Sunteți pe pagina 1din 24

24VDC ELECTRIC SUPPLY SYSTEM

ELECTRICAL SYSTEM DESCRIPTION Excessive consumption of water indicates leakage or


overcharging. Normal water usage for a unit operat-
The truck utilizes a 24VDC electrical system which ing eight hours per day is about one to two ounces
supplies power for all non-propulsion electrical com- per cell per month. For heavy duty operation (24
ponents. The 24VDC is supplied by four 12 volt stor- hour) normal consumption should run about one to
age batteries wired in series and parallel. The two ounces per cell per week. Any appreciable
batteries are a lead-acid type, each containing six 2- increase over these figures should be considered a
volt cells. With keyswitch ON, and engine not operat- danger signal.
ing, power is supplied by batteries. When engine is
operating, electrical power is supplied by a 24 volt Troubleshooting
alternator.
Two most common troubles that occur in the charg-
ing system are undercharging and overcharging of
the truck's batteries.
BATTERY An undercharged battery is incapable of providing
During operation, the storage batteries function as an sufficient power to the truck's electrical system.
electrochemical device for converting chemical Possible causes for an undercharged battery are:
energy into the electrical energy required for operat-
ing the accessories when the engine is shut down. ‰ Sulfated battery plates
‰ Loose battery connections
‰ Defective wire in electrical system
‰ Loose alternator drive belt
‰ A defective alternator
Lead-acid storage batteries contain sulfuric acid, ‰ A defective battery equalizer
which if handled improperly may cause serious
burns on skin or other serious injuries to person- Overcharging, which causes battery overheating, is
nel. Wear protective gloves, aprons and eye pro- first indicated by excessive use of water. If allowed to
tection when handling and servicing lead-acid continue, cell covers will push up at the positive ends
storage batteries. See the precautions in Section and in extreme cases the battery container will
A of this manual to insure proper handling of bat- become distorted and cracked.
teries and accidents involving sulfuric acid. Leakage can be detected by continual wetness of the
battery or excessive corrosion of the terminals, bat-
tery carrier and surrounding area. (A slight amount of
Maintenance and Service corrosion is normal in lead-acid batteries). Inspect
The electrolyte level of each cell should be checked the case, covers and sealing compound for holes,
at the interval specified in the Lubrication and Ser- cracks or other signs of leakage. Check battery hold
vice Section P, and water added if necessary. The down connections to make sure the tension is not
proper level to maintain is 3/8-1/2 in. (10-13 mm) great enough to crack the battery, or loose enough to
above the plates. To insure maximum battery life, allow vibration to open the seams. A leaking battery
use only distilled water or water recommended by the should be replaced.
battery manufacturer. After adding water in freezing To remove corrosion, clean the battery with a solu-
weather, operate the engine for at least 30 minutes tion of ordinary baking soda and a stiff, non-wire
to thoroughly mix the electrolyte. brush and flush with clean water. Make sure none of
the soda solution is allowed into the battery cells. Be
sure terminals are clean and tight. Clean terminals
are very important in a voltage regulated system.
Corrosion creates resistance in the charging circuit
which causes undercharging and gradual starvation
DO NOT SMOKE or allow flame around a dead of the battery.
battery or during the recharging operation. The
NOTE: When washing batteries, ensure cell caps are
expelled gas from a dead cell is extremely explo-
tight to prevent cleaning solution from entering the
sive.
cells.

D02028 24VDC Electrical Supply System D2-3


Addition of acid will be necessary if considerable The rate of self-discharge of a battery kept at 100°F
electrolyte has been lost through spillage. Before (38°C) is about six times that of a battery kept at
adding acid, make sure battery is fully charged. This 50°F (19°C) and self-discharge of a battery kept at
is accomplished by putting the battery on charge and 80°F (27°C) is about four times that one at 50°F
taking hourly specific gravity readings on each cell. (10°C). Over a thirty day period, the average self-dis-
When all the cells are gassing freely and three suc- charge runs about 0.002 specific gravity per day at
cessive hourly readings show no rise in specific grav- 80°F (27°C).
ity, the battery is considered charged. Additional acid
To offset the results of self-discharge, idle batteries
may now be added. Continue charging for another
should receive a booster charge (not a quick charge)
hour and again check specific gravity. Repeat the
at least once every thirty days. Batteries allowed to
above procedure until all cells indicate a specific
stand for long periods in a discharged condition are
gravity of 1.260-1.265 corrected to 80°F (27°C).
attacked by a crystallization of the lead sulfate on the
NOTE: Use 1.400 strength sulfuric acid when making plates. Such batteries are called sulfated and are, in
specific gravity adjustments. Acid of higher strength the majority of cases, irreparably damaged. In less
will attack the plates and separators before it has a severe cases, the sulfated battery may be restored to
chance to diffuse into the solution. limited service by prolonged charging at a low rate
(approximately normal rate).
If the temperature of the electrolyte is not reasonably
close to 80°F (27°C) when the specific gravity is An undercharged battery is extremely susceptible to
taken, temperature should be corrected to 80°F freezing when allowed to stand in cold weather.
(27°C):
The electrolyte of a battery in various stages of
• For every 10°F (5°C) below 80°F (27°C), 0.004 charge will start to freeze at temperatures indicated
should be subtracted from the specific gravity in the table.
reading.
The temperatures in table I indicate the points at
• For every 10°F (5°C) above 80°F (27°C), 0.004 which the first ice crystals appear. Lower tempera-
should be added to the reading. tures must be reached for a solid freeze. Solid freez-
ing of the electrolyte may crack the battery case and
damage the positive plates. As will be noted, a
Idle batteries should not be allowed to stand unat- charged battery is in no danger of freezing, therefore,
tended. If equipment is to stand unused for more a charge or better is desirable, especially during win-
than two weeks, the batteries should be removed ter weather.
and placed in a cool, dry place where they may be
checked periodically and charged when necessary.
Remember, all lead-acid batteries discharge slowly
when not in use. This self discharge takes place
TABLE 1.
even though the battery is not connected in a circuit
and is more pronounced in warm weather than in Specific Gravity Freezing Temperature
cold. Corrected to Degrees
80°F (27°C)
1.280 -90°F (-70°C)
1.250 -60°F (-54°C)
1.200 -16°F (-27°C)
1.150 +5°F (-15°C)
1.100 +19°F (-7°C)

