>> HVX
Vacuum circuit-breaker
up to 36 kV
Medium-Voltage Switching Devices
Selection List
AREVA T&D
Conditions of Delivery
The General Conditions of Delivery as amended shall apply.
Illustrations
The illustrations are not binding.
>> Contents
DESIGN
Design 6
Modules 7
Drive unit 7
HVX pole section, drawing unit, drive equipment 8
Secondary equipment 9
Power consumption and tripping range of releases 10
Electric circuit diagram 11
Type designation 12
SWITCHING TASKS
Applications 13
SELECTION TABLES
12 kV for drawing unit 16
17.5 kV for drawing unit 18
24 kV for drawing unit 20
36 kV for drawing unit and fixed-type models 22
12 kV for fixed-type models 24
17.5 kV for fixed-type models 28
24 kV for fixed-type models 30
MODELS / DIMENSIONS
Dimensions HVX-E 32
Dimensions HVX-F 36
ACCESSORIES 39
TRANSPORT
Transport 40
3
>>
COMPACT AND FUNCTIONAL Vacuum circuit-breaker
The result of consistent further development for
application in modern air-insulated switchgear units
GENERAL DESCRIPTION
4
ESSENTIAL FEATURES Fields of application:
> Overhead cables
> compact design > Cables
> good operator guidance thanks > Motors
to the functional arrangement of > Transformers
operating and signalling ele- > Generators
ments
> no free-standing pole column
> vacuum interrupter chamber sus-
pended free of external forces
> pole envelope with supporting
and insulating functions
> high mechanical protection
thanks to pole envelope
> flexible application options:
- for fixed installation
- for mounting on isolating truck
- for drawer-type use
> high reliability and availability
thanks to mature vacuum
switching technology and proven
single-shaft spring drive
> world-wide application for all
standards
> maintenance-free
Performance characteristics
Rated voltage Rated lightning Rated short-time Rated short- Rated short- Rated current
impulse power frequency circuit making circuit breaking
withstand withstand current current
voltage voltage
1)
kV kV kV kA kA A
12 75 28 40 16 630 - 1250
63 25 630 - 2500
63 25 630 - 2500
63 25 630 - 2500
80 31.5 630 - 2500
5
>> Design
DESIGN
Drawing unit with vacuum circuit- Drawing unit with vacuum circuit-breaker HVX-E ≤ 2500 A with 64-pole
breaker HVX-E ≤ 1250 A with connector attachment
64-pole connector attachment
X
HV
HVX 36 kV fixed-type model Drawing unit with vacuum circuit-breaker HVX-E > 2500 A, 50 kA with
64-pole connector attachment
6
MODULE Description tensioned further, storing the ener-
Thanks to the use of modern vacu- gy for a complete automatic re-
Drive unit um interrupter chambers, vacuum closing cycle.
circuit-breakers make for an opti-
Essential features mization of the entire drive kinema- The drive mechanism is available
> Single-shaft system with a single tics. in two basic models, i.e. as manual
spiral spring for ON and OFF spring mechanism FH 2-01 or the
> Optimum adaptation to the small Method of operation: motorized spring mechanism FK
contact travel of the vacuum The energy for a complete 2-01. Appropriate interlocks rule
interrupter chamber switching cycle can be stored in out faulty switching operations.
> Minimum energy requirement the spiral spring. The ON and OFF In addition to the mechanical
movement of the vacuum interrup- actuation of the manual ON/OFF
ter chamber is controlled via the pushbuttons, the drives can be
cam discs. Once closing (ON) has remote-controlled electrically or
been effected, the spring can be actuated via primary relays.
Main shaft
Basic equipment
Mechanical elements
OFF push-button • •
ON push-button • •
Switch position indicator • •
Mechanical operations counter • •
Switching spring position indicator • •
Electrical equipment
7
Pole section HVX ≤ 2500 A Drawing unit
The supporting component of the The drawing unit is the supporting
entire pole section is the multi- element for:
functional pole shell. Its functions > the drive unit to move the vacu-
comprise those of a mechanical um circuit-breaker HVX-E into its
supporting device for the top and operating / isolating position
bottom terminal contacts between > secondary terminals (64/36-pole)
which the vacuum interrupter > interface elements for
chamber is suspended free of - panel interlocks
mechanical constraints. In this - drawing unit position
case, there are no insulating indications
bridges between the phases. > drawing unit coding
Pole section HVX 12/24 kV > 1250 A Pole section HVX 36 kV Pole section HVX 12 kV > 2500 A
8
SECONDARY EQUIPMENT Auxiliary switches Relay
9
POWER CONSUMPTION AND TRIPPING RANGES OF THE RELEASES
Tripping ranges
Release Designation Rated current Tripping current
Ia in [A] at AC 50/60 Hz
0.5 90
Transformer-
operated F3 1 – at
release
5 100 % Ia
at 48 V DC, L/R = 10 ms 10 A
S11 8
at 125 V DC, L/R = 10 ms 3.8 A
15 A at 220 V DC, L/R = 10 ms 2 A
S12 8
at (110) 120/(220) 230 V AC 10 A
One NC contact and one NO contact of the auxiliary switch respectively are required for each closing or opening
coil respectively.
