Documente Academic
Documente Profesional
Documente Cultură
Table of Contents
Page
List of Figures
Fig. 1. Example of mini-load ASRS storage arrangement with open-top cellulosic and unexpanded
plastic containers ............................................................................................................................... 5
Fig. 2. Example of mini-load ASRS storage arrangement with cartoned commodity on unexpanded
plastic trays .......................................................................................................................................... 6
Fig. 3. Flowchart for determining the protection options for mini-load ASRS storage arrangements ........... 7
©2017-2020 Factory Mutual Insurance Company. All rights reserved. No part of this document may be reproduced,
stored in a retrieval system, or transmitted, in whole or in part, in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise, without written permission of Factory Mutual Insurance Company.
8-34 Protection for Automatic Storage
Page 2 FM Global Property Loss Prevention Data Sheets
Fig. 4. Determining whether protection options for mini-load ASRS storage arrangements can be
obtained from Data Sheet 8-9 or must be obtained from this section (2.1) ....................................... 9
Fig. 5. Determining if in-rack sprinklers are required for a mini-load ASRS storage arrangement ............ 13
Fig. 6. Horizontal spacing of in-rack sprinklers when required at every transverse flue space ................. 18
Fig. 7. Horizontal spacing of in-rack sprinklers when not required at every transverse flue space ........... 18
Fig. 8. Horizontal location of in-rack sprinklers from the face of the ASRS storage array ......................... 19
Fig. 9. Horizontal spacing of in-rack sprinklers within transverse flue spaces ........................................... 19
Fig. 10. Horizontal spacing of in-rack sprinklers within transverse flue spaces using a staggered
arrangement ................................................................................................................................... 20
Fig. 11. Maximum 2 ft (0.6 m) horizontal spacing of in-rack sprinklers in a maximum 2 ft (0.6 m)
wide longitudinal flue space ........................................................................................................... 20
Fig. 12. Example of which in-rack sprinklers to choose when the in-rack sprinkler design is based
on 9 sprinklers and longitudinal in-rack sprinklers are 2 ft (0.6 m) apart ...................................... 23
Fig. 13. Example of rack-structure ASRS storage arrangement with roller-type conveyor supports .......... 26
Fig. 14. Rack-structure ASRS storage arrangement with traditional horizontal supports ........................... 26
Fig. 15. Example of a vertically enclosed ASRS storage unit ...................................................................... 35
Fig. 16. Example of a top-loading ASRS arrangement showing maximum 100 ft (30 m) depth in one
direction .......................................................................................................................................... 39
Fig. 17. Example of solid-floored elevated mezzanine levels when span of top-loading ASRS exceeds
100 ft (30 m) in each direction ....................................................................................................... 40
Fig. 18. Example showing the installation of monitor nozzles at ceiling level as an alternative to
elevated mezzanines ...................................................................................................................... 41
Fig. 19. Example showing the use of vertical barriers within a top-loading ASRS arrangement ............... 41
Fig. 20. Top-loading ASRS arrangements where the maximum ceiling height is 25 ft (7.6 m) .................. 42
Fig. 21. Example of top-loading ASRS arrangement with monitor nozzles on perimeter mezzanine level . 46
Fig. 22. Example showing the use of vertical barriers within a top-loading ASRS arrangement ............... 47
Fig. 23. Top-loading ASRS arrangements where the maximum ceiling height is 25 ft (7.6 m) .................. 48
Fig. 24. Example of open-top plastic containers in mini-load ASRS storage arrangementi ....................... 52
Fig. 25. Example of an empty mini-load ASRS storage arrangement where rack uprights are about
2 to 3 in. (50 to 75 mm) wide and about 2 ft (0.6 m) horizontally apart ....................................... 53
Fig. 26. Example of rack-supported ASRS storage arrangement ............................................................... 54
Fig. 27. Example of motorized automated picking robot in a mini-load ASRS storage arrangement
with open-top unexpanded plastic containers ................................................................................ 55
List of Tables
Table 1. Spacing of Ceiling-Level Storage Sprinklers Under Unobstructed Ceiling Construction ............... 11
Table 2. Ceiling Sprinkler Designs for Noncmbustible Containers in Mini-Load ASRS Storage
Arrangements ................................................................................................................................. 15
Table 3. Ceiling Sprinkler Designs for Trays and Combustible Containers in Mini-Load ASRS
Storage Arrangements ................................................................................................................... 15
Table 4. Hose Demand and Water Supply Duration Design Guidelines ...................................................... 16
Table 5. Acceptable Conditions Where Vertical IRAS Increments can be 15 ft (4.5 m) Maximum ............. 21
Table 6. In-Rack Sprinkler Design Guidelines .............................................................................................. 22
Table 7. Ceiling Sprinkler Designs for Noncombustible Containers Protected by In-Rack Sprinklers ........ 24
Table 8. Ceiling Sprinkler Designs for Trays and Combustible Containers Protected by In-Rack Sprinklers . 24
Table 9. Hose Demand and Water Supply Duration Design Guidelines ...................................................... 25
Table 10. Hydraulic Design for In-Rack Sprinkler (IRAS) System Protecting a Rack-Structure ASRS
Storage Arrangement .................................................................................................................... 30
Table 11. Spacing of Ceiling-Level Storage Sprinklers Under Unobstructed Ceiling Construction ............. 32
Table 12. Determining the Hydraulic Design for Ceiling-Level Sprinkler Systems Protecting
Rack-Structure ASRS Storage Arrangements .............................................................................. 33
Table 13. Ceiling-Level Sprinkler Designs for the Protection of Rack-Structure ASRS Storage
Arrangements Supplemented with In-Rack Sprinklers ................................................................ 34
Table 14. Hose Demand Design Guidelines for the Protection of Rack-Structure ASRS Storage
Arrangements ................................................................................................................................ 35
Table 15. Sprinkler Pressure Requirements for the Protection of Vertically Enclosed ASRS Storage Units
Over 25 ft (7.6 m) and up to 55 ft (16.8 m) Tall ........................................................................... 37
Table 16. Spacing of Ceiling-Level Storage Sprinklers Under Unobstructed Ceiling Construction ............. 43
Table 17. Ceiling-Level Protection Guidelines for Top-Loading ASRS Storage Arrangements Using
Solid-Walled Plastic Containers; Storage Height up to and Including 20 ft (6.1 m) .................... 45
Table 18. Ceiling-Level Protection Guidelines for Top-Loading ASRS Storage Arrangements Using
Solid-Walled Plastic Containers; Storage Height in Excess of 20 ft (6.1 m) ............................... 45
1.0 SCOPE
This document provides loss prevention guidelines for mini-load, rack-structure, and vertically enclosed
automatic storage and retrieval systems (ASRS). This data sheet also provides loss prevention guidelines
for top-loading ASRS arrangements that use solid-walled (open- and closed-top) containers. The loss
prevention guidelines specific to this data sheet include Class 1 through 4 and plastic commodities.
Commodity hazards higher than plastics, such as Level 2 and 3 aerosols, ignitable liquids, flammable gasses,
and other special hazards are outside the scope of this data sheet.
Top-loading ASRS arrangements that use containers with walls that are not solid are currently outside the
scope of this data sheet. However, loss prevention guidelines for these types of containers are expected to
be added in 2021.
1.1 Changes
January 2020. Interim revision. Significant changes include the following:
A. Added loss prevention guidelines for top-loading ASRS arrangements that use solid-walled (open- and
closed-top containers).
B. Reformatted the document so each ASRS storage arrangement now has its own section.
2.1.1 General
2.1.1.1 Section 2.1 provides protection guidelines for mini-load automatic storage and retrieval systems
(ASRS) storage arrangements. See Figures 1 and 2 for examples of this type of storage arrangement.
What differentiates these storage racks from traditional pallet load type storage racks are the following:
• Rack uprights that are typically only about 2 ft (0.6 m) apart horizontally as opposed to about 8 ft (2.4
m),
• Tiers that are only about 12 to 18 in. (300 to 450 mm) high as opposed to about 5 ft (1.5 m),
• Product handling that consists of 18 in. x 24 in. (450 mm x 600 mm) trays or open-top containers as opposed
to 4 ft x 4 ft (1.2 m x 1.2 m) pallets,
• Material handling support accomplished by angle irons as opposed to horizontal supports
While the first three bullet points create a unique storage arrangement for the mini-load ASRS, it is the
presence of the angle irons within the mini-load ASRS rack structure that has a major impact on the protection
requirements for them. This is because the angle irons divert most of the sprinkler discharge out to the face
of the rack, thus limiting the amount of sprinkler discharge that can be distributed into the flue spaces of
the storage rack.
Fig. 1. Example of mini-load ASRS storage arrangement with open-top cellulosic and unexpanded plastic containers
2.1.1.2 As with any FM Global loss prevention data sheet, a complete and comprehensive understanding
of the information in this document can only be achieved by a thorough review of its contents. To assist with
the proper use of this section of the data sheet, however, a flowchart has been created. Use the flowchart
provided in Figure 3 in combination with the written text of Section 2.1 to determine the potential automatic
sprinkler protection options for a mini-load ASRS storage arrangement.
Fig. 2. Example of mini-load ASRS storage arrangement with cartoned commodity on unexpanded plastic trays
Fig. 3. Flowchart for determining the protection options for mini-load ASRS storage arrangements
2.1.2.1 General
2.1.2.1.1 Construct storage facilities in accordance with the relevant FM Global property loss prevention data
sheets. See the 1-series data sheets for guidelines relevant to the construction features of most storage
facilities.
2.1.2.1.2 Adhere to the recommendations in the relevant data sheet to ensure the construction features of
the facility are compatible with the ceiling-level storage sprinkler being used.
2.1.2.1.3 Properly anchor all mini-load ASRS rack structures to prevent them from falling over and causing
nearby racks to fall over (i.e., a “domino” effect). Take into consideration the effects of rack loads, the
additional load created by the collection of fire protection water by the stored commodity and its container
(see 2.1.2.1.6), the weight of water-filled, in-rack sprinkler piping (if provided), and any seismic conditions (see
Data Sheet 1-2, Earthquakes).
2.1.2.1.4 Design mini-load ASRS rack-supported structures taking into consideration the effects of weather
(wind, snow, rain, hail, etc.), rack loads, seismic conditions (see Data Sheet 1-2), and the additional load
created by the stored commodity and/or its container collecting or absorbing fire protection water (see
2.1.2.1.6), the weight of water-filled sprinkler piping (from ceiling or in-rack sprinklers), and any other loads
to which the rack or structure may be exposed.