D2-4 24VDC Electrical Supply System D02028


BATTERY CHARGING SYSTEM (Niehoff) TROUBLESHOOTING PROCEDURES
(On-Truck)
General Description
Most 24 volt charging system problems can be diag-
The Niehoff model N1227 or C609 (Figure 2-1) is a nosed with the alternator installed on the truck, oper-
heavy duty, 24 VDC unit rated at 240 amps. A solid ating under normal conditions. Many problems can be
state voltage regulator (6) mounted externally on the attributed to loose or corroded cable connectors. It is
end housing assembly provides voltage control during essential that all battery charging circuit cables are in
operation. A single output connection (5) is located on satisfactory condition and all connections are clean
the face of the control unit (4) for connection to the and securely tightened.
truck battery positive circuit. The ground circuit cable
can be attached to either of two terminals (10) located Equipment Required:
on the front housing. A fan guard (7) protects mainte-
nance personnel from the rotating fan when the • Belt tension scale
engine is operating. • Voltmeter, 0 - 40 volt range
• Ammeter, 0 - 400 amp range

FIGURE 2-1. ALTERNATOR EXTERIOR

1. Belt Tension Adjustment Capscrew 6. Voltage Regulator


2. Shaft Key 7. Fan Guard
3. Pulley Bushing 8. Cooling Fan Assembly
4. Control Unit 9. Mounting Lugs
5. Battery Positive Terminal 10. Ground Terminals

D02028 24VDC Electrical Supply System D2-5


Preliminary Checks Test Procedure
1. Check the drive belt tension as follows: 1. Start engine, accelerate to high idle and
observe meters.
a. Apply 20.9 lbs. (9.5 kg) force at center of belt
span.
b. Belt should deflect 0.50 in. (12.7 mm).
c. Adjust tension if necessary.
If voltmeter reading exceeds 30.5 volts, stop
Insure that an undercharged battery condition has engine immediately and refer to Table 2.
not been caused by accessories having been left ON
‰ If batteries are sufficiently discharged, amps
for extended periods.
should be "high" (220 amps ± 10%) and
2. If a battery defect is suspected, check battery voltage should be between 27.2 and 28.8
as specified in Battery - Troubleshooting in this volts (normal range) or may be less than 23.7
section. volts if the batteries are significantly
discharged.
3. Inspect the wiring for defects. Check all connec-
tions for tightness and cleanliness. Remove and 2. As the batteries approach full charge, the
clean battery cables. amperage should fall as voltage rises.
4. If truck is equipped with a battery equalizer sys- 3. When amps and volts readings stabilize, note
tem, verify proper operation of equalizer and readings and refer to Table 2 to diagnosis sys-
individual battery voltages. Refer to Battery tem condition.
Equalizer in Section D, 24VDC Electrical Sup-
ply System. TABLE 2. TROUBLESHOOTING CHART
AMPS VOLTS DIAGNOSIS
HIGH LOW Charging system is OK. Batteries
Test Setup are not yet fully charged. Wait for
charging system to bring to full
1. Discharge batteries sufficiently to insure ade- charge; amps should decrease
quate loading of alternator when engine is and voltage should stabilize
operated during tests. between 27.2 and 28.8 volts.

2. Open battery disconnect switch. Remove bat- HIGH NORMAL Watch until amps decrease or
voltage exceeds 28.8 volts. If
tery cable from alternator B+ terminal. amps decrease and volts remain
Refer to Figure 2-2 for the following steps. Meters normal, system is OK. If voltage
exceeds 28.9 volts, regulator and/
should be installed directly at the alternator as shown or alternator defective. Go to
to eliminate variations in readings due to cable Static Test.
lengths etc.:
HIGH HIGH STOP TEST! Regulator and/or
3. Install the ammeter (negative lead) to the bat- alternator defective. Go to Static
tery positive cable removed in step 2. Install the Test.
ammeter positive lead to the alternator B+ ter- LOW LOW 1. Recheck voltmeter leads. If
minal. connections are OK, alternator
and/or regulator defective.
4. Install a voltmeter between the alternator B+
2. Perform Regulator Bypass Test
terminal (positive lead) and the ground terminal per instructions on following page:
(voltmeter negative lead). a. If volts and/or amps
5. Secure all test equipment leads to prevent dam- increase, alternator is OK but reg-
ulator is defective.
age or short circuits when engine is started.
b. If no effect, replace alternator
Reconnect battery disconnect switch.
LOW NORMAL Charging system is OK.
LOW HIGH STOP TEST! If battery and volt-
meter check is OK, regulator and/
or alternator defective.

The following tests require working near the


engine when running. Use caution when working
near engine fan, alternator fan and belt.

D2-6 24VDC Electrical Supply System D02028


FIGURE 2-3. REGULATOR BYPASS TEST

1. Alternator Control Unit


FIGURE 2-2. TEST METER HOOKUP 2. “R” Terminal (Relay)
3. “E” Terminal (Energize)
4. Alternator “B+” Terminal
1. Alternator Under Test 5. Alternator / Voltage Regulator
2. 0 to 400 AMP Ammeter Harness Plug
3. 0 to 40 VDC Voltmeter
4. Alternator “B+” Terminal
5. Alternator Ground Terminal
6. Truck Batteries

Regulator Bypass Test


If the test procedure outlined on the previous page
indicates low current output and low voltage out-
put, perform the following test to determine if the
voltage regulator is defective or if the alternator is
defective.
1. Disconnect alternator/regulator harness plug
(3, Figure 2-3).
2. Momentarily touch the "F-" connector pin on the
alternator connector to ground.
3. Observe meter readings:
‰ If voltage or amperage rises, the alternator is
OK. The regulator is defective and should be
replaced.
‰ If grounding the harness male pin has no
effect, the alternator is defective and should
be replaced.

