Sunteți pe pagina 1din 6

IEEE Transactions on Power Delivery, Vol. 14, No.

3, July 1999 91 1

A NEW METHOD TO DECREASE GROUND


RESISTANCES OF SUBSTATION GROUNDING SYSTEMS
IN HIGH RESISTIVITY REGIONS

Qingbo Meng Jinliang He F. P. Dawalibi J. Ma


Dept. of Electrical Eng. Senior Member, IEEE Member, IEEE ?e-

Northeast China Power Bureau Tsinghua University Safe Engineering Services & technologies ltd.
Shenyang 11OOO6 Beijing 100084 1544 Viel, Montreal, Quebec
P. R. China P.R. China Canada, H3M 1G4

Abstract: Decreasing the ground resistance of a grounding An adequate grounding grid is a fundamental requirement to
system in high resistivity soil is often a formidable task. A maintain reliable power system operation [l-41. The earth
new method is proposed to decrease ground resistances. This surface potential distribution in a substation should meet the
method requires three steps: (1) drilling deep holes in the IEEE requirements [4] for touch and step voltages. This can
ground; (2) developing cracks in the soil by means of be achieved by various methods [5-91. On the other hand, the
explosions in the holes; (3) filling the holes with low ground resistance should also be kept low and meet the IEEE
resistivity materials (LRM) under pressure. Most of the requirements [4]. But in high soil resistivity regions,
cracks around the vertical conductors will be filled with LRM decreasing the ground resistance of a grounding system may
and a complex network of low resistivity tree-like cracks constitute a formidable task.
linked to the substation grid is formed. The principle of
The ground resistance of a grounding grid in uniform soil can
decreasing ground resistances using this new method is
be calculated approximately using [ 101
described and the effectiveness of the new method is
examined. Application of this method to power system
grounding is presented together with measurement results.

Keywords: grounding, ground resistance, low resistivity where A is the area of the grounding grid and p the soil
materials, soil resistivity, explosion resistivity. If the required ground resistance is 0.5 Q then
from (1)
1. Introduction A =pPz

The main purpose of power system substation grounding If the soil resistivity is 100 Q,m, the area of the grounding
grids is to maintain reliable operation and provide protection grid should be on the order of 100x100 m2 for a 0.5 Q ground
for personnel and apparatus during fault conditions. A recent resistance. With the increase of soil resistivity, the required
survey concluded that a series of serious failures had taken area of the grounding grid for a given resistance value
place in China because the ground resistances of some increases significantly. If the soil resistivity is 2000 Q.m, the
substations did not meet the required values. For example, the required area for a 0.5 Q resistance will be 2000x2000 m2.
required ground resistance of the grounding system in Fenyi Because the available area for a substation is usually limited,
Power Plant, Jiangxi Province, is 0.25 Q, but the actual one is large grounding systems are not practical. In general, the area
0.69 51. The failure in this plant on July 31, 1984, destroyed of a substation is on the order of 100x100 m2. Therefore, it is
the entire control system and the 50,000 kW No.6 generator. difficult for the ground resistance of a horizontal grid to reach
In 1986, a 100,000 kW generator was destroyed in Heshan 0.5 51, if the average soil resistivity is greater than 100 a . m .
Power Plant, Guangxi, because the ground resistance was Consequently, to meet the requirement of low ground
higher than the required value. In China, the ground resistance in high resistivity regions, the substation grounding
resistances of many power substation grounding systems can grid should extend downward in the soil.
not reach the required values in regions with high soil If a huge “deep” distributed grounding system in the
resistivity. These substations have been in this state for some substation area is created, then the current injected into the
time. grounding system disperses to deeper soil layers easily. At the
same time, the area available to dissipate fault currents
PE-196-PWRD-0-09-1998 A paper recommended and approved by
increases, resulting in the decrease of the ground resistance.
the IEEE Substations Committee of the IEEE Power Engineering
Society for publication in the IEEE Transactions on Power DeliieW. Realistically, it is difficult to construct a large grounding
Manuscript submitted April 10, 1998; made available for printing system within the area defined by property lines of most
October 7,1998. substations. In this paper, a new method based on building a
grounding system extending to great depths is described and
examined.