10
>> Electric circuit diagram
These circuit diagrams show the possible secondary equipment. Depending on the order volume, components shown may not be included.
Operating equipment which may be installed in the circuit- –S11, S12 Auxiliary switchgear
breaker -QO depending on the order specification –S2 Push switch actuated by energy-storing device
–F11, –F12 Shunt opening release (shunt release) –S41, S42 Push switch actuated by ON/OFF pushbutton
–F2 Shunt closing release (shunt release) –S43 Push switch actuated by OFF pushbutton
–F3 Secondary coil (transformer-operated release) –S6 Push switch actuated by drawing unit
–F4 Undervoltage release –X01 Terminal strip
–K01 Anti-pumping relay –Y1 Blocking coil
–M1 Motor to charge the energy storing device
11
TYPE DESIGNATION
HVX 12-25-06-E
Drawing unit
Type
F
Fixed type
Rated voltage
Rated current
Rated short-circuit
breaking current
Example:
OFF button
HVX 12-31-25-E
U 24 kV
Type
NO SW1 3340121001
Im 800 A
HVX 24 -16 -00 -21
1999
/ 50/60 Hz
Mechanical
Um 125 kV Isc 16 kA
0 - 3min - 00-3min-00
/th 3 s
operations counter
on drawing unit Made in Germany
Position indicator of
circuit breaker
99815
Position indicator of
closing spring
12
>> Switching tasks
and applications
0–3 min – CO – 3 min – CO without reclosing facility IEC 62271-100 see Selection Tables
0–0.3s – CO – 3 min – CO with reclosing facility IEC 62271-100 see Selection Tables
IEC 62271-100 see Selection Tables
CO – 15s – CO with reclosing facility
ANSI C37 column "with reclosing facility"
APPLICATIONS
> Auto-reclosing
13
>>
SAFE AND RELIABLE Specifications
and tests
STANDARDS TESTS
1)
Drawing unit with further standards available on
vacuum circuit-breaker request
ENVIRONMENTAL AND
OPERATING CONDITIONS
Ambient temperatures
Temperature class:
"minus 5 indoors” 1)
Min./max. ambient
temperature -5 / 40 °C 1)
Maximum installation 1)
altitude above sea-level 1000 m
1)
higher values on request
14
INSULATING LEVEL Thus, the following applies to the ENVIRONMENTAL
(TESTED ACCORDING TO selection of devices and switch- CONDITIONS
IEC 60 694 OR EN 60 694) gear:
Vacuum circuit-breakers HVX com-
HVX vacuum circuit-breakers are Rated withstand voltage ply with the environmental conditi-
suitable for installation at high alti- to be selected 1) ons defined in IEC 60 721-3-3,
tudes. They can be used in build- ≥ 1990.
ings with low thermal insulation or Required rated
low thermal capacity, heated or withstand voltage 1)
cooled, without temperature moni- ka DISPOSAL CONCEPT
toring. The heating or cooling
systems may fail to operate for a However, if the actual insulating A disposal manual is available on
period lasting several days. The level at the site of installation - the request.
values specified for the insulating withstand voltage – is to be deter-
level are referred to sea-level. mined, the reduction of the insulat-
In case of installation at altitudes ing level starting at 0 m (sea-level)
above 1000 m, a reduction of the must be taken into consideration
insulation level must be considered as follows:
using an altitude correction factor
(ka = correction factor). Withstand voltage 2) = ka · Rated
withstand voltage 1)
of the selected device.
