Rotor Earth Fault Protection of Alternator or Generator


Last updated March 15, 2020 by Electrical4U

The rotor of an alternator is wound by field winding. Any single earth fault occurring on the field winding or in the
exciter circuit is not a big problem for the machine. But if more than one earth fault occur, there may be a chance of short
circuiting between the faulty points on the winding. This short circuited portion of the winding may cause unbalance
magnetic field and subsequently mechanical damage may occur in the bearing of the machine due to unbalanced
rotation.

Hence it is always essential to detect the earth fault occurred on the rotor field winding circuit and to rectify it for normal
operation of the machine. There are various methods available for detecting rotor earth fault of alternator or generator.
But basic principle of all the methods is same and that is closing a relay circuit through the earth fault path.

Ad
Free Templates
Start collaborating in real time with an online design tool that's smart, simple and fast.

Moqups

LEARN MORE

There are mainly three types of rotor earth fault protection scheme used for this purpose.

1. Potentiometer method
2. AC injection method
3. DC injection method

https://www.electrical4u.com/rotor-earth-fault-protection-of-alternator-or-generator/ 1/7
9/13/2020 Rotor Earth Fault Protection of Alternator or Generator | Electrical4U

Let us discuss the methods one by one.

Potentiometer Method of Rotor Earth Fault Protection in Alternator


The scheme is very simple. Here, one resistor of suitable value is connected across the field winding as well as across
exciter. The resistor is centrally tapped and connected to the ground via a voltage sensitive relay.

NEW

As it is seen in the figure below, any earth fault in the field winding as well as exciter circuit closes the relay circuit
through earthed path. At the same time the voltage appears across the relay due to potentiometer action of the resistor.

This simple method of rotor earth fault protection of alternator has a big disadvantage. This arrangement can only sense
the earth fault occurred in the any point except the center of the field winding.

From the circuit it is also clear that in the case of earth fault on the center of the field circuit will not cause any voltage to
be appeared across the relay. That means simple potentiometer methods of rotor earth fault protection, is blind to the
faults at the center of the field winding. This difficulty can be minimized by using another tap on the resistor somewhere
else from the center of the resistor via a push bu on. If this push bu on is pressed, the center tap is shift and the voltage
will appear across the relay even in the event of central arc fault occurs on the field winding.

AC Injection Method of Rotor Earth Fault Protection in Alternator


Here, one voltage sensitive relay is connected at any point of the field and exciter circuit. Other terminal of the voltage
sensitive relay is connected to the ground by a capacitor and secondary of one auxiliary transformer as shown in the
figure below.

https://www.electrical4u.com/rotor-earth-fault-protection-of-alternator-or-generator/ 2/7
9/13/2020 Rotor Earth Fault Protection of Alternator or Generator | Electrical4U

Here, if any earth fault occurs in the field winding or in the exciter circuit, the relay circuit gets closed via earthed path
and hence secondary voltage of the auxiliary transformer will appear across the voltage sensitive relay and the relay will
be operated.

The main disadvantage of this system is, there would always be a chance of leakage current through the capacitors to the
exciter and field circuit. This may cause unbalancing in magnetic field and hence mechanical stresses in the machine
bearings.

Another disadvantage of this scheme is that as there is different source of voltage for operation of the relay, thus the
protection of rotor is inactive when there is a failure of supply in the AC circuit of the scheme.

DC Injection Method of Rotor Earth Fault Protection in Alternator


The drawback of leakage current of AC injection method can be eliminated in DC Injection Method. Here, one terminal
of DC voltage sensitive relay is connected with positive terminal of the exciter and another terminal of the relay is
connected with the negative terminal of an external DC source. The external DC source is obtained by an auxiliary
transformer with bridge rectifier. Here the positive terminal of bridge rectifier is grounded.

https://www.electrical4u.com/rotor-earth-fault-protection-of-alternator-or-generator/ 3/7
9/13/2020 Rotor Earth Fault Protection of Alternator or Generator | Electrical4U

It is also seen from the figure below that at the event of any field earth fault or exciter earth fault, the positive potential of
the external DC source will appear to the terminal of the relay which was connected to the positive terminal of the
exciter. In this way the rectifier output voltage appears across the voltage relay and hence it is operated.

Want More Electrical Knowledge?


Enter your email below to receive FREE informative articles on Electrical & Electronics Engineering

Your name

Your email address

Join (it’s free)

About Electrical4U

Electrical4U is dedicated to the teaching and sharing of all things related to electrical and electronics engineering.

...
Related Articles

Stator Earth Fault Protection of… Inter Turn Fault Protection of…

https://www.electrical4u.com/rotor-earth-fault-protection-of-alternator-or-generator/ 4/7

S-ar putea să vă placă și