Background
Today, with the accelerating of industrialization in the world; the demands
of energy consumption had been increased tremendously. And most of the
industries operators are now seriously looking into energy-saving in all
means of equipment they use.
Since 1980, Fuji Electric FA has become a global specialist dedicated to the
design, manufacture and supply of AC Frequency Inverter.
The global requirements for high performance, multifunction, protective
features, easy operation, easy maintenance and energy-saving have
increased to inverter systems.
In response to customer driven priorities for a simple, easy-to-use, energy-
saving and economical Inverter, Fuji Electric FA has designed a new range
of world-class product “FRENIC-Eco” series especially for the HVAC system.
Concept
The FRENIC-Eco has the functions best-suited for the HVAC (Heating,
Ventilating and Air Conditioning) market*, featuring small installation
space, simple operation, wide model variations, and support international
standards. The FRENIC-Eco contributes to energy-saving, labor-saving and
system integration of variable torque load including fans and pumps,
resulting in a total cost reduction.
*Chiller unit, Air handling unit (AHU), Fan coil unit (FCU), etc.
–2–
Capacity
Applicable IP20 enclosure IP54 enclosure
motor (NEMA1) (NEMA12)
rating 3-phase 3-phase 3-phase 3-phase
(kW) 200V 400V 200V 400V
0.75 0.75 0.75 0.75 0.75
1.5 1.5 1.5 1.5 1.5
2.2 2.2 2.2 2.2 2.2
3.7 3.7 3.7 3.7 3.7
5.5 5.5 5.5 5.5 5.5
7.5 7.5 7.5 7.5 7.5
11 11 11 11 11
15 15 15 15 15
18.5 18.5 18.5 18.5 18.5
22 22 22 22 22
30 30 30 30 30
37 37 37 37 37
45 45 45 45 45
55 55 55 55
75 75 75 75
90 90* 90 90
110 110* 110
132 132
160 160
200 200
220 220
280 280*
315 315*
355 355*
400 400*
450 450*
500 500*
*Available soon
–3–
• Principle of energy-saving of inverter
<Selection of motor capacity in equipment design and energy-saving policy of inverter>
[%] [%]
Power consumption (motor capacity)
100 100
Airflow controlled Flow rate controlled
by damper by valve
Energy-saving effect
Energy-saving effect
Damper reduction rate B
50 50
Flow rate controlled
by inverter
Airflow controlled
by inverter
0 0
Operation frequency Power supply frequency Actual lift rate A Operation frequency Power supply frequency
fRUN [Hz] fS [Hz] (Loss in actual lift) fRUN [Hz] fS [Hz]
Frequency (airflow) [Hz]([%]) Frequency (flow rate) [Hz]([%])
–4–
• User-friendly keypad
Multi-function keypad 7-segment LED
- The optional simple remote keypad is - Enlarged 5-digit display
also prepared. - Power monitor (power consumption,
cumulative watt-hours, cumulative
Simple remote control electricity cost, etc.)
- Remote control is realized, using LAN - Maintenance data display (cooling fan
cable. running time, main circuit capacitor
- Optional 1-, 3- and 5-meter straight capacity, cumulative inverter running
cables are prepared. time, cumulative motor running time,
No. of startup times, etc.)
–5–
Slow flowrate stopping function for stopping the fan or pump at speed lower than the A faulty state in the speed command can
lower limit is added to the lower limiter for keeping the lowest speed, to realize be detected to issue a signal.
further energy-saving in conjunction with PID control.
Broken
belt
Calculated torque accident! All 30kW or smaller capacity models are
Low torque now equipped with a longer-life cooling
detection level
t
M fan.
Do (U-TL) Power
supply
Detects the temperature of the heat sink
0 Time Digital output signal automatically to turn the cooling fan on
or off.
–6–
110
In FRENIC-Eco Series inverters developed exclusively for the
100
Current Component
100
Percentage
Harmonic percentage content(%)
90
content
Order 80
Without With Without DCR
DCR DCR 70
With DCR
5 82.8 32.5 60
7 67.7 17.7 50
11 34.8 8.7 40
13 20.7 6.2 30
17 4.5 5.2 20
Note: 19 5.0 3.9 10 Total Harmonic Distrortion(THD):
A measured example where 23 4.5 3.7 0 less than 40% (with DCR)
FRN30F1S-4A was used. 25 3.2 2.8 5 7 11 13 17 19 23 25
Order
Serial Communication
RS-485, Johnson Control (Metasys) N2*1, Siemens Protocol P1*1, Lon-Works*2... (Capable to connect to BMS)
Modbus-RTU, Field Bus-compatible DeviceNet*2, PROFIBUS-DP*2, Modbus PLUS*2, CC-Link*2 *1Available as separate series *2Option
Various protective functions back assured operation of the warning), stall prevention, alarm relay output (for any fault),
inverter. memory error, keypad communication error, CPU error, option
Overcurrent protective function, short-circuit protection, communication error, option error, operation error, tuning
ground fault protection, overvoltage protection, undervoltage error, RS-485 communication error, RS-485 communication
protection, input phase loss protection, output phase loss error (optional), data saving upon undervoltage, retry function,
protection, overheating protection, overload protection, surge protection, command loss detection function, momentary
external alarm input, fuse blown, charging circuit fault power failure protection function, active drive
detection, motor protection (electronic thermal relay function,
protection provided with PTC thermistor, overload early
Support for Galvanic Isolation The common terminals on the control circuit are
The power supply PC board is isolated from other control PC isolated from each other to reduce the effects of noise.
board, thereby assuring safety. The common terminals (terminal 11, CME and CMY) for digital
input signals, transistor output signals and analog input signals
are isolated from each other so that the noise immunity of the
signals is improved.