Fig. 4. Determining whether protection options for mini-load ASRS storage arrangements can be obtained from Data Sheet
8-9 or must be obtained from this section (2.1)
2.1.2.1.5.3 If open-top combustible containers are present, assume roughly one-third of the containers stored
vertically within the footprint of the in-rack sprinkler design will be filled with water up to the point where they
will vent, but the other two-thirds of containers will be completely consumed during a fire. The weight of water
is 8.33 lb (3.78 kg) for every 1.0 US gallon (3.8 L).
2.1.3 Occupancy
2.1.4 Protection
2.1.4.1 General
2.1.4.1.1 It is critical that no objects between the top of storage and the ceiling-level sprinklers interfere with
the sprinkler’s proper discharge pattern. See Data Sheet 2-0 for guidelines related to obstructions of storage
sprinklers.
2.1.4.1.2 In addition to the recommendations in this data sheet, follow the sprinkler, ceiling and in-rack,
installation guidelines indicated for storage sprinklers in Data Sheet 2-0.
2.1.4.1.3 For facilities located in earthquake-prone regions, refer to Data Sheet 2-8, Earthquake Protection
for Water-Based Fire Protection Systems.
2.1.4.1.4 To aid in manual firefighting and after-extinguishment mop-up operations, install small hose station
connections within the ASRS storage area. Consult with the local fire service or authority having jurisdiction
to determine their recommendations regarding (1) the use of wet- or dry-barrel connections, (2) the size of
the connection, and (3) the horizontal distance between stations. Arrange water supplies for these hose station
connections in one of the following ways:
A. A piping system dedicated solely for the small hose station connections
B. From a sprinkler system that is different than the one feeding the ASRS storage area
It may be preferable from an operations standpoint to locate hose station connections on the ends of racks.
2.1.4.1.5 Install smoke or heat detection to allow for early notification of a potential fire event. Arrange for
automatic shutdown of material handling systems upon detection activation.
2.1.4.2.1.2 When installing a single-interlock preaction sprinkler system, it must be arranged to be the
equivalent of a wet-pipe sprinkler system. See Data Sheet 5-48, Automatic Fire Detection, for
recommendations related to the installation of detection devices in order to achieve this equivalency.
2.1.4.2.1.3 See Data Sheet 2-0 for additional recommendations related to the installation of all sprinkler
system types.
2.1.4.2.2.3 Mixing Different Ceiling-Level Storage Sprinklers Within the Same Protected Area
2.1.4.2.2.3.1 For a sprinkler system protecting a mini-load ASRS storage arrangement, install ceiling-level
storage sprinklers having the same K-factor, coverage listing (i.e., standard or extended), orientation,
response time index (RTI) rating, and temperature rating throughout the protected area, whenever possible.
See Sections 2.1.4.2.2.3.2 through 2.1.4.2.2.3.5 for possible exceptions.
2.1.4.2.2.3.2 Sprinkler K-Factor. Mixing sprinklers that have different K-factors on the same ceiling-level
sprinkler system within the same ASRS protected area is acceptable when there is a change in the ceiling
height in the same area that requires a different ceiling-level sprinkler design. When this occurs, extend the
higher sprinkler system design a minimum of 15 ft (4.6 m) into the area protected by the lower sprinkler
system design.
2.1.4.2.2.3.3 Sprinkler Coverage Listing. Mixing sprinklers that have different coverage listings (e.g, standard-
coverage and extended-coverage) on the same ceiling-level sprinkler system within the same ASRS
protected area is acceptable when there is a change in the ceiling height in the same area that requires a
different ceiling-level sprinkler design. When this occurs, extend the higher sprinkler system design a minimum
of 15 ft (4.6 m) into the area protected by the lower sprinkler system design.
2.1.4.2.2.3.4 Sprinkler Orientation. Mixing sprinklers that have different orientations (i.e., pendent and upright)
on the same ceiling-level sprinkler system within the same ASRS protected area is acceptable when it is
for the purpose of eliminating obstructions to sprinkler discharge in accordance with Data Sheet 2-0.
2.1.4.2.2.3.5 Temperature Rating. Mixing sprinklers that have different nominal temperature ratings (e.g.,
160°F [70°C], 212°F [100°C], and 280°F [140°C]) on the same ceiling-level sprinkler system within the same
ASRS protected area is acceptable when ambient conditions, such as the immediate area around unit
heaters, require a higher temperature-rated sprinkler to avoid the potential for premature operation.
2.1.4.2.3 Ceiling-Only Sprinkler System Design Criteria
2.1.4.2.3.1 See Figure 5 to determine if a ceiling-only sprinkler protection option is a possibility for the
mini-load ASRS storage arrangement or if in-rack sprinklers are required.
2.1.4.2.3.2 Protect the mini-load ASRS storage arrangement with in-rack sprinklers in accordance with Section
2.1.4.3 when Figure 5 indicates in-rack sprinklers are required.
2.1.4.2.3.3 When Figure 5 indicates that a ceiling-only protection option is available, see Table 2 for the
ceiling-level sprinkler design options protecting noncombustible containers, or Table 3 for ceiling-level
sprinkler design options protecting trays and combustible containers.Note that the design options offered in
Tables 2 and 3 highlighted in green are ceiling-level sprinkler designs where the hose demand is 250 gpm
(950 L/min) and the water supply duration is 60 minutes.
2.1.4.2.3.4 The ceiling-level sprinkler system designs in Tables 2 and 3 are determined based on the maximum
ceiling height of the ASRS protected area. The applicable protection options are based on any ceiling height
indicated in Tables 2 and 3 that is equal to or greater than the maximum ceiling height of the ASRS protected
area.
Fig. 5. Determining if in-rack sprinklers are required for a mini-load ASRS storage arrangement
2.1.4.2.3.5 The ceiling-level sprinkler system design options in Tables 2 and 3 use a design format based
on an indicated number of operating sprinklers at a given minimum operating pressure from the hydraulically
most remote sprinkler. Do not interpolate or adjust the protection values obtained from these tables.
2.1.4.2.3.6 Extend the ceiling-level sprinkler system design at least 15 ft (4.6 m) beyond all edges of the
mini-load ASRS storage area, or to a wall, whenever there is a mixed-use occupancy. However, if the adjacent
storage area has a higher ceiling-level sprinkler system design than that recommended for the mini-load
ASRS storage area, extend the design for the higher hazard 15 ft (4.6 m) into the mini-load ASRS storage
area.
2.1.4.2.3.7 The minimum design area (i.e., the number of sprinklers in the design multiplied by the spacing
of the sprinklers) is 768 ft2 (71.3 m2), except when sprinklers are required in every channel created by
obstructed ceiling construction. When the design area is less than 768 ft2 (71.3 m2) in the presence of
unobstructed ceiling construction, increase the number of sprinklers in the ceiling design to meet or exceed
the required minimum design area.
2.1.4.2.3.8 The units for K-factor given in Tables 2 and 3 are gpm/psi0.5 ([L/min]/bar0.5).
Table 3. Ceiling Sprinkler Designs for Trays and Combustible Containers in Mini-Load ASRS Storage Arrangements
Max. Max. Wet System, Pendent Sprinklers Wet System, Upright Sprinklers
Storage Ceiling Quick-Response Standard-Response Quick-Response Standard-Response
Height Height K11.2 K14.0 K16.8 K22.4 K25.2 K25.2EC K11.2 K14.0 K19.6 25.2 K11.2 K14.0 K16.8 K25.2EC 11.2 K16.8 K25.2
ft (m) ft (m) (K160) (K200) (K240) (K320) (K360) (K360EC) (K160) (K200) (K280) (K360) (K160) (K200) (K240) (K360EC) (K160) (K240) (K360)
FM Global Property Loss Prevention Data Sheets
5 (1.5) 10 (3.0) 20 @ 12 @ 12 @ 10 @ 10 @ 10 @ 20 @ 20 @ 20 @ 20 @ 7 20 @ 20 @ 20 @ 10 @ 20 @ 20 @ 20 @ 7
30 (2.1) 25 (1.7) 18 (1.2) 15 (1.0) 15 (1.0) 22 (1.5) 30 (2.1) 18 (1.2) 16 (1.1) (0.5) 30 (2.1) 18 (1.2) 13 (0.9) 22 (1.5) 30 (2.1) 13 (0.9) (0.5)
15 (4.5) 25 @ 10 @ 10 @ 10 @ 10 @ 12 @ 25 @ 25 @ 25 @ 25 @ 25 @ 25 @ 25 @ 12 @ 25 @ 25 @ 25 @
50 (3.5) 35 (2.4) 25 (1.7) 15 (1.0) 15 (1.0) 38 (2.6) 50 (3.5) 32 (2.2) 16 (1.1) 10 (0.7) 50 (3.5) 32 (2.2) 22 (1.5) 38 (2.6) 50 (3.5) 22 (1.5) 10 (0.7)
Protection for Automatic Storage
10 (3.0)* 15 (4.5) 25 @ 10 @ 10 @ 10 @ 10 @ 12 @ 25 @ 25 @ 25 @ 25 @ 25 @ 25 @ 25 @ 12 @ 25 @ 25 @ 25 @
50 (3.5) 35 (2.4) 25 (1.7) 15 (1.0) 15 (1.0) 38 (2.6) 50 (3.5) 32 (2.2) 16 (1.1) 10 (0.7) 50 (3.5) 32 (2.2) 22 (1.5) 38 (2.6) 50 (3.5) 22 (1.5) 10 (0.7)
20 (6.0) 12 @ 12 @ 12 @ 12 @
50 (3.5) 35 (2.4) 20 (1.4) 20 (1.4)
2.1.4.3.1 General
Use the following procedure to determine the recommended protection options that include both ceiling and
in-rack sprinkler systems:
A. Determine the recommended in-rack sprinkler system types per Section 2.1.4.3.2.
B. Determine the recommended in-rack sprinklers per Section 2.1.4.3.3.
C. Determine the recommended location and positioning of in-rack sprinklers per Section 2.1.4.3.4.
D. Determine the recommended minimum and maximum horizontal spacing of in-rack sprinklers per
Section 2.1.4.3.5.
E. Determine the recommended maximum vertical distances between in-rack sprinklers per Section
2.1.4.3.6.
F. Determine the recommended in-rack sprinkler designs per Section 2.1.4.3.7.
G. Determine the recommended ceiling sprinkler designs when supplemented with in-rack sprinklers per
Section 2.1.4.3.9.
