Sunteți pe pagina 1din 6

Pasos

(1) CALCULO DE LA CARGA DE CADA DEPARTAMENTO

DPTO. 01 DPTO. 02 DPTO. 03 DPTO. 01 DPTO. 02 DPTO. 03


a 050-110(3) Area en m2 100 m2 50 m2 35 m2 100 m2 50 m2 35 m2

CARGAS DE ALUMBRADO Y TOMACORRIENTES

Regla Descripcion Potencia Instalada (W) F.D. Maxima Demanda (W)

b 050-202(1)(a)(i) Carga basica sobre los primeros 45 m2 1,500 W 1,500 W 1,500 W

c 050-202(1)(a)(ii) Carga adicional sobre los siguientes 45 m2 1,000 W

d 050-202(1)(a)(iii) Carga adicional (fraccion) 1,000 W 1,000 W

Suma Resultante 3,500 W 2,500 W 1,500 W 1.00 3,500 W 2,500 W 1,500 W

g CUALQUIER CARGA ADICIONAL > 1500 W

050-200(1)(a)(vi) Ducha Electrica 5,500 W 11,000 W 11,000 W 5,500 W 0.25 2,750 W 2,750 W 1,375 W
CUALQUIER CARGA ADICIONAL ≤ 1500 W

Secadora 1,200 W 1,200 W 1,200 W 1,200 W

050-200(1)(a)(vi) Microondas 1,100 W 1,100 W 1,100 W 1,100 W


Plancha 1,000 W 1,000 W 1,000 W 1,000 W

Suma Resultante 3,300 W 3,300 W 3,300 W 1.00 3,300 W 3,300 W 3,300 W

TOTAL 17,800 W 16,800 W 10,300 W 9,550 W 8,550 W 6,175 W

h DETERMINACION DEL CONDUCTOR DE ACOMETIDA

Suministro 220V / 3Ø / 60 Hz In 29 A 26 A 19 A
050-202(1)(b)
Factor de Potencia: 0.85 Id 37 A 33 A 24 A

(2) 050-202(3) CALCULO DE LA CARGA DE CADA UNIDAD DE VIVIENDA - CARGA DE CALEFACCION

a La unidad de vivienda con mayor carga 9,550 W 1 9,550 W 1 9,550 W

b Las dos siguientes 14,725 W 0.65 0.65 9,571 W

Suma resultante 19,121 W


(3) No aplica

(4) No aplica

(5) CALCULO DE LAS CARGAS FUERA DE LOS DEPARTAMENTOS AL 75% DEL F.D.
Areas comunes 250 W

Alumbrado 800 W

Electrobomba de agua 1,119 W

Puerta levadiza 373 W

Central de intercomunicador 500 W

Suma resultante 3,042 W 0.75 2,282 W

(6) Total de las cargas continuas del paso (5) 2,282 W

(7) Por lo tanto se requiere (125% +) Tabla 2 CNE 2,852 W

(8) CARGA TOTAL

Total paso (1) 19,121 W

Total paso (7) 2,852 W

21,973 W
Máxima demanda 22.0 kW

Factor de simultaneidad 0.80


Potencia a contratar 18.0 kW

Suministro 220V / 3Ø / 60 Hz

In 68 A → 16 mm2
Id 85 A → 100 A
Maxima
Tablero Circuito Descripcion Puntos Carga Carga Instalada F.D.
Demanda
C-1 Alumbrado Escaleras / Pasadizos 8 100 W 800 W 0.75 600 W

C-2 Tomacorrientes 2 250 W 500 W 0.75 375 W


T-SG C-3 Portero Eletrico 1 500 W 500 W 0.75 375 W

C-4 Bomba de agua 1 1,119 W 1,119 W 0.75 839 W

TOTAL 2,919 W 2,189 W

Maxima
Tablero Circuito Descripcion Puntos Carga Carga Instalada F.D.
Demanda
C-1 Alumbrado General 15 100 W 1,500 W 0.75 1,125 W

C-2 Tomacorrientes Dormitorios 9 200 W 1,800 W 0.75 1,350 W

C-3 Tomacorrientes Cocina / Lavanderia 7 200 W 1,400 W 0.75 1,050 W

C-4 Tomacorrientes Sala/Garaje 7 200 W 1,400 W 0.75 1,050 W


TD-1
C-5 Ducha Electrica Dormitorio Principal 1 5,500 W 5,500 W 0.40 2,200 W
C-6 Ducha Elecrtrica Dormitorio 1 y 2 1 5,500 W 5,500 W 0.40 2,200 W

C-7 Puerta Levadiza 1 373 W 373 W 0.75 280 W

TOTAL 17,473 W 9,255 W

Maxima
Tablero Circuito Descripcion Puntos Carga Carga Instalada F.D.
Demanda
C-1 Alumbrado General 9 100 W 900 W 0.75 675 W

C-2 Tomacorrientes Dormitorios 10 200 W 2,000 W 0.75 1,500 W

C-3 Tomacorrientes Sala Comedor / Cocina 7 200 W 1,400 W 0.75 1,050 W


TD-2
C-4 Ducha Electrica Dormitorio Principal 1 5,500 W 5,500 W 0.40 2,200 W

C-5 Ducha Elecrtrica Dormitorio 1 y 2 1 5,500 W 5,500 W 0.40 2,200 W

TOTAL 15,300 W 7,625 W

Maxima
Tablero Circuito Descripcion Puntos Carga Carga Instalada F.D.
Demanda
C-1 Alumbrado General 7 100 W 700 W 0.75 525 W