–7–
Technical Data
Applicable Rated Rated output Applicable Rated Required power
Inverter type motor rating current capacity Inverter type motor rating current supply capacity
(kW) (A) (kVA) (kW) (A) (kVA)
FRN0.75F1S-2 0.75 4.2 1.6 FRN0.75F1S-4 0.75 2.5 1.9
FRN1.5F1S-2 1.5 7.0 2.6 FRN1.5F1S-4 1.5 3.7 2.8
FRN2.2F1S-2 2.2 10 3.8 FRN2.2F1S-4 2.2 5.5 4.1
FRN3.7F1S-2 3.7 16.5 6.2 FRN3.7F1S-4 3.7 9.0 6.8
FRN5.5F1S-2 5.5 23.8(22.5) 8.3 FRN5.5F1S-4 5.5 12.5 9.5
FRN7.5F1S-2 7.5 31.8(29) 11 FRN7.5F1S-4 7.5 16.5 12
FRN11F1S-2 11 45 (42) 16 FRN11F1S-4 11 23 17
FRN15F1S-2 15 58 (55) 21 FRN15F1S-4 15 30 22
FRN18.5F1S-2 18.5 73 (68) 25 FRN18.5F1S-4 18.5 37 28
FRN22F1S-2 22 85 (80) 30 FRN22F1S-4 22 44 33
FRN30F1S-2 30 114 (107) 40 FRN30F1S-4 30 59 44
FRN37F1S-2 37 140 (130) 49 FRN37F1S-4 37 72 54
FRN45F1S-2 45 170 (156) 59 FRN45F1S-4 45 85 64
FRN55F1S-2 55 211 (198) 75 FRN55F1S-4 55 105 77
FRN75F1S-2 75 276 (270) 102 FRN75F1S-4 75 139 105
FRN90F1S-2 * 90 322 (320) 121 FRN90F1S-4 90 168 128
FRN110F1S-2 * 110 390 (384) 146 FRN110F1S-4 110 203 154
FRN132F1S-4 132 240 182
note: •A box ( ) in the above table replaces A or K depending on 221
FRN160F1S-4 160 290
the enclosure.
FRN200F1S-4 200 360 274
A: South East Asia and Oceania
K: Korea and Taiwan FRN220F1S-4 220 415 316
FRN280F1S-4 * 280 520 396
•If the ambient temperature is 40°C or more and the carrier
FRN315F1S-4 * 315 585 445
frequency is set at 3kHz or more, reduce the load so that
the output current is less than the value in the parenthesis. FRN355F1S-4 * 355 650 495
FRN400F1S-4 * 400 740 584
*Available soon FRN450F1S-4 * 450 840 640
FRN500F1S-4 * 500 960 731
Common Specifications
Power supply specifications Digital output signal
•Input power supply •Number of points: 3
Three-phase 200V 200 to 240V ±10% •Max. voltage level: 0 to 15V (input impedance: 22kΩ)
Three-phase 400V 380 to 480V ±10% •Max. current level: 0 to 30mA (input impedance: 250Ω)
(For 37kW or more, 380 to 440V ±10%) Relay output signal
•Power supply frequency: 50/60Hz •Number of points: 2 (30a, 30b, 30c and Y5A, Y5B)
•Power factor: 0.9 (with DC Reactor) •Contact capacity: 250V AC, 0.3A, cosØ=0.3 or 48V DC, 0.5A
Output ratings Analog output signal
•Output voltage: 0 to 240V, 0 to 460V •Number of points: 2
•Output frequency: 0 to 120Hz •Voltage output: Up to two measuring instruments with 0 to 10V DC
Output frequency (input impedance: 10kΩ) can be connected.
•Max. output frequency: 25 to 120Hz •Current output: A measuring instrument with 500Ω max. can be
•Base frequency: 25 to 120Hz connected.