D02028 24VDC Electrical Supply System D2-7


ON VEHICLE TROUBLESHOOTING GUIDE

ALTERNATOR ELECTRICAL CONDITIONS - Low Voltage - High Voltage - No Voltage

PRELIMINARY PROCEDURES HIGH VOLTAGE OUTPUT


Common problems, all applications: Causes of high voltage:
Check alternator drive belt (s). Wrong regulator.
Check alternator positive connection High regulator set point.
Check alternator ground connection on alterna- Defective regulator.
tor.
Defective alternator.
Check condition of connector between regulator
and alternator.
Identify model of alternator_______________ NO VOLTAGE OUTPUT

Identify model of regulator________________ Causes of no voltage output:

Record voltage regulator set points stated on No drive belt.


regulator tag: No battery (B+) voltage at alternator's "B+" ter-
1)_______ 2)_______ 3)_______ (if applicable) minal (except isolator type systems).
No "link" from "R" terminal to energize ("E") ter-
minal on alternator when engine operating.
TOOLS AND EQUIPMENT: Defective regulator.
1 - Voltmeter (Digital type preferred.) Defective alternator.
1 - Ammeter (Digital, Inductive type preferred.)
1 - 12 gauge lead, 12 inches long, with alligator clip
at each end.
BATTERY CONDITIONS AND CHARGE
VOLTAGE REACTIONS:
LOW VOLTAGE OUTPUT NOTE: Until electrical system component
Causes of low voltage: temperatures stabilize, these conditions may be
observed during cold start voltage tests.
Loose drive belt.
Maintenance type:
Low state of charge of battery.
Immediately after engine start, system volts are
Current load on system greater than alternator
lower than regulator set-point with medium
can produce.
amps.
Defective wiring or poor ground path.
3-5 minutes into charge cycle, higher system
Low regulator set point. volts and reduced amps.
Defective voltage regulator. 5-10 minutes into charge cycle, system volts are
at, or nearly at, regulator set point, and amps
Defective alternator.
are reduced to a minimum.

Low Maintenance types:


Same as above, except cycle times may be
longer.

D2-8 24VDC Electrical Supply System D02028


Maintenance Free types:
Immediately after engine start, system volts are Medium amps are defined as some multiple of
lower than regulator set-point with low amps. the low amp value, perhaps 30 amps for the
Group-8D and 10-15 amps for the Group-31.
15-30 minutes into charge cycle, still low volts
This rate of amperage will cause a rise in bat-
and low amps.
tery temperature over a long period of time (4-8
15-30 minutes into charge cycle, volts rise sev- hrs) and may lead to an overcharge condition if
eral tenths, amps increase gradually then temperature elevates too high.
increase quicker to medium to high amps.
20-35 minutes into charge cycle, volts rise to
High amps would be 50 to 75 amps for a Group-
set-point and amps lower.
8D, and 25 to 35 amps for a Group-31 size.
High amperage rates over a short period of time
(2-3 hrs.) can severely damage any battery by
High-Cycle Maintenance Free Types:
overheating the battery and causing thermal
These types respond much better than standard runaway. The battery, in effect, forgets its state
maintenance free types. The charge accep- of charge and will accept all amps offered. The
tance of these batteries may display character- electrolyte solution is boiled off as the battery
istics similar to standard, maintenance type moves into an excessive gassing stage.
batteries.

Charge voltage is the voltage delivered to the


battery when the alternator and regulator are
CHARGE VOLT AND AMP VALUES operating properly. This charge voltage value is
Voltage and amperage levels are functions of battery the voltage regulator's set-point. At times the
state of charge. If the batteries are charged 95% or charge voltage value may be less than the regu-
higher when the engine is cranked, the charge volt- lator's set-point but it will never be higher than
age will be near regulator set-point and the amps will that set-point.
taper quickly from medium to low. True battery volt-
age is obtained after removing any surface charge
from the battery or after 24 hours of non-use. Battery voltage is the steady state voltage of the
battery. The value of this voltage relates directly
to state of charge.

DEFINITIONS
NOTE: Charge voltage and amp rates vary from B+ voltage is battery positive voltage, but does
battery type to battery type, based on battery not refer to a specific value as does battery volt-
construction technology and physical size of battery. age.

Low amps are the necessary amps that a bat- Surface charge is a higher than normal terminal
tery will take continuously over a period of time voltage a battery has when it comes off a
without damage to the battery when the battery charger or after extended time in vehicle opera-
is in an operating system and is constantly tion. The surface charge must be removed to
cycling. Batteries such as the Group-8D may determine true battery voltage.
accept rates up to 15 amps over several hours
without raising their internal temperature more
than a few degrees. Group-31 batteries may
accept rates up to 5 amps over several hours
with minimal temperature rise.

D02028 24VDC Electrical Supply System D2-9


ADVANCED SYSTEM TROUBLESHOOTING
NO ALTERNATOR OUTPUT

Static Test - Engine OFF, Key ON, Battery Switch


ON.
Identify and locate "B+", "E", and "R" and ground DAMAGE WILL OCCUR IF UNIT IS OPERATED
("B-") terminals on alternator and check for link from WITH STRAP CONNECTED AND B+ APPLIED!
terminal "R" to "E".
Hold a steel wrench or screwdriver near alternator
drive pulley: wrench or screwdriver held near drive
pulley will be attracted to pulley by magnetism.
Go To Alternator
‰ If there is no magnetic attraction, alternator
Test for battery B+ voltage (__________V) at "B+" ter-
may not be turned on. Go to "Regulator Test"
minal on alternator: that follows and continue test.
‰ If there is no B+ voltage on "B+" terminal, • If there is magnetic attraction alternator is good
repair vehicle wiring as necessary. Continue and regulator should be considered good.
test. Alternator will produce electricity because
• If B+ voltage is present on "B+" terminal, continue regulator is on. This test only shows regulator as
test. either on or off.

Remove strap between "R" and "E" terminal. NOTE: Alternator may not be turned on when engine
is operating. Go to "R" terminal test next, to prove if
Connect a 12 gauge jumper wire from the "B+" termi- vehicle "E" circuit will turn alternator on.
nal on alternator to the "E" terminal on alternator.

