various cases on a typical power system and the pro- method for signal processing and compression in power quality
evaluation,” IEEE Trans. Power Del., vol. 19, no. 2, pp. 464–471, Apr.
posed algorithm is also tested offline using data collected from 2004.
a prototype laboratory three-phase power transformer. The test [18] T. M. Lai, L. A. Snider, E. Lo, and D. Sutanto, “High-impedance fault
results show that the proposed algorithm was also quick and detection using discrete wavelet transform and frequency range and
RMS conversion,” IEEE Trans. Power Del., vol. 20, no. 1, pp. 397–407,
accurate. Jan. 2005.
[19] M. M. Eissa, “A novel digital directional transformer protection tech-
nique based on wavelet packet,” IEEE Trans. Power Del., vol. 20, no.
REFERENCES 3, pp. 1830–1836, Jul. 2005.
[1] P. L. Mao and R. K. Aggarwal, “A novel approach to the classifica- [20] H. Mortazavi and H. Khorashadi-Zadeh, “A new inrush restraint al-
gorithm for transformer differential relay using wavelet transform,” in
tion of the transient phenomena in power transformers using combined
wavelet transform and neural network,” IEEE Trans. Power Del., vol. Proc. Int. Conf. Power System Technology-Powercon, Singapore, Nov.
21–24, 2004, pp. 1705–1709.
16, no. 4, pp. 654–660, Oct. 2001.
[2] ——, “A wavelet transform based decision making logic method for [21] S. A. Saleh and M. A. Rahman, “Modeling and protection of a three-
phase power transformer using wavelet packet transform,” IEEE Trans.
discrimination between internal faults and inrush currents in power
transformers,” Elect. Power Energy Syst., vol. 22, pp. 389–395, 2000. Power Del., vol. 20, no. 2, pt. 11, pp. 1273–1282, Apr. 2005.
[3] M. A. Rahman and B. Jeyasurya, “A state-of-the-art review of trans- [22] O. A. S. Youssef, “A wavelet-based technique for discrimination be-
tween faults and magnetizing inrush currents in transformers,” IEEE
former protection algorithms,” IEEE Trans. Power Del., vol. 3, no. 2,
pp. 534–544, Apr. 1988. Trans. Power Del., vol. 18, no. 1, pp. 170–176, Jan. 2003.
[23] A. Guzman, S. Zocholl, G. Benmouryal, and H. J. Altuve, “A current-
[4] P. Liu, O. P. Malik, C. Chen, G. S. Hope, and Y. Guo, “Improved opera-
tion of differential protection of power transformers for internal faults,” based solution for transformer differential protection—Part I: Problem
statement,” IEEE Trans. Power Del., vol. 16, no. 4, pp. 485–491, Oct.
IEEE Trans. Power Del., vol. 7, no. 4, pp. 1912–1919, Oct. 1992.
[5] T. S. Sidhu, M. S. Sachdev, H. C. Wood, and M. Nagpal, “Design, im- 2001.
plementation and testing of a micro-processor-based high-speed relay [24] S. H. Horowitz and A. G. Phadke, Power System Relaying, 2nd ed.
Somerset, U.K.: Research Studies Press, 1995.
for detecting transformer winding faults,” IEEE Trans. Power Del., vol.
7, no. 1, pp. 108–117, Jan. 1992.
[6] K. Inagaki and M. Higaki, “Digital protection method for power trans-
formers based on an equivalent circuit composed of inverse induc- Jawad Faiz (M’90–SM’93) received the Ph.D. degree in electrical engineering
tance,” IEEE Trans. Power Del., vol. 4, no. 4, pp. 1501–1510, Oct. from the University of Newcastle-upon-Tyne, Newcastle-upon-Tyne, U.K., in
1998. 1988.
[7] K. Yabe, “Power differential method for discrimination between fault Currently, he is a Professor in the Department of Electrical and Computer
and magnetizing inrush current in transformers,” IEEE Trans. Power Engineering, University of Tehran, Tehran, Iran.
Del., vol. 3, no. 3, pp. 1109–1117, Jul. 1997. Dr. Faiz is a member of the Iran Academy of Science. His teaching and re-
[8] T. S. Sidhu and M. S. Sachdev, “On line identification of magnetizing search interests are switched reluctance and VR motors design, and the design
inrush and internal faults in three phase transformers,” IEEE Trans. and modeling of electrical machines and drives.
Power Del., vol. 7, no. 4, pp. 1885–1890, Oct. 1992.
[9] G. D. Rockefeller, “Fault protection with a digital computer,” IEEE
Trans. Power App. Syst., vol. 88, no. 4, pp. 438–464, Apr. 1969. S. Lotfi-Fard (S’06) received the M.Sc degree in electrical engineering from
[10] A. Giuliante and G. Clough, “Advances in the design of differential the University of Tehran, Tehran, Iran, in 2006.
protection for power transformers,” in Proc. Georgia Technical Pro- His research interests are power quality analysis and signal processing and
tective Relaying Conf., Atlanta, GA, 1991, pp. 1–12. their application to transients and protection of power systems.

S-ar putea să vă placă și