Documente Academic
Documente Profesional
Documente Cultură
ABSTRACT: The test results for 21 full-scale concrete block walls sub-
jected to uniformly distributed loading normal to the surfaces of the
walls are reported. The variables included in this experimental study
include three wall lengths of 6.0 m (19 ft, 8 in.), 5.2 m (17 ft, 1 in.), and
Downloaded from ascelibrary.org by Monash University on 09/06/13. Copyright ASCE. For personal use only; all rights reserved.
3.6 m (11 ft, 10 in.) with a constant 2.8 m (9 ft, 2 in.) wall height. In
addition, tests were performed with simple support conditions on all
four boundaries, on the bottom and two sides, on only the two sides, and
on only the top and bottom of the wall. Also, one series of tests was
done with precompression loading in the vertical direction. Three
repetitions for each combination of parameters were performed to
provide a better statistical sample. The test results were compared with
both elastic-plate and yield-line analyses. In these analyses, the bending
strengths used were taken from tests of masonry assemblages con-
structed to allow testing of individual joints under bending normal to the
bed joint and parallel to the bed joint. Both the load forfirstcracking and
the failure load were investigated. A general evaluation of the compa-
rable allowable wind loadings permitted by current building codes is also
included.
INTRODUCTION
121
1 I 1 X~
SECTIONAL PLAN FOR EXPERIMENTAL
SETUP
i J.
ELEVATION OF SUPPORTING FRAME
II II I J LC
ELEVATION OF BACKUP WALL
matched the standard distance between the test wall and the backup wall.
The air bag was inflated using a 100-psi (690-kPa) supply incorporating a
pressure reduction valve and low pressure regulator on the intake.
Manometers using water columns were located at the intake and at the far
end of the air bag to serve as the accurate measure of air pressure.
For this wall test program it was decided not to try to simulate actual
edge conditions for block walls in buildings. Rather it was decided to
provide well-defined support conditions in order to facilitate the develop-
ment and verification of analytical models. Therefore simple support
conditions were chosen. At the bottom of the wall, individual steel plates
for each block transferred the reaction from the wall to a 40-mm diameter
(1-5/8 in.) roller located along the mid depth of the wall. The steel plate
under each block had a milled slot with a 20-mm radius to permit rotation
while a shear key prevented lateral displacement. The simple supports for
the sides and top of the walls consisted of 25-mm (1-in.) steel rods welded
to elements of the supporting frame. Lateral load was transferred to these
reactions through 5 mm (3/16 in.) thick, 25 mm (1 in.) wide steel strips
which were held against the rods while plaster of Paris was placed in an
approximate 6-mm (1/4-in.) gap between these strips and the wall. This
eliminated the effects of any imperfections in the initial alignment of either
the wall or the reaction supports.
LOAD BY
SAND BIN
BLOCKS OR JACK
=990
390
(a)
(b)
FIG. 2. Flexure Normal to Bed Joint: (a) Specimen; (b) Bond Wrench Test Setup
123
400
PF UJ UJ
z
Downloaded from ascelibrary.org by Monash University on 09/06/13. Copyright ASCE. For personal use only; all rights reserved.
z z
o
oaat
IK
O
§ 0.
o. r _i
, Q.
Z>
3 CO
10
(*)
-HYDRAULIC JACK
-LOAD CELL
-SHIMS
160 -LOAD DISTRIBUTION
115 BEAM
-BALLS ROLLER
215 -SPREADER BEAMS
-PLYWOOD STRIPS
190 -SPECIMEN
115 jvQ/t
400,| 300, 300 1 400
US -ROLLERS
95 1400 95
1590
(b)
FIG. 3. Flexure Parallel to Bed Joint: (a) Specimen; (b) Test Setup
taken after each regular increase in air pressure and the wall surface was
checked for cracks.
The mortar cubes belonging to each wall were tested on the day
following the wall test. Tests to determine block properties and flexural
strengths were performed at representative ages.
WALL TEST RESULTS
Block and Mortar Strengths
Table 1 contains a summary of the 21 wall test results. Walls WI-1 and
WIII-1 were preliminary tests done using autoclave cured 190-mm blocks.
125
(t)
10.00
- **>^ -
s
/'&*?.—"
Q
'.•*-•
s **'
Q-
/ / .
- I50«.
Downloaded from ascelibrary.org by Monash University on 09/06/13. Copyright ASCE. For personal use only; all rights reserved.
*: ,Ss" bVWj^——
hi 6.00
t£ /.S
.-••rs>"*-" ^"^
^ S ^
CO
- l00 3
CO
UJ ': / ^ - l ^ #•"'" co
#IlS<S**
a. 4.00 UJ
Q:
a. Q.
