Sunteți pe pagina 1din 6

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

90ACA10 400 kV ± 5% 60Hz S.S. ELEVADORA MAIN BUS BAR


A 90ACA20 TRANSFER BUS BAR
Symbols IEC 60617 A

11ACA20 11ACA10 11ACA20 90ACA10 90ACA20


GS202 GS201 GS201 GS200 GS200 Title Symbol Title Symbol

Fuse
cable, line
11ACA10
GS602 90ACA00 Fuse switch-disconnector;
GS100 Screened Conductor
On-load isolating fuse switch
11ACA10
GS100 Surge diverter;
Connection point
Lightning arrester
B 11ACA10 B
GS601 Neutral point Resistor

freigegeben/ Released
11ACA10
Potentiometer
GS200 Plug and socket
with movable contact

Cable sealing end Capacitor

Triode thyristor Semiconductor diode


11ACA10
GS600
Object Three-phase winding, delta
C C
Adjustability, pre-set Three-phase winding, star
SUBSTATION, FOR DETAILS SEE HV SLD SUBSTATION, FOR DETAILS SEE HV SLD
5
Three-phase winding, star
Adjustability step by step
POWER PLANT POWER PLANT with neutral brought out
Machine general symbol *
Thermal effect G: Generator, M: Motor

GEN STEP-UP TRANSFORMER Electromagnetic effect


Transformer
with two windings
11BAT10
350 MVA Transformer
Earth with three windings
ODAF
D 6O/70 K temp. rise (Oil/Winding) D
405 kV ± 2 x 2.5% / 18 kV (DETC) Contactor Current transformer
YNd1
u k = 15% to 350 MVA base
Circuit Breaker Voltage transformer

Disconnector; Isolator DC/DC converter


11BAA60
Switch-disconnector; ~
Rectifier
On-load isolating switch
11BAA40 Starter-regulator Inverter
11BAA30 11BAA50 with thyristors ~
E E
18 kV Reactor
Battery of primary or
secondary cells
TRANSF. COMPARTMENT TRANSF. COMPARTMENT
GEN CIRCUIT BREAKER L
57GL
11BAA30
GE Symbols
+11BAC10 GS600

Title Symbol Title Symbol


EXCIT. TRANSFORMER ISOLATION TRANSFORMER UNIT AUXILIARY TRANSFORMER 17

11MKC10 11BPT10 11BBT10


Earthing Facility Normally Open (NO)
2.5 MVA 8.75 MVA 26 MVA 76 Ohm
F AN AN ONAN / ONAF 50A/10sec F
18 kV / 0.95 kV 18 kV / 4.16 kV 18 kV ± 8 x 1.25% / 6.9 kV Isolated-Phase Bus Local Operated L
11BAA30 u k = 6% u k = 8% Dyn1 11BBT10
GS800 u k = 11% GB600 Voltage transformer Remote Operated
R
89G three windings from Control System
11MKA10 Static Transfer Switch Automatically Operated
GS200 D
with Manual Bypass for UPS from Device
L
Transfer via ECS
COMBINED STARTING AND Scope division
according Electrical Operating Concept
T
EXCITATION COMPARTMENT (LEC)
52G Container, Module, Cubicle, Variable Frequency Drive VFD
=11MKA10 Panel, Box, Enclousure
GS100 VOLTAGE
G MEASUREMENT
G
R T0 11BBT10GT200 Cable Thermal Short Circuit Current 1sec. I th
SHEET 3
57GG 41AC 52SS-1
L
11BAA20
GS600
11MKC10
GT200
11MBJ10
GU100 NOTES
D D
-ALL EQUIPMENT DATA ARE PRELIMINARY AND SUBJECT TO ADJUSTMENT AND AMENDMENT
89SS-1 -ALL SWITCHES ARE NORMALLY CLOSED; EXCEPTIONS ARE MARKED (NO)
11MKA10
GS101 DC REACTOR
-EQUIPMENT TYPE AND RATING PER DETAILED DESIGN AND LOAD LIST
LCI (SSD)
H 11MBJ 11MBJ10GT002
REFERENCES H
ONE LINE DIAGRAM GT: 126T4170
11BAA20 ONE LINE DIAGRAM ST: 126T4887
VOLTAGE
18 kV MEASUREMENT AC REACTOR HV SINGLE LINE DIAGRAMS:
- S.S. Elevadora: EVM-ELE-400-CB-GIQ-100-SL
11MBJ10GT001 - S.S. Maniobras: EVM-MAN-230-CB-GIQ-100-SL
EVM-MAN-400-CB-GIQ-100-SL
89MD-1 GRAPHICAL SYMBOLS FOR DIAGRAMS: IEC 60617-SN (2009-02)
11MBJ10
M GS100
J M
D
J
TO 12MBJ
SHEET 2
89TS R
11MBJ10
GS401

