10-600kW Gensets
Description
The optional Motorized Damper kits improve heat retention inside genset enclosures in cold climate conditions. Damper assemblies are held closed
by energized actuators when the genset is not running, and spring open when the actuator de-energizes when a genset start/run signal is present.
Actuator
• Spring-Return Direct Coupled Actuator
• 90 in-lb torque (10 Nm)
• Accepts 24-240VAC 50/60Hz power supply
• Ambient Temp Range: -22ºF to 122ºF (-30ºC to 50ºC)
• Ambient Humidity: 95%, non-condensing
• Manual override
• Optional auxiliary switches, two SPDT
• Factory wired to unit-mounted load center, 120VAC
• CE/CUL Listed
Dampers
• Frame construction: Extruded aluminum
• Damper blades: Aluminum shell injected with polyurethane DAMPER ACTUATOR
• Non-metalic side seals to reduce thermal bridging
• Maintenance-free bearings and linkage
• Blade Seals: Extruded EPDM
• Frame Seals: Extruded Silicone
• Leakage Class: 1A @ 1” WC (0.25 kPa) static presure
differential (AMCA Certified)
AIR INTAKE
MOTORIZED DAMPERS
TYPICAL LOCATION
ENCLOSURE
1 OF 1