FIGURE 2-4. ALTERNATOR


TERMINALS

1. Control Unit
2. “R” Terminal
3. Strap
4. “E” Terminal
5. “B+” Terminal
6. Ground Terminal

D2-10 24VDC Electrical Supply System D02028


Go To 'R' Terminal On The Alternator Go To Regulator (If Required)
With engine running, measure value of AC voltage Disconnect voltage regulator from alternator. There
from "R" terminal to "Ground". are no static tests available for the regulator. Con-
tinue test.
‰ If no AC volts are present, alternator is not
capable of turning on regulator.
NOTE: On a new, first time start up of an
Go To Regulator Connector On The Alternator
alternator, the alternator may test at less than 5
volts on "R" terminal. The cause of this problem Connect a jumper wire from ground on alternator into
may be loss of residual magnetism within the "F-" pin of connector attached to alternator.
alternator during shipping and handling of the
alternator. To restore the residual magnetism:
B+ F- E B-
With engine off and battery switch on,
momentarily (1-2 seconds) connect a jumper wire METRI-PACK™ Connector
from 'B+' terminal to 'E' terminal. (May spark -
this is OK.) Remove jumper and restart engine. Hold a steel wrench or screwdriver near alternator
Alternator should generate properly once the drive pulley; wrench or screwdriver held near drive
residual magnetism is restored. pulley will be attracted to pulley by magnetism.
• If AC voltage is approximately 14 Volts, alternator • If there is no attraction, alternator field is
is properly turned on and output of alternator will defective. Replace alternator.
be approximately 28 Volts.
• If there is magnetic attraction, alternator field is
‰ If AC voltage is 3 Volts to 5 Volts, alternator is good. Continue test.
NOT turned on (regulator is OFF) but
alternator is capable of turning on a good With jumper still connected between "B+" terminal
regulator. NOTE: This test shows only if and "E" terminal on alternator: Insert "+" probe of
alternator is capable of energizing regulator. voltmeter into "E" terminal of connector, and Ground
To check harness from alternator to regulator negative probe of voltmeter to alternator ground ter-
go to "Regulator Connector On Alternator" minal.
test.Continue testing.
• If meter shows no voltage, alternator is defective.
Replace alternator.

Vehicle Charging Circuit Test Is Now Complete: • If meter shows battery voltage, circuit is good.
Continue test.
Remove all jumper wires from alternator used to test
Insert "+" probe of voltmeter into "B" pin in connector.
charging circuit.
Insert negative probe of voltmeter into "B-" pin in
connector. (This is power circuit for voltage regula-
tor.)
Re-test Charging Circuit For Operation With The
Engine Running: • If circuit shows open (no voltage), alternator is
defective. Replace alternator.
Check charging system voltage with engine running.
• If circuit shows B+ voltage, regulator is defective.
‰ If no charge voltage, test for voltage at "E" Replace the regulator, only.
terminal of alternator, with engine running.
NOTE: Turn key and battery switch OFF before
‰ If no voltage on "E" terminal, shut engine installing new regulator. Turn battery switch and key
down and inspect link from "R" terminal to back on AFTER installing new regulator. Continue
"E". test.
Run engine and re-test charging circuit.

Remove all jumper wires from alternator used to test


charging circuit.
Reconnect link from "R" terminal to "E" terminal

D02028 24VDC Electrical Supply System D2-11


NOTES

D2-12 24VDC Electrical Supply System D02028


24 VDC REMOTE MOUNT PRELUB™ SYSTEM
The HD1500-5 is equipped with an engine pre-lubri-
cation system designed to reduce wear due to dry
starts.
The Prelub™ system automatically fills engine oil fil-
ters and all oil passages prior to cranking at each
engine startup. In addition, the system prevents star-
tup if no oil is present in the engine.
The Prelub™ system includes:
• Prelub pump
• Timer solenoid
• Oil pressure switch
• Oil suction line
• Oil outlet line
• Check valve FIGURE 2-5. REMOTE MOUNT PRELUB PUMP

• Electrical harness. 1. Prelub™ Pump 3. Outlet Line


2. Suction Line 4. Check Valve
OPERATION
(Refer to electrical schematic diagram, Figure 2-7.)
The Prelub™ system is activated when the operator
turns the key switch and holds it in the START posi-
tion. This allows current to flow to the timer solenoid.
Engine oil pressure switch (1, Figure 2-7) provides
the ground for the circuit. The switch contains nor-
mally closed contacts that are set to open when oil
pressure reaches 0.18 kg/cm2 (2.5 psi). While the
contacts are closed, the timer solenoid closes the
contacts that supply power from the alternator to the
prelube motor/pump. The pump has a dedicated
frame ground, and begins pumping oil into the engine
while the timer solenoid circuitry prevents the crank-
ing motors from operating.
When the pressure in the engine cam oil rifle reaches
0.18 kg/cm2 (2.5 psi), the pressure switch contacts
open, disabling the circuit to the timer solenoid. The
solenoid contacts for alternator power to the prelub
pump open, and current is directed to the magnetic
switches that control the cranking motor solenoids.
The cranking motors will then be activated and the FIGURE 2-6. PRELUB TIMER
pinion gears will be engaged into the flywheel ring
gear. Normal cranking will now occur with sufficient 1. Prelub Timer 3. Frame Ground
lubrication to protect the engine bearings and other 2. B+ From Alternator
components.
NOTE: The power circuit from the alternator to the
pump is protected by a 400 amp fusible link. A
clamping diode in the circuit dissipates voltage
spikes.

D02028 24VDC Electrical Supply System D2-13


FIGURE 2-7. PRELUB SCHEMATIC DIAGRAM

1. Prelub Pump 5. Diode


2. Oil Pressure Switch (N.C.) - 0.18 kg/cm2 (2.5 psi) 6. Prelub Timer Solenoid
3. Cranking Motors 7. Alternator
4. Magnetic Switch 8. 400 Amp Fusible Link

Pressure Switch

Pressure switch (1 Figure 2-8) is a 0.18 kg/cm2 (2.5


psi), normally closed (N.C.) switch, located so that it
can sense oil pressure after the engine oil has
passed through the filters. Normally, this location is
the cam cover at the rear of the engine block just
ahead of engine damper (2).