2.1.4.3.4 General Guidelines for the Location and Positioning of In-Rack Sprinklers
2.1.4.3.4.1 When installing in-rack sprinklers in accordance with the recommendations for horizontal
arrangements of in-rack sprinklers (Section 2.1.4.3.4) and their allowable vertical increments (Section
2.1.4.3.5), also incorporate the guidelines provided in Sections 2.1.4.3.4.2 through 2.1.4.3.4.7. Note that this
data sheet provides figures showing plan views for in-rack sprinkler arrangements protecting mini-load ASRS
storage arrangements to assist in the proper location and spacing of the in-rack sprinklers. These figures
use blue rectangles and squares to represent trays or containers and the flue spaces between them.
2.1.4.3.4.2 Locate all in-rack sprinklers (longitudinal and face) horizontally within the footprint of the ASRS
rack storage structure. Note that in-rack sprinklers installed within a longitudinal flue space that does not
exceed 2 ft (0.6 m) in width are considered installed within the footprint of the storage structure.
2.1.4.3.4.3 Locate all in-rack sprinklers (longitudinal and face) within the flue spaces they are intended to
protect and a minimum of 3 in. (75 mm) horizontally from rack uprights.
2.1.4.3.4.4 Locate longitudinal flue sprinklers (where needed) no more than 12 in. (300 mm) horizontally
from the edge of storage.
2.1.4.3.4.5 Locate all in-rack sprinklers (longitudinal and face) in accordance with the minimum and maximum
horizontal distances indicated in the applicable figure.
2.1.4.3.4.6 Locate the in-rack sprinkler’s deflector at or below the bottom of the rack’s horizontal support
member, when it is under full-load conditions, at each tier level where in-rack sprinklers are recommended.
2.1.4.3.4.7 Arrange in-rack sprinklers, and their associated sprinkler piping, to avoid mechanical damage
while still allowing for proper in-rack sprinkler distribution. Prior to installing the in-rack sprinklers, check the
proposed in-rack sprinkler locations to ensure both adequate protection against mechanical damage and
proper sprinkler discharge can be achieved.
Fig. 6. Horizontal spacing of in-rack sprinklers when required at every transverse flue space
Fig. 7. Horizontal spacing of in-rack sprinklers when not required at every transverse flue space
2.1.4.3.5.5 The maximum allowable horizontal in-rack sprinkler spacing within transverse flue spaces is 6 ft
(1.8 m) as demonstrated in Figure 9.
Fig. 8. Horizontal location of in-rack sprinklers from the face of the ASRS storage array
2.1.4.3.5.6 Where ASRS storage arrays can be protected with in-rack sprinklers installed at every other
transverse flue space in accordance with Section 2.1.4.3.5.3, arrange the in-rack sprinklers on a horizontal
stagger, as demonstrated in Figure 10, such that every transverse flue space is provided with in-rack
sprinkler protection.
Fig. 10. Horizontal spacing of in-rack sprinklers within transverse flue spaces using a staggered arrangement
2.1.4.3.5.7 When a longitudinal flue space, up to a maximum width of 2 ft (0.6 m), will be provided between
ASRS rows, as demonstrated in Figure 11, install in-rack sprinklers within the longitudinal flue space on a
maximum spacing of 2 ft (0.6 m). Treat any flue space wider than 2 ft (0.6 m) as an aisle (i.e., a space in which
in-rack sprinklers are not installed).
Fig. 11. Maximum 2 ft (0.6 m) horizontal spacing of in-rack sprinklers in a maximum 2 ft (0.6 m) wide longitudinal flue
space
Table 5. Acceptable Conditions Where Vertical IRAS Increments can be 15 ft (4.5 m) Maximum
Material Handling
Material Handling Composition Container Arrangement Commodity
Trays Noncombustible, Cellulosic, DNA Class 1, 2, 3, 4, Cartoned
or Unexpanded Plastic Plastics or Uncartoned
Unexpanded Plastics
Containers Noncombustible Closed-Top or Open-Top Any
Mesh Class 1, 2, 3, 4, Cartoned
Plastics or Uncartoned
Unexpanded Plastics
Cellulosic Closed-Top Class 1, 2, 3, 4 or Plastics
Vented Open-Top Class 1, 2, 3, 4, Cartoned
Plastics or Uncartoned
Unexpanded Plastics
Unexpanded Plastic Closed-Top Class 1, 2, 3, 4, Cartoned
Plastics or Uncartoned
Unexpanded Plastics
Vented Open-Top Class 1, 2, 3, 4, Cartoned
Plastics or Uncartoned
Unexpanded Plastics
2.1.4.3.7.2.2 In addition to the minimum in-rack sprinkler design flow obtained from Table 6, the minimum
in-rack sprinkler design pressure is 7 psi (0.5 bar).
2.1.4.3.7.2.3 The design obtained from Table 6 applies to the single most hydraulically remote in-rack sprinkler
level.
2.1.4.3.7.2.4 For in-rack sprinkler system design calculation purposes, when more than one line of in-rack
sprinklers is provided at a tier level (occurs once rack rows are more than 3 ft [0.9 m] deep), split the number
of sprinklers in the design evenly between the face sprinklers and the next closest line of sprinklers. If the
number of sprinklers in the in-rack sprinkler design is an odd number, use an odd number of sprinklers at the
face and an even number of sprinklers one line adjacent to the face sprinklers. In addition, where in-rack
sprinklers are spaced 2 ft (0.6 m) or closer, the design can be based on every other in-rack sprinkler operating.
See Figure 12 for an example of this guidance.
2.1.4.3.7.2.5 When the in-rack sprinkler system is installed in accordance with Section 2.1.4.3.7, the in-rack
sprinkler demand does not need to be hydraulically balanced with the ceiling-level sprinkler system, nor does
it have to be accounted for operating simultaneously with the ceiling-level sprinkler system.
2.1.4.3.9 Ceiling-Level Sprinkler System Design Guidelines Supplemented with In-Rack Sprinkler Protection
2.1.4.3.9.1 See Section 2.1.4.2.1 regarding recommendations pertaining to the ceiling-level sprinkler system
and Section 2.1.4.2.2 regarding recommendations pertaining to the spacing and characteristics of the
ceiling-level sprinklers.
Trays or 2 ft 4 ft
containers (0.6 m) (1.2 m)
10 in. to 18 in.
(250 to 450 mm)
< 6 ft
(1.8 m)
< 2 ft (0.6 m)
IRAS to include
in hydraulic
calculation
2.1.4.3.9.2 For noncombustible closed-top and open-top containers, design the ceiling sprinkler system in
accordance with Table 7 taking into account (a) the maximum storage height above the top in-rack sprinkler
level, and (b) the vertical distance between the top level of in-rack sprinklers and the ceiling above. Note
that the design options offered in Table 7 highlighted in green are ceiling-level sprinkler designs where the
hose demand is 250 gpm (950 L/min) and the water supply duration is 60 minutes.
2.1.4.3.9.3 For all trays and combustible containers, design the ceiling sprinkler system in accordance with
Table 8 taking into account (a) the maximum storage height above the top in-rack sprinkler level, and (b)
the vertical distance between the top level of in-rack sprinklers and the ceiling above. Note that the design
options offered in Table 8 highlighted in green are ceiling-level sprinkler designs where the hose demand is
250 gpm (950 L/min) and the water supply duration is 60 minutes.
2.1.4.3.9.4 The ceiling-level sprinkler system designs in Tables 7 and 8 are determined based on the maximum
ceiling height of the ASRS protected area. The applicable protection options are based on any ceiling height
indicated in Tables 7 and 8 that is equal to or greater than the maximum ceiling height of the ASRS protected
area.
2.1.4.3.9.5 The ceiling-level sprinkler system design options in Tables 7 and 8 use a design format based
on an indicated number of operating sprinklers at a given minimum operating pressure from the hydraulically
most remote sprinkler. Do not interpolate or adjust the protection values obtained from these tables.
2.1.4.3.9.6 The minimum design area (i.e., the number of sprinklers in the design multiplied by the spacing
of the sprinklers) is 768 ft2 (71.3 m2), except when sprinklers are required in every channel created by
obstructed ceiling construction. When the design area is less than 768 ft2 (71.3 m2) in the presence of
unobstructed ceiling construction, increase the number of sprinklers in the ceiling design to meet or exceed
the required minimum design area.
2.1.4.3.9.7 The units for K-factor given in Tables 7 and 8 are gpm/psi0.5 ([L/min]/bar0.5).
Table 8. Ceiling Sprinkler Designs for Trays and Combustible Containers Protected by In-Rack Sprinklers
Max. Vertical
Wet System, Pendent Sprinklers Wet System, Upright Sprinklers
Distance
Max. Storage Between Top Quick-Response Standard-Response Quick-Response Standard-Response
Height Above IRAS Level and
K11.2 K14.0 K16.8 K22.4 K25.2 K25.2EC K11.2 K14.0 K19.6 25.2 K11.2 K14.0 K16.8 K25.2EC 11.2 K16.8 K25.2
Top Level of the Ceiling, ft
(K160) (K200) (K240) (K320) (K360) (K360EC) (K160) (K200) (K280) (K360) (K160) (K200) (K240) (K360EC) (K160) (K240) (K360)
IRAS, ft (m) (m)
0 (0) Any 20 @ 7 12 @ 25 12 @ 18 10 @ 15 10 @ 15 6 @ 20 20 @ 7 20 @ 7 12 @ 16 12 @ 7 20 @ 7 12 @ 25 12 @ 18 6 @ 20 20 @ 7 20 @ 7 20 @ 7
(0.5) (1.7) (1.2) (1.0) (1.0) (1.4) (0.5) (0.5) (1.1) (0.5) (0.5) (1.7) (1.2) (1.4) (0.5) (0.5) (0.5)
5 (1.5) 10 (3.0) 20 @ 30 12 @ 25 12 @ 18 10 @ 15 10 @ 15 10 @ 22 20 @ 30 20 @ 18 20 @ 16 20 @ 7 20 @ 30 20 @ 18 20 @ 13 10 @ 22 20 @ 30 20 @ 13 20 @ 7
(2.1) (1.7) (1.2) (1.0) (1.0) (1.5) (2.1) (1.2) (1.1) (0.5) (2.1) (1.2) (0.9) (1.5) (2.1) (0.9) (0.5)
15 (4.5) 25 @ 50 10 @ 35 10 @ 25 10 @ 15 10 @ 15 12 @ 38 25 @ 50 25 @ 32 25 @ 16 25 @ 10 25 @ 50 25 @ 32 25 @ 22 12 @ 38 25 @ 50 25 @ 22 25 @ 10
2.2.1 General
2.2.1.1 Section 2.2 provides protection guidelines for rack-structure automatic storage and retrieval systems
(ASRS) storage arrangements. See Figures 13 and 14 for examples of this type of storage arrangement.
