Documente Academic
Documente Profesional
Documente Cultură
Dynamic Braking
Unit
600/690 VAC
User Manual
Important User Information
Solid state equipment has operational characteristics differing from those of
electromechanical equipment. “Safety Guidelines for the Application, Installation
and Maintenance of Solid State Controls” (Publication SGI-1.1 available from
your local Rockwell Automation Sales Office or online at http://
www.rockwellautomation.com/literature) describes some important differences
between solid state equipment and hard-wired electromechanical devices. Because
of this difference, and also because of the wide variety of uses for solid state
equipment, all persons responsible for applying this equipment must satisfy
themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation be responsible or liable for indirect or
consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative
purposes. Because of the many variables and requirements associated with any
particular installation, Rockwell Automation cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation with respect to use of
information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written
permission of Rockwell Automation is prohibited.
Throughout this manual, when necessary we use notes to make you aware of safety
considerations.
WARNING: Identifies information about practices or circumstances
that can cause an explosion in a hazardous environment, which may
! lead to personal injury or death, property damage, or economic loss.
Preface Overview
Who Should Use this Manual?. . . . . . . . . . . . . . . . . . . . . . . . P-1
Reference Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1
Manual Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-2
General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-2
Catalog Number Explanation. . . . . . . . . . . . . . . . . . . . . . . . . P-3
Description and Block Diagram. . . . . . . . . . . . . . . . . . . . . . . P-4
Line Voltage Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-7
Permissible Loading of the DBU . . . . . . . . . . . . . . . . . . . . . . P-8
Chapter 1 Installation/Wiring
Minimum Mounting Clearances . . . . . . . . . . . . . . . . . . . . . . 1-1
Grounding Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Fuses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Protection of Brake Resistors and Conductors . . . . . . . . . . . 1-3
Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
CE Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
Appendix A Specifications
DBU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3
Diagnostic Card BUB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-4
Resistor Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-4
Fuse Ratings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-4
Appendix B CE Conformity
General Installation & Wiring Guidelines for CE Conform. . B-1
Essential Requirements for CE Compliance . . . . . . . . . . . . . B-2
Mounting Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-3
Wiring Instruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-4
Configuration Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-6
Overview
The purpose of this manual is to provide the necessary information for
the installation, start-up and trouble shooting of the AK Dynamic
Braking Unit.
See See
For information on… page For information on… page
Who Should Use this Manual? P-1 Catalog Number Explanation P-3
Reference Materials P-1 Description and Block Diagram P-4
Manual Conventions P-2 Line Voltage Selection P-7
General Precautions P-2 Permissible Loading of the DBU P-8
Reference Materials
The following manuals are recommended for general drive information:
Title Publication Available Online at …
Wiring and Grounding Guide for DRIVES-IN001A-EN-P
PWM AC Drives www.ab.com/manuals/dr
Preventive Maintenance of DRIVES-SB001A-EN-E
Industrial Control and Drive
System Equipment
Reactors and Isol. Transformers 1321-TD001D-EN-P
Guarding Against Electrostatic 8000-4.5.2
Damage www.ab.com/manuals/gi
Safety Guidelines for the Appli- SGI-1.1
cation, Installation and Mainte-
nance of Solid State Control
A Global Reference Guide for 0100-2.10 Not available online, contact
Reading Schematic Diagrams your local RA Sales Office
Manual Conventions
• In this manual we refer to the AK Dynamic Braking Unit as DBU
and to the Adjustable Frequency AC Drive (AFD) as; drive, inverter
or PowerFlex Drive.
• The following words are used in the manual to describe an action:
Word Meaning
Can Possible, able to do something
Cannot Not possible, not able to do something
May Permitted, allowed
Must Unavoidable, you must do this
Shall Required and necessary
Should Recommended
Should Not Not Recommended
General Precautions
AK DBU F 300 N E
Product Voltage Rating Rating Enclosure Documentation
Product
Name Cat.Code
AK Dynamic Braking Unit AK DBU
Figure P.1 shows the block diagram of the DBU with the Dynamic Brake
Resistor. The DBU is shown connected to the positive (DC+) and nega-
tive (DC-) terminals of an AC PWM Drive.
