Sunteți pe pagina 1din 4

ANIMALA PSS_33kV LINE-2 (D2) CONTROL CABLE SCHEDULE & TERMINATION

SOURCE DESTINATION
10% Tolerance TOTAL
Core MEASURED
S.No CABLE ID TYPE FUNCTION on Measured ESTIMATED GLAND TYPE NOTES
EQUIPMENT Term No. Ferrule No. Ferrule Term No. EQUIPMENT LENGTH (mt) Length (mt) LENGTH (mt)
1S1 1S1(R) 1 1S1(R) TB1:1
1S2 1S2(R) 2 1S2(R) TB1:2
6c 4.0mm2
1S3 1S3(R) 3 1S3(R) TB1:3
1 D2 C01 D2CT1_R D2CT1_JB Cu/PVC/SWA/PVC CT CONNECTIONS 5 0.5 6.00 9
2S1 2S1(R) 4 2S1(R) TB2:1
CABLE
2S2 2S2(R) 5 2S2(R) TB2:2
2S3 2S3(R) 6 2S3(R) TB2:3

1S1 1S1(Y) 1 1S1(Y) TB1:4


1S2 1S2(Y) 2 1S2(Y) TB1:5
6c 4.0mm2
1S3 1S3(Y) 3 1S3(Y) TB1:6
2 D2 C02 D2CT1_Y D2CT1_JB Cu/PVC/SWA/PVC CT CONNECTIONS 3 0.3 4.00 9
2S1 2S1(Y) 4 2S1(Y) TB2:4
CABLE
2S2 2S2(Y) 5 2S2(Y) TB2:5
2S3 2S3(Y) 6 2S3(Y) TB2:6

1S1 1S1(B) 1 1S1(B) TB1:7


1S2 1S2(B) 2 1S2(B) TB1:8
6c 4.0mm2
1S3 1S3(B) 3 1S3(B) TB1:9
3 D2 C03 D2CT1_B D2CT1_JB Cu/PVC/SWA/PVC CT CONNECTIONS 5 0.5 6.00 9
2S1 2S1(B) 4 2S1(B) TB2:7
CABLE
2S2 2S2(B) 5 2S2(B) TB2:8
2S3 2S3(B) 6 2S3(B) TB2:9

TB1:1 C10 1 C10 X01:10


4c 4.0mm2
TB1:4 C30 2 C30 X01:12 PROTECTION CT
4 D2 C04 D2CT1_JB D2CRP Cu/PVC/SWA/PVC 60 6 66.00 8
TB1:7 C50 3 C50 X01:14 CONNECTIONS
CABLE
TB1:10 C70 4 C70 X01:16

TB2:3 D10 1 D10 X01:1


4c 4.0mm2
TB2:6 D30 2 D30 X01:3 METERING CT
5 D2 D01 D2CT1_JB D2CRP Cu/PVC/SWA/PVC 60 6 66.00 8
TB2:9 D50 3 D50 X01:5 CONNECTIONS
CABLE
TB2:10 D70 4 D70 X01:7

TB3:8 E10 1 E10 X02:1


4c 2.5mm2
TB3:9 E30 2 E30 X02:2 PT METERING
6 D2 E01 33kV BUS PT-1_JB D2CRP Cu/PVC/SWA/PVC 29 2.9 32.00 3
TB3:10 E50 3 E50 X02:3 CONNECTIONS
CABLE
TB3:11 E70 4 E70 X02:4

TB1:8 E110 1 E110 X02:5


4c 2.5mm2
TB1:9 E130 2 E130 X02:6 PT PROTECTION
7 D2 E02 33kV BUS PT-1_JB D2CRP Cu/PVC/SWA/PVC 29 2.9 32.00 3
TB1:10 E150 3 E150 X02:7 CONNECTIONS
CABLE
TB1:11 E170 4 E170 X02:8

16A MCB:Ph H1/D2 1 H1/D2 X03:15 2c 2.5mm2 D2SFDB TERMINALS TO BE VERIFIED AT


8 D2 H01 D2SFDB D2CRP AC SUPPLY 55 5.5 61.00 2
16A MCB:N H2/D2 2 H2/D2 X03:16 Cu/PVC/SWA/PVC SITE

6A MCB:Ph H1/52 1 H1/52 303 2c 2.5mm2 D2SFDB TERMINALS TO BE VERIFIED AT


9 D2 H02 D2SFDB D252 MOTOR AC SUPPLY 11 1.1 13.00 2
6A MCB:N H2/52 2 H2/52 304 Cu/PVC/SWA/PVC SITE

6A MCB:Ph M1/52 1 M1/52 301 2c 2.5mm2 D2SFDB TERMINALS TO BE VERIFIED AT


10 D2 H03 D2SFDB D252 MOTOR AC SUPPLY 11 1.1 13.00 2
6A MCB:N M2/52 2 M2/52 302 Cu/PVC/SWA/PVC SITE

16A MCB:R H1/89A 1 H1/89A TB2:2


4c 2.5mm2
16A MCB:Y H2/89A 2 H2/89A TB2:3 D2SFDB TERMINALS TO BE VERIFIED AT
11 D2 H04 D2SFDB D289A Cu/PVC/SWA/PVC MOTOR AC SUPPLY 11 1.1 13.00 3
16A MCB:B H3/89A 3 H3/89A TB2:4 SITE
CABLE
16A MCB:N H20/89A 4 H20/89A TB2:1