What differentiates these storage racks from traditional pallet load type storage racks are the following:
• Rack uprights that are typically only about 4 ft (1.2 m) apart horizontally as opposed to about 8 ft (2.4
m),
• Product handling that consists of either conveying rollers (see Figure 13) or automated robots that operate
on a track system integrated into the horizontal supports (see Figure 14),
• The lack of flue spaces, parallel to the loading aisle, between pallet loads
While the first two bullet points create a unique storage arrangement for the rack-structure ASRS, it is the
lack of flue spaces parallel to the loading aisle that has a major impact on the protection requirements for this
type of ASRS storage arrangement. While the transverse flue spaces are typically a minimum 6 in. (150
mm) wide and vertically aligned, the lack of flue spaces parallel to the loading aisle create the potential for
a long, shielded area under which fire can potentially spread horizontally unabated.
2.2.1.2 Use FM Approved equipment, materials, and services whenever they are applicable and available.
For a list of products that are FM Approved, see the Approval Guide, an online resource of FM Approvals.
2.2.1.3 Which Data Sheet to Use
2.2.1.3.1 Determine the protection options for a rack-structure ASRS storage arrangement from Data Sheet
8-9, Storage of Class 1, 2, 3, 4 and Plastic Commodities, when the following conditions are satisfied:
• The depth of the rack-structure ASRS storage arrangement does not exceed 16 ft (4.9 m), and
• The pallet loads are stored on the top rail of the horizontal support
2.2.1.3.2 Determine the protection options for a rack-structure ASRS storage arrangement from Data Sheet
8-9, Storage of Class 1, 2, 3, 4 and Plastic Commodities, when the following conditions are satisfied:
• Minimum 3 in. (75 mm) net wide flue spaces are provided a maximum of every 5 ft (1.5 m) horizontally,
or minimum 6 in. (150 mm) net wide flue spaces are provided a maximum of every 8 ft (2.4 m) horizontally,
and
• The flue spaces are aligned vertically, and
Fig. 13. Example of rack-structure ASRS storage arrangement with roller-type conveyor supports
Fig. 14. Rack-structure ASRS storage arrangement with traditional horizontal supports
• The pallet loads are stored on the top rail of the horizontal support
2.2.1.3.3 When the requirements of Section 2.2.1.3.1 or Section 2.2.1.3.2 are not satisfied, use Section 2.2.4
of this data sheet to determine the ceiling and in-rack sprinkler protection recommendations for the protection
of the rack-structure ASRS storage arrangement.
2.2.2.1 General
2.2.2.1.1 Construct storage facilities in accordance with the relevant FM Global property loss prevention data
sheets. See the 1-series data sheets for guidelines relevant to the construction features of most storage
facilities.
2.2.2.1.2 Adhere to the recommendations in the relevant data sheet to ensure the construction features of
the facility are compatible with the ceiling-level storage sprinkler being used.
2.2.2.1.3 Properly anchor all rack-structure ASRS rack structures to prevent them from falling over and
causing nearby racks to fall over (i.e., a “domino” effect). Take into consideration the effects of rack loads,
the additional load created by the collection of fire protection water by the stored commodity and its container
(see 2.2.2.1.6), the weight of water-filled, in-rack sprinkler piping (if provided), and any seismic conditions
(see Data Sheet 1-2, Earthquakes).
2.2.2.1.4 Design rack-structure ASRS rack-supported structures taking into consideration the effects of
weather (wind, snow, rain, hail, etc.), rack loads, seismic conditions (see Data Sheet 1-2), and the additional
load created by the stored commodity and/or its container collecting or absorbing fire protection water (see
2.2.2.1.6), the weight of water-filled sprinkler piping (from ceiling or in-rack sprinklers), and any other loads
to which the rack or structure may be exposed.
2.2.3 Occupancy
2.2.4 Protection
2.2.4.1 General
2.2.4.1.1 It is critical that no objects between the top of storage and the ceiling-level sprinklers interfere with
the sprinkler’s proper discharge pattern. See Data Sheet 2-0 for guidelines related to obstructions of storage
sprinklers.
2.2.4.1.2 In addition to the recommendations in this data sheet, follow the sprinkler, ceiling and in-rack,
installation guidelines indicated for storage sprinklers in Data Sheet 2-0.
2.2.4.1.3 For facilities located in earthquake-prone regions, refer to Data Sheet 2-8, Earthquake Protection
for Water-Based Fire Protection Systems.
2.2.4.1.4 To aid in manual firefighting and after-extinguishment mop-up operations, install small hose station
connections within the ASRS storage area. Consult with the local fire service or authority having jurisdiction
to determine their recommendations regarding (1) the use of wet- or dry-barrel connections, (2) the size of
the connection, and (3) the horizontal distance between stations. Arrange water supplies for these hose station
connections in one of the following ways:
A. A piping system dedicated solely for the small hose station connections
B. From a sprinkler system that is different than the one feeding the ASRS storage area
It may be preferable from an operations standpoint to locate hose station connections on the ends of racks.
2.2.4.1.5 Arrange for automatic shutdown of material handling systems upon detection or sprinkler activation.
2.2.4.2.1.4 See Data Sheet 2-0 for additional recommendations related to the installation of all sprinkler
system types.
2.2.4.2.3 General Guidelines for the Location and Positioning of In-Rack Sprinklers
2.2.4.2.3.1 When installing in-rack sprinklers in accordance with the recommendations for horizontal
arrangements of in-rack sprinklers (Section 2.2.4.2.4) and their allowable vertical increments (Section
2.2.4.2.5), also incorporate the guidelines provided in Sections 2.2.4.2.3.2 through 2.2.4.2.3.4.
2.2.4.2.3.2 Locate all in-rack sprinklers within the footprint of the rack-structure ASRS storage arrangement.
2.2.4.2.3.3 Locate the in-rack sprinkler’s deflector at or below the bottom of the rack’s horizontal support
member, when it is under full-load conditions, at each tier level where in-rack sprinklers are recommended.
2.2.4.2.3.4 Arrange in-rack sprinklers, and their associated sprinkler piping, to avoid mechanical damage
while still allowing for proper in-rack sprinkler distribution. Prior to installing the in-rack sprinklers, check the
proposed in-rack sprinkler locations to ensure both adequate protection against mechanical damage and
proper sprinkler discharge can be achieved.
C. 5 ft (1.5 m) when the highest commodity hazard within the rack-structure ASRS storage arrangement
will be uncartoned plastics (unexpanded or expanded) in either closed-top containers or in noncombustible
open-top containers, or any commodity that will be maintained in combustible open-top containers
When the maximum allowable horizontal distance between transverse flue spaces indicated above is
exceeded, install in-rack sprinklers as outlined in Sections 2.2.4.2.4.1 and 2.2.4.2.4.2 in between the
transverse flue spaces so that the maximum allowable horizontal distance between in-rack sprinklers is not
exceeded.
Table 10. Hydraulic Design for In-Rack Sprinkler (IRAS) System Protecting a Rack-Structure ASRS Storage Arrangement
Vertical Distance IRAS Design, Min.
Between IRAS Flow per IRAS, gpm No. of Installed IRAS IRAS Design, No. of
Commodity Hazard Levels, ft (m) (L/min) Levels IRAS
Class 1, 2 or 3 ≤ 5 (1.5) 30 (115) 1 6
2 or more 10 (5 on top 2 levels)
> 5 (1.5) 60 (230) 1 6
2 or more 10 (5 on top 2 levels)
Class 4 or Plastics ≤ 5 (1.5) 30 (115) 1 8
2 or more 14 (7 on top 2 levels)
> 5 (1.5) 60 (230) 1 8
2 or more 14 (7 on top 2 levels)
of the most remote two sprinklers on the most remote sprinkler branchline. For all other ceiling constructions,
the maximum water delivery time is required with the operation of the most remote two sprinklers on the
most remote two sprinkler branchlines (4 sprinklers total).
2.2.4.3.1.3 When installing a non-interlock or a double-interlock preaction ceiling-level sprinkler system, use
the dry-pipe protection options offered in the applicable protection table for design purposes.
2.2.4.3.1.4 When installing a single-interlock preaction ceiling-level sprinkler system, use the dry-pipe
protection options offered in the applicable table for design purposes. Note that wet-pipe protection options
can be utilized when ceiling-level heat detection is installed on spacing not exceeding the same spacing
used for the ceiling-level sprinklers. See Data Sheet 5-48, Automatic Fire Detection, for addition information
as well as potential other detection arrangements to achieve a wet-pipe sprinkler system design.
2.2.4.3.1.5 When installing a sprinkler system for freezer applications, see Data Sheet 8-29 for additional
recommendations regarding protection against ice plugs.
2.2.4.3.1.6 When installing a maximum 30% propylene glycol in water antifreeze solution, the ceiling-level
sprinkler system can be considered a wet-pipe for design purposes.
2.2.4.3.1.7 See Data Sheet 2-0 for additional recommendations related to the installation of all sprinkler
system types.
Table 11. Spacing of Ceiling-Level Storage Sprinklers Under Unobstructed Ceiling Construction
SprinklerK- Sprinkler Sprinkler RTI Sprinkler Linear Spacing, ft (m) Sprinkler Area Spacing, ft2 (m2)
Factor Orientation Listing Min. Max. Min. Max.
K11.2 (K160) Pendent or Quick or 8 (2.4) 12 (3.7) 80 (7.4) 100 (9.3)
Upright Standard
K14.0 (K200) Pendent Quick or 8 (2.4) 12 (3.6) 64 (6.0) 100 (9.3)
K16.8 (K240) Standard
K19.6 (K280) Upright Quick 8 (2.4) 12 (3.6) 64 (6.0) 100 (9.3)
K22.4 (K320) Standard 8 (2.4) 12 (3.7) 80 (7.4) 100 (9.3)
K25.2 (K360)
K28.0 (K400)
K25.2EC Pendent or Quick 10 (3.0) 14 (4.3) 100 (9.3) 196 (18.2)
(K360EC) Upright
K14.0 (K200) Pendent Quick or 8 (2.4) 10 (3.0) 64 (6.0) 100 (9.3)
K16.8 (K240) Standard
K19.6 (K280) Upright Quick 8 (2.4) 10 (3.0) 64 (6.0) 100 (9.3)
K22.4 (K320) Standard 8 (2.4) 10 (3.0) 80 (7.4) 100 (9.3)
K25.2 (K360)
K28.0 (K400)
K22.4 (K320) Pendent Quick 8 (2.4) 10 (3.0) 64 (6.0) 100 (9.3)
K25.2 (K360)
K28.0 (K400)
2.2.4.3.2.6 Mixing Different Ceiling-Level Storage Sprinklers Within the Same Protected Area
2.2.4.3.2.6.1 For a sprinkler system protecting a rack-structure ASRS storage arrangement, install ceiling-level
storage sprinklers having the same K-factor, coverage listing (i.e., standard or extended), orientation,
response time index (RTI) rating, and temperature rating throughout the protected area, whenever possible.
