MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 1/34


Overseas Support Team
Start - Up Date Mar. 20009

Annunciator

‹ Revision History
Rev. Prepared Checked Approved
Date Revision Contents
No. by by by
Mar. Harold
0 Release YS Kim DH Kim
2009 Lee
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 2/34


Overseas Support Team
Start - Up Date Mar. 20009

Index

1. Annunciator ___________________________________________________________ 4
1.1. Description of ANN screen _________________________________________________ 4

2. Operation mode by key inputting __________________________________________ 6

3. Annunciator Mode______________________________________________________ 9
3.1. LCD Initialize ___________________________________________________________ 9

3.2. OS ROM Version check ___________________________________________________ 9

3.3. DSP ROM Version check __________________________________________________ 9

3.4. Floor height measurement operation _______________________________________ 10

3.5. Car call registration _____________________________________________________ 11

3.6. Error TRACE Data read _________________________________________________ 11

3.7. Reset TRACE Data read _________________________________________________ 12

3.8. Statistic Data read_______________________________________________________ 12

3.9. Statistic Data Clear ______________________________________________________ 13

3.10. Non power failure Reset Count read________________________________________ 13

3.11. Emergency stop Trace Data read __________________________________________ 14

3.12. SPEC ROM Read/Write__________________________________________________ 14

3.13. TCD DISPLAY _________________________________________________________ 16

3.14. Error log table __________________________________________________________ 16

3.15. Error log table clear _____________________________________________________ 18

3.16. DSP Memory read_______________________________________________________ 18

3.17. DSP SPEC WRITE ______________________________________________________ 19

3.18. Manual LRT operation. __________________________________________________ 19

3.19. No load point setting _____________________________________________________ 20

3.20. Full load point setting ____________________________________________________ 21

3.21. Time setting mode _______________________________________________________ 22


Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 3/34


Overseas Support Team
Start - Up Date Mar. 20009

3.22. Door condition check ____________________________________________________ 23

3.23. Hall Check mode________________________________________________________ 24

3.24. Car Check mode ________________________________________________________ 25

3.25. POSI(PRS) TEST mode __________________________________________________ 25

3.26. Car load mode __________________________________________________________ 26

3.27. 110% Function test mode _________________________________________________ 27

3.28. 110% Cut Mode ________________________________________________________ 27

3.29. SDS Check Mode _______________________________________________________ 28

3.30. CRT Data Reset Mode ___________________________________________________ 29

4. Trace Data reference Method ____________________________________________ 30


4.1. Mode for Error Log Table reference ________________________________________ 30

4.2. Key function ___________________________________________________________ 30

4.3. Additional Information Flag Table _________________________________________ 32


Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 4/34


Overseas Support Team
Start - Up Date Mar. 20009

1. Annunciator
Function that only reading data is possible at DOC PCB. But for the writing and reading can
be done at DES PCB.
1.1. Description of ANN screen
a. Initial screen of annunciator
Initial screen: When the main power turn on, LCD display will show as below.
C1 C2 C3 C4 C5 C6 C7 C8 C9 C10 C11 C12 C13 C14 C15 C16
R1 A C D = 0 4 0 8 F L 0 0 %
R2 E 0 0 0 - 0 0 1 0 0 0 0 0 S
R3 1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
R4 K :

b. Row 1: Operation mode, present floor, load weight and speed of elevator.
a) ACD=27(Column1~ 6): Operation Code( ex: 27*Auto operation, 4*Maintenance
Operation, ...) ※ Refer to the MODE Description
b) 01FL (Column 8 ~11): Present floor
c) 00% (Column 13 ~ 16): On stop, present load weight (%) of the elevator.
c. Row 2: When an error occurs, it shows the trouble code of the top-level error, condition of
the operation, output of main signal and direction of elevator.
a) E000 (Column 2 ~ 4): Trouble code of high level error. (TCD No. 1 ~ 255)
031 DC Link Over-voltage 116 POSI(PRS) ON error(LDU)
052 INV reverse running detection 172 SD1U input error
084 R5SY relay ON error 200 CNET LON Comm. Error

b) 00(Column 6 ~ 7): Operation condition of the high level error


01 R5SC Cut 10 Fast Run Cut
02 R5SC Cut possible 20 Safety Drive operation Possible
04 C1ST Cut 40 Rest operation Possible
08 C1ST Cut possible 80 Hall Call Cut Possible

c) 100100 (Column 9 ~ 14): Displays output of main signals.


(a) "1": Means that switch, relay and contactor, etc. is operated.
(b) "0": Means that switch, relay and contactor, etc. is not operated.
(c) Each column means as follows;

C9 R5SY C10 C1ST C11 C1BR C12 C1BS


C13 Door Open Command C14 Door Close Command
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 5/34


Overseas Support Team
Start - Up Date Mar. 20009

d) S (C16): Displays the present direction of elevator.


- "S": STOP "U": UP "D": DOWN

d. Row 3: Displays input condition of main signal such as switches, relays and contactor, etc.

C1 R5SY C5 LDC(PRS) C9 C1ST C13 CDS


C2 24Vdc C6 LDCX C10 C1BR C14 DCLS
C3 UL C7 SDS1D C11 Suppress C15 DOLS
C4 DL C8 SDS1U C12 LDS C16 SES

a) "1": Means that switch, relay and contactors, etc. is operated.


b) "0": Means that switch, relay and contactors, etc. is not operated.

e. ACD MODE

Mode Description Mode Description Mode Description

00 Stop 01 ALP operation 02 Earthquake control door open

03 Failure 04 Maintenance operation 05 Earthquake control finished


Earthquake control slow Bottom floor slow operation
06 Earth quake control 07 08
operation (SPEC. ROM F/H error)
F height measurement Bottom floor slow operation
09 F/H measurement ready 0A 0B
operation (C RAM F/H error)
0C Unused 0D Unused 0E 2nd fire operation
All floors operation after
0F 1st fire operation 10 Arrival operation finished 11 earthquake control
12 Eme. Return Operation 13 Fireman operation 14 Fireman return operation
Rescue arrival operation
15 Rescue arrival Operation 16 Rescue operation 17 finished
18 Rescue return operation 19 Fire operation finished 1A Fire operation
T/M temp detection operation
1B 1C TM temp detection operation 1D Unused
finished
Eme Generator driven EME. Generator driven E&I PANEL temp. detection
1E operation finished 1F operation 20 operation finished
E&I PANEL temp. detection
21 22 Rest 23 Standby operation finished
operation
24 ATT operation 25 Semi- auto operation 26 Back-up operation
Air-conditioner water drain LRT operation
27 Auto operation 28 29
operation (Locked Rotor Test)
※ LRT operation: Whenever system starts newly, this operation will be done automatically.
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 6/34