Check Valve
Check valve (4, Figure 2-5) is installed between the
prelub pump pressure hose and the engine. The oil
flow through the valve (arrow on valve) must be
toward the engine. The check valve prevents back-
flow from the engine back to the prelub pump after
the engine is started. Failure to prevent backflow to
FIGURE 2-8. ENGINE OIL PRESSURE SWITCH the pump will result in pump failure.

1. Oil Pressure Switch 2. Engine Damper

D2-14 24VDC Electrical Supply System D02028


Timer Solenoid 2. Remove a Prelub™ pump capscrew (1) from
the electric motor. Remove the capscrew that is
Timer solenoid (1, Figure 2-6) controls the prelubri-
nearest the six o’clock position.
cation cycle, by completing the power supply circuit
to operate the prelub pump. Current is supplied to 3. Inspect the capscrew for any signs of oil. Oil
the timer solenoid through the key switch. The may be present in large amounts or as a light
ground path is completed by the normally closed mist. Oil in any quantity in the housing indicates
pressure switch (1, Figure 2-8) which is preset to a failed motor and repair or replacement is nec-
essary. Proceed to the next step to determine
open at 0.18 kg/cm2 (2.5 psi).
what components require repair.
When the switch opens, current is redirected to the
standard starting system magnetic switches for
engine cranking.

Brush dust will be present in all motors. Do not


confuse brush dust with oil. Brush dust will
appear as a black/brown, dry coating within the
motor.
DO NOT attempt to jump start the truck using the
terminals on the timer solenoid. Internal damage
to the timer will result. 4. If oil is present in the motor, disconnect output
line (3, Figure 2-5) from the pump. Place the
hose in a oil capture container, and secure. Use
care when securing the hose. Oil may exit the
MAINTENANCE line at normal operating pressures.
Prelub™ System Operation
Verify the system operates according to the two
phases of operation as listed in Troubleshooting Pre-
Use extreme caution when performing the follow-
lub Circuit on the following page. If a problem exists,
ing step. Hot oil can cause severe burns.
refer to the list of problems and possible causes for
troubleshooting system components. 5. Close the battery disconnect switches. Start the
engine, and observe the output line while the
If the system is operating properly, continue with the engine is operating to verify that check valve (4)
inspection of component parts below: is functioning properly.
Prelub Pump a. If there is no indication of oil flow/pressure,
only the Prelub™ pump must be replaced.
1. Open the battery disconnect switches to pre-
vent engine startup. b. If there is any indication of oil flow/pressure,
the check valve is faulty, and the Prelub™
pump and check valve must be replaced.

Check Valve
Verify no internal leakage exists in the check valve
when the engine is running. Check valve leakage
back to the Prelub™ pump will cause extensive dam-
age to the pump.
If check valve replacement is required, ensure the
valve is installed with the arrow pointed toward the
engine, not toward the pump.

Timer Solenoid

FIGURE 2-9. MOTOR COVER Inspect the timer solenoid for physical damage and
to verify wiring is in good condition.
1. Capscrew 2. Cover

D02028 24VDC Electrical Supply System D2-15


TROUBLESHOOTING PRELUB CIRCUIT
Two distinct phases are involved in a complete prelubrication cycle. The two phases are:
1. Prelubrication phase- Begins when the key switch is held in the start position. A circuit is provided to ground
through the normally closed pressure switch. The circuit is interrupted upon opening of the pressure switch when
the oil pressure reaches 0.18 kg/cm2 (2.5 psi).
2. Crank phase- Begins when the engine oil pressure switch opens, and cranking occurs.

PROBLEM POSSIBLE CAUSES


System prelubricates only. Cranking is inoperable. Oil pressure is not sufficient to open the pressure
switch.
a. No oil or low oil in engine. The pump can not
build sufficient pressure to open switch.
b. Pump failure.
c. Pressure switch has failed (closed) and is
grounding circuit.
d. Oil pressure switch wire chafed and shorting
to block.
Possible timer failure, or a cranking motor problem.
a. Install a jumper cable to the cranking motor
solenoid "S" post. If the engine starts to crank,
replace the prelub timer solenoid.
b. If the engine fails to crank when the "S" post is
energized with voltage; check cranking motors
and solenoids.

System prelubricates continuously regardless of key Indicates prelub timer solenoid contacts have welded.
switch position.
a. Low voltage can cause relay failure.
b. Jump starting of the vehicle with a voltage that
is higher than was designed for the system,
can cause solenoid contacts to weld.

Cranking motor “bounces” when cranking. Check for low or dead batteries.
Check alternator output.
Check for bad ground strap or missing ground wire
from the starter battery ground post to "G" terminal of
starter bendix solenoid.
Check for bad starter safety relays.

System prelubricates, but does not crank. Indication is either a timer failure, or a starter problem.
a. Place a jumper wire to the starter solenoid "S"
post. If the engine starts to crank, replace the
prelub timer solenoid.
b. If the engine fails to crank when the "S" post is
energized with voltage, check out starter ben-
dix solenoid and starter pinion drive.

D2-16 24VDC Electrical Supply System D02028


PROBLEM POSSIBLE CAUSES

No prelubrication mode, but cranking still operable. Indicates that a ground connection to the pressure
switch has been broken. Without a ground path, the
prelubrication unit will proceed to crank phase.
a. Check the wire to the pressure switch. If the
wire is removed or cut, replace it.
b. Check the ground strap to engine block. If the
ground strap is missing the block is not
grounded.
c. Check the pressure switch for an open circuit.
Remove the wire, then check for an open cir-
cuit between the switch terminal and the
switch base. If open, replace the pressure
switch.

System has very long prelubrication cycle. Except for severe cold weather starts, the Prelub cycle
should not exceed 45 seconds.
a. Low oil pressure.
b. Make sure oil of the proper viscosity is being
used in respect to outside temperature. (Refer
to engine manufacturer's specifications).
c. Check for suction side air leaks, loose con-
nections, cracked fittings, pump casting, or
hose kinks and blockage.
d. Make sure the suction hose is the correct
diameter. Reducing hose diameter will reduce
pump output, dramatically.
e. Check the oil pressure switch for the correct
location. Be certain that it has not been
moved into a metered oil flow, as in a bypass
filter or governor assembly.