16A MCB:R H1/89B 1 H1/89B TB2:2


4c 2.5mm2
16A MCB:Y H2/89B 2 H2/89B TB2:3 D2SFDB TERMINALS TO BE VERIFIED AT
12 D2 H05 D2SFDB D289B Cu/PVC/SWA/PVC MOTOR AC SUPPLY 20 2 22.00 3
16A MCB:B H3/89B 3 H3/89B TB2:4 SITE
CABLE
16A MCB:N H20/89B 4 H20/89B TB2:1

Page 1 of 4
ANIMALA PSS_33kV LINE-2 (D2) CONTROL CABLE SCHEDULE & TERMINATION
SOURCE DESTINATION
10% Tolerance TOTAL
Core MEASURED
S.No CABLE ID TYPE FUNCTION on Measured ESTIMATED GLAND TYPE NOTES
EQUIPMENT Term No. Ferrule No. Ferrule Term No. EQUIPMENT LENGTH (mt) Length (mt) LENGTH (mt)
DC SUB DB-1 16A MCB:+ve J1/D2 1 J1/D2 X03:1 2c 2.5mm2 DC SUB DB-1 TERMINALS TO BE
13 D2 J01 D2CRP DC SUPPLY 9 0.9 10 2
(BCR-D1) 16A MCB:-ve J2/D2 2 J2/D2 X03:2 Cu/PVC/SWA/PVC VERIFIED AT SITE

DC SUBDB-2 16A MCB:+ve J3/D2 1 J3/D2 X03:5 2c 2.5mm2 DC SUB DB-2 TERMINALS TO BE
14 D2 J02 D2CRP DC SUPPLY 9 0.9 10 2
(BCR-D1) 16A MCB:-ve J4/D2 2 J4/D2 X03:6 Cu/PVC/SWA/PVC VERIFIED AT SITE

TB:2 K101 1 M2 X04:11


TB:1 K113 2 M1 X04:12
TB:9 K114 3 M9 X04:13
TB2:5 K115 4 H4A X04:15
10c 2.5mm2
TB1:15 K116 5 K116 X04:17
15 D2 K01 D289A D2CRP Cu/PVC/SWA/PVC ISOLATOR INDICATION 54 5.4 60.00 4
TB1:16 K117 6 K117 X04:18
CABLE
TB1:2 K118 7 K118 X04:20
TB:11 K17 8 M11 X04:199
TB:12 K18 9 M12 X04:202
SPARE 10 SPARE

TB1:5 1K801 1 K1 X04:143


TB1:6 1K802 2 K70 X04:144
TB1:7 1K803 3 K3 X04:145
TB1:8 1K804 4 K4 X04:146
10c 2.5mm2
TB1:11 1K805 5 K11 X04:147
16 D2 K02 D289A D2CRP Cu/PVC/SWA/PVC ISOLATOR CONTROL 54 5.4 60.00 4
TB1:13 1K806 6 K13 X04:148
CABLE
TB1:12 1K807 7 K14 X04:149
SPARE 8 SPARE
SPARE 9 SPARE
SPARE 10 SPARE

TB:2 K101 1 M2 X04:24


TB:1 K121 2 M1 X04:25
TB:9 K122 3 M9 X04:26
TB2:5 K123 4 H4A X04:28
10c 2.5mm2
TB1:15 K124 5 K124 X04:30
17 D2 K03 D289B D2CRP Cu/PVC/SWA/PVC ISOLATOR INDICATION 66 6.6 73.00 4
TB1:16 K125 6 K125 X04:31
CABLE
TB1:2 K126 7 K126 X04:33
TB:11 K18 8 M11 X04:203
TB:12 K19 9 M12 X04:207
SPARE 10 SPARE

TB1:5 2K801 1 K1 X04:150


TB1:6 2K802 2 K70 X04:151
TB1:7 2K803 3 K3 X04:152
TB1:8 2K804 4 K4 X04:153
10c 2.5mm2
TB1:11 2K805 5 K11 X04:154
18 D2 K04 D289B D2CRP Cu/PVC/SWA/PVC ISOLATOR CONTROL 66 6.6 73.00 4
TB1:13 2K806 6 K13 X04:155
CABLE
TB1:12 2K807 7 K14 X04:156
SPARE 8 SPARE
SPARE 9 SPARE
SPARE 10 SPARE