0885-8977/99/$10.00 0 1998 IEEE


912

2. Description of the New Method (2) Reducing Contact Resistances: The low resistivity
materials which fill the holes provide a very low contact
First, several vertical holes are drilled, then appropriate resistance between the ground conductors and soil.
explosive agents are introduced into the holes. The resuIting ( 3 ) Decreasing the Leakage Resistance: The measured
explosions create various cracks in the soil. Finally, l w ground impedance of a grounding system consists of four
resistivity mkfials (LRM)are injected into the holes a d parts: the impedance of the bonding leads, the impedance of
cracks under high pressure. As a result, a large number of ground conductors, the contact resistance between the ground
cracks around the vertical conductors are filled with LRh4 conductors and the soil, and the distributed resistance to
and a large 3-dimensional grounding network consisting of
remote earth. The first and second parts are very small and
the ground conductors and cracks is formed as illustrated in can be neglected. The third part is normally ignored during
Fig. 1 (a). The basic idea of this method comes from the usual computation and is quite small when LRM are used to
practice of building the foundations of transmission line
decrease contact resistances as is the case here. Consequently
towers in rocky regions by triggering explosions in holes and
only the distributed (leakage) resistance is significant. The
filling them with concrete. It is noticed that these kinds of
ground resistance of a circular metallic plate or very dense
tower foundations have very low ground resistances. The
grid of radius r can be calculated approximately using the
LRM is usually an inorganic material with a resistivity less simple formula
than 5 a . m . The explosion course is carefully planned, and
the region close to the surface remains intact, as shown in Fig. R =p/4r (3)
1 (b).
The ground resistance of a hemispherical electrode of radius r
as shown in Fig. 2 is approximately
R, = p / 2 7 ~ (4)
The difference between the ground resistances of a dense
grounding grid and a hemispherical electrode is

P
A R = R - R , =(1-21~)-=0.363R (5)
4r
It can be seen that there is a 36.3% reduction in the ground
resistance using a hemispherical electrode instead of a
circular plate electrode with the same radius. When the radius
of the hemispherical electrode is increased to lSr, the total
reduction becomes 57.5%. Therefore, expanding the number
of conductive branches available for the current to dissipate in
the soil can effectively decrease the ground resistance.
Ground
4 Grqunding Grid

Fig. 2. Hemispherical electrode.


(b)
When the new method is used, a large network of soil cracks
Fig.1. The cubic grounding system (a) and its side view (b).
filled with LRM is formed. This network acts like a virtual
The basic principles upon which this new method is based extension of the grounding system to deeper soils, resulting in
are: lower ground resistances.

(1) Contacting Deep Soil Layers with Low Resistivity: It has (4) Links to the Intrinsic Soil Cracks: It is known that intrinsic
been observed that there are usually low soil resistivity layers cracks exist in rocky areas. The cracks caused by the
or layers saturated with underground water in the regions with explosion often connect with the intrinsic cracks in the rock.
high resistivity. The new method can effectively use these low These intrinsic cracks are typically filled with moisture and
resistivity layers to decrease ground resistances. usually extend to remote locations. The connected intrinsic
913
cracks and explosion cracks are filled with LRM by the high amount of explosives used. It is usually suitable to select a
pressure injection. When current is discharged from the rod span between 1.5-2.01.
grounding system, it can flow to remote locations through the
low resistivity soil cracks, as can be seen in Fig. 3. TABLE 1. Measured Ground Resistance R2 and Computed
Resistance of the Vertical Rods in Parallel R3
Rod SA Rz(i2) R3 (a) Usage
span s Factorf
30m 1.5 10.6 9.4 0.887
20m 1.0 16.4 11.9 0.726
10m 0.5 20.4 10.4 0.510
10m 0.5 15.8 8.6 0.544
20m 1.0 10.5 8.2 0.781
30m 1.5 15.9 13.1 0.824
L
40m 2.0 11.7 10.8 0.921

Fig. 3. Intrinsic cracks and explosion cracks. (1) Grounding 0.8 1 L


P
l
conductor; (2) Intrinsic crack; (3) Explosion crack;
(4) Soil.