15
>> Selection tables
HVX VACUUM CIRCUIT-BREAKER 12 KV WITH DRAWING UNIT FOR
AREVA SWITCHGEAR PANELS
out-of-phase conditions
Rated lightning impulse
withstand voltage
Type
Rated frequency
Rated voltage
CO-15 s-CO
voltage
3s
mm kV kV kV Hz A kA kA kA % A kA
1) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report
2) in case of PMA 210 mm panel with motor-driven fan
16
quence Number of operating cycles Breaker operating times
without overhaul
Drive mechanism
1)
1)
Opening time
Closing time
Arc duration
Break time
Weight
ms ms ms ms ms ms s
135
10000 30000 10000 100 35-53 45-63 55-62 2-12 20 4-12 135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
135
135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
160
160
160
135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 160
160
160
230
135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12
135
160
160
230
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 230
230
17
HVX VACUUM CIRCUIT-BREAKER 17.5 KV WITH DRAWING UNIT
FOR AREVA SWITCHGEAR PANELS
out-of-phase conditions
Rated lightning impulse
Rated power frequency
withstand voltage
withstand voltage
Type
Rated frequency
Rated voltage
CO-15 s-CO
component
3s
mm kV kV kV Hz A kA kA kA % A kA
1) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report
2) in case of PMA 210 mm panel with motor-driven fan
18
uence Number of operating cycles Breaker operating times
without overhaul
Drive mechanism
1)
1)
Opening time
Closing time
Arc duration
Break time
Weight
ms ms ms ms ms ms s
135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12
160
160
160
135
135
160
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12
160
160
230
135
160
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 160
160
230
19
HVX VACUUM CIRCUIT-BREAKER 24 KV WITH DRAWING UNIT
FOR AREVA SWITCHGEAR PANELS
out-of-phase conditions
Rated lightning impulse
withstand voltage
Type
Rated frequency
Rated voltage
CO-15 s-CO
voltage
3s
mm kV kV kV Hz A kA kA kA % A kA
1) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report
2) in case of PMA 210 mm panel with motor-driven fan
20
quence Number of operating cycles Breaker operating times
without overhaul
Drive mechanism
1)
1)
Opening time
Closing time
Arc duration
Break time
Weight
ms ms ms ms ms ms s
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
135
135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
160
160
230
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
160
160
21
VACUUM CIRCUIT-BREAKER HVX-E 36 KV WITH DRAWING UNIT
FOR AREVA SWITCHGEAR PANELS AND HVX-F 36 KV FIXED-TYPE MODEL
out-of-phase conditions
Rated lightning impulse
withstand voltage
Type
voltage
3s
mm kV kV kV Hz A kA kA kA % A A kA
1) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report
22
perating Number of operating cycles Breaker operating times
ence without overhaul
Drive mechanism
1)
1)
Opening time
Closing time
Arc duration
CO-15 s-CO
Break time
Weight
ms ms ms ms ms ms s
10000 30000 10000 100 40-53 45-63 47-65 7-12 20 4-9 155
10000 30000 10000 100 40-53 45-63 47-65 7-12 20 4-9 155
10000 30000 10000 100 40-53 45-63 47-65 7-12 20 4-9 155
10000 30000 10000 100 40-53 45-63 47-65 7-12 20 4-9 155
10000 30000 10000 100 40-53 45-63 47-65 7-12 20 4-9 155
10000 30000 10000 100 40-53 45-63 47-65 7-12 20 4-9 155
23
VACUUM CIRCUIT-BREAKER HVX-F 12 KV, FIXED-TYPE MODEL
out-of-phase condition
Rated (normal) current
withstand voltage
Type
Rated frequency
Rated voltage
voltage 3s
mm kV kV kV Hz A kA kA kA % A kA
1) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report
24
operating sequence Number of operating cycles Breaker operating times
without overhaul
Interrupter chamber
O-0.3 s-CO-15 s-CO
Drive mechanism
1)
1)
Opening time
Closing time
Arc duration
CO-15 s-CO
Break time
Weight
ms ms ms ms ms ms s
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
135
135
135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
135
135
160
160
25
VACUUM CIRCUIT-BREAKER HVX-F 12 KV, FIXED-TYPE MODEL
out-of-phase conditions
Rated lightning impulse
withstand voltage
Type
Rated frequency
Rated voltage
CO-15 s-CO
voltage
3s
mm kV kV kV Hz A kA kA kA % A kA
1) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report
26
quence Number of operating cycles Breaker operating times
without overhaul
Drive mechanism
1)
1)
Opening time
Closing time
Arc duration
Break time
Weight
ms ms ms ms ms ms s
135
135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
135
135
160
160
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 230