No prelubrication and no crank. Indicates a possible failure of the prelubrication timer


solenoid. Remove the wire from the pressure switch
(ground wire) and attempt to start the machine.
a. If the cranking motor now cranks, the prelub
timer solenoid is bad. Replace the timer sole-
noid assembly.
b. If the cranking motors do not crank, ensure all
relays, circuit breakers, switches, etc. are in
working condition. Repair as necessary.

D02028 24VDC Electrical Supply System D2-17


NOTES

D2-18 24VDC Electrical Supply System D02028


24 VDC ELECTRIC START SYSTEM
CRANKING MOTORS
Operation
Heavy duty batteries supply 24VDC to each of the
two cranking motors through magnetic switches acti-
vated by the key switch on the instrument panel.
When the keyswitch is moved to the START position,
the Prelub™ system is activated. (Refer to 24VDC
Remote Mount Prelub™ System.) The Prelub™ sys-
tem lubricates internal engine components with oil to
prevent excessive wear due to dry starts. When oil
pressure reaches 0.18 kg/cm2 (2.5 psi), current flow
is diverted to the cranking system by the Prelub™
timer solenoid. The magnetic switches close, con-
necting the motor solenoid "S" terminals to the bat-
teries. When the solenoid windings are energized, FIGURE 2-10. STARTER MOTORS
plunger (56, Figure 2-9) is pulled in, moving starter
drive (71) assembly forward in the nose housing to 1. Mounting Capscrews 3. Solenoid
engage the engine flywheel ring gear. Also, when the 2. Cranking Motor
solenoid plunger is pulled in, the main solenoid con-
tacts close to provide current to the motor armature
and cranking occurs. After the engine starts, an over-
running clutch in the drive assembly protects the
armature from excessive speed until the keyswitch is
released. When the keyswitch is released, a return
spring causes the drive pinion to disengage.
After the engine is running, a normally closed pres- Installation
sure switch senses engine oil pressure and opens
the electrical circuit to prevent actuation of the 1. Align motor (2, Figure 2-7) housing with the fly-
motor(s) after the engine has started. wheel housing adaptor mounting holes and
slide into position.
Removal 2. Insert motor mounting capscrews (1).
1. Disconnect battery power: 3. Connect marked wires and cables to motors
and solenoid terminals.
a. Open the battery disconnect switch to
remove power from the system. 4. Install in the following sequence:

b. Remove the battery cables using the follow- a. Install the battery negative (-) cables first.
ing sequence: b. Install the battery positive (+) cables.
1.) Remove the battery positive (+) cables c. Close the battery disconnect switch.
first.
2.) Remove the negative (-) cables last.
2. Mark wires and cables and remove from motor
(2, Figure 2-7) and solenoid terminals.
3. Remove motor mounting capscrews (1).
4. Remove motor assembly from flywheel hous-
ing.

D02028 24VDC Electrical Supply System D2-19


No-Load Test
Refer to Figure 2-8 for the following test setup.

Be certain the switch is open before connections


or disconnections are made during the following
procedures.
1. Setup the motor for test as follows:
a. Connect a voltmeter from the motor terminal
to the motor frame.
b. Use an rpm indicator to measure armature
speed.
c. Connect a carbon pile across one battery to
FIGURE 2-11. NO-LOAD TEST CIRCUIT limit battery voltage to 20 VDC.

CRANKING MOTOR
TROUBLESHOOTING
Do not apply voltages in excess of 20 volts.
If the cranking system is not functioning properly,
Excessive voltage may cause the armature to
check the following to determine which part of the
throw windings.
system is at fault:
d. Connect the motor and an ammeter in series
• Batteries- Verify the condition of the batteries,
with two fully charged 12 volt batteries.
cables, connections and charging circuit.
e. Connect a switch in the open position from
• Wiring- Inspect all wiring for damage or loose
connections at the keyswitch, magnetic switches, the solenoid battery terminal to the solenoid
solenoids and cranking motor(s). Clean, repair or switch terminal.
tighten as required. 2. Close the switch and compare the rpm, current,
If the above inspection indicates the starter motor to and voltage reading to the following specifica-
be the cause of the problem, remove the motor and tions:
perform the following tests prior to disassembly to • RPM: 5500 Minimum to 7500 Maximum
determine the condition of the motor and solenoid
• AMPS: 95 Minimum to 120 Maximum
and repairs required.
• VOLTS: 20 VDC

Interpreting Results of Tests


Preliminary Inspection
1. Rated current draw and no-load speed indi-
1. Check the cranking motor to be certain the cates normal condition of the cranking motor.
armature turns freely.
2. Low free speed and high current draw indi-
a. Insert a flat blade screwdriver through the cates:
opening in the nose housing.
a. Too much friction; tight, dirty, or worn bear-
b. Pry the pinion gear to be certain the arma- ings, bent armature shaft or loose pole
ture can be rotated. shoes allowing armature to drag.
2. If the armature does not turn freely, the motor b. Shorted armature. This can be further
should be disassembled, immediately. checked on a growler after disassembly.
3. If the armature can be rotated, perform the No-
c. Grounded armature or fields. Check further
Load Test before disassembly.
after disassembly.