See Sections 2.2.4.3.2.6.2 through 2.2.4.3.2.6.5 for possible exceptions.
2.2.4.3.2.6.2 Sprinkler K-Factor. Mixing sprinklers having different K-factors on the same ceiling-level sprinkler
system within the same ASRS protected area is acceptable when there is a change in the ceiling height in
the same area that requires a different ceiling-level sprinkler design. When this occurs, extend the higher
sprinkler system design a minimum of 15 ft (4.6 m) into the area protected by the lower sprinkler system
design.
2.2.4.3.2.6.3 Sprinkler Coverage Listing. Mixing of sprinklers having different coverage listings (i.e., standard-
coverage or extended-coverage) on the same ceiling-level sprinkler system within the same ASRS protected
area is acceptable when there is a change in the ceiling height in the same area that requires a different
ceiling-level sprinkler design. When this occurs, extend the higher sprinkler system design a minimum of 15
ft (4.6 m) into the area protected by the lower sprinkler system design.
2.2.4.3.2.6.4 Sprinkler Orientation. Mixing of sprinklers having different orientations (i.e., pendent or upright)
on the same ceiling-level sprinkler system within the same ASRS protected area is acceptable when it is
for the purpose of eliminating obstructions to sprinkler discharge in accordance with Data Sheet 2-0.
2.2.4.3.2.6.5 Temperature Rating. Mixing of sprinklers having different nominal temperature ratings (i.e., 160°F
[70°C], 212°F [100°C], or 280°F [140°C]) on the same ceiling-level sprinkler system within the same ASRS
protected area is acceptable when ambient conditions, such as the immediate area around unit heaters,
require a higher temperature-rated sprinkler to avoid the potential for premature operation.
adjacent storage area has a higher ceiling-level sprinkler system design than that recommended for the
rack-structure ASRS storage area, extend the design for the higher hazard 15 ft (4.6 m) into the rack-structure
ASRS storage area.
2.2.4.3.3.4 The minimum design area (i.e., the number of sprinklers in the design multiplied by the spacing
of the sprinklers) is 768 ft2 (71.3 m2), except when sprinklers are required in every channel created by
obstructed ceiling construction. When the design area is less than 768 ft2 (71.3 m2) in the presence of
unobstructed ceiling construction, increase the number of sprinklers in the ceiling design to meet or exceed
the required minimum design area.
2.2.4.3.3.5 Balance the ceiling-level sprinkler system water demand with the in-rack sprinkler water demand
at the point where the two sprinkler systems are connected.
2.2.4.3.3.6 The units for K-factor given in Table 13 are gpm/psi0.5 ([L/min]/bar0.5).
Table 12. Determining the Hydraulic Design for Ceiling-Level Sprinkler Systems Protecting Rack-Structure ASRS Storage
Arrangements
Maximum Storage
Height Above Top Clearance Between Designated Protection
In-Rack Sprinkler Top of Storage and Scheme Number in
Commodity Hazard Container Type Level, ft (m) Ceiling, ft (m) Table 13
Class 1, 2, or 3 Closed-Top or 10 (3.0) 20 (6.1) 1
Noncombustible
Open-Top
Combustible Open- 5 (1.5) 20 (6.1) 1
Top
Class 4 or Cartoned Closed-Top or 5 (1.5) 20 (6.1) 1
(Unexpanded or Noncombustible 10 (3.0) 5 (1.5) 1
Expanded) Plastics Open-Top 10 (3.0) 2
20 (6.1) 3
Combustible Open- 5 (1.5) 5 (1.5) 1
Top 10 (3.0) 2
20 (6.1) 3
Uncartoned Closed-Top 5 (1.5) 10 (3.0) 4
Unexpanded Plastics 20 (6.1) 5
10 (3.0) 5 (1.5) 5
10 (3.0) 6
20 (6.1) 7
Open-Top 5 (1.5) 10 (3.0) 4
20 (6.1) 5
Uncartoned Expanded Closed-Top 5 (1.5) 10 (3.0) 8
Plastics 20 (6.1) 9
10 (3.0) 5 (1.5) 10
10 (3.0) 11
20 (6.1) 12
Open-Top 5 (1.5) 10 (3.0) 8
20 (6.1) 9
Protection Wet System, Pendent, 160ºF (70ºC); No. of AS @ Pressure, psi (bar) (bar) Pressure, psi (bar)
Scheme Quick Response Standard Response Quick Response Standard Response Standard Response
No. from K14.0 K16.8 K22.4 K25.2 K25.2EC K28.0 K14.0 K19.6 K25.2 K14.0 K16.8 K25.2EC K11.2 K16.8 K25.2 K11.2 K16.8 K25.2
Table 12 (K200) (K240) (K320) (K360) (K360EC) (K400) (K200) (K280) (K360) (K200) (K240) K360EC) (K160)* (K240) (K360) (K160) (K240) (K360)
1 12 @ 50 12 @ 35 12 @ 20 12 @ 20 6 @ 25 12 @ 40 10 @ 7 12 @ 16 12 @ 7 12 @ 50 12 @ 35 6 @ 25 20 @ 7 20 @ 7 12 @ 20 25 @ 7 25 @ 7 20 @ 7
(3.4) (2.4) (1.4) (1.4) (1.7) (2.8) (0.5) (1.1) (0.5) (3.4) (2.4) (1.7) (0.5) (0.5) (1.4) (0.5) (0.5) (0.5)
2 12 @ 50 12 @ 35 12 @ 20 12 @ 20 6 @ 25 12 @ 40 15 @ 15 12 @ 16 12 @ 7 12 @ 50 12 @ 35 6 @ 25 15 @ 25 15 @ 15 12 @ 20 20 @ 25 20 @ 15 20 @ 7
(3.4) (2.4) (1.4) (1.4) (1.7) (2.8) (1.0) (1.1) (0.5) (3.4) (2.4) (1.7) (1.7) (1.0) (1.4) (1.7) (1.0) (0.5)
3 2 @ 50 12 @ 35 12 @ 20 12 @ 20 6 @ 25 12 @ 40 15 @ 35 12 @ 16 12 @ 10 12 @ 50 12 @ 35 6 @ 25 15 @ 50 15 @ 22 12 @ 20 20 @ 50 20 @ 22 20 @ 10
(3.4) (2.4) (1.4) (1.4) (1.7) (2.8) (2.4) (1.1) (0.7) (3.4) (2.4) (1.7) (3.4) (1.5) (1.4) (3.4) (1.5) (0.7)
4 12 @ 50 12 @ 35 12 @ 20 12 @ 20 10 @ 7 12 @ 40 20 @ 7 20 @ 16 20 @ 7 20 @ 7 20 @ 7 10 @ 7 20 @ 7 20 @ 7 20 @ 7 25 @ 7 25 @ 7 25 @ 7
(3.4) (2.4) (1.4) (1.4) (0.5) (2.8) (0.5) (1.1) (0.5) (0.5) (0.5) (0.5) (0.5) (0.5) (0.5) (0.5) (0.5) (0.5)
5 12 @ 50 12 @ 35 12 @ 20 12 @ 20 10 @ 12 12 @ 40 20 @ 10 20 @ 16 20 @ 7 20 @ 10 20 @ 7 10 @ 12 20 @ 16 20 @ 7 20 @ 7 25 @ 16 25 @ 7 25 @ 7
(3.4) (2.4) (1.4) (1.4) (0.8) (2.8) (0.7) (1.1) (0.5) (0.7) (0.5) (0.8) (1.1) (0.5) (0.5) (1.1) (0.5) (0.5)
6 12 @ 50 12 @ 35 12 @ 20 12 @ 20 10 @ 22 12 @ 40 20 @ 20 20 @ 16 20 @ 7 20 @ 20 20 @ 13 10 @ 22 20 @ 30 20 @ 13 20 @ 7 25 @ 30 25 @ 13 25 @ 7
(3.4) (2.4) (1.4) (1.4) (1.5) (2.8) (1.4) (1.1) (0.5) (1.4) (0.9) (1.5) (2.1) (0.9) (0.5) (2.1) (0.9) (0.5)
7 12 @ 50 12 @ 35 12 @ 25 12 @ 25 12 @ 40 12 @ 40 25 @ 35 25 @ 16 25 @ 10 25 @ 35 25 @ 25 12 @ 40 25 @ 50 25 @ 22 25 @ 10 30 @ 50 30 @ 22 30 @ 10
(3.4) (2.4) (1.7) (1.7) (2.8) (2.8) (2.4) (1.1) (0.7) (2.4) (1.7) (2.8) (3.4) (1.5) (0.7) (3.4) (1.5) (0.7)
8 12 @ 75 12 @ 52 12 @ 20 12 @ 20 10 @ 7 12 @ 40 20 @ 7 20 @ 16 20 @ 7 20 @ 7 20 @ 7 10 @ 7 20 @ 7 20 @ 7 20 @ 7 25 @ 7 25 @ 7 25 @ 7
(5.2) (3.6) (1.4) (1.4) (0.5) (2.8) (0.5) (1.1) (0.5) (0.5) (0.5) (0.5) (0.5) (0.5) (0.5) (0.5) (0.5) (0.5)
9 12 @ 75 12 @ 52 12 @ 20 12 @ 20 10 @ 12 12 @ 40 20 @ 10 20 @ 16 20 @ 7 20 @ 10 20 @ 7 10 @ 12 20 @ 16 20 @ 7 20 @ 7 25 @ 16 25 @ 7 25 @ 7
(5.2) (3.6) (1.4) (1.4) (0.8) (2.8) (0.7) (1.1) (0.5) (0.7) (0.5) (0.8) (1.1) (0.5) (0.5) (1.1) (0.5) (0.5)
10 12 @ 75 12 @ 52 12 @ 20 12 @ 20 10 @ 22 12 @ 40 20 @ 20 20 @ 16 20 @ 7 20 @ 20 20 @ 13 10 @ 22 20 @ 30 20 @ 13 20 @ 7 25 @ 30 25 @ 13 25 @ 7
(5.2) (3.6) (1.4) (1.4) (1.5) (2.8) (1.4) (1.1) (0.5) (1.4) (0.9) (1.5) (2.1) (0.9) (0.5) (2.1) (0.9) (0.5)
11 12 @ 75 12 @ 52 12 @ 25 12 @ 25 10 @ 40 12 @ 40 20 @ 35 20 @ 16 20 @ 10 20 @ 35 20 @ 25 10 @ 40 20 @ 50 20 @ 22 20 @ 10 25 @ 50 25 @ 22 25 @ 10
(5.2) (3.6) (1.7) (1.7) (2.8) (2.8) (2.4) (1.1) (0.7) (2.4) (1.7) (2.8) (3.4) (1.5) (0.7) (3.4) (1.5) (0.7)
12 12 @ 75 12 @ 52 12 @ 25 12 @ 25 12 @ 40 12 @ 40 25 @ 35 25 @ 16 25 @ 10 25 @ 35 25 @ 25 12 @ 40 25 @ 50 25 @ 22 25 @ 10 35 @ 50 35 @ 22 35 @ 10
Table 14. Hose Demand Design Guidelines for the Protection of Rack-Structure ASRS Storage Arrangements
No. of Sprinklers in the Ceiling-Level
Ceiling-Level Sprinkler Spacing Type Sprinkler Design Hose Demand, gpm (L/min)
Standard Coverage Up to 12 250
13 or more 500
Extended Coverage Up to 6 250
7 or more 500
2.3.1 General
2.3.1.1 Section 2.3 provides protection guidelines for vertically enclosed automatic storage and retrieval
systems (ASRS) storage arrangements. See Figure 15 for an example of this type of storage arrangement.