Overseas Support Team
Start - Up Date Mar. 20009

2. Operation mode by key inputting

MAIN MODE SUB MODE Resetting


Classification
MAIN MODE KEY Input SUB MODE KEY Input KEY Input
Floor height
A12E(DES) START 3 FFFF
measurement Op.
Input lowest floor call A13E(DES)
Input middle floor call A14E(DES)
Input highest floor call A15E(DES)
Operation
related mode Input lowest floor call A16E(DES)
(Hold)
Input middle floor call
A17E(DES) FFFF
(Hold)
Input highest floor call
A18E(DES)
(Hold)
Input random floor call A19E(DES) xxE -> Floor
A21E(DO+DE) Address INC 0
A22E(DO+DE) Address DEC 8
Address Input xxxxE
Data Read & Write FFFF
Address Re-input BBB
PROTECTION
AAE
release
Data Input xxE
A23E(DO+DE) Item INC 0
TRACE DATA READ
(TRACE when error Item DEC 8
FFFF
occurs Block INC 1
5000h ~ )
Block DEC 9

Memory A24E(DO+DE) Item INC 0


related mode TRACE DATA READ Item DEC 8
(TRACE when reset
FFFF
occurs Block INC 1
4400h ~ )
Block DEC 9
A25E(DO+DE) Item INC 0
Statistics Data read &
Item DEC 8 FFFF
Deletion
Data Deletion CCCC
Statistics Data deletion A26E(DO+DE) Deletion check E FFFF
Reset count without
A27E(DO+DE) FFFF
power failure
A28E(DO+DE) Item INC 0
Emergency stop
TRACE Item DEC 8 FFFF
Data read
Deletion all CCCC
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 7/34


Overseas Support Team
Start - Up Date Mar. 20009

A31E(DES) Address INC 0


Address DEC 8
Address Input xxxxE
Spec SPEC DATA READ &
FFFF
related mode WRITE A32E(DES) Address Re-input BBB
PROTECTION
AAE
release
Data Input xxE
TABLE INC 0
TCD DISPLAY A41E(DO+DE) FFFF
TABLE DEC 8
TABLE INC 0
TABLE DEC 8
Error First error 1
ERROR LOG DISPLAY A42E(DO+DE)
related mode Last error 9
FFFF
Display mode change C
(Time->Trace)
ERROR LOG CLEAR A43E(DO+DE)
TCD CLEAR A44E(DO+DE)
Address INC 0
Address DEC 8
DSP READ A51E(DES) FFFF
DSP mode Address Input xxxxE
Address Re-input BBB
DSP SPEC WRITE A52E(DES)
NO LOAD POINT SET A61E(DES) xxE FFFF
FULL LOAD POINT
A62E(DES) Load Input xxxE FFFF
SET
Parameter Zero Load point
A64E(DES)
related mode adjustment
HALF LOAD POINT
A65E(DES) Load Input N/A FFFF
SET
Date/Time mode
C
RTC SET A69E(DO+DE) change FFFF
Data Input xxE
OS ROM version check A01E(DO+DE) FFFF
DSP ROM version
A02E(DO+DE) FFFF
check
State check PCB Protection check A03E(DO+DE) FFFF
mode OS ROM version
DEEE
Check in DES PCB
Door condition check A71E(DO+DE) FFFF
Car Load display A86E(DO+DE) FFFF

Device Test Hall Check Mode A82E(DO+DE) FFFF


Mode Car Check Mode A83E(DO+DE) FFFF
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 8/34


Overseas Support Team
Start - Up Date Mar. 20009

Device Test PRS measurement UP operation UP Switch


mode mode A85E(DES) FFFF
DN operation DN Switch
PTM check A86E(DES) Current PTM input FFFF
110% Function test
A87E(DES) Testing Load Input (%) xxE FFFF
mode
SDS Test (UP) 3
SDS Test mode A89E(DES) FFFF
SDS Test (DN) 7
Other mode LCD INITIALIZE DOC+DES Input ‘0’ over 4 times FFFF
LRT operation A54E Start 3 FFFF
110% Cut mode A88E(DES)
CRT Data reset A90E(DOC+DES)
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 9/34


Overseas Support Team
Start - Up Date Mar. 20009

3. Annunciator Mode

3.1. LCD Initialize


a. Preparation
a) Checking of software version for annunciator
b) Set the S/W 3 to the DOA ‘ON’ position after connecting between DOA-100 and DOC-120.
b. Screen check
Press the '0' over 4 times and then LCD will be displayed within 3 sec.

3.2. OS ROM Version check


a. Screen check
a) Check the Ver. No and Date at Row 4 after input A01E.
C1 C2 C3 C4 C5 C6 C7 C8 C9 C10 C11 C12 C13 C14 C15 C16
R1 A C D = 2 7 [ 8 5 ] 5 0 %
R2 E 0 0 0 - 0 0 1 0 0 0 0 0 S
R3 1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
R4 V 0 1 . 0 0 9 9 / 0 7 / 1 5

b) Ex) Version 1.0, creation date is July 15th 1999.


c) Auto-reset about 2.5 sec later

3.3. DSP ROM Version check


a. Screen check
a) Check the Ver. No and Date at Row 4 after input A02E.
A C D = 2 7 [ 5 ] 5 0 %
E 0 0 0 - 0 0 1 0 0 0 0 0 S
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
V O 3 . 0 0 9 9 . 0 7
b) Ex) Version 3.00, creation date is July.1999.
c) Auto-reset about 2.5 sec later.
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 10/34