STATIC EXCITATION SYSTEM


11MKC Owner Contractor
GENERATOR
11MKA10 41DC
H53 11MKB10
K RATED POWER GS100 K
(AT 40°C COOLING GAS VOLTAGE
INLET TEMPERATURE) MEASUREMENT
D
328 MVA
cos = 0.90 G
18 kV ± 5%
3~
GT11
D 2018-05-23 R. Grosser R. Hug J. Huser GENERAL UPDATE
GEN TERMINAL ENCLOSURE C 2017-12-18 J. Menzel R. Hug J. Huser GENERAL UPDATE
+11BAA10 B 2017-10-13 J. Menzel R. Hug J. Huser SECOND ISSUE
L A 2017-07-13 J. Menzel R. Hug J. Huser FIRST ISSUE L
Rev. Revision/Date Created by Checked by Approved by Description
Revision History
Project
EVM II
Replaces Derived from Customer Code KKS
89ND ELA12716
11BAA10 R
Dept. Responsable Created by Checked by Approved by
GS101 (NC, ONLY OPEN
DURING STARTUP) GSEEE - CH R. Grosser R. Hug J. Huser
0.39 Ohm GE Document Code Document Type Scale Document Status Format
25 kVA
531 A 12 kV / 0.24 kV % ELECTRONICALLY RELEASED A1
GE Proprietary CLASS II (Internal) EMX/00/E/001b---004/SD/001 DRAWING
1 min Originator
© GE COPYRIGHT 2018. General Electric Company (USA) Title, Subtitle Identification number

M
All rights reserved. The information herein is Proprietary and Technically Exclusive content that is solely owned by General Electric Company
and/or its affiliates. Thus, it is being provided with the explicit expectation of restricted and privileged use. All persons or legal entities receiving GE POWER 2 x 1 7HA.02 MS Advant Edge 1GP006596 M
this information shall be deemed by the act of its receipt have contractually agreed to make no duplications, reproductions of any nature by any
means, modifications, disclosures, or use any portion of this material; except as is expressly authorized in writing by the General Electric Gas Power SINGLE LINE DIAGRAM Rev. Date Lang. Sheet

Company, and/or its legitimate affiliates. Systems D 2018-05-23 E 1/6


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

GIS, SF6 230 kV ± 5% 60Hz S.S. ELEVADORA 90ACA10 400 kV ± 5% 60Hz S.S. ELEVADORA MAIN BUS BAR
A 90ACA20 TRANSFER BUS BAR A

10ADA10 12ACA20 12ACA10 12ACA20


GS201 GS202 GS201 GS201

10ACA10 12ACA10
GS602 GS602

10ADA10 12ACA10
GS100 GS100

B 10ACA10 12ACA10 B
GS601 GS601

freigegeben/ Released
10ADA10 12ACA10
GS200 GS200

10ADA10 12ACA10
GS600 GS600

C C
SUBSTATION, FOR DETAILS SEE HV SLD SUBSTATION, FOR DETAILS SEE HV SLD

POWER PLANT POWER PLANT

GEN STEP-UP TRANSFORMER GEN STEP-UP TRANSFORMER


10BAT10 12BAT10
400 MVA 350 MVA
ODAF ODAF
D 6O/70 K temp. rise (Oil/Winding) 6O/70 K temp. rise (Oil/Winding) D
233 kV ± 2 x 2.5% / 18 kV (DETC) 405 kV ± 2 x 2.5% / 18 kV (DETC)
YNd1 YNd1
u k = 15.5% to 400 MVA base u k = 15% to 350 MVA base

12BAA60

12BAA30 12BAA40
18 kV
E 12BAA50 E

TRANSF. COMPARTMENT TRANSF. COMPARTMENT


GEN CIRCUIT BREAKER L
57GL
+12BAC10 12BAA30
GS600

EXCIT. TRANSFORMER ISOLATION TRANSFORMER UNIT AUXILIARY TRANSFORMER 17

12MKC10 12BPT10 12BBT10


2.5 MVA 8.75 MVA 26 MVA 76 Ohm
F AN AN ONAN / ONAF 50A/10sec F
18 kV / 0.95 kV 18 kV / 4.16 kV 18 kV ± 8 x 1.25% / 6.9 kV
12BAA30 u k = 6% u k = 8% Dyn1 12BBT10
GS800 u k = 11%
EXCITATION TRANSFORMER COMPARTMENT GB600
89G
12MKA10
GS200
L
EXICITATION TRANSFORMER COMBINED STARTING AND
=10MKC10 EXCITATION COMPARTMENT (LEC)
3.15 MVA
52G
10BAA40 =12MKA10 VOLTAGE T0 12BBT10GT200
G GS100
MEASUREMENT SHEET 3 G
R
18 kV / 1.05 kV
u k = 6% 57GG 41AC 52SS-2
L 12MKC10 12MBJ10
12BAA20 GT200 GU100
GS600
10BAA20 D D
18 kV
89SS-2
12MKA10
GS101 DC REACTOR
LCI (SSD)
H 12MBJ 12MBJ10GT002 H