3. Span Between Vertical Conductor Holes


f
0.6
- [
0.4-
The cost of applying the new method can be quite high. In
order to lower the cost, a suitable span between the vertical 0.2 -
holes should be determined for which the interaction effects
between the various elements of the grounding system
(vertical rods and cracks) lead to the optimum reduction
effect.
SI1
The field experiments for determining a suitable rod span
were completed in Benxi, China, in October 1992. First, one
Fig. 4. Usage factorffor different rod spacings.
vertical hole was drilled at one corner of the grounding grid
to be installed. Cracks were made by explosion in the hole
and then filled with low resistivity material. First, the ground 4. Effectiveness of the New Method in Decreasing
resistance of a metallic rod in this hole was measured. The Ground Resistances
measured resistance value divided by 4 is defined as R3,
representing the ground resistance of four vertical rods placed A. Ground Resistance of a Deep Distributed Grounding Grid
at the four corners of the grid, neglecting the interaction If a substation grounding system consists of a horizontal grid
between the rods. Second, three more holes were drilled at and vertical conductors, then an approximate value of the
the other three corners of the grounding grid to be installed ground resistance R can be computed using 141
and the explosion method was applied. After installing three
vertical rods in the three newly drilled holes and the R = ( R H R s - R H s Z ) / ( R H+ R s - 2 R H s ) (7)
horizontal grounding grid, the ground resistance of the
complex grounding network consisting of the grid, the where RH is the ground resistance of the horizontal grid, Rs
vertical rods and the low resistivity filled cracks was the ground resistance of the vertical conductors, and RHSthe
measured, yielding a value defined as R2. The length 1 of mutual resistance between the horizontal grid conductors and
every rod was 20 meters. The measured results for different the vertical conductors.
rod spans are listed in Table 1. It should be pointed out that a deep distributed grounding
The usage factorf is defined as system created using the new method is more effective in
dissipating fault currents than a usual grounding system
f =R3/R2 (6) consisting of a horizontal grid and vertical conductors. This is
where R3 is the measured resistance of one vertical rod because the LRM-filled cracks connect to one another and to
divided by 4 (resistance of four infinitely spaced vertical the soil's intrinsic cracks, resulting in a truly extensive
rods). The relationship between the usage factor f and SI1 is grounding system. The ground resistance of this grounding
shown in Fig. 4, where S is the rod span and 1 the rod length. system could be computed using (3) with a modified
The rod span is related to the geological structure and the equivalent radius r
914

r=h+D (8) arrangement is shown in Fig. 5 . Twelve vertical holes were


drilled, and the new method was applied. The experimental
where h is the depth of the deepest hole and D the equivalent
results are shown in Table 2. From a lot of experimental
reach of cracks, which is related to the geological structure in
results, the explosion and geology factor K has been classified
the substation area. In light weathering rock soil, D is in the
six types according to geological situation. The results
range of 5 to 10 meters. In medium weathering rock soil, D is given in Table 3.
in the w e of 10 to 15 meters, and in heavy weathering rock I
soil, D is in the range of 15 to 20 meters. TABLE 3. Explosion and Geob Factor Kin Different
Geological C o a tions
Because the deep distributed grounding system can connect
with deeper low resistivity soil via the intrinsic and explosion
cracks filled with LRM, an explosion and geology factor K
should be considered when computing the resistance of the
grounding system using the formula for a hemispherical
electrode of radius r as defined in (8)

(9)

The explosion and geology factor K is related to the degree of


explosion and geology. For example, K is dependent on the 5. Applications of the New Method in Power System
existence of deep low resistivity layers, the existence of Grounding
intrinsic cracks, and whether the cracks extend to remote
locations with low resistivity soil. A. Main Applications
Since 1989, the new method has been used in China in many
power system grounding projects such as the 220 kV Nan-Ge
transmission line, 220 kV Fen-Ge transmission line, and 220
kV Ping-Hu transmission line projects. The main applications
in substation grounding projects are shown in Table 4.
TABLE 4. List of Applications of the New Methods in
Substation Grounding Projects

-
Vertical Conductor

Fig. 5. The experimental arrangement.

TABLE 2. Effectiveness of the New Method


in Decreasing Ground Resistance

Soil Weathering Low Hole Ground Estimated Measured


Resisti- Condition Resistivity Depth Resis- Crack Factor
vitv Laver (m)
. . tance Reach D K
(ail) (a) (m)
3400 Heavy No 60 5.3 15 1.37
1500 Slight Yes 40 3.7 10 1.28
4300 Heavy No 60 6.3 15 1.45
1700 Medium Yes 40 3.6 15 1.35
2600 Heavy Yes 50 2.2 20 2.70
3800 Medium Yes 60 5.2 15 1.54
1900 Slight No 40 7.7 10 0.80
2100 Slight Yes 50 4.8 10 1.16
3600 Heavy Yes 60 3.7 20 1.96

