xP Expansion Point Assignments Mechanical

xP Expansion Module points add to the existing points within the controller.
The point assignment in the first xP module connected to a controller will be
one more than the highest point number that exists in the controller.
xP Expansion Module Reference for UL 864 30-3001-1010 Rev A

Subsequent Expansion modules plugged into other expansion modules assume


point assignments that are one higher than the previous module.
7.10 (180)

0.16 (4) 6.78 (172)


6.78

FIRST EXPANSION POINT ASSIGNMENTS


FOR bCX1-S CONTROLLER 3.21
(82)
First Expansion Point 2.55
INPUT OUTPUT (65)

1 1

0.33 (8)
4X .187 (5) THRU

Note: This equipment is intended for field installation within the


UL Listed enclosure model UL-ENCL.

xP Expansion Module Pin Assignments

xP DO2-S xP DO4-S xP DI8-S xP UI4-S


NC NC RTN RTN
1 C 1 C IN1 IN1
bCX1-S Controller
NO NO IN2 IN2
NC NC RTN RTN
2 C 2 C IN3 IN3
NO NO IN4 IN4
NC RTN
3 C IN5
NO IN6 Caution: Earth ground ( )
NC RTN ! must be connected to avoid
module damage
Modules Plug Together
4 C IN7
NO IN8 Adding an expansion module to a
controller may be done while the power
is applied.

Note: All inputs and outputs


are power-limited.

© 2010 Schneider Electric. All Rights Reserved. Schneider Electric - One High Street - North Andover MA USA 01845
xP Expansion Module Combinations xPDO2-S/xPDO4-S

Expansion I/O Module Features


MODULE POINTS Relay Output Module Output Override Control
OUTPUTS INPUTS
Digital Universal Digital NC OFF The output relay is de-energized to an ‘OFF’
state manually by setting the switch to OFF.
Digital Output Only: Programs have no effect on the output when
the switch is in this position.
xPDO2-S 2 LOAD
xPDO4-S 4 C
AUTO The action of the output relay is determined as
OFF AUTO ON
a direct result of program control.
Universal Input Only: ON The output relay is energized to an ‘ON’ state
manually by setting the switch to ON. Programs
xPUI4-S 4* LOAD have no effect on the output when the switch
NO
is in this position.
Digital Input Only :
xPDI8-S 8
Contact Rating: 3A @ 24 VAC
* xPUI4-S input 4 may be configured as a high speed (140Hz) counter input. 3A @ 30 VDC

Relays are evaluated for resistive load only.

Digital Output (relay/triac) maximum wire length: 660 ft. 14-18 AWG

Note: All circuits are Non-Supervised.

Basic Expansion Limitations xPDI8-S xPUI4-S


The number of expansion modules is limited by the controller firmware and the capacity
of the power supply current available from the controller. The firmware supports a maximum
of two modules as long as the power consumption does not draw more current than the
controller can supply.
Digital Input Module Universal Input Module
bCX1-S Controller: Maximum current available is 400mA.

Module # Channels Current Draw @ 24VDC


Digital logic IN x
xPDO2-S Digital Output Module 2 60mA Signal
IN x IN x
+
xPDO4-S Digital Output Module 4 100mA
IN x Thermistor
xPUI4-S Universal Input Module 4 50mA V DC Voltage

xPDI8-S Digital Input Module 8 25mA Contact RTN - RTN


Closure

Note: Cable length for I/O modules is n ot evaluated by UL. RET


Max DC Input Voltage = 5V

IN x
Contact
Closure

UL Listed Voltage Range: 0-5 VDC RTN

Universal inputs can also use contacts for counting. Inputs 1-3
support counting up to 4Hz (four contact closures per second).
UL 916 Listed product for the United States and Canada, Open Energy Management Equipment. Input 4 can support counting up to 140Hz (140 closures per second).
Minimum Pulse Width
Input 1-3 Min. ON/OFF time: 125 milliseconds.
Input 4 Min. ON/OFF time: 3.57 milliseconds.

UL Listed product for the United States. UL 864, 9th Edition


Smoke Control System Digital Input maximum wire length: 660 ft. 22 AWG
Thermistor Input maximum wire length: 250 ft. 18 AWG
Voltage Input maximum wire length: 660 ft. 22 AWG
Note: All circuits are Non-Supervised.
Note: Refer to the UL 864 Listed manuals (the UL 864 Infinet Smoke Control System Design Guide, 30-3001-1006, and the
UL 864 BACnet Smoke Control System Design Guide, 30-3001-1007, for specific wiring, operation, and compatibility information. Note: All circuits are Non-Supervised.