12BAA20 VOLTAGE
GEN TERMINAL ENCLOSURE 18 kV MEASUREMENT AC REACTOR
+10BAA10
12MBJ10GT001

89MD-2
12MBJ10
EXCITATION COMPARTMENT M GS100
J J
STATIC EXCITATION SYSTEM D
FROM 11MBJ
=10MKC SHEET 1
41AC
10MKC10
GT200

STATIC EXCITATION SYSTEM


12MKC
GENERATOR
GENERATOR 41DC 12MKA10 41DC
10MKA10 10MKB10 H53 12MKB10
K H53 GS100 RATED POWER GS100 K
RATED POWER (AT 40°C COOLING GAS VOLTAGE
(AT 40°C COOLING GAS R INLET TEMPERATURE) MEASUREMENT
D
INLET TEMPERATURE) 328 MVA
380 MVA G cos = 0.90 G
cos = 0.90
18 kV ± 5% 3~ 18 kV ± 5%
3~
ST10 GT12
GEN TERMINAL ENCLOSURE
+12BAA10
L L

89ND 89ND
10BAA10 L 12BAA10 R
GS101 (NC, ONLY OPEN GS101 (NC, ONLY OPEN
FOR TESTING) DURING STARTUP)
0.446 Ohm 0.39 Ohm GE Document Code Document Type Scale Document Status Format
25 kVA 25 kVA
466 A 12 kV / 0.24 kV 531 A 12 kV / 0.24 kV EMX/00/E/001b---004/SD/001 DRAWING % ELECTRONICALLY RELEASED A1
1 min 1 min Originator Title, Subtitle Identification number

M GE Proprietary CLASS II (Internal) GE POWER 2 x 1 7HA.02 MS Advant Edge 1GP006596 M


© GE COPYRIGHT 2018. General Electric Company (USA)
All rights reserved. The information herein is Proprietary and Technically Exclusive content of the General Electric Company and/or its legitimate Gas Power SINGLE LINE DIAGRAM Rev. Date Lang. Sheet

affiliates. Systems D 2018-05-23 E 2/6


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

A A
FROM 11BBT10 FROM 12BBT10
SHEET 1 SHEET 2

MAIN E-ROOM

L L MV ROOM
11BBT10 12BBT10
GS600 GS600

B B
52AUX 52AUX

freigegeben/ Released
11BBT10 12BBT10
GT200 GT200
L
00BBA10
R T U r = 6.9 kV (3P) R T L
00BBB10 U r = 6.9 kV (3P)
GS600 I r = 3150 A GS600 I r = 3150 A
TO 00BBA10 00BBA10 MV SWGR I th = 40 kA 00BBB10 MV SWGR I th = 40 kA TO 00BBB10
SHEET4 SHEET 5

00BFT10 00BBB10 00BFV10 00BFU10


C GT100 GS100 GT100 GT100 C
R (NO) R R
R T

L L L L
00BBB10
GS601

MAIN E-ROOM
D LV ROOM D
AUX TRANSFORMER AUX TRANSFORMER AUX TRANSFORMER
00BFT10 00BFV10 00BFU10
2.5 MVA 2.5 MVA 2.5 MVA
AN AN AN
6.9 kV ± 2 x 2.5% 6.9 kV ± 2 x 2.5% 6.9 kV ± 2 x 2.5%
0.48 kV 0.48 kV 0.48 kV
Dyn1 Dyn1 Dyn1
u k = 8.6% u k = 8.6% u k = 8.6%

E E
00BFT10 00BFV10 00BFU10
GT200 GT200 GT200
R T R T R T
U r = 480 V AC (3P+PE) U r = 480 V AC (3P+PE) U r = 480 V AC (3P+PE)
I r = 3200 A I r = 3200 A I r = 3200 A
00BFA10 REDUNDANT LOADS I th = 65 kA 00BFC10 NON REDUNDANT LOADS I th = 65 kA 00BFB10 REDUNDANT LOADS I th = 65 kA