D2-20 24VDC Electrical Supply System D02028


3. Failure to operate with high current draw indi- Cleaning and Inspection
cates: 1. The drive (71), armature (45) and fields (46)
a. A direct ground in the terminal or fields. should not be cleaned in any degreasing tank,
or with grease dissolving solvents, since these
b. "Frozen" bearings (this should have been
would dissolve the lubricant in the drive and
determined by turning the armature by
damage the insulation in the armature and field
hand).
coils.
4. Failure to operate with no current draw indi-
2. All parts except the drive should be cleaned
cates:
with mineral spirits and a clean cloth.
a. Open field circuit. This can be checked after 3. If the commutator is dirty, it may be cleaned
disassembly by inspecting internal connec- with No. 00 sandpaper.
tions and tracing circuit with a test lamp.
NOTE: Never use emery cloth to clean the
b. Open armature coils. Inspect the commuta-
commutator.
tor for badly burned bars after disassembly.
4. Inspect the brushes (13, Figure 2-9) for wear.
c. Broken brush springs, worn brushes, high
insulation between the commutator bars or a. If worn excessively when compared with a
other causes which would prevent good con- new brush, they should be replaced.
tact between the brushes and commutator. b. Ensure the brush holders (10) are clean and
5. Low no-load speed and low current draw indi- the brushes are not binding in the holders.
cates: c. The full brush surface should ride on the
a. High internal resistance due to poor connec- commutator. Check by hand to insure that
tions, defective leads, dirty commutator and the brush springs (16) are giving firm contact
causes listed under Number 4. between the brushes (13) and commutator.
6. High free speed and high current draw indicates d. If the springs (16) are distorted or discolored,
shorted fields. If shorted fields are suspected, they must be replaced.
replace the field coil assembly and check for
improved performance. Armature Servicing
If the armature commutator is worn, dirty, out of
Disassembly
round, or has elevated insulation, armature (45)
The cranking motor should be disassembled only as should be put on a lathe and the commutator turned
far as necessary to repair or replace defective parts. down. The insulation should then be undercut 0.031
1. Note the relative position of the solenoid (53, in. (0.79 mm) wide and 0.031 in. (0.79 mm) deep,
Figure 2-9), lever housing (78), nose housing and the slots cleaned out to remove any trace of dirt
(69), and C.E. frame (1) so the motor can be or copper dust. As a final step in this procedure, the
reassembled in the same manner. commutator should be sanded lightly with No. 00
sandpaper to remove any burrs left as a result of the
2. Disconnect field coil connector (42) from sole-
undercutting procedure.
noid motor terminal, and lead from solenoid
ground terminal. The armature should be checked for opens, short cir-
3. Remove the brush inspection plates (52), and cuits and grounds as follows:
brush lead screws(15). 1. Opens are usually caused by excessively long
4. Remove the attaching bolts (34) and separate cranking periods. The most likely place for an
the commutator end frame (1) from the field open to occur is at the commutator riser bars.
frame (35). Inspect the points where the conductors are
joined to the commutator bars for loose connec-
5. Separate the nose housing (69) and field frame
tions. Poor connections cause arcing and burn-
(35) from lever housing (78) by removing
ing of the commutator as the cranking motor is
attaching bolts (70).
used. If the bars are not too badly burned,
6. Remove armature (45) and drive assembly (71) repair can often be effective by soldering or
from lever housing (78). welding the leads in the riser bars (using rosin
7. Separate solenoid (53) from lever housing by flux), and turning down the commutator in a
pulling apart. lathe to remove the burned material. The insula-
tion should then be undercut.

D02028 24VDC Electrical Supply System D2-21


2. Short circuits in the armature are located by use
of a growler. When the armature is revolved in FIGURE 2-9 CRANKING MOTOR ASSEMBLY
the growler with a steel strip such as a hacksaw
blade held above it, the blade will vibrate above 1. C.E. Frame 42. Connector
the area of the armature core in which the short 2. Washers 43. Lock Washer
circuit is located. Shorts between bars are 3. O-Ring 44. Nut
sometimes produced by brush dust or copper 4. Insulator 45. Armature
between the bars. These shorts can be elimi- 5. Support Plate 46. Field Coil (6 Coils)
nated by cleaning out the slots. 6. Brush Plate Insulator 47. Shoe
3. Grounds in the armature can be detected by the 7. Washers 48. Insulator
use of a 110-volt test lamp and test points. If the 8. Plate & Stud 49. Screw
lamp lights when one test point is placed on the 9. Plate 50. Washer
commutator with the other point on the core or 10. Brush Holder 51. O-Ring
shaft, the armature is grounded. Grounds occur 11. Lock Washer 52. Inspection Plug
as a result of insulation failure which is often 12. Screw 53. Solenoid Housing
brought about by overheating of the cranking 13. Brush (12 req'd) 54. Lock Washer
motor produced by excessively long cranking 14. Lock Washer 55. Screw
periods or by accumulation of brush dust 15. Screw 56. Plunger
between the commutator bars and the steel 16. Brush Spring 57. Washer
commutator ring. 17. Screw 58. Boot
18. Screw 59. Washer
19. Screw 60. Spring
Field Coil Checks 20. Lock Washers 61. Retainer
21. Plate 62. Snap Ring
Field coils (46, Figure 2-9) can be checked for 22. Brush Holder Insulator 63. Shift Lever
grounds and opens by using a test lamp. 23. Screw 64. Nut
1. Grounds- The ground connections must be dis- 24. Lock Washer 65. O-Ring
connected during this check. Connect one lead 25. Washer 66. O-Ring
of the 110 volt test lamp to field frame (35) and 26. O-Ring 67. Snap Ring
the other lead to field connector (42). If the lamp 27. Bushing 68. Lever Shaft
lights, at least one field coil is grounded and 28. Insulator 69. Drive Housing
must be repaired or replaced. 29. Washer 70. Screw
30. Lock Washer 71. Drive Assembly
2. Opens- Connect test lamp leads to ends of field
31. Nut 72. Gasket
coils (46). If lamp does not light, the field coils
32. Nut 73. Plug
are open.
33. Lock Washer 74. Gasket
34. Screw 75. Brake Washer
35. Field Frame 76. Screw
Field Coil Removal 36. Stud Terminal 77. Lock Washer
Field coils can be removed from the field frame 37. Bushing 78. Lever Housing
assembly by using a pole shoe screwdriver. A pole 38. Gasket 79. Washer
shoe spreader should also be used to prevent distor- 39. Washers 80. O-Ring
tion of the field frame. Careful installation of the field 40. Washer
coils is necessary to prevent shorting or grounding of 41. Nut
the field coils as the pole shoes are tightened into
place. Where the pole shoe has a long lip on one
side and a short lip on the other, the long lip should
be assembled in the direction of armature rotation so
it becomes the trailing (not leading) edge of the pole
shoe.

D2-22 24VDC Electrical Supply System D02028


FIGURE 2-12. CRANKING MOTOR ASSEMBLY

D02028 24VDC Electrical Supply System D2-23


Solenoid Checks
A basic solenoid circuit is shown in Figure 2-10.
Solenoids can be checked electrically using the fol-
lowing procedure.