Field DBU PE
installed
Fuses
DC+ F1 DC+ BR1
Inverter R
BR2
Transistor >°C
Control
BUC RC
Snubber
F2 DC- to inverter's main
DC-
contactor circuit
115
to customer's
BUB M supplied
0 115 VAC
DC Power on Brake on
power source
11
to inverter's
>°C
main contactor
10
circuit
P-6 Overview
Theory of Operation
When the rotor of an induction motor is turning slower than the
synchronous speed set by the drive’s output power, the motor is
transforming electrical energy obtained from the drive into mechanical
energy available at the drive shaft of the motor. This process is referred
to as motoring. When the rotor is turning faster than the synchronous
speed set by the drive’s output power, the motor is transforming
mechanical energy available at the drive shaft of the motor into electrical
energy that can be transferred back into the utility grid. This process is
referred to as regeneration.
Most AC PWM drives convert AC power from the fixed frequency utility
grid into DC power by means of a diode rectifier bridge or controlled
SCR bridge before it is inverted into variable frequency AC power.
Diode and SCR bridges can only handle power in the motoring direction.
Therefore, if the motor is regenerating, the bridge cannot conduct the
necessary negative DC current. Depending on parameter setting, the
drive regulator will either increase the DC bus voltage and cause a Bus
Overvoltage trip at the drive, or extend the set deceleration rate or
increase the output frequency.
BUC-Card
600V 690V
100%
95%
0% VDC
Jumper at 600: 913V 950V
690: 1047V 1090V
The peak current (IPeak) in the following two examples is 300 Amp
(maximum current with Rmin = 3.2 ohm at 600 VAC line) and the
current-time area also meets the 750 Amp.-minutes requirement.
IPeak IPeak
300A 300A
112.5A
0 t 0 t
5 minutes 4 1 minutes
10 10
Installation/Wiring
This chapter provides the information needed for the installation and
wiring of the Allen-Bradley Dynamic Braking Module.
See See
For information on… page For information on… page
Minimum Mounting Clearances 1-1 Power Wiring 1-4
Grounding Requirements 1-2 Control Wiring 1-8
Fuses 1-3 CE Conformity 1-9
Protection of Brake Resistors and Conductors 1-3
The rate of cooling air for the forced ventilated DBU is 158 m3/h,
with a bottom to top of the unit air flow.
See Appendix A, Figure A.3 for detailed dimension information.
1-2 Installation/Wiring
Grounding Requirements
The Safety Ground terminal (PE) must be connected to the building
grounding scheme. Ground impedance must conform to the
requirements of national and local industrial safety regulations and/or
electrical codes. The integrity of all ground connections should be
periodically checked.
For installations within a cabinet, a single safety ground point or ground
bus bar connected directly to building steel should be used. All circuits
should be grounded independently and directly to this point/bar.
+DC +DC
PE - DC - DC
PE
Fuses
National and local industrial safety regulations and/or electrical codes
may determine additional requirements for these installations.
ATTENTION: The DBU does not provide DC Bus branch short
circuit protection. Specifications for the recommended fuse to provide
! protection against short circuits are provided in Appendix A.
Power Wiring
EMC Compliance
Refer to Appendix B for details.
Connect DBU, fuses and brake resistors according to the block diagram
in Figure P.1. Refer also to General Installation and Wiring Guidelines
for CE Conformity on page B-1.
Installation/Wiring 1-5
F2
DC- DC- BR2
Field
Installed
Fuses
10 11
Connection leads between the DBU and the Brake Resistor (R)
The cable length between the DBU and the Brake Resistor must not
exceed 30 meters, but the limiting factor for this connection is the time
constant of the brake resistor (Ratio of Inductance to Resistance).
See Brake Resistor Specifications on page A-4
PE
BR2 DC- DC+ BR1
(1) Max./Min. sizes the terminals will accept - these are not recommendations.