C-2 Tomacorrientes General 12 200 W 2,400 W 0.75 1,800 W


TD-3
C-3 Ducha Electrica 1 5,500 W 5,500 W 0.40 2,200 W

TOTAL 8,600 W 4,525 W


K = ρ*1.73
Tablero M.D. (kW) K Voltaje cos ɸ I nominal (A) I diseño (A) ITM Tablero I (A) L (m) cos Ø S (mm2) ΔV (V) Terna Σ ΔV < 5.5V % ΔV (<2.5%)
K = ρ*2
T-SG 2.19 W 1.73 0.22 0.85 6.77 A 8.46 A 3X32A T-SG 1.73 6.77 A 12 0.85 6 0.42 THW-90 [(3x6+1x6(T)]mm2 0.42 0.19

TD-1 9.25 W 1.73 0.22 0.85 28.61 A 35.76 A 3X40A TD-1 1.73 28.61 A 15 0.85 6 2.21 THW-90 [(3x6+1x6(T)]mm2 2.63 1.19

TD-2 7.63 W 1.73 0.22 0.85 23.57 A 29.46 A 3X40A TD-2 1.73 23.57 A 20 0.85 6 2.43 THW-90 [(3x6+1x6(T)]mm2 2.84 1.29
TD-3 4.53 W 1.73 0.22 0.85 13.99 A 17.48 A 3X40A TD-3 1.73 13.99 A 20 0.85 6 1.44 THW-90 [(3x6+1x6(T)]mm2 1.86 0.84
Pasos:

AREA

(1) 050-110 Area de la unidad de vivienda 159 m2

CARGAS DE ALUMBRADO Y TOMACORRIENTES


Potencia Maxima
Regla Descripcion F.D.
Instalada (W) Demanda (W)
(2) 050-200(1)(a)(i) Carga básica los primeros 90 m2 2,500 W

050-200(1)(a)(ii) Carga (fracción) 35 m2 1,000 W

Suma Resultante 3,500 W 1 3,500 W

CUALQUIER CARGA ADICIONAL > 1500W

(7) Ducha Electrica 3,000 W

Microondas 1,100 W

Lavadora 1,119 W

Suma Resultante 5,219 W 1 5,219 W

TOTAL 8,719 W 8,719 W

Máxima demanda 8.7 kW

Factor de simultaneidad 0.80

Potencia a contratar 7.0 kW

Suministro 220V / 1Ø / 60 Hz

Selección del conductor de acometida In 44 A → 6 mm2

Selección de la Llave General Id 55 A → 63 A


Maxima
Tablero Circuito Descripcion Puntos Carga Carga Instalada F.D.
Demanda
C-1 TOMACORRIENTES 11 200 W 2,200 W 0.50 1,100 W

C-2 TOMACORRIENTES HABITACIONES 9 200 W 1,800 W 0.50 900 W


C-3 TERMA ELECTRICA 1 1 1,500 W 1,500 W 1.00 1,500 W

TG C-4 TERMA ELECTRICA 2 1 1,500 W 1,500 W 1.00 1,500 W

C-5 ALUMBRADO 10 100 W 1,000 W 1.00 1,000 W

C-6 ALUMBRADO 7 100 W 700 W 0.80 560 W


TOTAL 8,700 W 6,560 W
Capacidad de
Conductor Tuberia a usar Potencia Instalada Factor de Maxima Demanda Tensión de k = 1.73 (3Ø) Corriente Corriente de Caida de % Caida de
Tablero Circuito Descripcion Tipo de Cable corriente del Longitud (m) Σ ΔV < 8.8V
a usar (mm) (W) Demanda (W) Servicio (V) k = 2.00 (1Ø) Nominal (A) Diseño (A) Tensión (V) Tension
conductor (A)
TOTAL THW-90 6.0 m2 44 10 35 8,700.00 6,560.00 220 2 29.82 37.27 0.0 0.00 0.00

C-1 TOMACORRIENTES THW-90 4.0 m2 34 25 20 2,200.00 0.50 1,100.00 220 2 5.00 6.25 1.1 1.12 0.51

C-2 TOMACORRIENTES HABITACIONES THW-90 4.0 m2 34 25 20 1,800.00 0.50 900.00 220 2 4.09 5.11 0.9 0.91 0.41
TD-1 C-3 TERMA ELECTRICA 1 THW-90 4.0 m2 34 15 20 1,500.00 1.00 1,500.00 220 2 6.82 8.52 0.9 0.91 0.41

C-4 TERMA ELECTRICA 2 THW-90 4.0 m2 34 16 20 1,500.00 1.00 1,500.00 220 2 6.82 8.52 1.0 0.97 0.44
C-5 ALUMBRADO THW-90 2.5 m2 27 27 20 1,000.00 1.00 1,000.00 220 2 4.55 5.68 1.8 1.75 0.80
C-6 ALUMBRADO THW-90 2.5 m2 27 32 20 700.00 0.80 560.00 220 2 2.55 3.18 1.2 1.16 0.53