11BHD10 90BLT10 11BHC11 12BHC12 00BTL20 11BMC10 00BFC10 00BLT10 00BFC10 00BTM20 12BMC10 90BLU10 12BHD10 11BHC12 12BHC11
GS101 GT100 GS101 GS101 GS100 GS101 GS101 GT100 GS102 GS100 GS101 GT100 GS101 GS101 GS101
(NO) (NO)
F F
R R R L R R T R R T L R R R R

TO 11BHD TO 90BLT10 CABLE FEEDERS M TO 11BHC11 TO 12BHC12 TO 11BMC10 M CABLE FEEDERS TO 00BLT10 TO 12BMC10 M CABLE FEEDERS TO 90BLU10 TO 12BHD TO 11BHC12 TO 12BHC11
SHEET 4 HV SWYD AUX AS PER SHEET 6 SHEET 6 SHEET 6 AS PER SHEET 4 SHEET 6 AS PER HV SWYD AUX SHEET 5 SHEET 6 SHEET 6
SUPPLY LOAD LIST DRIVES AS PER DRIVES AS PER LOAD LIST DRIVES AS PER LOAD LIST SUPPLY
G (< 630A) LOAD LIST LOAD LIST (< 630A) LOAD LIST (< 630A)
G
MAX 250 kW MAX 250 kW MAX 250 kW
FROM 11BMC10 FROM 12BMC10
SHEET 6 SHEET 6

U r = 480 V AC (3P+PE)
I r = 2500 A
00BMC10 ESSENTIAL BOARD I th = 65 kA

11BMD10 00BNT10 00BTL10 00BRT10 00BRU10 00BTM10 90BMD10 12BMD10


H GS101 GT100 GS100 GS103 GS103 GS100 GS100 GS101 H
R R L
BATTERY ROOM L L
BATTERY ROOM L R
00BTA10 00BTB10

00BTL20 00BTL10 00BTA10 00BTB10 00BTM10 00BTM20


~ ~ GS100 GS100 ~ ~
(2 x 50%) (2 x 50%) (2 x 50%) (2 x 50%)
J = = = = J

TO 11BMD TO 00BNT10 CABLE FEEDERS M TO 90BMD10 TO 12BMD


SHEET 4 SHEET 4 AS PER 00BVA10 00BVC10 00BRT10 L 00BRU10 L 00BVC10 00BVB10 HV SWYD AUX SHEET 5
L L
LOAD LIST DRIVES AS PER GS100 GS101 GS101 GS101 GS102 GS100 SUPPLY
(< 630A) LOAD LIST
MAX 250 kW
U r = 220 V DC U r = 220 V DC
I r = 800 A 00BRT10 00BRU10 I r = 800 A
00BVA10 I th = 25 kA / 1s = = 00BVB10 I th = 25 kA / 1s
K ~ ~ K

U r = 127 V AC U r = 127 V AC
I r = 250 A I r = 250 A
00BRA10 I th = 15 kA 00BRB10 I th = 15 kA
U r = 220 V DC
I r = 800 A
00BVC10 I th = 25 kA / 1s

L L

NOTE : THE POWER SUPPLY SHALL FULFIL THE FOLLOWING REQUIRED


POWER CONDITIONS AT THE CONSUMER TERMINALS:
RATED FERQUENCY 60Hz (-5% TO +5%) DC DC
RATED VOLTAGE AT CONSUMER (STEADY-STATE VOLTAGE): 6.6 kV (-10% TO +10%) STARTER STARTER
RATED VOLTAGE AT CONSUMER (STEADY-STATE VOLTAGE): 575 V (-10% TO +10%) GE Document Code Document Type Scale Document Status Format
RATED VOLTAGE AT CONSUMER (STEADY-STATE VOLTAGE): 460 V (-10% TO +10%) EMX/00/E/001b---004/SD/001 DRAWING % ELECTRONICALLY RELEASED A1
M M Originator Title, Subtitle Identification number

M GE Proprietary CLASS II (Internal) EMERGENCY LUBE OIL EMERGENCY SEAL OIL GE POWER 2 x 1 7HA.02 MS Advant Edge 1GP006596 M
© GE COPYRIGHT 2018. General Electric Company (USA) PUMP MOTOR PUMP MOTOR SINGLE LINE DIAGRAM Rev. Date Lang. Sheet
All rights reserved. The information herein is Proprietary and Technically Exclusive content of the General Electric Company and/or its legitimate Gas Power
affiliates. Systems D 2018-05-23 E 3/6
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

