Sheet: 1 of 4
BBP
BFP
• CB Closed.
• CB Open →BFP Blocked.
• BFP start input + 0.2A → BFP Trip.70ms (T1) 120 ms (T2)
• BO check T1 (Trip to Local CB)
• BO check T2 (Remote Trip, Zone Trip)
EFP
Trip Transfer
• BFP trip + CB Trip Block from BCU activ → No Local CB trip → trip all feeders
connected to faulty bus (including one BC and one BS) with <T1 (50ms)
Logic
• Maintenance
• Test plug
o BB isolator forced to open
o BBP is blocked
o BFP activ with BFP start (Local / T1 and Remote feeder / T2 only)
o EFP activ with CB open
• Maintenance –F500
• Maintenance –F503
BBP initiation
BFP operation
Surrounding CB 250ms
• BFP trip all feeders connected to faulty bus (including one BC and one BS) with T2 only
with BFP Start input connectd via CB Closed Aux contact, no need of current.
• This will clear the zone.
Zone Formation
No bus transfer