EDC - EXTENDED DIGITAL CONTROLLER

PANEL MOUNTED

The EDC is a high capacity, stand-alone


intelligent building management controller. It is
provided with built-in network communications,
user programmable building control strategies,
and is suitable for larger HVAC applications.
The EDC 72 has 48 universal inputs (analog,
digital or pulse) and 24 universal outputs (analog
or digital), with optional on-board output relays
and On/Off/Auto switches.
The EDC 36 has 24 universal inputs (analog,
digital or pulse) and 12 universal outputs (analog
or digital) with a relay board option.
Each controller can be provided with an optional
2 x 40 character vacuum fluorescent display with
keypad to access and configure all the controller
data. The display can be integral or remote with a
2 metre lead and an optional bezel for flush
mounting.

Features
l Over 50 Standard Building Management & l Compatible with all York ISN Products, York
Control Application Features Chillers and Air Handling Equipment
l Fully Configurable from Optional l RS232 Printer Interface
Integral/Remote Keyboard and Display l Expandable Utilising York Field Input/Digital
l Keyboard Access to Other Network/Modem Output Modules
Controllers l RS232 Universal Interface
l Easily Constructed, Multi Level User Reports

Physical
EDC 36/72 Panel Mounting Enclosure EDC Remote Keyboard and Display

A = 4 x mounting holes 6 mm dia. Dimensions in mm A = 3 x mounting holes for M3 screws


B = Cutout for lead
VIEWED FROM FRONT Dimensions in mm
6 305 114*
78 78
VIEWED FROM FRONT
A A
17 242 17
265
61
EDC 72
820
A A
EDC 36
* Extra 230 mm 119
560 211
required for 20
hinged door 126
access
56 B

32 A

145 33
A A 276
6

45

Data Sheet 1.2


Issue Date: 1/3/00
EDC - Panel Mounted
ISN
Installation
Network
Power Supply &
Termination Card Previous Node
Network Address
Set the node number
USHL
switch to a unique P3
P2
valid address 1-92 GND
Example: 5VDC

The address is NODE


formed by NUMBER Next Node
1
summing the 2
4
values of each 8 Network Connections
switch that is in 16
32 The network cable screen is earthed at one end only for each
the ON position. A 64
B section of the network by connecting as shown.
1 + 4 + 8 = 13 ON The LAN speed is 19.2K baud, with a typical response time of 100mS.

Field Wiring
Universal I/O Card Field Output Module 1 Output Wiring
FOM 1 Digital Outputs
provide 24Vdc at
Input Wiring 50mA.
RELAY NOTE:
0-5V
I VOLTAGE COIL
Ensure diode
fitted across
X
X
X

DC MAX R R I V AO FS

+
I VOLTAGE
DO O relay coil
0-10V if FOM 3
DC MAX R R I V 24V AC
not used.
I RESISTIVE AO O
R R I V DO R
VALVE
I DIGITAL
R R I V Analog Outputs provide
PULSED
VOLT
I PULSE 0-10Vdc at 4mA. Set
FREE
CONTACT R R I V selector link (AO/DO) to
4-20
I CURRENT suit output requirement
MA R
R I V
+

FS
I CURRENT Field Output
EXT Universal I/O Card
+

PSU
4-20MA
R R I V Module 2
FOM 2 Digital Outputs
Set input RELAY OUTPUT
Analog SWITCH FUNCTIONS
selector link SWITCH IN AUTO Integral
Outputs
(R/I/V) to REL C
NO volt-free
suit sensor 0-10V
O NC
relay
THE OUTPUTS ARE
type used. DC O/P R CONTROLLED BY outputs
THE PROCESSOR
SWITCH with
On/Off/
ON OFF AUTO
Auto
switch.
Contacts are
rated at 2
Amps at 240Vac.

All input cables should be All analog output cables should All digital output cables
screened with the screen be screened with the screen must be separated from
connected into the earth terminal connected into the earth terminal other cabling in the
blocks provided at the controller blocks provided at the controller controller to prevent
end only. end only. electrical noise pick-up.

Power Wiring
A 2 metre length of power cable (L, N and E) is provided for connection to an external non-switched fused spur.

Please refer to ISN Control Systems Wiring Specification for further details.

