800SD & 800SD-2 PANEL DIMENSIONS

selec Operating Instructions


22.5mm
100.5mm 80
m
m 11.5mm
OP530-V01

4.

R
8 9

10

61.0mm
7 10
76.85 6 75
mm 5
4 35 mm
3 0
mm

0
2 1
ON

105.5mm Mounting holes

SPECIFICATIONS TERMINAL CONNECTIONS


SUPPLY VOLTAGE
230 VAC, 110 VAC (Tolerance: -15 to + 10%) A1 25
COM
(Factory set) 15 26
200 VAC to 450 VAC, AC : 50 or 60 Hz

Y relay
800SD
S

relay
U
OUTPUT CONTACT P
P
800SD : 1NO contact each for star and L
Y
delta relay. 16 28
NO
800SD-2 : 1C/O contact each for star and 18 A2
delta relay.
(Rated at 5A@230 VAC, resistive.)

LED INDICATION A1 25
Star relay, Delta relay. 15 26
800SD-2

COM
S

relay
NC
TIME RANGE
Y relay

U NO
Run up time : 30/60 sec. P NO
COM
P NC
Change over time : 50/100 ms. L
Y
(User selectable via DIP switches) 16 28
18 A2
ACCURACY
Setting : ± 5% of full scale.
Repeat : ± 0.5% or 50 ms TERMINAL
(whichever is greater) DESCRIPTION
800SD 800SD-2
RESET A1 A1 Timer Supply (L)
On interruption of power. A2 A2 Timer Supply (N)
Reset time less than 100 ms.
15 15 Y relay COM
MOUNTING 16 Y relay NC
DIN rail / Screw mounting.
18 18 Y relay NO
SIZE (In mm) 15 25 relay COM
22.5(W) x 75(H) X 101(D).
26 relay NC
HOUSING 28 28 relay NO
CE marked products : Flame retardant
plastic.
Non CE products : ABS plastic.

TEMPERATURE
Operating : 0OC to 50OC.
Storage : - 20OC to 75OC.

HUMIDITY
Up to 95% RH.

WEIGHT
115 grams.
Doc. name : OP INST 800SD / 800SD-2
OP530-V01/d(Page 1 of 2)
PLEASE MAINTAIN THESE INSTRUCTIONS PRINCIPLE OF OPERATION
AND REVIEW THEM PRIOR TO USING THE UNIT:
L N
S1 K2 K2 K2

WIRING DIAGRAM
WARNING K1
1. The Equipment is built-in type with class II KIT
S2
construction and is protected by Reinforced
K1
Insulation. Terminals are a part of the front K3
15 18
panel and are protected by means of finger K1 K3
guards. Finger guards are not to be removed 25 28

during, wiring, installation, operation or


NOTE : For 800SD, terminal nos 15 to 25 are internally shorted.
maintenance.
2. The power should be turned off while wiring L1 L2 L3

and maintenance to prevent the risk of electric

SCHEMATIC DIAGRAM
shock. Do not touch any terminals when the
power is ON.
3. Wiring shall be done strictly according to the K2 K3 K1

terminal layout with shortest connections.


4. Fuse Protection: The equipment does not
have Built- in fuse. External fuse of rating
W1 W2
275 VDC/1 A is recommended. V1 M V2
U1 U2
3~
CAUTION
1. This unit is not intended for outdoor use. MODE OF OPERATION
2. The power connection cable must have a cross-
section ofatleast 1sq.mm and insulation Supply voltage
capacityof atleast 1.5kV. Use lugged terminals Star NO
to meet M3 screws. relay contact
3. The output connections must not be loaded Delta NO
relay contact t1 t2
beyond the specified values/range.
4. Avoid inflow of dust and contact of conductive t1 = Run up time, t2 = Change-over time
material with the internal circuitry of the unit.
5. Clean the equipment with a clean, soft cloth. Do
not use any organic solvents like Isopropyl
alcohol for cleaning.

DIP switch setting for time range selection

For Run time range


TIME RANGE SW1 SW2
30sec ON OFF
60sec OFF ON

For Pause time range

TIME RANGE SW3 SW4


50msec ON OFF
100msec OFF ON (Specifications are subject to change, since development is a
continuous process.)
Switch setting example
Selec Controls Pvt. Ltd., India
Run-up time range - 30sec.
Pause time range - 50msec Factory Address :
EL-27/1, Electronic Zone, TTC Industrial Area, MIDC, Mahape,
Navi Mumbai - 400 710, INDIA.
Tel. No. : +91-22-41 418 419/430 | Fax No. : +91-22-28471733
ON Toll free : 1800 227 353 (BSNL/MTNL Subscribers only)
1 2 3 4 Website : www.selec.com | Email : sales@selec.com
Disclaimer : "This product is strictly for industrial use and for sale in non European countries only"

Doc. name : OP INST 800SD / 800SD-2


OP530-V01/d(Page 2 of 2)