TB3:2 K101 1 M2 X04:34


TB3:1 K127 2 M1 X04:35
TB3:9 K128 3 M9 X04:36
TB3:17 4K801 4 K1 X04:167
10c 2.5mm2 EARTH SWITCH
TB3:18 4K802 5 K2 X04:168
19 D2 K05 D257B D2CRP Cu/PVC/SWA/PVC INDICATION & 61 6.1 68.00 4
TB3:19 4K803 6 K3 X04:169
CABLE INTERLOCK
TB3:20 4K804 7 K3A X04:170
SPARE 8 SPARE
SPARE 9 SPARE
SPARE 10 SPARE

Page 2 of 4
ANIMALA PSS_33kV LINE-2 (D2) CONTROL CABLE SCHEDULE & TERMINATION
SOURCE DESTINATION
10% Tolerance TOTAL
Core MEASURED
S.No CABLE ID TYPE FUNCTION on Measured ESTIMATED GLAND TYPE NOTES
EQUIPMENT Term No. Ferrule No. Ferrule Term No. EQUIPMENT LENGTH (mt) Length (mt) LENGTH (mt)
TB:2 K101 1 M2 X04:65
TB:1 K151A 2 M1 X04:66
TB:9 K152A 3 M9 X04:67
TB2:5 K153A 4 H4A X04:68
10c 2.5mm2
TB1:15 K154A 5 K154A X04:69
20 D2 K06 D189E D2CRP Cu/PVC/SWA/PVC ISOLATOR INDICATION 31 3.1 35.00 4
TB1:16 K155A 6 K155A X04:70
CABLE
TB1:2 K156A 7 K156A X04:71
SPARE 8 SPARE
SPARE 9 SPARE
SPARE 10 SPARE

TB1:5 1K301 1 K1 X04:182


TB1:6 1K302 2 K70 X04:183
TB1:7 1K303 3 K3 X04:184
TB1:8 1K304 4 K4 X04:185
10c 2.5mm2
TB1:11 1K305 5 K11 X04:186
21 D2 K07 D189E D2CRP Cu/PVC/SWA/PVC ISOLATOR CONTROL 31 3.1 35.00 4
TB1:13 1K306 6 K13 X04:187
CABLE
TB1:12 1K307 7 K14 X04:188
SPARE 8 SPARE
SPARE 9 SPARE
SPARE 10 SPARE

354 K101 1 U43 X04:1


353 K105 2 U41 X04:2
355 K106 3 U45 X04:3
351 K107 4 K111 X04:4
418 K108 5 M5 X04:5
410 K109 6 K13 X04:6
14c 2.5mm2
414 K110 7 K21 X04:7
22 D2 K08 D252 D2CRP Cu/PVC/SWA/PVC CB INDICATION 52 5.2 58.00 5
408 K111 8 K77 X04:9
CABLE
406 K112 9 K73A X04:10
SPARE 10 SPARE
SPARE 11 SPARE
SPARE 12 SPARE
SPARE 13 SPARE
SPARE 14 SPARE

203 K8 1 K3 X04:208
204 K16 2 K4 X04:209
208 K17 3 K11 X04:210
209 K19 4 K4 X04:211
201 K1 5 J1 X04:214
202 K2 6 J2 X04:215
14c 2.5mm2
253 K3 7 K1 X04:216 TC-1 CLOSE &
23 D2 K09 D252 D2CRP Cu/PVC/SWA/PVC 52 5.2 58.00 5
254 K4 8 K54 X04:217 CONTROL
CABLE
256 K5 9 K55 X04:218
259 K6 10 K52 X04:219
260 K7 11 K54 X04:220
SPARE 12 SPARE
SPARE 13 SPARE
SPARE 14 SPARE

251 K51 1 J3 X04:223


252 K52 2 J4 X04:224
263 K53 3 K61 X04:225
264 K54 4 K67 X04:226
10c 2.5mm2
265 K55 5 K69 X04:227
24 D2 K10 D252 D2CRP Cu/PVC/SWA/PVC TC-2 CONTROL 52 5.2 58.00 4
261 K56 6 K63 X04:228
CABLE
262 K57 7 K67 X04:229
SPARE 8 SPARE
SPARE 9 SPARE
SPARE 10 SPARE