A MAIN E-ROOM A

MV ROOM

B U r = 6.9 kV (3P) B
I r = 3150 A
I th = 40 kA

freigegeben/ Released
00BBA10 MV SWGR FROM 00BBA10
SHEET 3
11BPA11 12BPA12 00BFT60 00BFT30 00BFT40 00BFT50 00BFT70
GT100 GT100 GT100 GT100 GT100 GT100 GT100
R R R R R R R

R
C C
L L L L L L L L

FROM 11BPA12GT100 MAIN E-ROOM SPARE


SHEET 5
SECONDARY E-ROOM PI UNIT 11 TRANSFORMER COMPARTMENT TRANSFORMER COMPARTMENT LV ROOM

TO 12BPA12, UNIT 12
SHEET 5 AUX TRANSFORMER AUX TRANSFORMER AUX TRANSFORMER AUX TRANSFORMER
00BFT60 00BFT30 00BFT40 00BFT50
D
H
AUX TRANSFORMER
H
AUX TRANSFORMER
M 2.0 MVA 3.15 MVA 3.15 MVA 1.6 MVA
D
AN AN AN AN
11BPA11 11BPA12 6.9 kV ± 2 x 2.5% 6.9 kV ± 2 x 2.5% 6.9 kV ± 2 x 2.5% 6.9 kV ± 2 x 2.5%
3 MVA / 1.5 MVA / 1.5 MVA 3 MVA / 1.5 MVA / 1.5 MVA 10LCB10AP001
10LCB20AP001 0.48 kV 0.6 kV 0.6 kV 0.48 kV
6.9 kV ± 2 x 2.5% / 1.8 kV / 1.8 kV 6.9 kV ± 2 x 2.5% / 1.8 kV / 1.8 kV Dyn1 Dyn1 Dyn1 Dyn1
Dd0y1 Dd0y1 CONDENSATE PUMP
415 kW u k = 7% u k = 9% u k = 9% u k = 7%
Y X u k H-Y = 7% Y X u k H-Y = 7%
u k H-X = 7% u k H-X = 7% (3 x 50%)
HOLD HOLD
u k X-Y = 12.1% u k X-Y = 12.1%
ROP E-ROOM ACC E-ROOM
LV SWGR LV SWGR

E E
VFD 11BPA11 VFD 11BPA12
00BFT60 00BFT30 00BFT40 00BFT50
GT200 GT200 GT200 GT200
R T R T R R T
U r = 480 V AC (3P+PE) U r = 600 V AC (3P+PE) U r = 600 V AC (3P+PE) U r = 480 V AC (3P+PE)
I r = 2500 A I r = 3200 A I r = 3200 A I r = 2500 A
00BFA60 ROP I th = 50 kA 00BFA30 ACC I th = 57.5 kA 00BFA40 ACC I th = 57.5 kA 00BFA50 CCW I th = 50 kA
FROM 11BMD10

00BLT60 00BFB60 00BFB30 00BFB40 00BFB50


M M GT100 GS100 GS100 GS100 GS100
(NO) (NO) (NO) (NO)
F 11LAC50AP001 11LAC60AP001 R T F
R T R R T
HP IP FEEDWATER PUMP HP IP FEEDWATER PUMP
1 x 2600 kW 1 x 2600 kW
00BNT60 00BLT60
250 kVA 250 kVA
480 V / 220 V 480 V / 220 V
u k = 7% u k = 7%

TO 00BFB60 TO 00BFB30 TO 00BFB40 TO 00BFB50


SHEET 5 SHEET 5 SHEET 5 SHEET 5
00BNT60 00BLT60
GT200 GT200
U r = 220/127 V(3P+N+PE) U r = 220/127 V(3P+N+PE)
I r = 630 A I r = 630 A
G 00BND60 I th = 15 kA / 1s 00BLA60 I th = 15 kA / 1s
G

M CABLE FEEDERS M M M M
AS PER
DRIVES AS PER LOAD LIST 00PGC10AP001
LOAD LIST (< 630A) ACC FANS ACC FANS CCW FANS 00PGC30AP001
MAX 250 kW 8 x 160 kW 8 x 160 kW 8 x 16 x 2.2 kW (TYPICAL) CCW PUMPS
H 2 x 250 kW H
FROM 00BMC10 FROM 00BFC10
SHEET 3 SHEET 3

MAIN E-ROOM SECONDARY E-ROOM POWER ISLAND UNIT 11


LV ROOM

00BMC10 00BFC10
FROM 00BMC10 FROM 00BFC10 GS103 GS113
J SHEET 3 SHEET 3 J
R U r = 480 V AC (3P+PE) R U r = 480 V AC (3P+PE)
I r = 630 A I r = 630 A
11BMD10 ESSENTIAL HRSG I th = 50 kA 11BHD10 HRSG I th = 50 kA

