ACS800
Hardware Manual
ACS800-207 Cabinet-installed IGBT Supply Units
"Uncontrolled Copy"
ACS800 Multidrive Manuals
Codes refer to English manuals.
ACS800-207
Cabinet-installed IGBT Supply Units
Hardware Manual
3AFE68233810 Rev B
EN
EFFECTIVE: 30.12.2005
Table of contents
Table of contents
Hardware description
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Layout of an ACS800 multidrive with an IGBT supply unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Supply with frame R7i module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Supply with two frame R8i modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Single-line diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Supply with one frame R7i or R8i module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Supply with two frame R8i modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
IGBT supply module, frame R7i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Single-line diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Module layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Printed circuit boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
IGBT supply module, frame R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Single-line diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Printed circuit boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
LCL filter module types ALCL-04-05, -05-05, -04-07 or -05-07 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
LCL filter modules types ALCL_1x_x and ACLC_2x_x . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Control interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Control connections to the RDCU (RMIO board) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Type code of cabinet-installed IGBT Supply unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Basic code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Option codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Table of contents
"Uncontrolled Copy"
6
Electrical installation
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Checking the insulation of the assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Power connections for cabinet-installed IGBT supply unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Unit equipped with frame R7i module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Connection procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Unit equipped with R8i module(s) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Connection procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Control connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Connection procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Installation of optional modules and PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Fibre optic links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Connections and tap settings of the auxiliary voltage transformer . . . . . . . . . . . . . . . . . . . . . . . . . 36
Start-up
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Installation check-list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Basic checks with no voltage connected . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Connecting voltage to input terminals and auxiliary circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Starting the IGBT supply unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Checks after start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
On-load checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Setting parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Maintenance
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Maintenance intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Cleaning the heatsink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Checking and replacing the air filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Checking and cleaning the power connections via quick connector . . . . . . . . . . . . . . . . . . . . . . . 43
Replacing and reforming the capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Reforming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Capacitor replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Replacing the cooling fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Supply module, frame size R7i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Supply module, frame size R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Table of contents
"Uncontrolled Copy"
7
Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
LCL filter type ISU_LCL_5R7 and -6R7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
LCL filter type ALCL-1x and -2x . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Replacing the supply module, frame size R7i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Replacing the supply module, frame size R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Removing the module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Inserting the module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Redundancy (Reduced run capability) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Table of contents
"Uncontrolled Copy"
8
Table of contents
"Uncontrolled Copy"
9
Compatibility
The manual is compatible with the cabinet-installed IGBT supply units (ACS800-
207). Some chapters are also valid for ACS800-104 IGBT modules to be installed
into cabinet by the user.
Safety instructions
Follow all safety instructions delivered with the drive.
• Read the complete safety instructions before you install, commission, or use
the drive. The complete safety instructions are given in ACS800 Multidrive Safety
Instructions (3AFE64760432 [English])
• Read the software function specific warnings and notes before changing the
default settings of the function. For each function, the warnings and notes are
given in the section describing the related user-adjustable parameters.
• Read task specific safety instructions before starting the task. See the section
describing the task.
Reader
The reader is expected to know the standard electrical wiring practices, electronic
components, and electrical schematic symbols.
Contents
• How the IGBT supply unit operates
• Hardware description
• Electrical installation
• Start-up
• Maintenance
• Technical data - ACS800-207
• Technical data - ACS800-104 IGBT supply module
• IGBT supply unit example circuit diagrams
Other documents
User documentation of a multidrive delivery contains technical drawings and a set of
manuals. Technical drawings are tailor-made for each delivery. The composition of
the manual set depends on the composition of the drive.
The manuals are listed below. The codes refer to the original English manuals.
Manual Included in …
General drive manuals
• ACS800 Multidrive Safety Instructions (3AFE64760432) every delivery
• ACS800 Multidrive Mechanical Installation (3AFE68233402)
• ACS800 Multidrive Planning the Electrical Installation (3AFE64783742)
Line-side converter manuals
• ACS800-307 and -507 Diode Supply Unit User’s Manual (3AFE64494023) delivery which
• ACS800-207 IGBT Supply Unit Hardware Manual (3AFE68233810) includes the
corresponding
• ACS800 IGBT Supply Control Program Firmware Manual (3AFE68315735) supply module
Motor side-converter hardware manual every delivery
• ACS800-107 Inverter Unit Hardware Manual
Motor side-converter firmware manuals
• ACS800 System Application Program Firmware Manual delivery which
• ACS800 Standard Application Program Firmware Manual (3AFE64527592) includes the
and Adaptive Program Application Guide (3AFE64527274) corresponding
program
• ACS800 Master/Follower Application Guide (3AFE 64590430)
• ACS800 PFC Application Program Firmware Manual (3AFE64649337)
• ACS800 Crane Application Program 7.x Firmware Manual (3BSE 11179)
… etc.