2.00
- 50
^&;•"»«•""'*
V i
«"«ar-'-" i i i i
1.0 2.0 3.0 4.0 5.0
PANEL CENTRE DEFLECTION (mm)
Fig. 4(a) for wall WI-2, that is what occurred. However, what had not been
expected is the initial formation of a horizontal crack running nearly the
full length of the panel along a bed joint near midheight of the panel. The
sharp change in slope in curve (a) in Fig. 5 corresponds to the formation of
this initial horizontal crack.
2. Series WII: For the combination of flexural tensile strengths, the
aspect ratio for this series was expected to produce an X-shaped cracking
pattern composed of two diagonal cracks joining opposite corners of the
wall panels. However, again the initial crack was a horizontal crack
running nearly the full length of the panel along a bed joint near midheight.
The collapse mechanism was formed when additional cracks extended at
roughly 45° from this horizontal crack to the corners of the panel. A very
good example of this type of crack pattern is shown in Fig. 4(b). Deflection
curve (b) in Fig. 5 is also typical for this test series. The plateau
corresponds to the development of the horizontal crack.
3. Series Will: This series was expected to and did produce cracking
patterns similar to that which occurred for series WII. Again the plateau in
deflection curve (c) in Fig. 5 corresponds to the development of the initial
horizontal crack.
The results of these first three test series are consistent in that first crack
and failure pressures decreased with increasing horizontal span. Also the
amount of deflection that occurred during formation of the horizontal crack
increased with increased horizontal span and length of horizontal crack.
Test series WP was similar to test series WII except that the precom-
pression loading indicated in Table 1 was added. Since this precompres-
sion should delay the development of cracking stresses, the higher first
cracking and failure pressures would be expected. The crack pattern
shown in Fig. 4(b) was for this test series. Curve (d) in Fig. 5 shows the
typical deflection behavior where the precompression also seems to result
in a stiffer wall prior to formation of the first horizontal crack.
127
Test series WH comprised tests of walls supported only along the sides.
The photograph in Fig. 4(d) shows the typical vertical crack located near
the middle of the horizontal span. As can be seen, the crack alternately
passed through head joints and blocks in a nearly straight line. Deflection
curve (f) in Fig. 5 shows the typical nearly linear pressure versus deflection
relationship that is consistent with the sudden propogation of this crack to
form the collapse mechanism. Test series WV is the final series listed in
Table 1 and contains the failure pressures for the walls spanning vertically
between top and bottom supports. The observed cracking pattern consist-
ing of a horizontal crack along a bed joint near midheight of the wall panels
is obvious and has not been reproduced here. However deflection curve (g)
in Fig. 5 is the typical linear relationship up to the pressure producing the
horizontal crack.
The mean pressures for first cracking and for failure have been repro-
duced in Table 2 to facilitate comparison with predicted results. However,
to be able to predict the strengths of the block walls, it was necessary to
provide data for individual tensile strengths for bending both normal and
parallel to the bed joints.
Fig. 2 shows the bond wrench (Hughes and Zsembery 1980) apparatus
used to determine flexural tensile strengths normal to the bed joints. For
the specimens made with autoclaved blocks, the mean tensile strength was
0.372 MPa (54 psi) and the coefficient of variation was 24% for the ten
joints tested. Similar tests of 86 joints in specimens made with the
bubble-cured blocks gave a mean of 0.471 MPa (68 psi) and a coefficient of
variation of 37%.
For flexural tension parallel to the bed joints, the beam test shown in
Fig. 3(b) provided a region of constant bending moment in which all
failures occurred. For the autoclaved blocks and the bubble-cured blocks,
the mean tensile strengths were 1.32 MPa (191 psi) and 1.54 MPa (223 psi),
respectively. Also the corresponding coefficients of variation were 8.5%
and 7.2% for the respective groups of 20 and 14 tests.
For the following discussion it should be noted that all of the predicted
values given in Table 2 were based on results for the bubble-cured blocks.
This procedure was adopted because 19 of the 21 walls were made using
this type of block and also because it would be confusing to incorporate
changing material properties when discussing trends observed from the
analytical results. Because the properties were reasonably similar, neglect-
ing to account for the effects of having two walls made using the
autoclaved block does not significantly affect the overall comparison.
However, for completeness, the appropriate predicted pressures for walls
WI-1 and WIII-1 are included in the discussion of test series WI and Will.
128
Briefly the basis for the prediction of cracking and failure pressures are
as follows:
129
Series WI
Downloaded from ascelibrary.org by Monash University on 09/06/13. Copyright ASCE. For personal use only; all rights reserved.