00BNT60 11BNU10 11BHD10 11BLU10


GT100 GT100 GS100 GT100
(NO)
L

FOR MAINTENANCE ONLY


K K
00BNT10 00BLT10 11BNU10 11BLU10
400 kVA 400 kVA 250 kVA 250 kVA
480 V / 220 V 480 V / 220 V TO 00BNT60 480 V / 220 V 480 V / 220 V
u k = 7% u k = 7% (ROP E-ROOM) u k = 7% u k = 7%

00BNT10 00BLT10 11BNU10 11BLU10


GT200 GT200 GT200 GT200
U r = 220/127 V(3P+N+PE) U r = 220/127 V(3P+N+PE) U r = 220/127 V(3P+N+PE) U r = 220/127 V(3P+N+PE)
L I r = 1250 A L I r = 1250 A L I r = 630 A L I r = 630 A
00BNC10 SMALL POWER I th = 15 kA / 1s 00BLC10 SMALL POWER I th = 15 kA / 1s 11BND10 SMALL POWER I th = 15 kA / 1s 11BLD10 SMALL POWER I th = 15 kA / 1s

L 00BLC10 11BLD10 L
GS100 GS100
(NO) (NO)
L L
FOR MAINTENANCE ONLY FOR MAINTENANCE ONLY

NOTE : THE POWER SUPPLY SHALL FULFIL THE FOLLOWING REQUIRED GE Document Code Document Type Scale Document Status Format
POWER CONDITIONS AT THE CONSUMER TERMINALS: EMX/00/E/001b---004/SD/001 DRAWING % ELECTRONICALLY RELEASED A1
RATED FERQUENCY 60Hz (-5% TO +5%) Originator Title, Subtitle Identification number

M GE Proprietary CLASS II (Internal) RATED VOLTAGE AT CONSUMER (STEADY-STATE VOLTAGE): 6.6 kV (-10% TO +10%) GE POWER 2 x 1 7HA.02 MS Advant Edge 1GP006596 M
© GE COPYRIGHT 2018. General Electric Company (USA)
All rights reserved. The information herein is Proprietary and Technically Exclusive content of the General Electric Company and/or its legitimate
RATED VOLTAGE AT CONSUMER (STEADY-STATE VOLTAGE): 575 V (-10% TO +10%)
Gas Power SINGLE LINE DIAGRAM Rev. Date Lang. Sheet

affiliates. RATED VOLTAGE AT CONSUMER (STEADY-STATE VOLTAGE): 460 V (-10% TO +10%) Systems D 2018-05-23 E 4/6
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

A A
MAIN E-ROOM
MV ROOM

B U r = 6.9 kV (3P) B
I r = 3150 A
I th = 40 kA

freigegeben/ Released
FROM 00BBB10 00BBB10 MV SWGR
SHEET 3
12BPA11 11BPA12 00BFU60 00BFU30 00BFU40 00BFU50 00BFT90
GT100 GT100 GT100 GT100 GT100 GT100 GT100
R R R R R R R

R
C C
L L L L L L L L

FROM 12BPA12GT100 MAIN E-ROOM


SHEET 4
LV ROOM GE
SECONDARY E-ROOM PI UNIT 12 TRANSFORMER COMPARTMENT TRANSFORMER COMPARTMENT
TO 11BPA12, UNIT 11 OTHERS
SHEET 4 AUX TRANSFORMER AUX TRANSFORMER AUX TRANSFORMER AUX TRANSFORMER
00BFU60 00BFU30 00BFU40 00BFU50 00BFT90
D
H
AUX TRANSFORMER
H
AUX TRANSFORMER
M 2.0 MVA 3.15 MVA 3.15 MVA 1.6 MVA
D
AN AN AN AN
12BPA11 12BPA12 6.9 kV ± 2 x 2.5% 6.9 kV ± 2 x 2.5% 6.9 kV ± 2 x 2.5% 6.9 kV ± 2 x 2.5%
3 MVA / 1.5 MVA / 1.5 MVA 3 MVA / 1.5 MVA / 1.5 MVA 10LCB30AP001
CONDENSATE PUMP 0.48 kV 0.6 kV 0.6 kV 0.48 kV
6.9 kV ± 2 x 2.5% / 1.8 kV / 1.8 kV 6.9 kV ± 2 x 2.5% / 1.8 kV / 1.8 kV Dyn1 Dyn1 Dyn1 Dyn1
Dd0y1 Dd0y1 415 kW
(3 x 50%) u k = 7% u k = 9% u k = 9% u k = 7%
Y X u k H-Y = 7% Y X u k H-Y = 7%
u k H-X = 7% u k H-X = 7%
HOLD HOLD
u k X-Y = 12.1% u k X-Y = 12.1%
ROP E-ROOM ACC E-ROOM
LV SWGR LV SWGR