B. Effectiveness of the New Method


Note that the computed resistance values in Table 4
In order to analyze the effectiveness of the new method in correspond to the grid and vertical rods only, without
decreasing ground resistances, several experiments were considering the LRM filled cracks. The computation method
carried out in different test regions. The experiment is described in [ l l ] . This new method is accepted as an
915
effective method to decrease the grounding resistance of grounding have been presented. It is shown ’that the new
grounding system in high resistivity regions in China. method is quite effective in reducing ground resistances in
roc@ areas.
B. The 110 kV Gangbei Substation Grounding Project
200 m
The newly built 110 kV Gangbei substation grounding system k
in Zhuhai adopted the new method. The average soil
resistivity is about 1100 Q.m which is very high, but the
measured ground resistance of the grounding grid is 0.43 a,
which is below the required value for safe operation. The
500 kV
project was completed in three months from March to June in
Substation
1993. It should be pointed out that the computed ground
resistance of the grid with four vertical rods of 100 m in Grounding

1 I 1:
length at its four corners is 3.2 9 with a 1100 Q-m soil Grid
resistivity.
The horizontal grounding grid was about 120 m x 120 m.
First, 4x100 m vertical holes at four corners of the grid were
drilled and explosives were used to develop the cracks. Then
LRM was injected under high pressure into the holes. And
II 220 kV Substation
Grounding Grid

other 13 vertical rods with the depths of 30-50 m by the new


methods were arranged near electrical equipments inside grid. Grounding Grid of Paver
A total of seven tons of LRM were used in this project. The Generating Station
explosion and geology factor was estimated to be about 3.4. 400 m
Moreover, the substation has safely operated since it is put P I
into operation.
Fig. 6. The Fengzhen Power Station Grounding System.
C. The Fengzhen Power Generating Station Project
7. References
The grounding system of Fengzhen Power Generating Station
is shown in Figure 6. The original grounding system consists [I] F. Dawalibi and D. Mukhedkar, “Parametric analysis of
of the grounding grids of the power generating station, the grounding grids,” IEEE Trans. Power Apparatus and Systems,
Vol. PAS-98, No. 5 , Sept./Oct. 1979, pp. 1659-1668.
220 kV substation and the 500 kV substation. The measured
ground resistance is 0.69 R. The soil resistivity is 560 a.m. [2] F. Dawalibi and D. Mukhedkar, “Influence of ground rods on
grounding grids,” IEEE Trans. Power Apparatus and Systems,
In October, 1997, the grounding system was enhanced by Vol. PAS-98, No. 6, Nov./Dec. 1979, pp. 2089-2098.
adding a new grounding grid as shown in Figure 6. The new
method was applied when the new grid was added. 12x40 m [3] A. P. Meliopoulos, R. P. Webb, and E. B. Joy, “Analysis of
grounding systems,” IEEE Trans. Power Apparatus and
and 2x80 m vertical holes with the new method were Systems,Vol. PAS-100, No. 3, March 1981,pp. 1039-1046.
arranged around the peripheries of the new added grid. The
[4] IEEWANSI Std. 80-1986, Guide for Safety in AC Substation
measured ground resistance of the enhanced grounding Grounding.
system is 0.26 Q.
[5] F. Dawalibi and D. Mukhedkar, “Optimum design of substation
grounding in two-layer earth structure - Part I, analytical
6. Conclusions study,” IEEE Trans. Power Apparatus and Systems, Vol. PAS-
94, N0.2, MarchIApril 1975, pp. 252-261.
A massive grounding system made of grounding conductors
and a network of soil cracks is constructed using a new [6] F. Dawalibi and D. Mukhedkar, “Optimum design of substation
grounding in two-layer earth structure - Part 11, comparison
method. The mechanisms by which the ground resistance is between theoretical and experimental results,” IEEE Trans.
decreased significantly are: (1) development of deep Power Apparatus and Systems, Vol. PAS-94, No.2,
conductive soil cracks using explosives and low resistivity MarcWApril 1975, pp. 262-266.
materials; (2) linkage of cracks created by the explosions with [7] F. Dawalibi and D. Mukhedkar, “Optimum design of substation
intrinsic (natural) cracks; (3) connection of the various cracks grounding in two-layer earth structure - Part 111, study of
with low resistivity soil layers. grounding grids performance and new electrode configuration,”
IEEE Trans. Power Apparatus and Systems, Vol. PAS-94,
It has been found from extensive field tests that an optimum N0.2,MarcNApril 1975, pp. 267-272.
(suitable) span between vertical conductors is in the range of [8] J. G. Sverak, “Optimized grounding grid design using variable
1.51 to 2.01 with 1 being the length of the vertical conductors. spacing technique,” IEEE Trans. Power Apparatus and
The explosion and geology factors in different soils have also Systems, Vol. PAS-95, No. 1, Jan.lFeb. 1976,pp. 362-374.
determined by field tests. The effectiveness of the new [9] L. Huang, X. Chen, and H. Yan, “Study of unequally spaced
method in decreasing ground resistance has been examined grounding grids,” IEEE Trans. Power Delivery, Vol. 10, No.2,
and actual applications of the new method in substation April 1995, pp. 716-722.
916
[lo] IEEE Std.665-1995, IEEE Standard for Generating Station computer software code development. In 1976, he joined
Grounding. Montel-Sprecher & Schuh, a manufacturer of high voltage
[ 111 F.P. Dawalibi and F. Donoso, "Integrated Analysis Software equipment in Montreal, as Manager of Technical Services
for Grounding, EMF, and EMI",IEEE Computer Applications p d was involved in power system design, equipment
in Power, 1993, Vol. 6, No. 2, pp. 19-24. selection and testing for systems ranging from a few to
several hundred kV.
8. Biography
In 1979, he founded Safe Engineering Services &
Mr. Qingbo Meng was born in 1951, in Shenyang, P. R. Technologies, a company which specializes in soil effects on
China. He graduated from Northeast China Electrical power networks. Since then he has been responsible for the
Engineering University in 1975. He worked in the department engineering activities of the company including the
of power construction of Northeast China Power Bureau, development of computer software related to power system
where he is a senior engineer. He received his M. Eng. from applications.
Wuhan University of Hydraulic and Electrical Engineering in He is the author of more than one hundred papers on power
June 1994. His research interests are in power transmission, system grounding, lightning, inductive interference and
construction of substations and transmission lines, and electromagneticfield analysis. He has written several research
grounding techniques. reports for CEA and EPRI.