York ®
Data Sheet 1.2
Issue Date: 1/3/00
EDC - Panel Mounted
ISN
Software Specification

INPUT, OUTPUT & MANAGEMENT & CONTROL DATA YORK INTERFACE


ALARMS DIAGNOSTIC DATA AVAILABLE ON
REQUEST
SYSTEM ALARMS 8 EQUIPMENT HRS RUN 48 FIXED SEQUENCING 4 ALARM ROUTE 10 ANALOG SELECT 8
ANALOG INPUTS 99 ANALOG HISTORY 48 TIME PROGRAMS 12 ALARM 2
ANALOG STEER
DIGITAL HISTORY 48 CONFIGURATION 8
MATHS CALCULATIONS 99 OPTIMAL CONTROL 16 DIGITAL STEER 2
METERED INPUTS OPTIMAL HISTORY 16 TIME SCHEDULE ENQUIRY 1
48 16 8
YORK TALK
DIGITAL INPUTS 99 UTILITY PERFORMANCE 4 MAXIMUM DEMAND 1 PRINTER
CONFIGURATION 1 NOTE OTHER FEATURES
DIGITAL OUTPUTS 99 UTILITY SUPPLY 48 LOAD SEQUENCING 6 CHANGE WITH THIS
CHANNEL
EVENT CONFIGURATION 1 OPTION
ANALOG OUTPUTS 32 LEAD/LAG 12 CONFIGURATION 1
SCHEDULED EVENT DATA 1 ANALOG CONTROL 24 NETWORK STATUS 1
RESET/CONTROL 8 PRINTER CONTROL 1 DIGITAL CONTROL 24 CARD CONFIGURATION 2
SYSTEM CALENDAR 1 DATA ACCESS 15 ANALOG INTERLOCK 99 REPORT
ANALOG ALARMS 99 POINT INVOLVEMENT 1 CONFIGURATION 10
DIGITAL INTERLOCK 99
DIGITAL ALARMS 99 ADVISORY MESSAGE 20 USER ACCESS 5
SENSOR INPUT TABLES 8 NETWORK DATA 8 DIAGNOSTICS 1
DEMUTLIPLEXING 24 ANALOG TRANSFER 48 NETWORK GROUP 8
DIGITAL TRANSFER 48 SYSTEM STRUCTURE 1

The system cycle time is set at 1 second as standard, when using the Maximum Demand Feature (Feature 60)
it should be set to 2 seconds.

System Access/Data Entry


Keyboard & Display (Optional) Remote Access
The integral/remote keyboard and display Remote access via the on-board RS232
allows access and configuration of all EDC port provides the same level of access
data, providing the facility to view/edit/add/ and configuration as the integral/remote
delete under the dictates of the password keyboard & display.
structure.
Connections
1
F36 LEAD/LAG S01 GROUP 01 2 x 40
Characters
4
P01 HWS PUMP 1 ON NORMAL DUTY 6
RX1 2
TX1 3
GND1 5
SCR3 7 PC
Display Entry OR TERMINAL
PORT2 8 1200 - 9600 BAUD
PROMPT/
ASSIST FEATURE 1 2 3 9 WAY

CLEAR
DATA
SECTION
4 5 6
SELECT
DATA PAGE 7 8 9 RX1 2
TX1 3
GND1 7
PRINT/
ACKNOW ENTER 0 +/- SCR3 MODEM
25 WAY 1200 - 9600
PORT2 D-TYPE BAUD

Features

l Password Entry l Alarms CTS 19


TX2 3
l Configuration l Manual Overrides GND2 7
SCR4
l Communications l Diagnostics 25 WAY
PORT3 D-TYPE SERIAL
l User Reports l Over 19500 Pages PRINTER
1200 - 9600 BAUD