E E
VFD 12BPA11 VFD 12BPA12
00BFU60 00BFU30 00BFU40 00BFU50 00BFT90
GT200 GT200 GT200 GT200 GT200
R T R T R R T
U r = 480 V AC (3P+PE) U r = 600 V AC (3P+PE) U r = 600 V AC (3P+PE) U r = 480 V AC (3P+PE)
I r = 2500 A I r = 3200 A I r = 3200 A I r = 2500 A
00BFB60 ROP I th = 50 kA 00BFB30 ACC I th = 57.5 kA 00BFB40 ACC I th = 57.5 kA 00BFB50 CCW I th = 50 kA

00BLU60
M M GT100

12LAC50AP001 12LAC60AP001 WATER WELL


F HP IP FEEDWATER PUMP HP IP FEEDWATER PUMP
F
1 x 2600 kW 1 x 2600 kW
00BLU60 WELL WATER PUMPS
250 kVA SUPPLY TP101
480 V / 220 V <= 500 kVA
u k = 7%

00BLU60 FROM 00BFA60 FROM 00BFA30 FROM 00BFA40 FROM 00BFA50


GT200 SHEET 4 SHEET 4 SHEET 4 SHEET 4
U r = 220/127 V(3P+N+PE)
I r = 630 A
00BLB60 I th = 15 kA / 1s
G G

M ERMS POWER SUPPLY CABLE FEEDERS M M M M


TP100 (20A) AS PER
DRIVES AS PER 90EKU LOAD LIST 00PGC20AP001
LOAD LIST (< 630A) ACC FANS ACC FANS CCW PUMP CCW FANS
MAX 250 kW 8 x 160 kW 8 x 160 kW 250 kW 8 x 16 x 2.2 kW (TYPICAL)
H FROM 00BMC10 FROM 00BFC10 H
SHEET 3 SHEET 3

SECONDARY E-ROOM POWER ISLAND UNIT 12

00BMC10 00BFC10
GS104 GS114

J R U r = 480 V AC (3P+PE) R U r = 480 V AC (3P+PE) J


I r = 630 A I r = 630 A
12BMD10 ESSENTIAL HRSG I th = 50 kA 12BHD10 HRSG I th = 50 kA

12BHD10
12BNU10 GS100 12BLU10
GT100 (NO) GT100
L

FOR MAINTENANCE ONLY

12BNU10 12BLU10
K 250 kVA 250 kVA
K
480 V / 220 V 480 V / 220 V
u k = 7% u k = 7%

12BNU10 12BLU10
GT200 GT200
U r = 220/127 V(3P+N+PE) U r = 220/127 V(3P+N+PE)
L I r = 630 A L I r = 630 A
12BND10 SMALL POWER I th = 15 kA / 1s 12BLD10 SMALL POWER I th = 15 kA / 1s

L 12BLD10 L
GS100
(NO)
NOTE : THE POWER SUPPLY SHALL FULFIL THE FOLLOWING REQUIRED L
POWER CONDITIONS AT THE CONSUMER TERMINALS:
RATED FERQUENCY 60Hz (-5% TO +5%) FOR MAINTENANCE ONLY
RATED VOLTAGE AT CONSUMER (STEADY-STATE VOLTAGE): 6.6 kV (-10% TO +10%)
RATED VOLTAGE AT CONSUMER (STEADY-STATE VOLTAGE): 575 V (-10% TO +10%)
RATED VOLTAGE AT CONSUMER (STEADY-STATE VOLTAGE): 460 V (-10% TO +10%)
GE Document Code Document Type Scale Document Status Format
EMX/00/E/001b---004/SD/001 DRAWING % ELECTRONICALLY RELEASED A1
Originator Title, Subtitle Identification number

M GE Proprietary CLASS II (Internal) GE POWER 2 x 1 7HA.02 MS Advant Edge 1GP006596 M


© GE COPYRIGHT 2018. General Electric Company (USA)
All rights reserved. The information herein is Proprietary and Technically Exclusive content of the General Electric Company and/or its legitimate Gas Power SINGLE LINE DIAGRAM Rev. Date Lang. Sheet

affiliates. Systems D 2018-05-23 E 5/6


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

A A

+00BRV10 +00BRW10

STANDBY DIESEL STANDBY DIESEL


1000 kW 1000 kW
B B

freigegeben/ Released
G G

00BRV10 00BRW10
GS100 GS100
(NO) (NO)
D D

C C

MAIN E-ROOM
GT LV SWGR
D D
FROM 00BFA10 FROM 00BFB10 FROM 00BFA10 FROM 00BFB10 FROM 00BFA10 FROM 00BFB10
SHEET 3 SHEET 3 SHEET 3 SHEET 3 SHEET 3 SHEET 3