Option device manuals
• RAIO-01 Analogue I/O Extension User's Manual (3AFE64484567) delivery which
• RDIO-01 Digital I/O Extension User's Manual (3AFE64485733) includes the
corresponding
… etc. option device
Operation principle
The IGBT supply unit consists of an IGBT supply module, a line filter (LCL filter), AC
and DC fuses and optional devices. The IGBT supply module rectifies three-phase
AC current to direct current for the intermediate DC link of the drive. The
intermediate DC link is further supplying the inverter that runs the motor. There might
be one inverter only (single drive) or several inverters (multidrive) connected to the
intermediate circuit. The line filter suppresses the AC voltage distortion and current
harmonics.
The IGBT supply module is a four-quadrant switching-mode converter, i.e. the power
flow through the converter is reversible. As default, the converter controls the DC link
voltage to the peak value of the line-to-line voltage. The DC voltage reference can be
set also higher by a parameter. Two line currents and the DC link voltage are
measured and used for the control.
AC input DC output
I [A], U [VAC]
1200 uUV
800
iU
400
0 t [ms]
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38
-400
-800
-1200
A typical spectrum of the voltage distortion at the output of the transformer is shown
below. Each harmonic is presented as compared to fundamental voltage (reference
value = 1). n denotes the ordinal number of the harmonic.
1,5
0,5
0 No. of harmonic
THD 11 21 31 41 51 61 71 81 91 101 111 121 131 141 151 161 171 181 191
Hardware description
Doors closed
A B C
Description
1 A Auxiliary control cabinet
1. Auxiliary circuit switch-fuse [Q10]
2. Meters, main breaker control switch, emergency stop switch
3. Auxiliary voltage transformer (230 or 115 VAC) [T10]
2 4. Swing-out frame with auxiliary control relays, circuit breakers, etc.
5. IGBT supply module control unit [RDCU]
8 13
5 10
12
4
6
9
3
Hardware description
"Uncontrolled Copy"
14
Doors closed
A B C D E
Description
1 A Auxiliary control cabinet
1. Auxiliary circuit switch-fuse [Q10]
9
2. Meters, main breaker control switch, emergency stop switch
3. Auxiliary voltage transformer (230 or 115 VAC) [T10]
2 4. Swing-out frame with auxiliary control relays, circuit breakers, etc.
5. IGBT supply module control unit [RDCU] and branching unit
8 [APBU]
B Incoming cabinet
6. Input power cable and PE terminals
7. IGBT supply charging resistors and contactor [K2, R]
8. Withdrawable main circuit breaker [Q1]
9. Grounding switch [Q9]
6
3 7
Hardware description
"Uncontrolled Copy"
15
Single-line diagrams
Control circuitry 2) 3)
1
0
START RMIO
board
Supply
transformer 2×ACS800
U< -104
Q1 F2 LCL F1
~
= DC supply for
Q10 F20 inverters
Q9 ~
4
=
K2 R
T10
1) Power supply for IGBT supply module
fan (only with constant speed fan) 1) n
2) Power supply for LCL filter module fan
3) Temperature supervision
4) Module control via fibre optic link
2)
Fan on/off control and temperature
supervision (only with constant speed Control circuitry 3) 4)
fan)
1
0
START RMIO APBU
board board
Hardware description
"Uncontrolled Copy"
16
Single-line diagram
3 2
2 No. Marking Explanation
7
1 U2…W2 Power input busbars (3 phase AC)
2 2 +, - Power output busbars (DC)
6 3 X50 Socket for fan control. Not in use.
5 Cooling fan
1 Module connects to the cabinet ground busbar via the fixing bolts
3 and the cabinet frame.
Module layout
The figure below shows the IGBT supply module. The control unit (type RDCU)
containing the RMIO board is external (not shown).