Test
1. With all leads disconnected from the solenoid,
make test connections as shown to the sole-
noid, the switch terminal and the second switch
terminal "G", to check the hold-in winding (Fig-
ure 2-11).
2. Use the carbon pile to decrease battery voltage
to 20 volts. Close the switch and read current.
a. The ammeter should read 6.8 amps max.
3. To check the pull-in winding, connect from the
solenoid switch terminal "S" to the solenoid
motor "M" or "MTR" terminal (Figure 2-12).

To prevent overheating, do not leave the pull-in


winding energized more than 15 seconds. The FIGURE 2-14. SOLENOID HOLD-IN WINDING
current draw will decrease as the winding tem- TEST
perature increases.
4. Use the carbon pile to decrease battery voltage
to 5 volts. Close the switch and read current.
a. The ammeter should read 9.0 to 11.5 amps.
NOTE: High readings indicate a shorted winding.
Low readings indicate excessive resistance.
5. To check for grounds, move battery lead from
"G" (Figure 2-11) and from "MTR" (Figure 2-12)
to the solenoid case. Ammeter should read
zero. If not, the winding is grounded.

FIGURE 2-15. SOLENOID PULL-IN


WINDING TEST
FIGURE 2-13. SIMPLIFIED SOLENOID CIRCUIT

D2-24 24VDC Electrical Supply System D02028


Assembly
Lubricate all bearings, wicks and oil reservoirs with
SAE No. 20 oil during assembly.

Bearing Replacement:
1. If any of the bronze bearings are to be replaced,
dip each bearing in SAE No. 20 oil before
pressing into place.
2. Install wick, soaked in oil, prior to installing
bearings.
3. Do not attempt to drill or ream sintered bear-
ings. These bearings are supplied to size. If
drilled or reamed, the I.D. will be too large and
the bearing pores will seal over.
4. Do not cross-drill bearings. Because the bear-
ing is so highly porous, oil from the wick touch-
ing the outside bearing surface will bleed
through and provide adequate lubrication.
5. The middle bearing is a support bearing used to
prevent armature deflection during cranking.
The clearance between this bearing and the
armature shaft is large compared to the end
frame bearings.

Motor Assembly:
1. Install the end frame (with brushes) onto the FIGURE 2-16. PINION CLEARANCE CHECK
field frame as follows: CIRCUIT

a. Insert the armature (45, Figure 2-9) into the


field frame (35). Pull the armature out of the 5. Using a new gasket (72), install drive housing
field frame just far enough to permit the (69) and secure with screws (70).
brushes to be placed over the commutator. 6. Assemble field coil connector (42) to solenoid.
b. Place the end frame (1) on the armature 7. Adjust pinion clearance per instructions on the
shaft. Slide end frame and armature into following page.
place against the field frame. 8. After pinion clearance has been adjusted, install
c. Insert screws (34) and washers (33) and gasket (74) and plug(73).
tighten securely.
Pinion Clearance
2. Assemble lever (63) into lever housing (78) If
removed. To adjust pinion clearance, follow the steps listed
below.
3. Place washer (79) on armature shaft and install
new O-ring (80). Position drive assembly (71) in 1. Make connections as shown in Figure 2-13.
lever (63) in lever housing. Apply a light coat of 2. Momentarily flash a jumper lead from terminal
lubricant (Delco Remy Part No. 1960954) on "GC to terminal "MTR". The drive will now shift
washer (75) and install over armature shaft. into cranking position and remain so until the
Align lever housing with field frame and slide batteries are disconnected.
assembly over armature shaft. Secure with 3. Push the pinion or drive back towards the com-
screws (76) and washers (77). mutator end to eliminate slack movement.
4. Assemble and install solenoid assembly 4. The distance between the drive pinion and
through lever housing and attach to field frame. housing should be between 0.330 - 0.390 in.
Install nut (64) but do not tighten at this time. (8.3 - 9.9 mm) as shown in Figure 2-14.
Install brush inspection plugs (52).
5. Adjust clearance by turning shaft nut (64, Fig-
ure 2-9).

D02028 24VDC Electrical Supply System D2-25


Coil Test
1. Using an ohmmeter, measure the coil resis-
tance across the coil terminals.
a. The coil should read approximately 28W at
72°F (22.2° C).
b. If the ohmmeter reads OL, the coil is open
and the switch must be replaced.
c. If the ohmmeter reads 0 Ω, the coil is shorted
and the switch must be replaced.
2. Place one of the ohmmeter probes on a coil ter-
minal and another on the switch mounting
bracket. If the meter displays any resistance
reading, the coil is grounded and the switch
must be replaced.
3. The ohmmeter should display OL when the
probes are placed across the switch terminals.

FIGURE 2-17. CHECKING PINION CLEARANCE NOTE: The switch terminals should show continuity
when 24 VDC is applied to the coil terminals,
however high resistance across the internal switch
Magnetic Switch contacts due to arcing etc. could prevent the switch
from delivering adequate current to the cranking
The magnetic switch is a sealed unit and not repair-
motor. If the coil tests are satisfactory, but the switch
able.
is still suspect, it should be replaced with a new part.
Removal
1. Remove battery power as described in Crank-
ing Motor - Removal.
2. Disconnect cables from the switch terminals
and wires from coil terminals (Figure 2-15).
NOTE: If the magnetic switch being removed has a
diode across the coil terminals, mark the leads prior
to removal to ensure correct polarity during
installation.
3. Remove mounting capscrews and washers.
Remove switch from mounting bracket.
4. The switch coil circuit can be tested as
described below.

Installation
1. Attach magnetic switch to the mounting bracket
using the capscrews and lockwashers removed
previously. FIGURE 2-18. MAGNETIC SWITCH ASSEMBLY
2. Inspect cables and switch terminals. Clean as
required and install cables.
3. Install the diode across the coil terminals if
required. Be certain diode polarity is correct.
(Refer to the wiring diagram, Figure 2-7.) Attach
wires from the truck harness to the coil termi-
nals (See Figure 2-15).
4. Connect battery power as described in Crank-
ing Motor - Installation.

D2-26 24VDC Electrical Supply System D02028

S-ar putea să vă placă și