Page 3 of 4
ANIMALA PSS_33kV LINE-2 (D2) CONTROL CABLE SCHEDULE & TERMINATION
SOURCE DESTINATION
10% Tolerance TOTAL
Core MEASURED
S.No CABLE ID TYPE FUNCTION on Measured ESTIMATED GLAND TYPE NOTES
EQUIPMENT Term No. Ferrule No. Ferrule Term No. EQUIPMENT LENGTH (mt) Length (mt) LENGTH (mt)
X03:9 3K101 1 3K101 X03:22
4c 2.5mm2
X03:10 3K202 2 3K202 X03:23 LBB SUPPLY / LBB
25 D2 K11 D1CRP D2CRP Cu/PVC/SWA/PVC 8 0.8 9.00 3
X04:196 K329 3 K329 X04:196 INTERTRIP
CABLE
SPARE 4 SPARE

X04:52 K904 1 K146 X04:237 2c 2.5mm2 ETHERNET SWITCH


26 D2 K12 D2CRP D1CRP 8 0.8 9 2
SPARE 2 SPARE Cu/PVC/SWA/PVC FAIL

X04:49 K905 1 K101 X04:230


4c 2.5mm2
X04:50 K907 2 K145 X04:231 DC FAIL/BCPU
27 D2 K13 D2CRP D1CRP Cu/PVC/SWA/PVC 8 0.8 9.00 3
X04:80 K909 3 K113A X04:233 FAIL/BCPU MCB TRIP
CABLE
X04:82 K911 4 K114A X04:235

NOTE
1 D2CT1_R Cable BOQ Lugs BOQ
1) LOOP 2S3 TO S' GLAND
CABLE TYPE Total Length (Mts) Total GLANDS Lug Size Total Lugs
TYPE
2 D2CT1_Y 1 10pr 1.0mm2 Shield/Armour CABLE 0 0 1.0 Sq.mm Lug 0
1) LOOP 2S3 TO S' 2 2c 2.5mm2 Cu/PVC/SWA/PVC CABLE 116 12 2.5 Sq.mm Lug 288
3 4c 2.5mm2 Cu/PVC/SWA/PVC CABLE 117 12 4.0 Sq.mm Lug 52
3 D2CT1_B 4 10c 2.5mm2 Cu/PVC/SWA/PVC CABLE 462 16 6.0 Sq.mm Lug 0
1) LOOP 2S3 TO S' 5 14c 2.5mm2 Cu/PVC/SWA/PVC CABLE 116 4 16.0 Sq.mm Lug 0
6 19c 2.5mm2 Cu/PVC/SWA/PVC CABLE 0 0 25.0 Sq.mm Lug 0
4 D2CT1_JB 7 2c 4.0mm2 Cu/PVC/SWA/PVC CABLE 0 0 35.0 Sq.mm Lug 0
1) LOOP TB1:3,6,9,10 AND CONNECT TO EARTH 8 4c 4.0mm2 Cu/PVC/SWA/PVC CABLE 132 4 70.0 Sq.mm Lug 0
2) LOOP TB2:1,4,7,10 AND CONNECT TO EARTH 9 6c 4.0mm2 Cu/PVC/SWA/PVC CABLE 16 6 200.0 Sq.mm Lug 0
10 10c 4.0mm2 Cu/PVC/SWA/PVC CABLE 0 0 400.0 Sq.mm Lug 0
5 D289A 11 4c 6.0mm2 Cu/PVC/SWA/PVC CABLE 0 0
1) LOOP TB:2,10, TB2:6, TB1:3,14 12 4c 16.0mm2 Al/XLPE/SSA/PVC CABLE 0 0
2) LOOP TB1:9,10 13 1c 25.0mm2 Cu/PVC/SSA/PVC CABLE 0 0
14 3.5c 70.0mm2 Al/XLPE/SSA/PVC CABLE 0 0
6 D289B 15 3.5c 400.0mm2 Al/XLPE/SSA/PVC CABLE 0 0
1) LOOP TB:2,10, TB2:6, TB1:3,14
2) LOOP TB1:9,10

7 D257B
1) LOOP TB3:2,10

8 D252
1) LOOP 354,356,352,419,411,415,407,405

9 D2CRP
1) X01:2,4,6,8,9 TERMINALS DISCONNECTING LINKS TO
BE KEPT OPEN
2) X01:11,13,15,17,18 TERMINALS DISCONNECTING LINKS
TO BE KEPT OPEN
3) LOOP X04:230,232
4) DISCONNECT CONNECTION FROM MCB-19(1) TO
X03:22
5) DISCONNECT CONNECTION FROM MCB-19(3) TO
X03:23

10 GENERAL
1) ALL CABLE LENGTHS TO BE VERIFIED AT SITE

Client : ANIMALA WIND POWER PRIVATE LIMITED


Title: 33kV LINE-2 (D2) CONTROL CABLE SCHEDULE& TERMINATION
FOR CONSTRUCTION
Substation: 220/33kV POOLING SUBSTATION AT ANIMALA
Rev.
Drawing. No. 005-WPL-26-002
A

Page 4 of 4

S-ar putea să vă placă și