Overseas Support Team
Start - Up Date Mar. 20009

3.4. Floor height measurement operation


a. Preparation
Check if the E.STOP switch on E&I panel is ‘Off’ position.
b. Screen check
a) Verify that ACD = 09 after inputting "A12E" and press '3'. (This is maintained until
bottom Floor DL S/W is inputted.)
A C D = 0 9 0 0 F L 0 0 M
E 0 0 0 - 0 0 1 0 0 0 0 0 S
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
W E n a b l e K :
b) When ‘W Enable’ is displayed, Check if the S/W2 on DOC PCB to ‘Write’. Then FHM
MD is displayed on LCD.
c) When the car has reached the bottom floor and stopped by DL switch, press button #3,
the floor height measuring command.
d) The LCD screen state is as follows;
A C D = 0 A [ 0 F ] 1 5 M
E 0 0 0 - 0 0 1 0 0 0 0 U
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
F H M S T K :
e) When floor height measuring operation has started, FHM ST displays in row 4.
f) The car will travel until UL switch operates.
g) When floor height measuring has completed, LCD screen state is;
A C D = 0 A [ 1 6 ] 5 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
F H M P A S S K :
h) If FHM is successful, FHM PASS will display.

b. Observances
a) Enter 'FFFF' to clear the floor height measuring operation mode.
b) LCD Screen State is as follows;
A C D = 2 7 [ 1 6 ] 5 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
K :
c) ACD=27 will display in automatic mode.
d) If FHM has failed, the screen will be;
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 11/34


Overseas Support Team
Start - Up Date Mar. 20009

A C D = 0 9 [ ] 0 0 M
E 0 0 0 - 0 0 1 0 0 0 0 S
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
F H M F A I L K :
e) FHM Fail, which means floor height measuring has failure, will display.
f) The car will return to the bottom floor automatically.

3.5. Car call registration


a. Screen check
After inputting ‘A19E’, check if ‘CALL’ is displayed at 4th row.
b. Call
To make a service for 12th floor, key in ‘12E’ with decimal value.

3.6. Error TRACE Data read


a. Screen check
a) "TRC X-Y" will be displayed after input A23E
X : Traced Total Block No. Y : Present Block No.
Screen of A23E

A C D = 0 3 [ F ] 5 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
Item No. 0 0 : 5 0 0 0 = 0 8 2 4 1 6 2 2
T R C 5 3 0- 1 K :
Address

Total Block No. Traced Block No.

b) To read the higher Item No., input '0'. For the lower, input '8'
ex) If you input '0' two times on A23E initial screen, indicates as below. (Address will be
increase 4 per one)
c) LCD Screen
A C D = 0 3 [ F ] 5 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
0 2 : 5 0 0 8 = 0 0 0 0 0 0 9 1
T R C 3 - 1 K :
d) The displayed data and address are Hexadecimal value.
e) To read the higher block No., input '0'. For the lower, input '8'
ex) If you input '1' one time on A23E initial screen, indicates as below. (Address will be
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 12/34


Overseas Support Team
Start - Up Date Mar. 20009

increase 400 per one)


A C D = 0 3 [ F ] 5 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
0 0 : 5 4 0 0 = 0 8 2 4 1 6 2 2
T R C 3 - 2 K :
Note] Refer to the Trace Data reference Method
f) To cancel A23E mode, input 'FFFF'

3.7. Reset TRACE Data read


a. Screen check
a) The method is same as above A23E mode.
(Address start from 4400)
A C D = 0 3 [ F ] 5 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
0 0 : 4 4 0 0 = 0 8 2 4 1 6 2 2
T R C 3 - 1 K :
b) To cancel A24E mode, input 'FFFF'

3.8. Statistic Data read


a. Screen check
a) "STA DATA" will be displayed at Row 4 after input A25E.
LCD Screen.
A C D = 2 7 [ F ] 5 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S Note] Refer to the Trace Data reference Method
0 1 = 4 5 . 0 2 3 k M
S T A D A T A K :

Statistic data Number Statistic value

b) To read the higher data., input '0'. For the lower, input '8'
ex) If you input '0' two time on A25E initial screen, indicates as below.
LCD Screen.
A C D = 2 7 [ F ] 5 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
0 3 = 2 3 8 5 c n t
S T A D A T A K :

Statistic data Number Total running count

c) To clear the value of Data number, input 'CCCC'. But, numbers 1~9 are impossible to
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 13/34


Overseas Support Team
Start - Up Date Mar. 20009

clear.
ex) If you input "CCCC" at data number 12, the original data will be changed to '0'.
LCD Screen Note] The Units of statistic data
A C D = 2 7 [ F ] 5 0 % 1) Distance [km]
E 0 0 0 - 0 0 1 0 0 0 0 S
2) Time [hh:mm:ss]
1 2 = 0 c n t
C C C C 3) Count [cnt]
S T A D A T A K :
4) Rate [%]
d) To cancel A25E mode, input 'FFFF'.

3.9. Statistic Data Clear


a. Screen check
a) All statistic data in Data number 10~22 will be clear after input A26'E'.
A C D = 2 7 [ F ] 5 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
S T A D A T A R E S E T
[ E ] E N T E R K :
b) To cancel A26E mode, input 'FFFF' without clear.