2.3.1.2 The protection options in this section for a vertically enclosed ASRS storage unit focus solely on the
protection provided within the unit itself. See the applicable FM Global data sheet for the surrounding
occupancy hazard to determine recommendations pertaining to the construction, occupancy, and protection
of the area in which the vertically enclosed ASRS storage unit is located.
2.3.1.3 Use FM Approved equipment, materials, and services whenever they are applicable and available.
For a list of products and services that are FM Approved, see the Approval Guide, an online resource of FM
Approvals.
2.3.3.1 General
2.3.3.1.1 In addition to the recommendations in this data sheet, follow the sprinkler installation guidelines
indicated for Storage sprinklers in Data Sheet 2-0,Installation Guidelines for Automatic Sprinklers.
2.3.3.1.2 For facilities located in earthquake-prone regions, refer to Data Sheet 2-8, Earthquake Protection
for Water-Based Fire Protection Systems.
2.3.3.1.3 To aid in manual firefighting and after-extinguishment mop-up operations, provide a small hose
station connection near the vertically enclosed ASRS storage unit. Consult with the local fire service or
authority having jurisdiction to determine their recommendation regarding (1) the size of the connection, and
(2) the provision of hose lines. Water supplies for these connections can be either of the following:
A. A piping system dedicated solely for the small hose station connection
B. A sprinkler system that is adjacent to the vertically enclosed ASRS storage unit
2.3.3.1.4 Arrange the vertically enclosed ASRS storage unit for automatic shutdown upon fire/smoke detection
or sprinkler activation.
2.3.3.1.5 If the materials being maintained within the vertically enclosed ASRS storage unit are (a) of high
value, and/or (b) could result in a major interruption to business if damaged, consider the installation of an FM
Approved total flooding gaseous suppression system in accordance with the applicable FM Global 4-Series
Data Sheet to supplement the sprinkler protection recommended in Section 2.3.3.3.
Table 15. Sprinkler Pressure Requirements for the Protection of Vertically Enclosed ASRS Storage Units Over 25 ft (7.6
m) and up to 55 ft (16.8 m) Tall
Maximum Ceiling
Height of
Wet System, Quick Response, 160F (70C), Pendent Storage Sprinklers; Pressure, psi (bar)
Vertically
K14.0 (K200) K16.8 (K240) K22.4 (K320) K25.2 (K360) K28.0 (K400)
Enclosed ASRS
Unit, ft (m)
30 (9.1) 50 (3.4) 35 (2.4) 20 (1.4) 20 (1.4) 40 (2.8)
35 (10.7) 75 (5.2) 52 (3.6) 30 (2.1) 30 (2.1) 40 (2.8)
40 (12.2) 75 (5.2) 52 (3.6) 40 (2.8) 40 (2.8) 40 (2.8)
45 (13.7) 50 (3.4) 50 (3.4) 40 (2.8)
50 (15.2) 63 (4.3) 50 (3.4) 40 (2.8)
55 (16.8) 80 (5.5)
2.3.3.3.2.3 As part of the sprinkler system design include a hose demand allowance of 250 gpm (950 L/min)
for manual intervention and size the water supply so both the sprinkler system and hose demand flows are
available at adequate pressure for a minimum duration of 60 minutes.
2.3.3.3.2.4 As an alternative to the sprinkler options offered in Section 2.3.3.3.2.1, provide sprinkler protection
within the vertically enclosed ASRS storage unit as follows:
A. Install sprinklers at the top of the ASRS unit using standard-coverage, 160°F (70°C) nominally rated,
minimum K11.2 (K160) Storage sprinklers on maximum 8 ft (2.4 m) linear spacing and maximum 64 ft2 (6.0
m2) area spacing, and
B. Install intermediate levels of quick response, 160°F (7°C) nominally rated, minimum K8.0 (K115)
Nonstorage sidewall or extended-coverage sidewall sprinklers installed at both ends of the ASRS unit.
Locate the intermediate levels of sprinklers on a maximum vertical spacing of 10 ft (3.0 m) while leaving
no more than 15 ft (4.6 m) of storage above the top level of intermediate sprinklers, and
C. Design the sprinkler system to account for all sprinklers (ceiling and intermediate) within the vertically
enclosed ASRS storage unit operating at a minimum flow of 30 gpm (115 L/min) from the most remote
sprinkler, and
D. Include a hose demand allowance of 250 gpm (950 L/min) for manual intervention and size the water
supply so both the sprinkler system and hose demand flows are available at adequate pressure for a
minimum duration of 60 minutes
2.3.3.3.2.5 If the top of the ASRS unit is open to the surrounding area, reduce the sprinkler spacing indicated
in Section 2.3.3.3.2.4(a) to a maximum 4 ft (1.2 m) linear spacing and a maximum 16 ft2 (1.5 m2) area
spacing.
2.4 Top-Loading Automatic Storage and Retrieval Systems (ASRS) Using Solid-Walled (Open- and
Closed-Top) Containers
2.4.1 General
This section provides protection guidelines for top-loading automatic storage and retrieval system (ASRS)
storage arrangements that use solid-walled containers.
What differentiates these storage arrangements from other ASRS arrangements is that the containers are
loaded and unloaded vertically from the storage array using automated robots that move about the storage
area on an elevated gridded track network. Since material handling is done in a vertical manner, traditional
material-handling equipment, such as fork-lifts, are not required, eliminating the need for storage aisles.
Due to the lack of aisles, the recommended protection in this section not only focuses on automatic sprinkler
protection for the top-loading ASRS storage array, but also includes recommendations that focus on
extinguishment of the fire by the local fire services.
2.4.1.1 Use FM Approved equipment, materials, and services whenever they are applicable and available.
For a list of products that are FM Approved, see the Approval Guide, an online resource of FM Approvals.
2.4.2.1 General
2.4.2.1.1 Construct storage facilities in accordance with the relevant FM Global property loss prevention data
sheets. See the 1-series data sheets for guidelines relevant to the construction features of most storage
facilities.
2.4.2.1.2 Adhere to the recommendations in the relevant data sheet to ensure the construction features of
the facility are compatible with the ceiling-level storage sprinkler being used.
Fig. 16. Example of a top-loading ASRS arrangement showing maximum 100 ft (30 m) depth in one direction
C. The maximum ceiling height over the storage area is 25 ft (7.6 m) and the ceiling-level sprinklers are
quick-response, minimum K14.0 (K200) standard-coverage pendent Storage sprinklers as shown in
Figure 20.
Fig. 17. Example of solid-floored elevated mezzanine levels when span of top-loading ASRS exceeds 100 ft (30 m) in
each direction
2.4.2.6 Drainage
2.4.2.6.1 Due to the expected water application duration during a fire event, when possible provide minimum
4 in. (100 mm) high curbing in combination with properly designed floor drainage (account for both ceiling
sprinkler discharge and an additional 500 gpm [1900 L/min] for manual firefighting efforts).
Fig. 18. Example showing the installation of monitor nozzles at ceiling level as an alternative to elevated mezzanines
Fig. 19. Example showing the use of vertical barriers within a top-loading ASRS arrangement
Fig. 20. Top-loading ASRS arrangements where the maximum ceiling height is 25 ft (7.6 m)
2.4.3 Occupancy
2.4.3.2 Robots
2.4.3.2.1 Arrange the robots so they are void of as much exterior combustible materials as possible. Use
noncombustible materials whenever decorative covers, sidings or other similar identification methods are
needed for the robots.
2.4.3.2.2 When robots must be equipped with combustible exterior covers or sidings, provide a FM Approved
very-early warning fire detection system over the charging stations area and arrange for manual inspection
and release of the robot to the ASRS grid once the robot’s charge level has been reached.
2.4.3.2.3 Program the robots to proceed to the designated Robot Holding Area during a fire alarm condition.
2.4.4 Protection
2.4.4.1 General
2.4.4.1.1 It is critical that no objects between the top of storage and the ceiling-level sprinklers, including
the robots, interfere with the sprinkler’s proper discharge pattern. See Data Sheet 2-0 for guidelines related
to obstructions of storage sprinklers.
2.4.4.1.2 In addition to the recommendations in this data sheet, follow the sprinkler installation guidelines
indicated for Storage sprinklers in Data Sheet 2-0.
2.4.4.1.3 For facilities located in earthquake-prone regions, refer to Data Sheet 2-8, Earthquake Protection
for Water-Based Fire Protection Systems.
Table 16. Spacing of Ceiling-Level Storage Sprinklers Under Unobstructed Ceiling Construction
Max.