2 No. Explanation
2
1 Power input busbars (3 phase AC)
3
2 Power output busbars (DC)
5 Cooling fan
1
4
Hardware description
"Uncontrolled Copy"
17
V1 V68
Phase current
X7 V2 V57
measurements
(3)
M
1~
Item Explanation
1)
The RDCU can optionally equipped be with an auxiliary power interface board (RAPI). The RAPI
board ensures the “POWER FAIL” function of the RMIO board can be carried out in case the 24 V
auxiliary power to the RDCU is interrupted, i.e. the fault and alarm loggers have enough time to write
collected data into the flash memory.
Hardware description
"Uncontrolled Copy"
18
General
Modules of frame size R8i are used to achieve output powers from 200 kW upwards.
It can be used in single or parallel configurations. The module runs on wheels, and it
can easily be removed from the cabinet for service.
Single-line diagram
2
5 4 No. Connection/measurement
n
1 (U2, Quick connector for power input (3 phase AC)
2 V2, W2)
1 Module connects to the cabinet ground busbar via the fixing bolts
and the cabinet frame.
3
Hardware description
"Uncontrolled Copy"
19
Layout
The figure below shows the IGBT supply module. The control unit (type RDCU)
containing the RMIO board is external (not shown).
5
2
Item Explanation
1 DC (output) connections
2 Input busbars. To be aligned with the quick connector socket mounted in the cabinet.
Direct connection of cables without using a quick connector is also possible.
3 Fibre optic connectors of the AINT board. Connected to the RDCU drive control unit (via
an NPBU/APBU branching unit in case of parallel modules).
5 Handle
6 Cooling fan
7 Socket for cooling fan power supply and control (only for a constant speed fan)
Hardware description
"Uncontrolled Copy"
20
V1 V68
Phase current
X7 V2 V57
measurements
(3) V5
AFPS AFIN
Intermediate M
DC link input X1 X2 X1 X2 3~
2
V1
(1
Fan power
supply and X50
control
Item Explanation
RDCU Drive control unit. Note that in units with several modules in parallel, there is a branching
unit (APBU or NPBU) between the modules and the control unit.
AFPS Power supply for inverter feeding motor of module fan (only in units with speed-controlled
fan)
AFIN Inverter feeding motor of module fan (only in units with speed-controlled fan)
1)
Fan power supply alternatives: Constant speed fan has an external power supply via X50. Speed-
controlled fan is supplied from module DC via an inverter.
2)
The RDCU can optionally equipped be with an auxiliary power interface board (RAPI). The RAPI
board ensures the “POWER FAIL” function of the RMIO board can be carried out in case the 24 V
auxiliary power to the RDCU is interrupted, i.e. the fault and alarm loggers have enough time to write
collected data into the flash memory.
Hardware description
"Uncontrolled Copy"
21
Item Explanation
4 1 AC input busbars
2
2 AC output busbars
3 Cooling fan
Hardware description
"Uncontrolled Copy"
22
ALCL_1x_x ALCL_2x_x
3
1 1
3
4
2
4
Item Explanation
1 AC input busbars
4 Cooling fan
Hardware description
"Uncontrolled Copy"
23
Control interfaces
The following diagram shows the control interfaces and I/O options of the supply
unit.
Input power
= ~ To motor
~ =
Supply unit Inverter unit
Hardware description
"Uncontrolled Copy"
24
Hardware description
"Uncontrolled Copy"
25
Basic code
Digit no. Name Alternatives Description
5 380…500 V
7 380…690 V
Option codes
This is a common list for the ACS800 supply units. Not all options are available/used
for the IGBT Supply Unit (ACS800-207).
Category Value Description
Input B052 IP21, UL type 1, NEMA 1
B053 IP22, UL type 1, NEMA 1
B054 IP42, UL type 1, NEMA 1
B055 IP54, UL type 12, NEMA12
Degree of C121 Marine Construction
protection C128 Cooling air through bottom
C129 UL-approved components-approved components
C130 Channelled Air Outlet
C134 CSA
Construction E202 EMC/RFI-filter modules
E210 2nd Environment
Line options F250 Line Contactor
F251 Fuses
F253 Disconnector
F254 Switch Fuse
F255 Circuit Breaker (SACE)
F259 Earthing Switch
Cabinet G300 Cabinet Heater
options G301 Cabinet Lightning
G304 115 VAC
G307 Terminals for External Control Voltage
G314 Aluminium
Hardware description
"Uncontrolled Copy"
26
Hardware description
"Uncontrolled Copy"
27
Basic code
Digit no. Name/Description Alternatives Description
Option codes
Ident. Name/Description Alternatives Description
letter
C Cooling fan control C126 Speed-controlled cooling fan supplied from the
DC bus. Frame R8i only.