1-8 Installation/Wiring
Control Wiring
Recommendations for the selection and wiring of the control cables:
ATTENTION: The DBU and the drive(s) do not offer protection for
externally mounted brake resistors. Risk of fire exists if the brake
! resistors are not protected. Resistor packages must be self-protected
from overtemperature or a circuit equivalent to the one shown in Figure
1.5 must be supplied.
K1M
R
R (L1)
S (L2) F2
T (L3)
Temperature Resistor
Sensor Thermostat
F3 >°C F4 >°C
10 11
11
Power
Source
K1M
K1M
CE Conformity
For Mounting and Wiring Instructions concerning CE Conformity refer
to Appendix B.
1-10 Installation/Wiring
Chapter 2
Start Up / Troubleshooting
This chapter provides the necessary information for the start up and
troubleshooting of the DBU.
Start-Up
❏ 1. Verify all inputs are connected to the correct terminals and are
properly torqued.
❏ 3. Verify the control power voltage is correct (115V AC for the fan).
❏ 4. Verify the DBU Overtemperature N.C. contact output is correctly
wired. This normally closed contact output is used to stop the
drive(s) when an overtemperature condition exists. Verify this
interlocking circuit has been wired correctly according to customer’s
application. See Figure 1.5 on page 1-9.
❏ 1. Apply AC power to the drive(s) and control voltage (115V AC) to the
fan of the DBU.
The red DC Power ON LED on the DBU should be on if power is
applied to terminals R, S, T (L1, L2, L3) of the connected drive(s).
See Figure 2.1.
❏ 2. If the red DC Power ON LED is not on at this point, refer to the Table
2.A for troubleshooting guidelines.
Start Up / Troubleshooting 2-3
DC Power ON LED
The red DC Power ON LED is visible through the front panel and will
illuminate when power is applied to the drive and the DC bus voltage has
exceeded 50V.
ATTENTION: The LEDs on the DBU are only operational when the
unit is energized. Servicing energized equipment can be hazardous.
! Severe injury or death can result from electrical shock, burn, or
unintended actuation of the controlled equipment. Follow Safety related
practices of NFPA 70E, ELECTRICAL SAFETY FOR EMPLOYEE
WORKPLACES. DO NOT work alone on energized equipment!
DC Power On Brake On
2-4 Start Up / Troubleshooting
Troubleshooting
Table 2.A Possible Faults and Corrective Actions
Specifications
This appendix provides electrical, environmental, functional and
physical specifications for the DBU and the diagnostic card BUB.
See See
For information on… page For information on… page
DBU A-1 Brake Resistor Specifications A-4
Dimensions A-3 Fuse Ratings A-4
Diagnostic Card BUB A-4
DBU
Specifications
Power Ratings
Input Voltage 600V 690V
Peak Braking Power 268 kW 305 kW
Specifications
Approvals and Standards Compliance
The DBU is designed to meet the following specifications:
NFPA 70 - US National Electrical Code
NEMA ICS 3.1 - Safety standards for Construction and Guide for Selection,
Installation and Operation of Adjustable Speed Drive Systems.
IEC 146 - International Electrical Code.
UL and cUL Listed to UL508C
and CAN/CSA-C2.2 No. 14-M91
(600V AC only)
Marked for all applicable European
Directives
C EMC Directive (89/336/EEC)
Emissions: EN 61800-3 Adjustable
Speed electrical power drive
systems Part 3
Immunity: EN 61800-3 Second
Environment, Category C3
Low Voltage Directive (73/23/EEC)
EN 50178 Electronic Equipment for use
in Power Installations
Environmental Specifications
Altitude: 1000 m (3300 ft.) max. without derating.
Above 1000 m the derating for the
nominal current is 1% per 100 m
(330 ft.).
Degree of protection Open / IP00
Ambient Operating Temperature 0 to 40°C (32 to 104°F)
without derating: For temperatures higher than 40°C up to
max 55°C (131°F), the max. peak
braking current must be derated by 1.5%
per °C (0.8% per °F)
Storage Temperature: –25 to 55°C (–25 to 131°F)
Transportation Temperature: –25 to 70°C (–25 to 158°F)
(70°C max 24 hours)
Relative Humidity: 5 to 95% non-condensing
Shock: 15G peak for 11ms duration (±1.0 ms)
Vibration: 0.152 mm (0.006 in.) displacement,
1G peak
Specifications A-3
Dimensions
Figure A.3 Dimensions and Location of Bus-Bar Customer Connection Points
Min.