E E
00BRV10 00BRW10
GS200 GS200

L L
U r = 480 V AC (3P+PE) U r = 480 V AC (3P+PE) U r = 480 V AC (3P+PE) U r = 480 V AC (3P+PE) U r = 480 V AC (3P+PE) U r = 480 V AC (3P+PE)
I r = 1200 A I r = 1200 A I r = 2500 A I r = 1200 A I r = 1200 A I r = 2500 A
11BHC11 (GT11 MCC1) I th = 65 kA 11BHC12 (GT11 MCC2) I th = 65 kA 11BMC10 (GT11 MCC1E) ESSENTIAL BOARD I th = 65 kA 12BHC11 (GT12 MCC1) I th = 65 kA 12BHC12 (GT12 MCC2) I th = 65 kA 12BMC10 (GT12 MCC1E) ESSENTIAL BOARD I th = 65 kA

11BTL20 11BRT10 00BMC10 11BTL10 11BNT10 12BTL20 12BRT10 00BMC10 12BTL10 12BNT10
GS100 GS103 GS101 GS100 GT100 GS100 GS103 GS102 GS100 GT100
(NO)
F L L R T L L R T F
R R R R R R 12BNT10
11BNT10 31.5 kVA
31.5 kVA 480 V L-L / 120 V L-N
480 V L-L / 120 V L-N

12BNT10
GT200
U r = 120 V (1P+N+PE)
11BNT10
L I r = 400 A
TO 00BMC10 GT200 TO 00BMC10
U r = 120 V (1P+N+PE) 12BNC10 I th = 15 kA / 1s
SHEET 3 I r = 400 A SHEET 3
L
11BNC10 I th = 15 kA / 1s
G G
L

M LOADS AS PER M LOADS AS PER M LOADS AS PER M LOADS AS PER M LOADS AS PER M LOADS AS PER
LOAD LIST LOAD LIST LOAD LIST LOAD LIST LOAD LIST LOAD LIST
H DRIVES AS PER DRIVES AS PER DRIVES AS PER DRIVES AS PER DRIVES AS PER DRIVES AS PER H
LOAD LIST LOAD LIST LOAD LIST LOAD LIST LOAD LIST LOAD LIST
MAX 250 kW MAX 250 kW MAX 250 kW MAX 250 kW MAX 250 kW MAX 250 kW

BATTERY ROOM 11BTL20 11BTL10 12BTL20 12BTL10 BATTERY ROOM


~ ~ ~ ~
11BTA10 (2 x 100%) (2 x 100%) (2 x 100%) (2 x 100%) 12BTA10
= = = =

J 11BTA10
12BTA10 J
GS100
GS100

11BVC10 11BTT10 11BRT10 12BVC10 12BTT10 12BRT10


GS100 GS100 GS101 GS100 GS100 GS101
L L L L L L

11BTT10 11BRT10 12BTT10 12BRT10

~ ~
K K
U r = 220 V DC U r = 220 V DC
I r = 800 A I r = 800 A
11BVC I th = 25 kA / 1s 12BVC I th = 25 kA / 1s
U r = 120 V (1P+N+PE) U r = 120 V (1P+N+PE)
I r = 400 A I r = 400 A
11BRC I th = 15 kA / 1s 12BRC I th = 15 kA / 1s

11BUG 24 V DC 12BUG 24 V DC

L L
DC DC DC DC
STARTER STARTER STARTER STARTER

M M M M
EMERGENCY LUBE OIL EMERGENCY SEAL OIL EMERGENCY LUBE OIL EMERGENCY SEAL OIL
PUMP MOTOR PUMP MOTOR PUMP MOTOR PUMP MOTOR
GE Document Code Document Type Scale Document Status Format
EMX/00/E/001b---004/SD/001 DRAWING % ELECTRONICALLY RELEASED A1
Originator Title, Subtitle Identification number

M GE Proprietary CLASS II (Internal) GE POWER 2 x 1 7HA.02 MS Advant Edge 1GP006596 M


© GE COPYRIGHT 2018. General Electric Company (USA)
All rights reserved. The information herein is Proprietary and Technically Exclusive content of the General Electric Company and/or its legitimate Gas Power SINGLE LINE DIAGRAM Rev. Date Lang. Sheet

affiliates. Systems D 2018-05-23 E 6/6