Advanced Three Phase


Electronic Revenue Meter
Genius Series - Class 0.5S

PRODUCT INFORMATION

Utilizing the same advanced meter design and


firmware platform as the original Mk6, the new Mk6N
meter updates this platform to address new IEC
standards and to incorporate an updated power
supply and input protection technology utilized by our
latest range of energy meters.

KEY FEATURES

AMI READY HIGH LARGE LARGE MEASURE UPGRADEABLE TAMPER SCRIPT


ACCURACY DATA STORAGE LCD DISPLAY EVERYTHING PROOF EXTENSIONS
Mk6N Genius Series - Class 0.5S

Advanced Three Phase


Electronic Revenue Meter
SPECIFICATIONS

Accuracy Communications Options Time Clock Equipment Failure


• Class 0.5S • ANSI Type 2 Optical Port (ANSI • Accuracy (internal) within 30 seconds Alarms (EFAs)
• IEC62052-11, IEC62053-22 C12.18) or IEC 62056-21 (IEC 61107) per month A single user defined alarm condition
IEC62053-23 Optical FLAG Port • Backup time of 2 years without power (via extensions) is available plus
• RS232 (RTS/CTS and DTR/DCD) • Backup utilizing either lithium battery pre-programmed alarms based
Measurement Modes on numerous:
• RS485 (2 or 4 wire multidrop) or optional SuperCap
• Single Phase (3 Circuits) • Mains synchronised or internal crystal • Self-Checks
• SCADA
• 3 Phase 3 Wire time keeping. Mains synchronised • Tamper and wiring checks
• Modems (PSTN/GPRS/GSM/C DMA)
• 3 Phase 4 Wire reverts to internal crystal on loss of
• Internal Modem Power Supply These Alarms Can:
voltage on all phases
Measured Energy Values • MV-9OTM Compatible • Turn on LED, LCD indicator or relay
• 3 Elements, 4 Quadrants • PPP / GPRS Data Storage output
• Import/Export Wh, varh and VAh • MODBUS (Configuration, TOU Data and Load • Record an event in the event log
• Absolute Wh, varh and VAh • DNP3 Survey Data) • Trigger an event such as a remote
• Phase A, B, C or Total • Master / Slave arrangement with up to • FlashRAM alarm, dial an emergency number,
31 ‘Slave’ meters accessed through • Battery backed up RAM send an SMS to a programmable
Other Measured and one ‘Master’ gateway meter number or send alarm messages via
Displayed Values Sag / Swell GPRS to a programmable server
Voltage • 5 Cycle Resolution
• W, var, VA
• Operating Range of 57.7/100 - 230/400V Extensions for
• True RMS Voltage (3 Phase) • Records time / date / phase / duration
Customer Applications
• True RMS Current (3 Phase) • Burden of < 10VA per phase @ Vn and worst excursion
(3 Phase) • Programmable trigger levels The Mk6N inherits the ability to use
• Power Factor Extensions to increase the functionality
• Frequency of 45 to 65Hz
• Frequency LCD Display of the standard metering platform. A
• Phasor Angles Current • 16 Character by 2 line simple yet powerful scripting language
alphanumeric display allows complex register manipulations
Load Survey / Load Profile • CT Range: 1(4)A, 5(10)A
to be performed that can create
• Short time over-current of 20 times • Programmable units, multipliers and
• NEM Compliant customized functions within the
‘max for 0.5 seconds leading zeros
• Standard 400 day-channel capacity at meter without the need for a firmware
• Burden of less than 0.5VA • Up to 64 user definable upgrade. EDMI is always developing
30 minute intervals
per phase screen displays new extensions and we offer custom
• Optional additional storage to increase
• Displays any available extension creation for specific customer
to over 2,500 day-channel capacity at Auxiliary Supply Options meter parameter needs. Contact us to find out more
30 minute intervals
• 240V, 110V Aux Only (other voltages about Extensions for the Genius range
• Up to 50 Channels available on special order) Optional Functions of meters
• Per survey interval programmable from • Quality of Supply (QOS) features
1 second to 1 month Pulsing Inputs / Outputs Examples of currently available
• Waveform Capture
• Multiple independent surveys • Maximum of 8 I/O with up to 8 outputs Extensions for EDMI Genius
• Harmonic analysis to the Energy Meters:
• Energy, instantaneous readings and (2 standard) or 6 inputs 50th harmonic
pulsing inputs as potential survey • Output voltage - 5 - 220V DC, • Send SMS at percentage of
• THD Measurement
channel sources 12 - 240V AC maximum demand
• Fundamental energy measurement
• Ability to store average / minimum / • Output current of 0.1A maximum • Average power factor for billing period
maximum values over interval duration • Output pulse width 2 output Software • LCD menu system
for individual channels independent LEDs of lms to 250ms • Magnetic tamper detection
• EDMI EziView software available for
Time of Use • Programmable output polarity programming and reading of meter • Power factor control extension
• Input Voltages of 5, 12, 48, 110, 240V (Runs on Windows 98/ME/NT/ • Maximum demand control of loads via
• 8 rates plus unified rate 2000/XP)
AC / DC pulsing outputs
• Up to 12 separate import and • EziView also allows offline
• Time synchronised (optional) • Average voltage / current / unbalance,
export registers configuration of tariff programs and THD etc.
• Up to 200 programmable Environmental all meter parameters, for later upload • Voltage Sag / Swell or Power Outage
special days • Operating Range of -10 to +60°C to meters
• Voltage Quality
• Daily, Weekly, Monthly, Yearly, Special • Storage Range of -40 to +85°C
Dimensions • Send SMS / GPRS Alarm on
• 13 or more previous periods
Equipment Failure Alarm
• Block or Rolling Maximum Demand • 292.5mm (L) x 175mm (W) x 94mm (D)
• Detect Individual Phase VT Failures
• Time of Maximum Demand
• Configurable Billing Reset Button