Hardware description
"Uncontrolled Copy"
28
Basic code
Digit no. Name/Description Alternatives Description
Option codes
Ident. Name/Description Alternatives Description
letter
Hardware description
"Uncontrolled Copy"
29
Electrical installation
Electrical installation
"Uncontrolled Copy"
30
Q1 K1
L1
L2 ~
L3
=
PE
Connection procedure
Release the handle and open the door of the cabinet.
Remove the shrouds that protect the input busbars and cable lead-through.
Lead the cables into the cabinet and connect:
• Twist the cable shields to bundles and connect to cabinet PE (ground) busbar.
Connect the separate ground conductors/cables (if exist) to cabinet PE (ground)
busbar.(1) For minimal interference, it is a recommended practise to run the cable
unstripped up to the phase busbars and ground the cable shield 360 degrees.(2)
• Connect the phase conductors to the input power terminals.(3) Tightening
torque = 70 Nm [55 lb.ft].
Replace the shrouds and close the door.
Electrical installation
"Uncontrolled Copy"
31
Converter cubicle
Door open, shrouds removed
Recommendation: 360°
grounding of the cable shield at
the lead-through suppresses
interference.
3
2
3
PE
PE
Electrical installation
"Uncontrolled Copy"
32
U<
Q1
L1
L2 ~
L3
=
PE
Connection procedure
Release the handle and open the door of the incoming cabinet. (See chapter
Hardware description.)
Remove the shrouds that protect the input busbars and cable lead-through.
Lead the cables into the inside of the cabinet and connect as follows:
• Twist the cable shields to bundles and connect to cabinet PE (ground) busbar.
Connect the separate ground conductors/cables (if exist) to cabinet PE (ground)
busbar.
• Connect the phase conductors to the input power terminals. Tightening
torque = 70 Nm [55 lb.ft].
• Replace the protecting shrouds and close the door.
Electrical installation
"Uncontrolled Copy"
33
Control connections
General
Typically, the cabinet-installed IGBT supply unit is controlled using the local control
devices mounted on the cabinet door: The off/on/start switch, the reset button and
the emergency stop button. No additional control connections are used or needed.
However, it is also possible to:
• halt the unit by an external emergency stop button. If the unit is equipped with a
local emergency stop button, external buttons can be connected in series.
• read the fault indication through a relay output
• communicate with the unit through a serial communication interface.
See the circuit diagrams delivered with the unit for the default control connections
and the connection terminals.
Connection procedure
If additional control cables need to be installed, proceed as follows:
Disconnect the main circuit from power supply and open the auxiliary circuit switch-disconnector.
Release the door handle and open the door of the control and I/O cabinet.
Remove the two locking screws at the edge of the swing-out frame and open the frame.
Run the cables into the inside of the cabinet through the grommets provided.
Top entry units only: If several cables need to be run through one grommet, use Loctite 5221 (cat. no.
25551) under the grommet to seal the cable entry.
Side view
Strain relief EMI conductive
cushions
Electrical installation
"Uncontrolled Copy"
34
If the outer surface of a cable shield is non-conductive, turn the shield inside out as shown below and
apply copper foil to keep the shielding continuous. Do not cut the grounding wire (if present).
Copper foil
Grounding wire
Sort the cables so that the thinnest and thickest cables are at opposite ends of the opening.
Top view
Run the cables to the swing-out frame as shown below. Wherever possible, use the existing cable trunking
(1) in the cabinet. Use sleeving wherever the cables are laid against sharp edges. Leave some slack in the
cable at the hinge (2) to allow the frame to open fully. Tie the cables to the braces (3) to provide strain
relief.
Note: Actual equipment may differ from what is shown below.
Swing-out frame open Cable routing example
3
1
Cut the cables to suitable length. Strip the cables and conductors.
Electrical installation
"Uncontrolled Copy"
35
Twist the cable shields into bundles and connect them to the ground terminal nearest to the terminal block.
Keep the unshielded portion of the cables as short as possible.
Connect the conductors to appropriate terminals (see the circuit diagrams delivered with the unit).
Close the swing-out frame, refasten it, and close the doors.