For the elastic prediction of first cracking, the correlation with test
results would be improved if the 3.79-kPa (79-psf) value obtained using the
correct strengths for wall WI-1 were included. However, similar inclusion
of the predicted 7.94-kPa (166-psf) failure pressure would make the
predicted values more conservative than the 0.92 ratio shown. Similarly,
for the yield-line analysis, weighting the predicted pressure to account for
the lower calculated failure pressure of 9.53 kPa (199 psf) for wall WI-1
would make this slightly more conservative.
Series WII
The wall dimensions for this series were also used for most of the other
series. Elastic analysis predicted the formation of the horizontal crack but
at a much lower load than was observed. Part of this difference may be
attributable to the very high variability of tensile strength normal to the bed
joints. The elastic and yield-line predictions of failure pressures are slightly
conservative but, as was the case for series WI, are remarkably close to
each other. Retesting of series WV walls supported on all four sides after
failure along bed joints for the original vertical bending gave a mean
capacity of 7.06 kPa compared to the 6.82 kPa capacity for the similar WII
series. Also the stiffnesses after horizontal cracking were very similar.
Series Will
For this largest wall, all predictions overestimated the mean test results.
However if the predicted values were weighted to take into account the
different flexural strengths for wall WIII-1, better agreement would be
achieved. Using flexural strengths from the autoclaved block specimens,
elastic analysis predicted first cracking and failure at pressures of 2.17 kPa
(45 psf) and 4.14 kPa (86 psf), respectively. For the yield-line analysis, the
calculated failure pressure assuming continuity across the horizontal crack
was 4.73 kPa (99 psf), whereas the value was 4.14 kPa (86 psf) with no
continuity at the horizontal crack.
Series WP
The analytical results shown in Table 2 take into account the increased
flexural strength for bending in the vertical direction (tension normal to the
bed joints) that resulted from the precompression. The strength ratios
indicate that this approach is relatively conservative. The reason for this
conservative prediction may be explained by examination of Fig. 4(b). The
fact that the diagonal failure cracks tend to follow a stepped pattern around
the blocks rather than cracking through the blocks means that precom-
pression will also increase the cracking resistance in these regions through
increased friction. Rather than omitting this effect, flexural tensile strength
parallel to the bed joints could be arbitrarily assumed to be increased by
vertical precompression in the same proportion as for tension normal to
130
Series WF
For these walls supported on three edges, both the elastic and the
yield-line analyses provide very good estimates of the essentially simulta-
neous first cracking and failure pressures.
Series WH
For those walls subject to simple horizontal bending, the elastic and
yield-line predictions are equal and provide a very good estimate of the
identical first cracking and failure pressure. The relative low variability
found from tests of small specimens to determine flexural tensile strength
parallel to the bed joints is an argument for expecting very little influence
of specimen size.
Series WV
The wall capacity for this final series of tests was controlled by the
formation of a single horizontal crack along a bed joint near midheight of
the wall. Therefore, the first cracking and failure pressures are identical,
and the elastic and yield-line analyses predict the same capacity. The
relatively conservative ratio of predicted failure pressure versus the
experimental results may simply be a result of the very high variability for
tension normal to the bedjoints. In fact, similar vertical bending tests on
undamaged parts of the previously tested horizontal bending walls from
series WH gave a strength ratio of 1.00. When these three tests were
combined with the WV series, the mean capacity of 2.68 kPa resulted in a
ratio of 0.84. These latter tests are not recorded here because they were
not complete walls.
CONCLUSIONS
adequate for walls supported on four sides. In this case, the ratio of the
mean failure test loads to allowable loads controlled by diagonal cracking
ranged from 3.57-4.55. Use of the characteristic failure test loads as
described previously reduced the ratio to values from 2.44-3.03. For other
support conditions, particularly where a wall is supported only at the top
and the bottom, the justification for these provisions is marginal as the
previously defined ratio or safety factor was 2.63 using mean load and 1.79
using characteristic load.
4. It is suggested that current practice for the design of masonry walls
subject to out-of-plane bending should be reviewed. In this regard the dual
objectives of assuring adequate safety and maintaining or improving the
economic position for this type of construction may not be opposing
directions. The linking of design stresses, method of structural analysis,
and construction (support) conditions can result in walls that are not only
very safe but have considerable margin for additional economic advantage.
The retest of the series WV walls as walls supported on all four sides
clearly demonstrated the applicability of considering the initial horizontal
crack as a free edge for failure prediction of these types of walls.
ACKNOWLEDGMENTS
This research was funded through operating grants from the Natural
Science and Engineering Research Council of Canada and the Masonry
Research Foundation of Canada. The authors appreciate the contribution
of the mason's time made available through the Ontario Masonry Contrac-
tors Association and the Ontario Masonry Industry Promotion Fund, and
we thank the Ontario Concrete Block Association for their donations of the
blocks. The test data and analytical results form part of the second
author's doctoral dissertation.
APPENDIX. REFERENCES
133