Dr. Jinliang He was born in Changsha, P. R. China, in Dr. Dawalibi is a corresponding member of various IEEE
January, 1966. He received the B.Sc. degree from Wuhan Committee Working Groups, and a senior member of the
University of Hydraulic and the Electrical Engineering, the IEEE Power Engineering Society and the Canadian Society
M.Sc. Degree from Chongqing University., and the Ph.D. for Electrical Engineering. He is a registered Engineer in the
degree from Tsinghua University, all in Electrical Province of Quebec.
Engineering, in July 1988, Jan. 1991 and March 1994,
respectively. Dr. Jimi Ma was born in Shandong, P.R. China in December
1956. He received the B.Sc. degree in radioelectronics from
From April 1994 to June 1996, he was a lecturer in the Shandong University, and the M.Sc. degree in electrical
Electrical Engineering Department, Tsinghua University. In engineering from Beijing University of Aeronautics and
July 1996, he became an associate professor in the same Astronautics, in 1982 and 1984, respectively. He received the
department. From 1994 to Jan 1997, he was the head of high Ph.D. degree in electrical and computer engineering from the
voltage laboratory in Tsinghua University. Since 1996, he has University of Manitoba, Winnipeg, Canada in 1991. From
also held a concurrent position as an associate professor in 1984 to 1986, he was a faculty member with the Dept. of
the National Key Laboratory of Safety, Control and Electrical Engineering, Beijing University of Aeronautics
Simulation of Power System in Tsinghua University. Since and Astronautics. He worked on projects involving design
April 1997, he has been a visiting scientist in Korea and analysis of reflector antennas and calculations of radar
ElectrotechnologyResearch Institute, involved in research on cross sections of aircraft.
metal oxide varistor and high voltage polymeric metal oxide
surge arrester. His research interests are in overvoltages and Since September 1990, he has been with the R & D Dept. of
EMC in power systems and electronic systems, grounding Safe Engineering Services & Technologies in Montreal,
technology, and power apparatus. where he is presently serving as manager of the Analytical R
& D Department. His research interests are in transient
Dr. Farid P. Dawalibi (M72, SM'82) was born in Lebanon electromagnetic scattering, EM1 and EMC, and analysis of
in November 1947. He received a Bachelor of Engineering grounding systems in various soil structures.
degree from St. Joseph's University, affiliated with the
University of Lyon, and the M.Sc. and Ph.D. degrees from Dr. Ma has authored and coauthored more than forty papers
Ecole Polytechnique of the University of Montreal. From on transient electromagnetic scattering, analysis and design of
1971 to 1976, he worked as a consulting engineer with the reflector antennas, power system grounding, lightning and
Shawinigan Engineering Company, in Montreal. He worked electromagnetic interference analysis. He is a corresponding
on numerous projects involving power system analysis member of the IEEE Substations Committee and is active on
and design, railway electrific ation studies and specialized Working Groups D7 and D9.

S-ar putea să vă placă și