Electrical installation
"Uncontrolled Copy"
36
3~ Input
Primary
Secondary
Output
Supply Tap settings Supply 230 V 115 V 400 V (50 Hz) 320 V (60 Hz)
Terminals
voltage A1 to... B1 to… C1 to… voltage Terminals Tap setting Terminals Tap setting Terminals Terminals
690 V A1, B1, C1 C2 A2 B2 690 V a3, n1 230– a4, n1 115– a1, b1, c1 a2, b2, c2
660 V A1, B1, C1 C2 A2 B2 660 V a3, n1 230+ a4, n1 115+ a1, b1, c1 a2, b2, c2
600 V A1, B1, C1 C3 A3 B3 600 V a3, n1 230– a4, n1 115– a1, b1, c1 a2, b2, c2
575 V A1, B1, C1 C3 A3 B3 575 V a3, n1 230+ a4, n1 115+ a1, b1, c1 a2, b2, c2
525 V A1, B1, C1 C4 A4 B4 525 V a3, n1 230– a4, n1 115– a1, b1, c1 a2, b2, c2
500 V A1, B1, C1 C4 A4 B4 500 V a3, n1 230+ a4, n1 115+ a1, b1, c1 a2, b2, c2
480 V A1, B1, C1 C5 A5 B5 480 V a3, n1 230– a4, n1 115– a1, b1, c1 a2, b2, c2
460 V A1, B1, C1 C5 A5 B5 460 V a3, n1 230+ a4, n1 115+ a1, b1, c1 a2, b2, c2
440 V A1, B1, C1 C6 A6 B6 440 V a3, n1 230– a4, n1 115– a1, b1, c1 a2, b2, c2
415 V A1, B1, C1 C6 A6 B6 415 V a3, n1 230+ a4, n1 115+ a1, b1, c1 a2, b2, c2
400 V A1, B1, C1 C7 A7 B7 400 V a3, n1 230– a4, n1 115– a1, b1, c1 a2, b2, c2
380 V A1, B1, C1 C7 A7 B7 380 V a3, n1 230+ a4, n1 115+ a1, b1, c1 a2, b2, c2
Electrical installation
"Uncontrolled Copy"
37
Start-up
WARNING! Only qualified electricians are allowed to commission the drive. Read
and follow the safety instructions delivered with the drive. Neglecting the safety
instructions can cause injury or death.
Start-up
"Uncontrolled Copy"
38
Start-up
"Uncontrolled Copy"
39
Start-up
"Uncontrolled Copy"
40
Start-up
"Uncontrolled Copy"
41
Maintenance
Maintenance intervals
If installed in an appropriate environment, the drive requires very little maintenance.
Routine maintenance intervals recommended by ABB are given below.
Every year of storage Capacitor reforming See document Capacitor Reforming Guide (Code:
3BFE 64059629 [English]).
Every 6 to 12 months Heatsink temperature check See section Cleaning the heatsink.
(depending on dustiness of and cleaning
environment)
Every year (IP22, IP22R, IP42 Air filter check, replacement if See section Checking and replacing the air filters.
and IP42R units) necessary
Every 3 years (frame R8i) Quick connector connection See section Checking and cleaning the power
surfaces check, cleaning and connections via quick connector.
greasing
Every 6 years IGBT supply module and LCL See section Replacing the cooling fans.
filter module cooling fan
change
Every 6 years (parallel- Memory backup battery Locate APBU unit. Switch off power to unit.
connected IGBT supply renewal of the APBU branching Remove cover. Replace battery with new CR 2032
modules) unit battery.
Every 10 years Capacitor renewal See Replacing and reforming the capacitors.
Maintenance
"Uncontrolled Copy"
42
• Remove the module cooling fan (see section Replacing the cooling fans
on page 44).
• Blow dry clean compressed air from bottom to top and simultaneously use a
vacuum cleaner at the air outlet to trap the dust. Note: Prevent the dust from
entering adjoining equipment.
• Refit the cooling fan.
• Check the air filters and replace them if necessary. See chapter Technical data -
ACS800-207 for the correct filter types. To access the inlet (door) filters: remove
the fastener(s) at the top of the grille, lift the grille and pull it away from the door.
The outlet (roof) filter in IP54 units has a similar mechanism.
• Check the cleanliness of the cabinet. Clean the interior of the cabinet if necessary
using a soft brush and a vacuum cleaner.
• Close the cabinet doors.