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
160
160
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 230
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 230
27
VACUUM CIRCUIT-BREAKER HVX-F 17.5 KV, FIXED-TYPE MODEL
out-of-phase conditions
Rated lightning impulse
withstand voltage
Type
Rated frequency
Rated voltage
CO-15 s-CO
voltage
3s
mm kV kV kV Hz A kA kA kA % A kA
1) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report
28
uence Number of operating cycles Breaker operating times
without overhaul
Drive mechanism
1)
1)
Opening time
Closing time
Arc duration
Break time
Weight
ms ms ms ms ms ms s
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
135
135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12
135
160
160
135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
160
160
230
135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12
160
160
230
29
VACUUM CIRCUIT-BREAKER HVX-F 24 KV, FIXED-TYPE MODEL
out-of-phase conditions
Rated lightning impulse
withstand voltage
Type
Rated frequency
Rated voltage
CO-15 s-CO
voltage
3s
mm kV kV kV Hz A kA kA kA % A kA
1) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report
30
uence Number of operating cycles Breaker operating times
without overhaul
Drive mechanism
1)
1)
Opening time
Closing time
Arc duration
Break time
Weight
ms ms ms ms ms ms s
135/260
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135/260
135/260
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
135
135/260
135/260
135/260
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12
135/260
160/260
160/260
135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12
135
160
160
31
>> Models/dimensions
DIMENSIONS HVX-E
A A
16
16
A
A
A
Ø 60
16
32
DIMENSIONS HVX-E ≤ 1250 A
22
250 176
340
648
220
F 305 80
G 416 B
E
C C
A
22
Ur (kV) 12 kV
Ir (A) ≥ 1250
A 653
B 195/126
C 185
D 507
E 527
F 466
G 498
Dimensions in mm
33
DIMENSIONS HVX-E > 1250 A
C C
137
H (for installation in PIX only)
340
697
220
G
416 B E
E
C C
A
22
Dimensions in mm
– PID105, PID106
– PIA106, PID106,
– PN104/106
For panel
PIN106
– PID104
– PN104
– PIX 12
– PIX 12
– PIX 17
– PIX 24
– PIX 12
– PIX 17
– PIX 24
– PI104
– PI104
– PI106
– PIX-C
– PIX-S
A 563 653 569 653 563 653 753 569 569 653 753 763 653 763 653 653 763
B 126 195 126 195 126 195 294 126 195 195 294 294 195 294 195 195 294
H 805 805 735 805 735 735 805 735 805
C 185 210 254
D 507 570 658
E 527 577 665
F 466 516 604
G 497.5 547.5 635.5
34
DIMENSIONS HVX-E 3150 A
A
349 178
807 (for PIX 12 kV only)
340
732
743
669
B
11
C 23
735
472
D D
849
kV kV Ir A B C D
12 75 1250 688 220 502 254
12 75 2000 688 220 502 254
12 75 2500 688 220 502 254
12 75 3150 688 220 502 254
12 95 1250 723 239 537 254
12 95 2000 723 239 537 254
12 95 2500 723 239 537 254
12 95 3150 723 239 537 254
17.5 95 1250 723 239 537 254
17.5 95 2000 723 239 537 254
17.5 95 2500 723 239 537 254
17.5 95 3150 723 239 537 254
Dimensions in mm
35
DIMENSIONS HVX-F ≤ 1250 A
429
179
239
558
206
136
B
A A
Ur (kV) 12 kV
Ir (A) ≤ 1250
A 150
B 440
C 450
Dimensions in mm
≤ 1250 A
Vacuum circuit-breaker
HVX-F ≤ 1250 A
36
DIMENSIONS HVX-F > 1250 A
D
327 176
25
458
348
C
A A
Ir ≤ 1600 A Ir ≥ 2000 A
Dimensions in mm
37
DIMENSIONS HVX-F 3150 A
340
732
735
B
22
706
A
254 254
Ur (kV) Up (kV) A B
12 75 688 220
12 95 723 239
17.5 95 723 239
Dimensions in mm
38
>> Accessories
Transport trolley
The vacuum circuit-breaker HVX-E
can be transported by means of
the transport trolley.
Chassis frame
A floor chassis frame can be used
to transport the HVX.
39
>> Transport
TRANSPORT
Shipping unit
>50¡
40
41
42
AREVA Energietechnik GmbH · Sachsenwerk Mittelspannung · Rathenaustraße 2 · D-93055 Regensburg
Postfach 10 01 55 · D-93001 Regensburg · Phone +49 (0)9 41/46 20-0 · Fax +49 (0)9 41/46 20-4 18
www.areva-td.com
Tel.: +44 (0) 1785 250 070
AREVA T&D Worldwide Contact Centre:
http://www.areva-td.com/contactcentre/
SYSTEMS-L4-FACTS-1016-EN-2- © - AREVA - 2006. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA.
All trade names or trademarks mentioned herein, whether registered or not, are the property of their owners. - 389191982 RCS PARIS
Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up-to-date literature, this brochure should only be regarded as a guide and is intended for information
purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it. We cannot be held responsible for any reliance on any decisions based on its contents without specific advice. SW.06.34/0906 EN