3.10. Non power failure Reset Count read


a. Screen check
a) "ResetCnt" will be displayed at Row 4 after input A27E.
LCD Screen

A C D = 2 7 [ F ] 5 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
C n t = 0 0 1 1 1 0 1 1 3 3 1 the latest occurred reset (Nov. 1st 13:31)
R e s e t C n t K :

Non power failure Reset Count

b) To cancel A27E mode, input 'FFFF'.


c) Non power failure Reset Count will be cleared when the Log Clear (A43E) mode is
accomplished.
d) To clear the reset count when the maintenance finish by A43E.
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 14/34


Overseas Support Team
Start - Up Date Mar. 20009

3.11. Emergency stop Trace Data read


a. Screen check
a) "ESTPxx-yy" will be displayed at Row 4 after input A28E.
LCD Screen

A C D = 2 7 [ F ] 5 0 %
F L = 0 5 D A T A = 0 0 0 2
D A T E = 0 7 / 1 0 1 6 : 1 5
E S T P 0 2 - 0 1 K :

Total Traced data count The rank of the present Traced data count

b) Row 2 "FL=" Emergency stop occurred floor, "DATA=" The reason of the emergency stop,
it is related to TCD 164.
c) Row 3 "DATE=" Data of emergency stop occurred time. (Occur on July. 10th 16:15 at 5th
floor by safety circuit off)
d) 0' key for displaying the next data and before data is displayed by '8' key.
e) To clear all data has been stored, input 'CCCC' and auto-reset the mode.
f) 'FFFF' is reset this mode without data clear

3.12. SPEC ROM Read/Write


a. Preparation
Set E.STOP S/W to ‘Stop’ in E&I panel.
b. Screen check
a) Enter A31E and verify that ‘SPEC : DAT’ is displayed in row 4.
A C D = 0 3 [ F ] 0 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
S P E C : D A T K :
b) Enter the four-place address to read, using HEX.
Ex.) If '0068' is entered as address, LCD Screen State is;
A C D = 0 3 [ F ] 0 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
0 0 6 8 : x 0 1 K :
c) Address and data displayed is in a HEX.
'x' in 'x01' means HEX value and '01' actual data.
d) Address increment
To read the data of the address that is higher than 2 address, enter '0'.
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 15/34


Overseas Support Team
Start - Up Date Mar. 20009

e) Address decrement
To read the data of the address that is lower than 2 address, enter '8'.
f) Address input conversion
To read another address when reading data, enter 'BBB'.
LCD screen state
A C D = 0 3 [ F ] 0 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
A D D R : D A T K :

**Note**
ⓐ As SPEC data uses only the lower 8BIT of 16BIT, always use even number only.
ⓑ If an odd number is entered by mistake, it is considered as the appropriate even number.

g) Data protection cancel and data input


Read the data of the address to make correction and enter 'AAE'.
LCD Screen State
A C D = 0 3 [ F ] 0 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
0 0 6 8 : x 0 1 K : A A E

** Note**
In case ‘W enable’ is displayed on 4th row, check if SW2 is at write position. And key in ‘AAE’
again

h) Enter the two-place data to correct, using HEX.


ex)If the data to correct is '13' of decimal number, enter '0C'.
LCD Screen state
A C D = 0 3 [ F ] 0 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
0 0 6 8 : x 0 1 K : 0 C E
i) If writing data is failed, 'FAIL' is displayed, check following points when writing SPEC fails.
* Verify that E.STOP S/W to ‘Stop’ in E&I panel.
* Be sure to verify that SW2 is at ‘WE’.
* Do not operate SW2 while E/L is running.
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 16/34


Overseas Support Team
Start - Up Date Mar. 20009

* During SPEC write, addresses of 0x0000~3fff may be entered.


(Actual address is 50000~53FFF.)
* Address moves by 2 addresses during SPEC write/read.

3.13. TCD DISPLAY


a. Screen check
a) Enter A41E.
LCD Screen State
A C D = 2 7 [ F ] 0 0 %
E 1 2 1 - 9 0 0 7 2 0 2 0 1 8
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
T 0 4 - 0 1 K :
* Row 2 column 1~Row 2 column 7: Displays the TCD number and operation of the error
occurring first.
* Row 4 column 1~Row 4 column 4: Displays the number of all current errors.
* Row 2 column 1~Row 2 column 8: Displays ‘001’ that means the error occurred first.
b) TCD search
* To search all errors in their occurring sequence, enter '0'.
* To search current error with reverse, enter '8'.
c) To escape from the mode, enter FFFF.

3.14. Error log table


a. Screen check
a) Enter A42E.
LCD screen state
A C D = 2 7 [ F ] 0 0 %
E 1 2 1 - 9 0 0 7 2 0 2 0 1 8
C n t = 0 0 1 0 7 2 0 2 1 3 2
L O G 0 4 - 0 1 K :
* Row 2: Displays the TCD code and operation code.
* Row 2 column: 8th~16th : Break down time , 20 July 8:18 PM
* Row 3 : Break down times is counted and displayed as Cnt=xxx.
* Row 3 column: 8th~16th : Trouble cleared time , 20 July 9:32 PM
* Row 4 : Displays stored total TCD by LOG xx in Log Table.

b. TCD search
a) To search all errors in their occurring sequence, enter '0'.
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 17/34


Overseas Support Team
Start - Up Date Mar. 20009

b) To search current error with reverse, enter '8'


c) To search first error, enter ‘1’. But for the latest error, Enter ‘9’.
d) Only 16errors can be scanned.
e) Error log table structure is FIFO.

c. Change of display mode


a) Enter ‘C’ under break down time mode.
LCD screen state.
A C D = 2 7 [ 5 ] 0 0 0 M
E 1 2 1 - 9 0 0 5 0 % S
E 1 F 1 8 0 8 0 0 0 0 0 0
T R C 0 4 - 0 1 K :
* Row 1: Displays ACD code, floor and speed when the error occurred.
* Row 2 : Displays the TCD code and operation code.
* Row 2, column: 8th~16th : Car load and traveling direction
* Row 3 : Displays 24 of main input and 8 of output with hexa code
- C1~C6 8 4 2 1
C1 R5SX R5SY R5SC SURP
C2 C1ST C1BR DOLS LDS
C3 CDS LDU LDC LDD
C4 UL SD1U SD2U SD2D
C5 SDS1 DL SHOE RDMC
C6 Mainte M High R1MM CLS

- C8~C9 8 4 2 1
C7 R5CS SUPRS C1ST C1BR
C8 R2OP R2CL R1MM R2DM
# C of C1= 12(decimal) = 8+4 : R5SX and R5SY normal signals are inputted
# 1 of C2= 1(decimal) = 1 : LDC normal signal is inputted
# F of C3= 15(decimal) = 8+4+2+1 : CDS,LDU, LDC and LDD normal signal are inputted
# 7 of C8 = 7(decimal) = 8 : SUPRS,C1ST and C1BR normal signal are inputted
# 2 of C9 = 2(decimal) = 2 : R2CL normal signal is inputted
- Speed profile step when break down is occurred.
0 1 2 3 4 5 6 7 8

Bottom Bottom
Top of Top of Finish
Accele- of Normal Decele- of
Stop accele- decele- speed
ration accele- speed ration decele-
ration ration profile
ration ration
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 18/34


Overseas Support Team
Start - Up Date Mar. 20009

3.15. Error log table clear


a. Screen check
a) Enter A43E.
LCD screen state
A C D = 2 7 [ 8 ] 0 0 0 M
E 0 5 5 - 0 0 1 0 0 0 0 S
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
L O G C L E A R
※ If this mode is proceeded, breakdown contents and trace data are erased.
b) After displaying ‘ LOG CLEAR’ 4 seconds, it returns to normal mode (ACD=27).