Maintenance
"Uncontrolled Copy"
43
• Extract the supply module from the cabinet. See section Replacing the supply
module, frame size R8i below.
• Check the tightness of the cable connections at the quick connector. See the
tightening torque table in chapter Technical data - ACS800-104 IGBT supply
module.
• Clean all contact surfaces of the quick connector and apply a layer of suitable
joint compound (e.g. Isoflex® Topas NB 52 from Klüber Lubrication) onto them.
• Re-insert the module.
• Repeat the procedure for all remaining modules.
Reforming
Reform (re-age) spare part capacitors once a year according to Capacitor Reforming
Guide (code: 64059629 [English]), available from your local ABB representative.
Capacitor replacement
Contact an ABB service representative.
Maintenance
"Uncontrolled Copy"
44
Maintenance
"Uncontrolled Copy"
45
Maintenance
"Uncontrolled Copy"
46
2 2
Maintenance
"Uncontrolled Copy"
47
ALCL-1x ALCL-2x
2 2
1
3
Maintenance
"Uncontrolled Copy"
48
Maintenance
"Uncontrolled Copy"
49
5
4
Maintenance
"Uncontrolled Copy"
50
WARNING! The IGBT supply modules are heavy and have a high centre of gravity.
Be careful when manoeuvring the modules. In order to minimise the danger of
toppling over, keep the support legs of the modules extended whenever
manoeuvring outside the cabinet.
Maintenance
"Uncontrolled Copy"
51
4a
2
1
6
7a 7b 4c
4d
4b
Maintenance
"Uncontrolled Copy"
52
LEDs
This table describes LEDs of the IGBT supply unit that are visible to the user.
Maintenance
"Uncontrolled Copy"
53
Ratings
IGBT Supply Unit Basic Module Frame Nominal ratings (no overload use) Light overload use Heavy-duty use
ACS800-104… Icontmax Icont.max Imax SN Pcont.max In PN Ihd Phd
A (AC) A (DC) A (DC) kVA kW (DC) A (DC) kW A (DC) kW
UN=400 V (Range 380-415 V)
ACS800-207-0135-3 -0145-3 R7i 182 221 330 131 130 212 124 165 97
ACS800-207-0155-3 -0175-3 R7i 224 272 406 161 159 261 153 203 119
ACS800-207-0200-3 -0260-3+E205 R8i 284 344 471 204 202 331 194 258 151
ACS800-207-0260-3 -0320-3+E205 R8i 378 458 627 272 269 440 258 343 201
ACS800-207-0330-3 -0390-3+E205 R8i 473 573 784 340 336 550 323 429 252
ACS800-207-0440-3 -0510-3+E205 R8i 630 764 1046 453 448 733 430 571 335
ACS800-207-0660-3 -0390-3+E205 2×R8i 945 1146 1568 679 672 1100 646 857 503
ACS800-207-0860-3 -0510-3+E205 2×R8i 1235 1497 2049 888 879 1437 844 1120 657
ACS800-207-1270-3 -0510-3+E205 3×R8i 1833 2223 3042 1318 1304 2134 1252 1662 976
ACS800-207-1680-3 -0510-3+E205 4×R8i 2419 2933 4015 1739 1722 2816 1653 2194 1288
ACS800-207-2490-3 -0510-3+E205 6×R8i 3591 4354 5960 2581 2555 4180 2453 3257 1911
UN=500 V (Range 380-500 V)
ACS800-207-0165-5 -0175-5 R7i 180 218 327 156 154 210 148 163 115
ACS800-207-0195-5 -0215-5 R7i 220 267 399 191 189 256 181 200 141
ACS800-207-0230-5 -0320-5+E205 R8i 270 327 475 234 231 314 222 245 173
ACS800-207-0310-5 -0400-5+E205 R8i 360 436 633 312 309 419 296 327 231
ACS800-207-0390-5 -0460-5+E205 R8i 450 546 792 390 386 524 370 408 289
ACS800-207-0520-5 -0610-5+E205 R8i 600 727 1056 520 514 698 494 544 385
ACS800-207-0780-5 -0460-5+E205 2×R8i 900 1091 1584 779 772 1048 741 816 577
ACS800-207-1020-5 -0610-5+E205 2×R8i 1176 1426 2069 1018 1008 1369 968 1067 754
ACS800-207-1510-5 -0610-5+E205 3×R8i 1746 2117 3072 1512 1497 2032 1437 1584 1120
ACS800-207-2000-5 -0610-5+E205 4×R8i 2304 2794 4054 1995 1975 2682 1896 2090 1478
ACS800-207-2960-5 -0610-5+E205 6×R8i 3420 4147 6017 2962 2932 3981 2815 3102 2193