Sprinkler Linear Spacing, ft Sprinkler Area Spacing, ft2
Ceiling
(m) (m2)
Height, Sprinkler Sprinkler Sprinkler RTI
Min. Max. Min. Max.
ft (m) K-Factor Orientation Listing
30 K11.2 (K160) Pendent or Quick or 8 (2.4) 12 (3.7) 80 (7.4) 100 (9.3)
(9.1) Upright Standard
K14.0 (K200) Pendent Quick or 8 (2.4) 12 (3.6) 64 (6.0) 100 (9.3)
K16.8 (K240) Standard
K19.6 (K280) Upright Quick 8 (2.4) 12 (3.6) 64 (6.0) 100 (9.3)
K22.4 (K320) Standard 8 (2.4) 12 (3.7) 80 (7.4) 100 (9.3)
K25.2 (K360)
K28.0 (K400)
K25.2EC Pendent or Quick 10 (3.0) 14 (4.3) 100 (9.3) 196 (18.2)
(K360EC) Upright
35 K14.0 (K200) Pendent Quick or 8 (2.4) 10 (3.0) 64 (6.0) 100 (9.3)
(10.7) K16.8 (K240) Standard
K19.6 (K280) Upright Quick 8 (2.4) 10 (3.0) 64 (6.0) 100 (9.3)
K22.4 (K320) Standard 8 (2.4) 10 (3.0) 80 (7.4) 100 (9.3)
K25.2 (K360)
K28.0 (K400)
45 K22.4 (K320) Pendent Quick 8 (2.4) 10 (3.0) 64 (6.0) 100 (9.3)
(13.7) K25.2 (K360)
K28.0 (K400)
2.4.4.2.2.3 Mixing Different Ceiling-Level Storage Sprinklers Within the Same Protected Area
2.4.4.2.2.3.1 For a sprinkler system protecting a top-loading ASRS storage arrangement, install ceiling-level
Storage sprinklers having the same K-factor, coverage listing (i.e., standard or extended), orientation,
response time index (RTI) rating, and temperature rating throughout the protected area, whenever possible.
See Sections 2.4.4.2.2.3.2 through 2.4.4.2.2.3.5 for possible exceptions.
2.4.4.2.2.3.2 Sprinkler K-Factor. Mixing sprinklers having different K-factors on the same ceiling-level sprinkler
system within the same ASRS protected area is acceptable when there is a change in the ceiling height in
the same area that requires a different ceiling-level sprinkler design. When this occurs, extend the higher
sprinkler system design a minimum of 15 ft (4.6 m) into the area protected by the lower sprinkler system
design.
2.4.4.2.2.3.3 Sprinkler Coverage Listing. Mixing of sprinklers having different coverage listings (i.e., standard-
coverage or extended-coverage) on the same ceiling-level sprinkler system within the same ASRS protected
area is acceptable when there is a change in the ceiling height in the same area that requires a different
ceiling-level sprinkler design. When this occurs, extend the higher sprinkler system design a minimum of 15
ft (4.6 m) into the area protected by the lower sprinkler system design.
2.4.4.2.2.3.4 Sprinkler Orientation. Mixing of sprinklers having different orientations (i.e., pendent or upright)
on the same ceiling-level sprinkler system within the same ASRS protected area is acceptable when it is
for the purpose of eliminating obstructions to sprinkler discharge in accordance with Data Sheet 2-0.
2.4.4.2.2.3.5 Temperature Rating. Mixing of sprinklers having different nominal temperature ratings (i.e., 160°F
[70°C], 212°F [100°C], or 280°F [140°C]) on the same ceiling-level sprinkler system within the same ASRS
protected area is acceptable when ambient conditions, such as the immediate area around unit heaters,
require a higher temperature-rated sprinkler to avoid the potential for premature operation.
2.4.4.2.3 Ceiling-Level Sprinkler System Design Criteria
2.4.4.2.3.1 Use Table 17 to determine the ceiling-level sprinkler system designs for top-loading ASRS storage
arrangements using solid-walled containers having a maximum storage height of 20 ft (6.1 m).
2.4.4.2.3.2 Use Table 18 to determine the ceiling-level sprinkler system designs for top-loading ASRS storage
arrangements using solid-walled containers having a storage height in excess of 20 ft (6.1 m).
2.4.4.2.3.3 The ceiling-level sprinkler system designs in Tables 17 and 18 are determined based on the
maximum ceiling height of the ASRS protected area. The applicable protection options are based on any
ceiling height indicated in Tables 17 and 18 that is equal to or greater than the maximum ceiling height of the
ASRS protected area.
2.4.4.2.3.4 The ceiling-level sprinkler system design options in Tables 17 and 18 use a design format based
on an indicated number of operating sprinklers at a given minimum operating pressure from the hydraulically
most remote sprinkler. Do not interpolate or adjust the protection values obtained from these tables.
2.4.4.2.3.5 For ceiling heights over 45 ft (13.7 m), install a flat, continuous noncombustible false ceiling over
the ASRS storage area and for a minimum of 15 ft (4.6 m) beyond it in all directions. Design the false ceiling
to be capable of withstanding a minimum uplift pressure of 3 lb/ft2 (14.4 kg/m2). Provide sprinkler protection
under this false ceiling in accordance with the applicable protection table.
2.4.4.2.3.6 Extend the ceiling-level sprinkler system design at least 15 ft (4.6 m) beyond all edges of the
mini-load ASRS storage area, or to a wall, whenever there is a mixed-use occupancy. However, if the adjacent
storage area has a higher ceiling-level sprinkler system design than that recommended for the mini-load
ASRS storage area, extend the design for the higher hazard 15 ft (4.6 m) into the mini-load ASRS storage
area.
2.4.4.2.3.7 The minimum design area (i.e., the number of sprinklers in the design multiplied by the spacing
of the sprinklers) is 768 ft2 (71.3 m2), except when sprinklers are required in every channel created by
obstructed ceiling construction. When the design area is less than 768 ft2 (71.3 m2) in the presence of
unobstructed ceiling construction, increase the number of sprinklers in the ceiling design to meet or exceed
the required minimum design area.
2.4.4.2.3.8 The units for K-factor given in Tables 17 and 18 are gpm/psi0.5 ([L/min]/bar0.5).
Table 18. Ceiling-Level Protection Guidelines for Top-Loading ASRS Storage Arrangements Using Solid-Walled Plastic Containers; Storage Height in Excess of 20 ft (6.1 m)
Ceiling-Level Sprinkler Protection Options for Top-Loading ASRS Arrangements Using Solid-Walled Plastic Containers; No. of AS @ psi (bar)
Max. Ceiling Wet System, Pendent Storage Sprinklers, 160ºF (70ºC) Wet System, Upright Storage Sprinklers, 160ºF (70ºC)
Height, ft Quick-Response Standard-Response Quick-Response Standard-Response
Protection for Automatic Storage
(m) K11.2 K14.0 K16.8 K22.4 K25.2 K25.2EC K28.0 K11.2 K14.0 K19.6 K25.2 K11.2 K14.0 K16.8 K25.2EC K11.2 K16.8 K25.2
(K160) (K200) (K240) (K320) (K360) (K360EC) (K400) (K160) (K200) (K280) (K360) (K160) (K200) (K240) (K360EC) (K160) (K240) (K360)
25 (7.6) 15 @ 50 10 @ 50 10 @ 35 10 @ 20 10 @ 20 7 @ 38 10 @ 40 15 @ 50 15 @ 32 15 @ 16 15 @ 10 15 @ 50 12 @ 50 12 @ 35 7 @ 38 15 @ 50 15 @ 22 15 @ 10
(3.5) (3.5) (2.4) (1.4) (1.4) (2.6) (2.8) (3.5) (2.2) (1.1) (0.7) (3.5) (3.5) (2.4) (2.6) (3.5) (1.5) (0.7)
30 (9.1) 20 @ 50 12 @ 50 12 @ 35 12 @ 20 12 @ 20 10 @ 38 12 @ 40 20 @ 50 20 @ 32 20 @ 16 20 @ 10 20 @ 50 12 @ 50 12 @ 35 10 @ 38 20 @ 50 20 @ 22 20 @ 10
(3.5) (3.5) (2.4) (1.4) (1.4) (2.6) (2.8) (3.5) (2.2) (1.1) (0.7) (3.5) (3.5) (2.4) (2.6) (3.5) (1.5) (0.7)
Fig. 21. Example of top-loading ASRS arrangement with monitor nozzles on perimeter mezzanine level
2.4.4.3.2 When solid-floored elevated mezzanine levels are provided, install fixed monitor nozzles on them
in accordance with 2.4.4.3.1 and provide sprinkler protection under the elevated mezzanines in accordance
with 2.4.4.2.3. Similar to the perimeter mezzanine monitor nozzles, the monitor nozzles installed on the
elevated mezzanine can be either anchored to the elevated mezzanine or attached to the ceiling structure.
2.4.4.3.3 Arrange monitor nozzles to be controlled and operated from a dedicated remote location. Install
visible or infrared cameras over the entire storage grid with dedicated feeds to the remote location that will
allow for a means of detecting where the fire area is located. In addition, arrange the monitor nozzles with the
capability of being manually overridden by operators at the monitor nozzles.
2.4.4.3.4 The installation of fixed-in-place monitor nozzles can be avoided when one of the following
conditions are satisfied:
A. Vertical barriers are installed in accordance with Section 2.4.1.2.3(B) and as shown in Figure 22.
B. The maximum ceiling height is 25 ft (7.6 m) and the ceiling-level sprinklers are quick-response, minimum
K14.0 (K200) standard-coverage pendent Storage sprinklers as shown in Figure 23.
C. At the discretion of the local fire service when they can discharge water to all points of the storage
grid area via the use of small hose streams.
Fig. 22. Example showing the use of vertical barriers within a top-loading ASRS arrangement
Fig. 23. Top-loading ASRS arrangements where the maximum ceiling height is 25 ft (7.6 m)
2.4.4.3.5 Water supplies for the monitor nozzles can be arranged in one of the following methods:
A. A piping system dedicated solely for the monitor nozzles
B. From sprinkler systems that are different than the one feeding the ASRS storage area
2.4.4.4 Visible or Infrared Camera Installation for Fixed Monitor Nozzle Operation
2.4.4.4.1 To allow for guided discharge of the monitor nozzles to the point of fire origin, install infrared (IR)
cameras over the entire storage grid, in accordance with this section, using dedicated feeds to the remote
location designated for monitor nozzle operation.
2.4.4.4.2 Arrange the IR cameras as follows:
A. Install longwave infrared (LWIR) cameras, capable of panning and tilting, that have a spectral range
of 8-12 µm, a minimum spatial resolution of 15 pixels/ft (45 pixels/m), measured at the farthest position from
the camera along the top surface of the storage array, and a field of view (FOV) that does not exceed
25°. Avoid the use of IR cameras that use charge-coupled device (CCD) sensors.
B. Locate the cameras vertically as high as possible over the storage grid while also avoiding obstruction
to the camera’s view. Position the cameras horizontally as close as possible to the halfway mark
in-between the locations of the fixed-in-place monitor nozzles. Maintain a minimum horizontal distance
of 10 ft (3.0 m) from any camera to the nearest fixed-in-place monitor nozzle.
C. Install the cameras so that every column of the storage array can be viewed by a minimum of two
cameras.
D. When possible, incorporate data into the camera view that can communicate to the remote location
operator the specific location of the storage grid the camera is viewing.