York ®
Data Sheet 1.2
Issue Date: 1/3/00
EDC - Panel Mounted ISN
Hardware Specification
General Universal Input/Output Card (UIOC)
Primary Power Source 230/115 Volts AC +/- 10% via 2m Number of I/O
“Flying Lead” to IEC plug EDC 36 24 Universal Inputs
Fuse 2.0 amps Slow Blow 12 Universal Outputs
Frequency 50Hz + 30%-10% EDC 72 48 Universal Inputs
Power Consumption Nominally 75 VA 24 Universal Outputs
Storage Temperature -40 to 70 Degrees Celcius Universal Inputs
Operating Temperature 0 to 50 Degrees Celcius Analog 0 to 5 Volts; 0 to 10 Volts, 4 to 20mA
Operating Humidity 20 to 90% Non Condensing Thermistor (8K - 70K Ohms)
Emission Complies with EMC Pulse Max 20 Hz
Directive 89/336/EEC Link 1 Selects Fast Input Processing (A) or
LVD Standard EN 60950 Averaged Values (B)
Weight EDC 36 14Kg Link 2 Selects De-bounce (A) or No De-
EDC 72 17Kg bounce Processing (B)
Enclosure IP54 Rated Protection Digital Volt Free Clean Contacts
Dimensions Voltages Read by IPC Less than 2.5V; Digital Input Open
EDC 36 572mm H x 461mm W x 114mm D Greater than 2.5V; Digital Input Made
EDC 72 832mm H x 461mm W x 114mm D Input Impedance 10 Kilo Ohms for a 10V Input
Remote Display 211mm H x 276mm W x 33mm D 2 Mega Ohms for a 5V input
Termination All terminal strips removable ADC Resolution 10 Bits
Max Cable Size 1.5mm² CSA. Accuracy Nominally +/-0.1% of full scale
Field Supply 1000mA Maximum Repeatability Nominally +/-0.1%
Power Supply & Termination Card (PSTC) Signal Filtering Local Processor Averaging
PSTC Supply 24 Vac Isolation Pulse Transformer
User Connections 1 RS485 LAN (Port 1) 19.2K Baud Universal Outputs
1 RS232 Universal Utility Port (Port 2) Output Types Analog - 0 to 10 Volts dc
1200, 2400, 4800, 9600 Baud Digital - Switched Return Open
1 RS485 YorkTalk Port (Port 2) Collector Transistors
1 RS232 Printer Port (Port 3) DAC Accuracy Nominally +/-0.5% of full scale
1200, 2400, 4800, 9600 Baud DAC Resolution 8 Bits
Watchdog contacts 1 Amp @ 60V ac Repeatability Nominally +/-0.5%
Alarm contacts 1 Amp @ 60V ac Signal Filtering Local Processor Averaging
User Functions Node Selection Switch Isolation Pulse Transformers
LAN Status LEDs Drive Current 0 to 10 V dc @ 4mA
Printer & Universal Port Status LEDs Field Output Module 1
System Status LED Number of Outputs 12 Analog (0 to 10 Volts dc) or
Power Line Status LEDs Digital
RS232 Universal Port (Switched Return Open Collector
RS485 YorkTalk Selector Link Transistor)
Manual/Auto Selector Link Transistor Rating 24 Vdc 50mA
Fuse Schedule 24V AC - 3.15 amps Slow Blow Output Selection Link Selectable
24V DC (I/O) - 1.0 amp Slow Blow Protection Each Channel is Fuse Protected
Integrated Processor Card (IPC) Field Output Module 2
Processor NEC V25 Operating at 8MHz Number of Outputs 12 Analog (0 to 10 Volts dc) or
Memory PROM Up to 256 kBytes of CMOS EPROM Digital (Relay Contacts)
Memory RAM Up to 128 kBytes of battery-backed Relay Contact Rating Max 2.0 Amps at 240 Volts ac
CMOS RAM Max 4.0 Amps at 120 Volts ac
Battery Back-Up Data maintained for 2 years (Typical) Power Factor = 0.8 - 1
5 year life span Relay Contact Control Via a 3 Position Switch
Battery Enable/Disable Link On/Off/Auto
Real Time Clock Accuracy +/- 30 seconds per year Output Selection Relevant Terminals Selected

YORK INTERNATIONAL reserves the right to make changes to the specification, operation and construction of their products,
without obligation to notify any person of such changes.

York ®
YORK CONTROLS GROUP
Unit 1, Red Shute Hill, Hermitage
Newbury, Berks RG18 9QL
Data Sheet 1.2
Issue Date: 1/3/00
Telephone: +44 (0)1635 202200 Fax: +44 (0)1635 202222