3.16. DSP Memory read


a. Screen check
a) After entering A51E, verify row 4 is DSP ADDR.
LCD screen state
A C D = 2 7 [ 5 ] 0 0 0 M
E 0 0 0 - 0 0 1 0 0 0 0 S
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
D S P A D D R K :
b) After entering address to read to four places of Hex, enter 'E'.
Ex.) If '1000' address is entered,
LCD screen state
A C D = 2 7 [ 5 ] 0 0 0 M
E 0 0 0 - 0 0 1 0 0 0 0 S
1 0 0 0 = x 3 2 1 F A A 5 5
D S P A D D R K :
* ADDRESS and DATA are displayed in row 3.
* ADDRESS and DATA displayed are Hex.
* The 'x' in 'x321F AA55' means Hex value and '321F AA55' is actual DATA.
* DATA displayed is amount of 4 bytes of Hex.
c) ADDRESS INCREMENT
To read high address, enter '0'.
Data of the 4 upper address above already entered address is displayed.
d) ADDRESS DECREMENT
To read low address, enter '8'.
Data of the 4 lower address below already entered address is displayed.
e) If mode is released, enter FFFF.
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 19/34


Overseas Support Team
Start - Up Date Mar. 20009

3.17. DSP SPEC WRITE


a. Preparation
a) Set E.STOP S/W to ‘Stop’ in E&I panel.
b) Check if J1J S/W of DPC-11X PCB is set to 3rd and 4th pin to write data.
c) Check if SW2 of DOC-120 PCB is ‘WRITE’ position
[When DSP WRITE is not performed, ERROR occurs. (=TCD 60)]
b. Screed check
a) Enter A52E.
LCD screen state
A C D = 0 3 [ F ] 0 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
1 0 0 0 = x 3 2 1 F A A 5 5
D S P A D D R K :
b) Below characters are displayed in LCD row 4 in order.
DSP SPEC
WAIT
SUCCESS OR FAIL
c) If mode released, enter FFFF.

3.18. Manual LRT operation.


a. Preparation
Set E.STOP S/W to ‘RUN’ in E&I panel.
b. Screen check
a) Check that operation mode is ACD=29.
LCD screen status
A C D = 2 9 [ 5 ] 5 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
R O T M D K :
b) After checking car stop, press ‘3’ button to start
LCD screen status
A C D = 2 9 [ 5 ] 5 0 %
E 0 0 0 - 0 0 1 0 0 0 0 U
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
R O T S T K :
c) Then ‘ROT ST’ is displayed
d) After LRT operation, ‘LRT PASS’ is displayed
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 20/34


Overseas Support Team
Start - Up Date Mar. 20009

LCD screen status


A C D = 2 9 [ 5 ] 5 0 %
E 0 0 0 - 0 0 1 0 0 0 0 U
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
L R T P A S S K :
c. Caution
a) To escape from this mode, enter FFFF.
b) Then ACD=27 is displayed

3.19. No load point setting


a. Preparation
a) Set E.STOP S/W to ‘STOP’ in E&I panel.
b) Verify SW2 of DOC-120 PCB is at ‘WRITE’ position.
c) Verify R5SY (for checking safety circuit) RELAY of DOC-120 PCB is OFF.
b. Screen check
a) When the ‘NO LOAD POINT’ setting is completed by ‘A61E’, 'SUCCESS' is displayed in
row 4.
LCD screen state
A C D = 0 3 [ 1 6 ] 0 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
S U C C E S S K :
※ Reference
* If car is not at bottom floor, ‘MOV BOT’ is displayed at 4 row.
* If R5SY relay is not turned off, ‘R5SY OFF’ is displayed.
* If ‘W Enable’ is displayed, Check if the SW2 on DOC PCB is at ‘Write’ position.
b) When NO LOAD POINT setting failed, 'FAIL' is displayed.
LCD Screen State
A C D = 0 3 [ 1 6 ] 0 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
F A I L K :

If ‘FAIL’ is displayed on Ann, set NO LOAD POINT again.


Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 21/34


Overseas Support Team
Start - Up Date Mar. 20009

3.20. Full load point setting


a. Preparation
a) Bring the car to bottom floor, and load 100% weight (POT sensor)
b) Set E.STOP S/W to ‘Stop’ in E&I panel..
c) Verify SW2 of DOC-120 PCB is at WRITE position.
d) Verify R5SY (for checking safety circuit) RELAY of DOC-120 PCB is OFF.
b. Screen check
a) Key in ‘A62E’.
LCD Screen Status.
A C D = 0 3 [ 1 6 ] 0 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
L O A D ? K : 1 0 0 E
When ‘Load’ message is displayed at 4th row, key in the real load in car with decimal at 3
digits.
Ex) 100% →100E.
b) When the F’ULL LOAD POINT’ setting is finished by A62E, 'SUCCESS' is displayed in
row 4.
LCD screen state
A C D = 0 3 [ 1 6 ] 1 0 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
S U C C E S S K :
c) When the ‘FULL LOAD POINT’ setting failed, 'FAIL' is displayed.
LCD screen state
A C D = 0 3 [ 1 6 ] 0 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
F A I L K :

If ‘FAIL’ is displayed on Ann, set ‘FULL LOAD POINT’ again.