100
(4.0) 42 36 36 36 25 50 89 5
(1.65) (1.42) (1.42) (1.42) (1.0) (2.0) (3.5) (0.2)
32 ø6.5
(1.3) (0.26)
PE
BR2 DC- DC+ BR1
2)
350 356
(13.8) 310 (14.0)
(12.2)
Air Flow
8
(0.3)
80
(3.15)
5 215 5
Min. (0.2) (8.46) (0.2)
100 225 157
(4.0) (8.86) (6.18)
Fuse Ratings
Table A.2 provides the recommended fuse ratings for the DBU.
The recommended fuses meet the UL and IEC requirements and are
based on 40°C (104°F) and the U.S. National Electrical Code. Other
country, state or local codes may require different ratings.
If the available fuse ampere ratings do not match those recommended,
the next higher fuse rating should be chosen.
• IEC – BS88 (British Standard) Parts 1 & 2,
EN60269-1, Parts 1 & 2, type aR or equivalent should be used.
• UL – Recognised; A100P (Ferraz) or FWJ (Bussmann) must be used.
Table A.2 Recommended Short Circuit Protection Fusing
CE Conformity
This appendix provides the installation and wiring instructions necessary
for the CE-conformity of the Dynamic Braking Unit.
See See
For information on… page For information on… page
General Installation and Wiring Guidelines B-1 Mounting Instructions B-3
for CE Conformity Wiring Instructions B-4
Essential Requirements for CE Compliance B-2 Configuration Examples B-6
Mounting Instructions
Wiring Instructions
General
• Earth conductors must be either 16 mm2 or 50% of the cross section
of the phase conductor whichever is larger.
• The connections between the inverter and the DBU should not
exceed 3 m (10 ft.).
• Signal leads inside the cabinet must be separated from power leads.
• Input power wires on the line side of the drive or EMC filter for the
drive should be widely separated from other wiring inside the cabinet
or should be shielded.
Plastic insulation
Cable Glands
• Use suitable EMC-tested cable glands only.
• The conductivity of the shield to earth connection is ensured by
laying the braid over a plastic cone which will press it to the inner
side of the gland when mounted.
• It is important that the connection area is 360 degree around the
cone.
• The cable glands provide pull-relief through the cable jacket.
B-6 CE Conformity
Configuration Examples
Figure B.2 Cabinet Mounted Drive and Related Components
Cabinet
DBU R Panel
Brake resistor
Inverter
DC+, DC-
RFI Filter
(if used)
U, V, W R, S, T
(T1,T2,T3) (L1,L2,L3)
External
line reactor
(if used)
Input contactor
Input fuses
Cabinet protective
1 ground bus bar
3 1 Cable bracket
4 2 Shield
K1M
DC+
DC-
>°C >°C
to DC+ BR1 PE R
R, S, T U, V, W K1M DC- 10 11 BR2
(L1,L2,L3) (T1,T2,T3) control
circuit
6 6 6
3
4
Notes:
Appendix C
Design Information
This appendix provides the design information which is necessary for
calculating and selecting an external brake resistor for connecting to the
Dynamic Braking Unit.
ωo
0 t1 t2 t3 t4 t1 + t4 t
Torque
T(t)
0 t1 t2 t3 t4 t1 + t4 t
Power
P(t)
0 t1 t2 t3 t4 t1 + t4 t
-Pb
C-4 Design Information
Load Speed
GR = -----------------------------
Motor Speed
1
If the gear ratio is 2:1 then GR = -- = 0.5
2
JL = Load inertia (kg-m2 or WK2 in lb.-ft.2)
1.0 lb.-ft.2 = 0.042 kg-m2
Calculate Total Inertia:
JT =
Design Information C-5
Pb =
Calculate Pb1:
Compare the Pb1 to the Maximum Peak Braking Power of the DBU
(Pmax). If Pb1 is greater than Pmax, the decel time must be increased, or
the inertia or the speed must be decreased, so that the drive does not
enter current limit.
