(SE970891)
Features • Earth fault and flash-over functions in the • Can be connected either to the neutral
same relay package point of the system or to the phases
• Operates for earth fault resistances less • Two variants; one for system voltages
than 5 kohm within 380-500 V and one for 380-660 V
• Operates for flash-overs in the source • Trip relay included
transformer
• Flag for indicating flash-over operation
• Operation not affected by harmonics or
• Test switch included
capacitances to earth
Application RAERA is used for supervision of isolated Operation is obtained, after 5-10 seconds,
neutral systems with frequency converters. when the resistance to earth measures 5 kohm
RAERA operates for earth faults within the or lower. Filter-circuits are used to attenuate
entire regulated frequency range. Not even the influence of the ac voltages and capaci-
the high harmonics, caused by the frequency tances to earth.
converter and which are capacitively earthed,
3
affect the operation of RAERA. The harmon- ~
M
ics are especially high when the frequency ~ ~
converter is pulse-width-modulated (PWM).
4
Conventional earth fault relays that measure ~
M
the neutral point voltage are therefore not –
–
suitable for use on such systems. 6
500
Application (cont’d) The flash-over protection operates in less voltage dependent resistor to earth, thus
than 100 ms for a flash-over between the pri- avoiding incorrect earth fault current measur-
mary and secondary side of the source trans- ing. The neutral-point equipment also con-
former. tains a resettable fuse and a resistor. The
resistor limits the fault current to values
For application on systems without an avail- which the fuse is capable of interrupting. To
able neutral point, RAERA is connected to reduce humidity, a radiator with a thermostat
the phases via supervised fuses. To systems is included.
with a neutral point available, RAERA is
connected via neutral point equipment.
~ –
U
For connection to a system with a neutral M
point either variant can be used along with – ~
the neutral point equipment. If RAERA vari-
ant 2 is used the three inputs should, in this
U
(96000135)
case, be connected in parallel. R <
(96000136)
tem limits the current to 25 A.
Design Two variants of the RAERA relay are avail- Variant 1 is a 4U 30C assembly and has a test
able. switch. Variant 2 is without the test switch
and assembled on an insulating plate. Power
Variant 1 is intended for system voltages resistors are included to provide an artificial
between 380 and 500 V. Variant 2 is intended neutral point.
for system voltages between 380 and 660 V.
RAERA consists of a supply unit, RXTUE 4,
a measuring unit, RXNAF 4, and an RXMA 1
medium-duty output relay with two change-
over contacts and an RXME 18 heavy-duty
output relay with a red flag and two make
contacts. The RSMA 1 operates for earth
faults and the RXME 18 operates for and
indicates flash-over.
Technical data
Rated voltage, Ur
variant 1 380-500 V, 50-60 Hz
variant 2 380-660 V, 50-60 Hz
Operate value:
Earth fault, R< 5-10 kohm at ac (0,5-150 Hz)
5-220 kohm at dc, fixed value1)
Flash-over, U> 300-900 V, 50-60 Hz adjustable
Graduation error (% of highest setting) < 3%
Reset ratio:
Earth fault < 200%
Flash-over > 70%
Operate time:
Earth fault 5-10 s
Flash-over 70 ms at 2 × set value
Indicator at flash-over Flag
Permitted earth leakage capacitance 10 µF/phase
Overload capacity
Continuously 550/2000 V, variant 1
1s 750/5000 V, variant 2
Overload capacity for the neutral point
equipment 25 A during 0,5 s
Input impedance 15 kohm resistive
Permitted ambient temperature -20 to +55°C
Auxiliary voltage 110-120/220-240 V 50-60 Hz, reconnectable
Permitted auxiliary voltage deviation -20% to +10%
Power consumption in auxiliary voltage
circuit <10 VA
Dimension/weight:
variant 1 4U 30C/3,6 kg
variant 2 Height 420 mm
Width 248 mm/8 kg
Insulation tests:
Dielectric tests
variant 1 50 Hz, 2,0 kV, 1 min
variant 2 50 Hz, 5,0 kV, 1 min
Impulse voltage test 1,2/50 µs, 5,0 kV, 0,5 J
Disturbance tests:
Power frequency test 50 Hz, 0,5 kV, 2 min
Fast transient test 4-8 kV, 2 min
1 MHz burst test 2,5 kV, 2 s
Interruptions in auxiliary voltage 2-500 ms
operation is not interrupted at interruptions in auxiliary
voltage <100 ms
Contact data see 1MRK 508 015-BEN (RXMA and RXME)
1
) The operate value is influenced by the earth fault dc potential to earth according to the formula:
40 + U FN
R ≈ -------------------------- – 15 [kohm]
1, 8
where:
R = The operate value
UFN = The dc voltage between the fault point and the neutral point
Earth fault protection for isolated neutral RAERA
systems with frequency converters 1MRK 509 017-BEN
Page 5
Diagrams
30C
R 101 U 4S
9A 325
12A
1) 101
107:313
18A
101
3A
1A
2A
1) TRIP, FLASH-OVER
2) TRIP, EARTH FAULT
3) ALARM, FLASH-OVER
4) ALARM, EARTH FAULT
U2=220-240V, 50-60Hz 5) NEUTRAL POINT EQUIPMENT
+ + + -
U1=110-120V, 50-60Hz
0V
ø9( 2x )
L1(R)
L2(S)
L3(T)
R5 R2 1)
X1
1 2 2 1 X1
1 R5 R2 1
K1 R6 R3
2
7423 046-DA RAERA 1 2 1 2 2 3
R R7 R4 4
R6 R3
113:112 1 2 1 2 3 oo ø7( 2x )
101:225 4 X2,X3
X2 R7 R4
420
5 119:15
oo
378
6 319:17 K1
7 119:25
178
8 319:27
101:315
101:314
101:313
319:26
319:16
119:26
119:16
34
X2
X3
4
3
2
1
3
2
1
20
24 216
U2 = 50-60 Hz 220-240 V 248
1) CONNECTION WIRES WITH
+ + + +
U1 = 50-60 Hz 110-120 V 5 kV DIELECTRIC TEST VOLTAGE
0 K1 RAERA
R2-R7 RESISTOR
X1 TERMINAL
X2,X3 RTXG 8-1
Sample Earth fault/Flash-over relay with or without Two output relays, one for earth fault and one
specification neutral point equipment. The relay shall oper- for flash-over operation shall be included.
ate after 5-10 seconds for an earth fault, reset
ratio shall be < 200%. It shall operate in less The relay shall be suitable for 19” rack
than 100 ms for a flash-over, reset ratio shall mounting and provided with a test-switch for
be > 70%. It shall be unaffected by main secondary injection testing.
frequency-, converter-, and harmonic volt-
ages transferred to the relay via system capa-
citance to earth.
Description RK 667-301 E