Note: No load setting must be always done before Full load setting.
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 22/34


Overseas Support Team
Start - Up Date Mar. 20009

3.21. Time setting mode


a. Cautions
Verify that E.STOP S/W of E&I panel is ‘Stop’ position
b. Screen check
a) After entering A69E, verify row 4 is RTC SET.
b) In row 3, date and time set are displayed.
c) To release MODE, enter 'FFFF' two times.
d) When changing date/time MODE, enter 'C'.
A C D = 0 3 [ F ] 0 0 %
a 9 / 1 7 / 0 7 / S U N
1 3 : 5 0 : 3 0
R T C S E T K :
c. Year, Month, day and a day of week set
a) For changing date, enter 'C', and verify that row 4 is displaying ‘DateSet’.
b) Enter Year, Month, Day to change in order.
Ex.) For entering Jan. 14. 2004(Wed) : Enter ‘04E,01E,14E,03E’
c) Check Year, Month, Day and days of week are entered to row 4.
D A T A S E T K : 0 4 E

0 4 / K : 0 1 E

0 4 / 0 1 / K : 1 4 E

0 4 / 0 1 / 1 4 K : 0 3 E

d) To release MODE, enter FFFF.


e) If setting Month & Day is wrong, key error is displayed.
Ex.) 13th month, 25 hour, etc.
d. Time set
a) For changing time, enter 'C' 2 times, and verify row 4 of LCD screen is displaying
‘TimeSet’.
T I M E S E T K :

b) Enter Hour, Minute, Second to change in order.


Ex.) For entering P.M 03:45, 30 sec: enter 15E, 45E, 30E. (24hour system)
c) Check hour, minute, second entered in row 4.
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 23/34


Overseas Support Team
Start - Up Date Mar. 20009

d) To release MODE, enter FFFF.

T I M E S E T K : 1 5 E

1 5 / K : 4 5 E

1 5 / 4 5 / K : 3 0 E

1 5 / 4 5 / 3 0 K : F F F F

3.22. Door condition check


a. Screen check
a) "INV DOOR" will be displayed at Row 4 after input A71E.
LCD Screen
A C D = 0 3 [ 1 ] 0 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
O : 0 0 0 I : 0 0 0 0 0 0 0 1
I N V D O O R K :

b) Row 3 Door output status


O:0 0 0
Disabled persons door signal ( '1' On )
Nudging signal output ( '1' On )
Door E&I PANELU Retry signal ( '1' On )

c) Row 3 Door input status

I:0 0 0 0 0 0 0 0
DOOR E&I PANELU WDT Signal( '1' Normal )
DOOR Error #1
DOOR Error #2
DOOR Error #3
MON Signal ( '1' Detection )
CLS Signal ( '1' Detection )
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 24/34


Overseas Support Team
Start - Up Date Mar. 20009

b. Door Error compounding


Door error3 Door error2 Door error1
Door position 0 0 1
Temperature 0 1 1
Voltage 1 0 1
Electric current 1 1 1
Command signal 1 1 0

3.23. Hall Check mode


a. Caution
This mode for checking the Hall B/T ID, Indicator, Hall call register lamp, Hall Lantern...
b. Screen check
"HALL CHK" will be displayed at Row 4 after input ‘A82E’. This mode is available under
attendant operation and OLS ON status.
LCD Screen State
A C D = 2 7 [ F ] 0 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
H A L L C H K K :

c. Check point
a) Dip S/W setting condition of Floor ID on DHG PCB. (HEX value)
b) DC 24V check between HA connector 3 and 4.
c) Check if light on of B/T lamp till 2~3sec after press the B/T under HA is connected
correctly.
d) Check if IND Digital, Direction lamp and additional lamp (Inspect, Full) are in due order
flickering.
e) Separates the HA connector from DHG PCB, when above 2,4 items are normal condition.
f) Repeats above ‘a ~ e’ items on each floors B/T.
g) Separates the HA connector from DHG PCB, when all indicators are turned off for
protection of PCB from electric shock.
h) To cancel A82E mode, input 'FFFF'.
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 25/34


Overseas Support Team
Start - Up Date Mar. 20009

3.24. Car Check mode


a. Caution
This mode for checking the DCL PCB ID in car side.
b. Screen check
a) "CAR CHECK" will be displayed at Row 4 after input A83E. This mode is available under
attendant operation and OLS ON status.
LCD Screen State
A C D = 2 7 [ F ] 0 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
C A R C H K K :

b) Displays the floor character (B2~B1, 1 ~ 10, 20, 30...) in due order.
c) Lights on the E&I PANELI lamp (UP, DOWN, FULL, OUT OF SERVICE) in due order.
d) Repeats above ‘a ~ b’ items per 6 sec.
e) To cancel A83E mode, input 'FFFF'.

3.25. POSI(PRS) TEST mode


a. Preparation
a) ERO switch of E&I panel must be at ‘ON’ position.
Measuring POSI must be performed at Hall through E&I panel.
b) Use UP/DOWN button of E&I panel to run car
c) In POSI measuring MODE, car must be in the other floor than top, bottom floors.
d) Car may not be in DOOR ZONE. Performing in any floor has the same result.
b. Screen check
a) After entering A85E, verify row 4 is PRS TEST. (Verify ACD = 04.)
LCD screen state
A C D = 0 4 [ F ] 0 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
P O S I T E S T K :
(a) If car is in DOOR ZONE, 'POSI TEST' is displayed.
(b) If car is out of DOOR ZONE, 'UP Drive' is displayed just after 'POSI TEST' displayed.
Move car according to directions of LCD screen.
b) When car is in DOOR ZONE.
(a) Use UP/DOWN button of E&I panel to run car to move out of DOOR ZONE.
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 26/34