For the purposes of this document, it is assumed that the motor used in
the application is capable of producing the required regenerative torque
and power.
C-6 Design Information
Pb ( ωb + ωo )
----- × ------------------------
2 ωb
Pav =
ATTENTION: The DBU and most drives do not offer protection for
externally mounted brake resistors. Risk of fire exists if external
! braking resistors are not protected. External resistor packages must be
self-protected from overtemperature or circuit equivalent to the one
shown in Figure 1.5 must be supplied.
The choice of the Dynamic Brake resistance value should be less than
the value calculated in this step. If the value is greater, the drive can trip
on DC bus overvoltage.
⎛P
----b-⎞ × ( t 3 – t 2 ) = watt-seconds
⎝ 2⎠
Pb
Watt-second losses = ------x ( t – t ) x [ 1 – ( motor efficiencyxdrive efficiency ) ]
2 3 2
Example Calculation
A 250 HP, 600 Volt motor and drive are accelerating and decelerating as
depicted in Figure C.1.
• Cycle period (t4) is 40 seconds
• Rated speed is 1600 RPM
• Deceleration time from rated speed to 0 speed is 2.0 seconds
• Motor load can be considered purely as an inertia and all power
expended or absorbed by the motor is absorbed by the motor and
load inertia.
• Load inertia is 44.0 lb-ft2 directly coupled to the motor
• Motor inertia is 166 lb-ft2
• A PowerFlex 700H, 250 HP, 600V Normal Duty rating is chosen.
• Drive efficiency is 0.975 and motor efficiency is 0.86.
Proceed with the following calculation to verify the AKDBU300 is
suitable for the application, and select the Dynamic Brake Resistor.
This information was given and must be known before the calculation
process begins. This can be given in HP, but must be converted to watts
before it can be used in the equations.
1600 167.5 Rad
Rated Speed = ω b = 1600 RPM = 2π × ---------- = -----------------------
60 s
0 0 Rad
Lower Speed = ω o = 0 RPM = 2π × ----- = -------------
60 s
This information was given and must be known before the calculation
process begins. This can be given in RPM, but must be converted to
radians per second before it can be used in the equations.
This value can be in lb.-ft.2 or Wk2, but must be converted into kg-m2
before it can be used in the equations.
Design Information C-11
All of the preceding data and calculations were made from knowledge of
the application under consideration. The total inertia was given and did
not need further calculations as outlined in Step 1.
Step 2 Calculate the Peak Braking Power (Pb) and (Pb1) then
compare (Pb1) to the Peak Braking Power of the DBU (Pmax)
JT [ ωb ( ωb – ωo ) ]
Peak Braking Power = Pb = ----------------------------------------
( t3 – t2 )
8.82 [ 167.5 ( 167.5 – 0 ) ]
P b = ----------------------------------------------------- = 123700 watts
2
Pb1 = Pb x (motor effic. x drive effic.)
Pb1 = 123 700 x (0.975 x 0.86) = 103 722 watts < Pmax
Note that this is 56% of rated power and is less than the maximum drive
limit of 150% current limit. This calculation determines the power that
must be dissipated by the Dynamic Brake Resistor.
The DBU is suitable for this application because Pb1 is less than Pmax.
The choice of the Dynamic Brake resistance value should be less than
the value calculated in this step. If the value is greater, the drive can trip
on DC bus overvoltage.
Headquarters for Allen-Bradley Products, Rockwell Software Products and Global Manufacturing Solutions
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: +1 414.382.2000, Fax: +1 414.382.4444
Europe/Middle East/Africa: Rockwell Automation SA/NV, Vorstlaan/Boulevard du Souverain 36, B-1170 Brussels, Belgium, Tel: +32 2 663 0600, Fax: +32 2 663 0640
Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: +852 2887 4788, Fax: +852 2508 1846