2.4.4.4.3 The installation of visible imaging cameras can be used in lieu of infrared cameras under any of
the following conditions:
A. The maximum ceiling height will be 25 ft (7.6 m) and the ceiling-level sprinklers will be quick-response,
minimum K14.0 (K200) standard-coverage pendent Storage sprinklers, or
B. The space between the top of the storage grid and the ceiling will be unconfined and the ceiling-level
sprinklers will be quick-response, minimum K14.0 (K200) standard-coverage pendent Storage sprinklers,
or
C. The space between the top of the storage grid and the ceiling will be confined, but manually operated,
ceiling-level ventilation will be provided that can be turned on upon fire service arrival to clear the storage
grid area of visible smoke.
2.4.4.4.4 When visible imaging cameras are an acceptable option per Section 2.4.4.4.3, install visible imaging
cameras over the entire storage grid, using dedicated feeds to the remote location designated for monitor
nozzle operation, as follows:
A. Install cameras, capable of panning and tilting, that have a minimum spatial resolution of 15 pixels/ft
(45 pixels/m), measured at the farthest position from the camera along the top surface of the storage array.
B. Locate the cameras vertically as high as possible over the storage grid while also avoiding obstruction
to the camera’s view. Position the cameras horizontally as close as possible to the halfway mark
in-between the locations of the fixed-in-place monitor nozzles. Maintain a minimum horizontal distance
of 10 ft (3.0 m) from any camera to the nearest fixed-in-place monitor nozzle.
C. Install the cameras so that every column of the storage array can be viewed by a minimum of two
cameras.
D. When possible, incorporate data into the camera view that can communicate to the remote location
operator the specific location of the storage grid the camera is viewing.
E. Arrange the recording equipment so that review of the video is possible to help identify where flames
have been visually observed.
2.4.4.6.2 When fixed monitor nozzles are not provided, include an allowance of 500 gpm (1,900 L/min) for
local fire service hose stream application.
2.4.4.8 Detection
2.4.4.8.1 Install a FM Approved very-early warning fire detection system at ceiling level over the top-loading
ASRS storage area that is intended to operate prior to sprinkler operation in accordance with Data Sheet
5-48. Arrange the detection system to (1) send an alarm to a constantly attended location, as well as (2) trigger
an alarm condition that automatically sends the robots to the Robot Holding Area. When the ceiling over
the storage grid area meets the definition of “obstructed ceiling construction” per Data Sheet 2-0, install
detection in every channel formed by obstructed ceiling construction when the vertical ceiling members are
deeper than 12 in. (300 mm).
2.4.4.8.2 Install a FM Approved smoke detection system specifically for the robot charging station area that
upon activation will (1) deactivate the robot charging stations, (2) deactivate the robots on the storage grid,
and (3) send an alarm to a constantly attended location.
Fig. 24. Example of open-top plastic containers in mini-load ASRS storage arrangementi
Fig. 25. Example of an empty mini-load ASRS storage arrangement where rack uprights are about 2 to 3 in. (50 to 75
mm) wide and about 2 ft (0.6 m) horizontally apart
Fig. 27. Example of motorized automated picking robot in a mini-load ASRS storage arrangement with open-top
unexpanded plastic containers
an open-top container hazard. Unexpanded plastic containers are typically either solid throughout or
collapsible where the hinge is located near the bottom of container. This hinge does allow for water to vent
from the container in a timely fashion provided that the hinge is located close enough to the bottom of the
container and the product inside the container doesn’t block the water from escaping.
3.1.4.1 General
A top-loading ASRS storage arrangement consists of an open metal grid structure that is supported by metal
columns located at the corner of each of the grid openings. Under each grid opening is a solid-piled column
of storage containers that are vertically aligned due to the angle irons provided on the metal support columns.
The containers used in top-loading ASRS storage arrangements are almost always open-top and made from
high-density polyethylene (HDPE) plastic. The top of the grid acts as a track across which remotely operated
robots transverse; the robots are used to either remove containers from the storage grid for picking
operations, or are used to return containers to their designated storage location. The track that the robots
operate on is about the same width as the flue spaces surrounding each container.
3.1.4.3 Batteries
In general, the batteries in use are one of two types: lead-acid or lithium-ion with the latter gaining more
popularity in recent times. For designs with Li-ion batteries, charging rates could be substantially higher than
for the lead acid counterparts. This can put additional stress on the current carrying parts of the battery pack
and charger in addition to the batteries themselves, which tend to heat at higher current levels. A Battery
Management System (BMS) is provided for the safe operation of the Li-ion battery pack.
Batteries use different chemistries. As indicated above, the chemistries typically observed in top-loading ASRS
robots are lead-acid and lithium-ion batteries. Lead-acid batteries are typically of the sealed type. Li-ion
batteries consist of several Li-ion cells (cylindrical or prismatic) connected in series/parallel combination to
meet the voltage, power and capacity requirements of the application. The battery pack also consist of the
BMS and instrumentation to continuously monitor the battery state of charge, state of health. The BMS also
provides safety operation limits on charge/discharge voltage and currents. The chargers for these Li-ion
batteries follow specific charging profiles depending on the Li-ion chemistry used in the cells.
4.0 REFERENCES
4.1 FM Global
Data Sheet 1-2, Earthquakes
Data Sheet 1-10, Smoke and Heat Venting in One-story Sprinklered Buildings
Data Sheet 2-0, Installation Guidelines for Automatic Sprinklers
Data Sheet 2-1, Corrosion in Automatic Sprinkler Systems
Data Sheet 2-8, Earthquake Protection for Water-Based Fire Protection Systems
Data Sheet 5-48, Automatic Fire Detection
Data Sheet 7-43, Process Safety
Data Sheet 7-110, Industrial Control Systems
Data Sheet 8-1, Commodity Classification
Data Sheet 8-9, Storage of Class 1, 2, 3, 4 and Plastic Commodities
Data Sheet 8-29, Refrigerated Storage
Data Sheet 10-1, Pre-Incident Planning
Data Sheet 10-8, Operators
Mini-load ASRS storage arrangement: An automatic storage and retrieval system that uses trays or small
totes/containers for material handling as opposed to traditional pallet loads. They are differentiated from other
storage racks due to the presence of angle irons, which result in the diversion of sprinkler discharge toward
the face of the rack and away from both the longitudinal and transverse flue spaces. Mini-load ASRS rack
structures typically use rack uprights that are about 18 to 24 in. (450 to 600 mm) horizontally apart and are
about 2 to 3 in. (50 to 75 mm) in size (both width and depth). Tier heights are roughly 1 ft (0.3 m) and product
handling is typically supported on angle irons (see Figure 24).
Modular in-rack sprinkler protection arrangement: An in-rack sprinkler protection arrangement that is
designed to prevent the vertical spread of fire beyond the first level of in-rack sprinklers that the fire
encounters. This in-rack sprinkler arrangement therefore allows the in-rack design to be based on the
operation of a given number of sprinklers at only one level and does not need to account for ceiling sprinkler
operation as part of its design.
Monitor nozzle: A nozzle used for water discharge to a fire area that can turn 360º in a horizontal plane
while also having a limited play in a vertical plane.
Net Flue Space Width: The gross horizontal width of the flue space minus the width of any horizontal support
members, such as angle irons, that are located within the flue space.
Rack structure ASRS storage arrangement: An automatic storage and retrieval system that is similar to
traditional open-frame storage racks except that (1) the horizontal distance between rack uprights is sized for
only one pallet load, and (2) the support within the rack for the pallet loads tends to be either roller-type
conveyors or horizontal supports that are oriented perpendicular to the loading aisle as opposed to parallel
to it (see Figures 13 and 14).
Solid-walled container: Containers that do not allow the external release of water from them in a timely
fashion into the transverse flue space. Containers that do not meet the guidelines outlined for vented
containers are treated as solid-walled containers for sprinkler protection design purposes.
Top-loading ASRS: An automatic storage and retrieval system that consists of a metal grid structure under
which containers, usually open-top and made of unexpanded plastic, are stacked one on top of another in
vertically aligned columns. They are accessed from the top of the grid by service robots that have been
programmed to either retrieve a specific container for commodity picking purposes, or for replenishing the
amount of commodity maintained within the storage container.
Tray: A product material handling unit that has an extension around its perimeter that does not rise
more than 1 in. (25 mm) vertically.
Vented container: Containers that release water into the transverse flue space from within them in a timely
fashion. Containers that meet this definition include (1) collapsible containers that are hinged along the
bottom perimeter of the container, or (2) containers whose sides, when loaded parallel to the transverse flue
space, have a minimum 30% venting area within 0.5 in. (13 mm) vertically from the internal bottom of the
container.
Vertical barrier: A barrier that is installed within the transverse flue space of a storage rack for the purpose
of preventing fire from spreading beyond it. It spans the entire height of the rack as well as its depth, including
across any longitudinal flue spaces, from one face of the rack to the other. It is not intended to span across
a material-handling aisle located between storage racks.
Vertically enclosed ASRS: An ASRS unit that typically works with a vertical lift system or a vertical carousel.
The lift system uses a robotic picker that will store and remove trays that rest on fixed storage supports within
the unit and deliver it to the user. The carousel conveyor system uses a rotating storage arrangement that
brings the storage tray to the user. Typical systems are package units where metal trays supported on a rack.
C. Incorporated the results of recent full-scale fire testing of top-loading automatic storage and retrieval
systems using solid-walled plastic containers.
January 2018. Interim revision. Clarifications were made to section 2.2.4.2, Longitudinal Flue Spaces,
corrected reference to the table in sections 2.2.4.1.3 and 2.3.4.1.2. Also corrections were made to Table 11,
IRAS Design Guidelines.
October 2017. Interim revision. Minor editorial changes were made.
July 2017. This data sheet has been completely rewritten. The following major changes were made:
A. This data sheet now addresses protection options for ASRS vertically enclosed, rack-structure,
mini-load, and other storage arrangements in which the horizontal support for product material handling
uses rails, angle irons, or other similar supporting structures. When in-rack automatic sprinkler (IRAS)
protection is needed, the protection now offered in this data sheet is designed to prevent the fire from
growing vertically past the in-rack sprinkler protection that has been installed. With this arrangement, the
ceiling and in-rack sprinkler systems operate independent of each other and thus do not need to be
hydraulically balanced nor designed with both systems operating concurrently.
B. The term “storage sprinkler” has been incorporated into this data sheet to replace “Control Mode Density
Area (CMDA) sprinkler.”
C. Ceiling-level sprinkler designs now use the “number of sprinklers @ minimum pressure” design format
in place of the previously used “density/demand area” design format.
D. Added terms to Appendix A, Glossary of Terms.
January 2003. Clarification regarding the storage clearance was added.
September 2000. This revision of the document has been reorganized to provide a consistent format.