Overseas Support Team
Start - Up Date Mar. 20009

(b) If car moves out of DOOR ZONE, 'UP DRIVE' meaning up-running is displayed.
LCD screen state
A C D = 0 4 [ F ] 0 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
U P D R I V E K :
(c) If UP DRIVE is displayed, Press Up button in E&I panel
(d) Measure PRS characteristics passing by DOOR ZONE.
(e) After measuring finished, 'DN Drive' meaning reverse in car direction is displayed.
LCD screen state
A C D = 0 4 [ F ] 1 5 M
E 0 0 0 - 0 0 1 0 0 0 0 S
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
D N D R I V E K :
(f) If 'DN DRIVE' is displayed, Press Down button in E&I panel.
(g) Measure PRS characteristics passing by DOOR ZONE.
(h) If car is out of DOOR ZONE, 'STOP' message is displayed.
A C D = 0 4 [ F ] 1 5 M
E 0 0 0 - 0 0 1 0 0 0 0 S
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
S T O P K :
c) If measuring PRS is finished. 'POSI FIN' is displayed in row 4.
LCD screen state
A C D = 0 4 [ F ] 0 0 %
E 0 0 0 - 0 0 1 0 0 0 0 S
1 1 0 0 1 1 0 0 0 0 1 1 1 0 1
P O S I F I N K :
d) If measuring PRS is failed, 'FAIL' is displayed in row 4.
Then, re-perform measuring PRS test after releasing MODE(FFFF),
e) To release MODE, enter FFFF.

3.26. Car load mode


a. Screen check
a) Check if “WD:XXX%’ is displayed at row 4 after entering ‘A86E’
b) ‘XXX’ is present load in car that is calculated by system.

LCD screen State


Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 27/34


Overseas Support Team
Start - Up Date Mar. 20009

A C D = 2 7 [ F ] 0 4 %
E 0 0 0 - 0 0 1 0 0 0 0 S
1 4 F 0 0 0 0 0 0 0 0 0
W D : 0 0 4 % K :
(a) 4 numbers at 3rd row are AD converter values that are inputted from each load sensor
through channel. In case one of POTENSIOMETER is applied, the left one is first input.
(b) The message ‘WD’ at 4th row is calculated data to real load
b. To release MODE, enter FFFF.

3.27. 110% Function test mode


a. Screen Check
a) The message "110-> " will be displayed at Row 4 after input A87E.
LCD Screen State
A C D = 2 7 [ F ] 0 4 %
E 0 0 0 - 0 0 1 0 0 0 0 S
1 4 F 0 0 0 0 0 0 0 0 0
1 1 0 - > K :
b) The invalid data for input on "110->XX" is from 0 to 99.
ex) When you try to 110% load test with 20% of car load, input "20E".
"110->20" will be displayed at Row 4 after input "20E".
c) If the load is heavier than displayed data, light in "FULL" lamp, BZ operation and door
close holding.
d) To cancel A87E mode, input 'FFFF'.

3.28. 110% Cut Mode


* 110% Cut Mode is a function that E/L can running one time with 110% load in car under
superintendent inspect.
a. Screen Check
a) The message "110% CUT" will be displayed at Row 4 after inputting A88E. Then it will
disappear after about 2.5 sec passed.
A C D = 2 7 [ F ] 0 4 %
E 0 0 0 - 0 0 1 0 0 0 0 S
1 4 F 0 0 0 0 0 0 0 0 0
1 1 0 % C U T K :
b) The mode will be auto-canceled after car running start.
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 28/34


Overseas Support Team
Start - Up Date Mar. 20009

3.29. SDS Check Mode


a. Screen Check
a) The message "SDS CHK" will be displayed at 4th Row after inputting ‘A89E’.
LCD Screen
A C D = 2 7 [ F ] 0 4 %
1 U : 0 0 0 0 1 D : 1 7 3 9
S/W operates distance (unit:mm)
2 U : 0 0 0 0 2 D : 2 6 7 3
S D S C H K K :

b) Check of SDS operates position


-> If the car is not reached at top floor, 1U/2U data will be show "0000".
After running to top floor, will be shows measured data as below;
A C D = 2 7 [ F ] 0 4 %
1 U : 1 7 3 4 1 D : 1 7 3 9
2 U : 2 6 6 8 2 D : 2 6 7 3
S D S C H K K :

c) Compulsion deceleration function test


** Caution: Testing without passenger and under door closed (DMC S/W ON).

Key in "3" for the Up direction test after the


A C D = 2 7 [ F ] 0 4 %
1 U : 1 7 3 4 1 D : 1 7 3 9 car is located at below than middle floor.
2 U : 2 6 6 8 2 D : 2 6 7 3 Check if the car deceleration is changing
S D S C H K K : 3 well by SDS operates.
Deceleration running till UL S/W operates)

Key in "7" for the Down direction test after


A C D = 2 7 [ F ] 0 4 % the car is located at above than
1 U : 1 7 3 4 1 D : 1 7 3 9
middle floor.
2 U : 2 6 6 8 2 D : 2 6 7 3
Check if the car deceleration is changing
S D S C H K K : 7
well by SDS operates.
(Deceleration running till DL S/W operates)
d) To cancel A89E mode, input 'FFFF'.
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 29/34


Overseas Support Team
Start - Up Date Mar. 20009

3.30. CRT Data Reset Mode


All recorded CRT control data reset in Main B/D
(CRT control data: Service floor data & Door timer)
a. Screen Check
A C D = 2 7 [ F ] 0 4 %
E 0 0 0 - 0 0 1 0 0 0 0 S
1 1 0 0 1 0 0 0 0 0 1 1 1 0 0
C R T R E S E T K :

The message "CRT Reset" will be displayed at Row 4 after inputting A90E. Then it will
disappear after about 2.5 sec passed.
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 30/34


Overseas Support Team
Start - Up Date Mar. 20009

4. Trace Data reference Method


4.1. Mode for Error Log Table reference
: Key in ‘A42E’ under normal mode
4.2. Key function
‘0’ : Log Table Index Increment
‘8’ : Log Table Index Decrement
‘1’ : Scanning of the first occurred TCD
‘9’ : Scanning of the last occurred TCD
‘C’ : Displays TCD occurrence time ÅÆ Displays Trace Data (Toggle)
‘FFFF’ : Escape from Error Log Table reference mode

Key usage is same as under trace data displaying mode.

a. Occurrence time displaying

Breakdown time
Each 2 digit display Month,
A C D = 2 7 [ 1 2 ] 1 0 % day, hour, minute
E 2 2 3 - 0 0 0 5 1 5 1 4 2 0 May 15th14H 20M
C n t = 3 0 0 0 0 0 0 0 0
L O G 1 1 - 0 1 K : Trouble solved time

