Project: ETAP Page: 1

Location: 18.1.1C Date: 05-15-2019

Contract: SN: BISAINGPE

Engineer: Study Case: GRD1 Filename: GROUND CERRO VERDE

Electrical Transient Analyzer Program

Ground Grid Systems

Finite Element Method

Number of Ground Conductors: 17

Number of Ground Rods: 8

Total Length of Ground Conductors: 324.00 m

Total Length of Ground Rods: 24.00 m

Total Computational Time: 0.00 minutes

Frequency: 60.0

Unit System: Metric

Project Filename: GROUND CERRO VERDE

Output Filename:
S:\GP\4-Proyectos\207-SMCV\0129A\3Ingenieria\Documentos\06ELECTRICA\01TRABAJO\
SPT\0.3 kA_SISTEMA DE PUESTA A TIERRA.GR1S
Project: ETAP Page: 2

Location: 18.1.1C Date: 05-15-2019

Contract: SN: BISAINGPE

Engineer: Study Case: GRD1 Filename: GROUND CERRO VERDE

Ground Grid Input Data

System Data

Short-Circuit Current Fault Duration (Seconds)

Total Sf Cp Tf Tc Ts Extended
Ambient Fault Division Projection for for Sizing for Plot Boundary
Freq. Weight Temp. Current Factor Factor Total Fault Ground Available Step Length
Hz kg °C kA X/R % % Duration Conductors Body Current m m
60.0 50 40.00 0.300 10.00 100.0 100.0 0.50 0.50 0.50 1.0 0.00

Soil Data

Surface Material Upper Layer Soil Lower Layer Soil

Resistivity Depth Resistivity Depth Resistivity


Material Type ohm.m m Material Type ohm.m m Material Type ohm.m

Clean limestone 3000.0 0.150 Moist soil 300.0 1.15 Moist soil 1400.0

Material Constants
Resistivity of Thermal
r Factor Fusing Ground Conductor Capacity
Conductivity @ 20 °C K0 @ Temperature @ 20°C Per Unit Volume
Conductor/Rod Type % 1/°C 0 °C °C micro ohm.cm J/(cm³.°C)

Conductor Copper, annealed soft-drawn 100.0 0.00393 234.0 1083.0 1.72 3.42

Rod Copper, annealed soft-drawn 100.0 0.00393 234.0 1083.0 1.72 3.42

Conductor Data

From To
Length Insulated Cost
Label Type mm² X Y Z X Y Z m Yes/No $/m

7.12 Copper, annealed soft-drawn 120 51.25 7.12 0.76 51.25 23.27 0.76 16.15 NO 10.00

C58 Copper, annealed soft-drawn 120 10.00 10.00 0.76 42.55 10.00 0.76 32.55 NO 10.00

C60 Copper, annealed soft-drawn 120 10.00 15.10 0.76 40.70 15.10 0.76 30.70 NO 10.00

C61 Copper, annealed soft-drawn 120 10.00 20.80 0.76 40.70 20.80 0.76 30.70 NO 10.00

C62 Copper, annealed soft-drawn 120 10.00 26.42 0.76 40.70 26.42 0.76 30.70 NO 10.00

C63 Copper, annealed soft-drawn 120 10.00 10.00 0.76 10.00 26.42 0.76 16.42 NO 10.00

C64 Copper, annealed soft-drawn 120 19.00 10.00 0.76 19.00 26.42 0.76 16.42 NO 10.00

C65 Copper, annealed soft-drawn 120 25.50 10.00 0.76 25.50 26.42 0.76 16.42 NO 10.00

C67 Copper, annealed soft-drawn 120 32.00 10.00 0.76 32.00 26.42 0.76 16.42 NO 10.00

C68 Copper, annealed soft-drawn 120 40.70 10.00 0.76 40.70 26.42 0.76 16.42 NO 10.00

C70 Copper, annealed soft-drawn 120 40.70 23.27 0.76 42.55 23.27 0.76 1.85 NO 10.00

C72 Copper, annealed soft-drawn 120 42.55 7.12 0.76 42.55 23.27 0.76 16.15 NO 10.00

C79 Copper, annealed soft-drawn 120 59.25 7.12 0.76 59.25 23.27 0.76 16.15 NO 10.00

C80 Copper, annealed soft-drawn 120 42.55 7.12 0.76 59.25 7.12 0.76 16.70 NO 10.00

C81 Copper, annealed soft-drawn 120 42.55 13.42 0.76 59.25 13.42 0.76 16.70 NO 10.00
Project: ETAP Page: 3

Location: 18.1.1C Date: 05-15-2019

Contract: SN: BISAINGPE

Engineer: Study Case: GRD1 Filename: GROUND CERRO VERDE

Conductor Data

From To
Length Insulated Cost
Label Type mm² X Y Z X Y Z m Yes/No $/m

C82 Copper, annealed soft-drawn 120 42.55 19.40 0.76 59.25 19.40 0.76 16.70 NO 10.00

C83 Copper, annealed soft-drawn 120 42.55 23.27 0.76 59.25 23.27 0.76 16.70 NO 10.00

Rod Data

Diameter From To
Length Insulated Cost
Label Type cm X Y Z X Y Z m Yes/No $/Rod

R10 Copper, annealed soft-drawn 2.000 10.00 10.00 0.15 10.00 10.00 3.15 3.00 NO 100.00

R11 Copper, annealed soft-drawn 2.000 10.00 26.42 0.15 10.00 26.42 3.15 3.00 NO 100.00

R12 Copper, annealed soft-drawn 2.000 40.70 26.42 0.15 40.70 26.42 3.15 3.00 NO 100.00

R17 Copper, annealed soft-drawn 2.000 32.00 10.00 0.15 32.00 10.00 3.15 3.00 NO 100.00

R5 Copper, annealed soft-drawn 2.000 59.25 7.12 0.15 59.25 7.12 3.15 3.00 NO 100.00

R6 Copper, annealed soft-drawn 2.000 42.55 7.12 0.15 42.55 7.12 3.15 3.00 NO 100.00

R8 Copper, annealed soft-drawn 2.000 59.25 23.27 0.15 59.10 23.27 3.15 3.00 NO 100.00

R9 Copper, annealed soft-drawn 2.000 52.30 23.27 0.15 52.30 23.27 3.15 3.00 NO 100.00

Cost

Conductor Rod

Total Total Length Cost Total Total Length Cost Total Cost
No. m $ No. m $ $
17 324 3238.50 8 24 800.00 4038.50
Project: ETAP Page: 4

Location: 18.1.1C Date: 05-15-2019

Contract: SN: BISAINGPE

Engineer: Study Case: GRD1 Filename: GROUND CERRO VERDE

Ground Grid Summary Report

Rg GPR Maximum Touch Potential Maximum Step Potential


Ground Ground
Resistance Potential Rise Tolerable Calculated Coordinates (m) Tolerable Calculated Coordinates (m)

ohm Volts Volts Volts % X Y Volts Volts % X Y


14.998 4617.3 748.9 406.1 54.2 59.3 8.4 2503.6 473.1 18.9 10.00 26.40

Total Fault Current 0.300 kA Reflection Factor (K): -0.818

Maximum Grid Current: 0.308 kA Surface Layer Derating Factor (Cs): 0.792

Decrement Factor (Df): 1.026