•Starting frequency: 0 to 60Hz Others
•Carrier frequency: 0.75 to 15kHz, 0.75 to 10kHz, 0.75 to 6kHz •Enclosure: IP20 or IP54
•Accuracy: •Vibration:
Analog setting: Within ±0.2% of max. output frequency (at 25°C±10°C) Smaller than 75kW: 3mm (vibration width): 2 to 9Hz, 9.8m/s2: 9 to
Keypad setting: Within ±0.01% of max. output frequency (at -10 to +50°C) 20Hz, 2.0m/s2: 20 to 55Hz, 1.0m/s2: 55 to 200Hz
•Resolution : 90kW or more: 3mm (vibration width): 2 to 9Hz, 2.0m/s2: 9 to 55Hz,
Analog setting: 1/1,000 of max. output frequency 1.0m/s2: 55 to 200Hz
Keypad setting: 0.01Hz (99.99Hz or less), 0.1Hz (100.0Hz or more) •Ambient temperature: -10 to 50°C (Upon side-by-side installation
Torque characteristics without clearance: -10 to 40°C)
•Overload capability: 120% (1min.) of rated output current •Ambient humidity: 5 to 95%RH (No condensation)
•Starting torque: Up to 100% (50% or more at factory default setting) •Altitude: 1,000m or less
•Acceleration torque: 100% •Ambient temperature for storage: -25 to 65°C
•Overload torque: 120% •Ambient humidity for storage: 5 to 95%RH (No condensation)
Digital input signal EMC Directive supported as standard
•Number of points: 7 •IP54 (Built-in EMC filter and DC REACTOR)
(Where the function codes are assigned to all the terminals including •IEC61800-3
terminals FWD and REV.) •Model 15kW or less with integral EMC filter include filter for 2nd
•Voltage level: 0 to 24V environment (200V input class) or Group 1 class A (400V input class)
•Max. input voltage: 27V Product compliance
Analog input signal •Low Voltage Directive 73/23/EEC with supplements
•Number of points: 1 •EMC Directive 89/336/EEC with supplements (Applying)
•Max. voltage level: 0 to 15V (input impedance: 22kΩ) •Quality assuarance systems ISO9001 and Environmental ISO14001
•Max. current level: 0 to 30mA (input impedance: 250Ω) •CE, UL and cUL approvals
–8–
External Dimensions
150 163
7 136 7 101.5 61.5
2x 6 5
7
Power supply
Type
voltage
FRN0.75F1S-2
FRN1.5F1S-2
260
246
Three-phase
FRN2.2F1S-2
200V
FRN3.7F1S-2
FRN5.5F1S-2
FRN0.75F1S-4
7
6
Three-phase FRN1.5F1S-4
45 30 30
400V FRN2.2F1S-4
23.5
PULL
FRN3.7F1S-4
3x 27
FRN5.5F1S-4
note: A box ( ) in the above table replaces A or K depending on
the enclosure.
98.9
W D
12 W1 12 D1 D2
2x 10 11.2
11
voltage
H
W W1 W2 W3 W4 H H1 H2 H3 D D1 D2 A B
FRN7.5F1S-2
27 34
FRN11F1S-2 220 196 63.5 46.5 46.5 260 238 141.7 16 118.5 96.5
Three-phase FRN15F1S-2 136.7 21
200V 215
FRN18.5F1S-2 34 42
67 58 58 166.2 2
FRN22F1S-2 250 226 400 378 85 130
11
10 FRN30F1S-2 — — — — — — —
A FRN7.5F1S-4
141.7 16 27 34
W2 W3 W4 FRN11F1S-4 220 196 63.5 46.5 46.5 260 238 118.5 96.5
2x B Three-phase FRN15F1S-4 136.7 21
400V 215
FRN18.5F1S-4 34 42
H3
166.2 2
PULL
the enclosure.
A: South East Asia and Oceania
K: Korea and Taiwan
2x 10 W D3 D
W1 D1 D2
12
FRN37F1S-4
H
–9–
External Dimensions
210
(40) 65 65 40 3x 6 225
2.4
15
Power supply
7
Type
voltage
FRN0.75F1B-2
FRN1.5F1B-2
Three-phase
FRN2.2F1B-2
200V
470
486
500
FRN3.7F1B-2
FRN5.5F1B-2
FRN0.75F1B-4
Three-phase FRN1.5F1B-4
400V FRN2.2F1B-4
(15)
(7)
6
FRN3.7F1B-4
FRN5.5F1B-4
note: A box ( ) in the above table replaces A or K depending on
the enclosure.
A: South East Asia and Oceania
K: Korea and Taiwan
W
Power supply Dimensions (mm)
(W2) W1 W2 2x C 280 voltage
Type
2.4 W W1 W2 H H1 H2 H3 H4 D C S
H4
H2
FRN7.5F1B-2
FRN11F1B-2 300 200 50 600 580 550 280
4x S FRN15F1B-2
Lifting hole 10 25 10 15
Three-phase FRN18.5F1B-2
200V FRN22F1B-2 350 290 30 800 780 750
320
FRN30F1B-2
FRN37F1B-2 400 360 20 1100 1073 1030
15 35 15 18
H1
H3
FRN45F1B-2
FRN7.5F1B-4
FRN11F1B-4 300 200 50 600 580 550 280
FRN15F1B-4
10 25 10 15
FRN18.5F1B-4
FRN22F1B-4 350 290 30 800 780 750
Three-phase
FRN30F1B-4 320
400V
(H2)
(H4)
C FRN37F1B-4
400 360 20 1100 1073 1030
FRN45F1B-4
FRN55F1B-4 15 35 15 18
450 1170 1140 1100 350
FRN75F1B-4 400 25
FRN90F1B-4 450 1280 1250 1210 360