Displays Occurrence sequence: The first breakdown of all 11 trouble

Breakdown times : Initialized when log table be cleared

Trouble code
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 31/34


Overseas Support Team
Start - Up Date Mar. 20009

b. Trace Data Displaying

Lift position when breakdown

Operation mode when breakdown Running speed when breakdown

Car run direction


A C D = 0 3 [ 1 0 ] 6 0 M
Current when breakdown
E 2 2 3 - 0 0 1 0 0 % U
reference TCD
C 1 F 0 0 0 0 0 0 0 0 0 0
T R C 1 1 - 0 1 K : Load when
breakdown

Displays Log Data


Sequence and Trace Additional
Data reference mode information
Step Profile About each
Output contact
Step when breakdown
Input contact when breakdown
break down
when breakdown Refer to B.
Refer to C.
Refer to A.

a) Input contact Bit Table

23 22 21 20 19 18 17 16 15 14 13 12

R5SX R5SY R5SC SUPRS C1ST C1BR DOLS LDS CDS LDU LDC LDD

11 10 9 8 7 6 5 4 3 2 1 0

Maint
UL SD1U SD2U SD2D SD1D DL SHOE RDMC High R1MM CLS
M
* SUPRS : DSP RUN Flag * R1MM : MSK operation signal input
* Maint M : Machine room Maint signal Input * High : Car high switch input

b) Output Contact Bit Table


7 6 5 4 3 2 1 0
R5SC SUPRS C1ST C1BR R2OP R2CL R1ML R2DM
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 32/34


Overseas Support Team
Start - Up Date Mar. 20009

c) Speed Profile Step


0 1 2 3 4 5 6 7 8
Smooth Smooth Smooth Smooth
wave in wave in wave in wave in Finish
Steady Normal Steady
beginnin finishing beginning finishing
Stop
g part
accelerat
part
speed
part
decelerat
part
speed
ion running ion Profile
accelerat accelerati decelerati decelerat
ion on on ion

4.3. Additional Information Flag Table


th th
13 ~ 16 column of 3rd Row
TCD 5 10 56 70 74 92 96 97 98 99 114
Servo Hexa High DOC Gear ΦB ON CLS CLS R5SC OFF
0

deci- mode B/D miss CAR error


I/O mal R7RD T/M ΦA IN CDS CDS C1ST ON
1

value miss CAR error


Car Rated Norma LDS LDS C1BR
2

speed l (CAR)
Mode Norma OLS OLS R2LD
l
(Russi
3
Additional Information Bit

a m/c
room)
Encoder
7 6 5 4

Hall OLS
Motor LDC
CRT IGBT SD1U
Error CT turn SD1D
Duplex RPD M/C
magnet room
8

quantity maint
ANN Floor Norma
9

Number l (CAR)
Dispat
C B A

ch
Spec

SVC
F E D

device
The displayed data is

opened, the relevant

Input Contact status

Input Contact status

Input Contact status

If an iput is detected
In case a SPEC data

under breakdown(If

under breakdown(If

under breakdown(If
Set:

The set bit displays

relevant bit is set..


detection position
number of interrupt

Over speed under

In case a phase is
relevant bit is set.
Remark

as an error, the
The Set bit is a
reason of WDT

activated, :01)

acti ated 01)


activated, :01)
is wrong, the
detection

bit is set
normal
vector.
Bit: 0
Bit
Remark

TCD
F E D C B A 9 8 7 6 5 4 3 2 1 0

ON
OFF

error
error
116
FOD

ON
OFF

error
error
117
Overseas Support Team

If a switch is off error, the


relevant bit is set
SD2D

SD1U
SD2U
SD1D
119

ration
Comp
ulsion
decele
Counted speed in
operation control part
when the error detected.
126
Hexadecimal
Value (m/min)

Load status when error


detected
value
Start - Up

(15th bit : minus load)


130
Hexadecimal
MUSE ED Elevator

Input Contact status under


LDS
CLS

RDZ
OLS
CDS

breakdown(If activated, :01)


132

Input Contact status under


LDS
CLS

RDZ
OLS
Date
Part.

CDS
Page

breakdown(If activated, :01)


133
Ctrl. No.

Input Contact status under


LDS
CLS

RDZ
OLS
CDS

breakdown(If activated, :01)


134

Input Contact status under


Cut
Cut
LDS
CLS
33/34

OLS
CDS

breakdown(If activated, :01)


Safety
135
Mar. 20009
Annunciator

Running
MUSE ED-SR-02-0
Part. Annunciator
MUSE ED Elevator Ctrl. No. MUSE ED-SR-02-0

FOD Page 34/34


Overseas Support Team
Start - Up Date Mar. 20009

TCD 136 164 168 171 188 190 191~195 196 238
Mode R5SX Off Low 500mm CLS Param Door Re Parameter
error speed level eter Error1 open Error
detection error SPEC time is
0

Error exceed
ed
ARD R5SY Off Over CDS Off Door Speed
error speed Error Error2 Error
1

detection
Over R5SC Off LDS Down Door Temperat
speed On Error3 ure error
2

error
Run LDS Off OLS Up On LDC error
3

Error error
Floor CDS Off Speed Over
height error speed
sum under detection
4

power
failure
Runni On Car Direction Comm.
ng ON error Error
CUT under
5
Bit

power
failure
Safety In Car SDS Battery
CUT ON Over Fault
6

Speed
Error Back up Direction
detection RAM error
7

error
Noraml
8

Off
C1BR Off
A 9

C1ST Off
DL is
B

detected
UL is
C

detected
E D
F

In case the Bit 0 is reset,


Photo shoe input time is
breakdown(If activated, :01)
Input Contact status under

I The Set bit is a reason of


The Set bit is a reason of

The Set bit is a reason of

The Set bit is a reason of

The Set bit is a reason of

The Set bit is a reason of


Refer to Door Manual
Remark

exceeded.
breakdown

breakdown

breakdown

breakdown

breakdown

breakdown