Documente Academic
Documente Profesional
Documente Cultură
FIGURE 16.3 Positive-, negative-, and zero sequence representation of three-phase vectors.
16.3.1.1 Conclusion
Transformer sequence impedances are described here.
Positive-sequence impedance:
Z1 5 Z% (transformer percentage impedance)
Negative-sequence impedance:
Z2 5 Z% (transformer percentage impedance)
Zero-sequence impedance:
Refer to Fig. 16.10.
Cable sequence impedances are described here.
Positive-sequence impedance:
Z1 can be calculated or determined by testing.
Power System Fault Analysis Chapter | 16 167
Negative-sequence impedance:
Z2 5 Z1
Zero-sequence impedance:
Z0 . Z1
Motor sequence impedances are described here.
Power System Fault Analysis Chapter | 16 169
Positive-sequence impedance:
X1 5 subtransient reactance
Negative-sequence impedance:
X2 5 X1
Zero-sequence impedance:
Z0 5 0
Transmission line sequence impedances are described here.
Positive-sequence impedance:
Z1 can be calculated
170 Practical Power System and Protective Relays Commissioning
Negative-sequence impedance:
Z2 5 Z1
Zero-sequence impedance:
Z0 can be calculated or determined by testing.
Synchronous generator sequence impedances are now described.
The positive-sequence impedance of a generator is approximately equal
to: Xs (steady state reactance).
The negative-sequence impedance of a generator is approximately equal
to: Xsv (sub transient reactance).
The zero-sequence impedance of a generator is approximately equal to:
XL (leakage reactance).
FIGURE 16.16 The different sequence voltage phasors for different fault types.
Refer to Fig. 16.16 for the different sequence voltage phasors for differ-
ent fault types.
For example, a 240 MVA SGT has a name plate rating of 20%;
20 3 100
Rating on 100 MVA 5
240
5 8:33%
2. MVA
Fault rating and fault in-feed are expressed in MVA. This is related to
percent impedance by the following:
Percent impedance 5 10; 000=MVA if the base is 100 MVA
For example, if the fault infeed at a particular substation is 35,000
MVA, then the source impedance, expressed as a percentage on 100
MVA base, will be 0.286.
Similarly, if it is calculated that the impedance to a particular fault is
2% (on 100 MVA), then the fault infeed will be 5000 MVA.
To derive the fault current (If), either:
a. Use If 5 fault infeed (MVA)/(kV 3 1.732) kA
b. Or If 5 10,000/(kV 3 1.732 3 Z%) kA
3. Ohmic impedance
To convert percent impedance to primary ohmic impedance:
Taking Z% 5 percent impedance on 100 MVA
104
Z% 5
MVA
V2
MVA 5
Z
104 3 Z
Z% 5
V2
constructed, starting from an infinite source and leading to the fault posi-
tion. All values of impedance used to construct the network must refer to
the same MVA base. For consistency, always use the percent impedance to
a base of 100 MVA.
If the fault being considered is a three-phase fault, then there will only be
positive-sequence quantities present, therefore only positive-sequence impe-
dances need to be considered.
The impedance to the fault can now be calculated, and from this the fault
current can then be calculated (IF). The fault current in other parts of the net-
work can be derived using network analysis techniques, with the fault current
at the relay point.
If the protection relay is an impedance measuring type (i.e., distance pro-
tection) then it may only be necessary to calculate the impedance to the
fault.
Example 1:
Three-phase balanced fault (Fig. 16.17)
Calculations:
Total impedance 5 Z 5 0.4 1 1.5 1 8.3 5 10.2
MVAF 5 10,000/Z% 5 10,000/10.2 5 980 MVA
IF 5 MVAF/(kV 3 1.732) 5 980/(132 3 1.732) 5 4.286 kA
Example 2:
Single phase-to-earth fault (Fig. 16.18)
Calculations:
Ztotal 5 10.2 1 (10.2 1 ((0.4 1 4 1 8.2) 3 12.8)/(0.4 1 4 1 8.2 1 12.8))
5 26.25%
I1 5 I2 5 I0 5 10,000/(Z%) 5 10,000/26.25 5 381 MVA
IF 5 I1 1 I2 1 I0 5 3 3 381 5 1143 MVA
IF 5 MVAF/kV 3 1.732 5 1143/(132 3 1.732) 5 4.999 kA
Power System Fault Analysis Chapter | 16 177
Example 3:
Phase-to-phase fault (Fig. 16.19)
Calculations:
Ztotal 5 10.2 1 10.2 5 20.4%
MVAF 5 10,000/20.4 5 490 MVA
IF 5 I1 5 I2 5 490 MVA
IY 5 IB 5 1.732 3 490 5 849 MVA