UN=690 V (Range 525-690 V)
ACS800-207-0155-7 -0175-7 R7i 119 144 216 142 141 139 135 108 105
ACS800-207-0175-7 -0215-7 R7i 135 164 245 161 160 157 153 122 119
ACS800-207-0220-7 -0260-7+E205 R8i 180 218 327 215 213 210 204 163 159
ACS800-207-0300-7 -0400-7+E205 R8i 250 303 453 299 296 291 284 227 221
ACS800-207-0360-7 -0440-7+E205 R8i 300 364 544 359 355 349 341 272 266
ACS800-207-0480-7 -0580-7+E205 R8i 400 485 726 478 473 466 454 363 354
ACS800-207-0720-7 -0440-7+E205 2×R8i 600 727 1088 717 710 698 682 544 531
ACS800-207-0940-7 -0580-7+E205 2×R8i 784 951 1422 937 928 913 890 711 694
ACS800-207-1390-7 -0580-7+E205 3×R8i 1164 1411 2111 1391 1377 1355 1322 1056 1030
ACS800-207-1840-7 -0580-7+E205 4×R8i 1536 1862 2786 1836 1817 1788 1745 1393 1359
ACS800-207-2730-7 -0580-7+E205 6×R8i 2280 2764 4136 2725 2698 2654 2590 2068 2018
ACS800-207-3630-7 -0580-7+E205 8×R8i 3040 3686 5514 3633 3597 3539 3453 2757 2690
ACS800-207-4550-7 -0580-7+E205 10×R8i 3800 4607 6893 4541 4496 4423 4316 3446 3363
ACS800-207-5450-7 -0580-7+E205 12×R8i 4560 5529 8271 5450 5395 5308 5179 4136 4036
00184674.xls / G
Nominal ratings
Icont.max continuous rms input (AC) or output (DC) current. No overload capability at 40°C.
Imax maximum output current. Available for 10 s at start, otherwise as long as allowed by module temperature.
Pcont.max nominal output power
See www.luftfilter.com.
13 [0.51] 40 [1.57]
M12 70 Nm n × 60 mm
2)
(½”) (50 lb.ft) (n × 2.36“)
50 [1.97]
1) n = 9 for units with one to two parallel IGBT supply modules, n = 18 for units with three to four parallel
Degree of protection
IP21, IP22, IP42, IP54, IP22R, IP42R, IP54R (with air duct outlet) and UL approved
NEMA 1 and NEMA 12.
Materials
Cabinet Hot-dip zinc-coated (thickness approx. 20 µm) sheet steel with polyester thermosetting powder
coating (thickness approx. 80 µm) on visible surfaces. Colour: RAL 7035 (light beige, semigloss).
Packaging Frame of wood or plywood with PE-LD wrapping and PP or steel bands.
Disposal The drive contains raw materials that should be recycled to preserve energy and natural resources.
The package materials are environmentally compatible and recyclable. All metal parts can be
recycled. The plastic parts can either be recycled or burned under controlled circumstances,
according to local regulations. Most recyclable parts are marked with recycling marks.
If recycling is not feasible, all parts excluding electrolytic capacitors and printed circuit boards can be
landfilled. The DC capacitors (C1-1 to C1-x) contain electrolyte and the printed circuit boards contain
lead, both of which will be classified as hazardous waste within the EU. They must be removed and
handled according to local regulations.
For further information on environmental aspects and more detailed recycling instructions, please
contact your local ABB distributor.
Other data
The following subsections in chapter Technical data - ACS800-104 IGBT supply
module are also valid for ACS800-207:
• Derating
• LCL filter types
• AC and DC fuses
• Input power connection
• Ambient conditions
• RMIO board specifications
Ratings
Nominal ratings (no overload use) Light overload use Heavy-duty use
Basic module Frame
Module type Icontmax Icont.max Imax SN Pcont.max In PN Ihd Phd
ACS800-104…
A (AC) A (DC) A (DC) kVA kW (DC) A (DC) kW A (DC) kW
400 V
ACS800-104-0145-3 -0145-3 R7i 182 221 330 131 130 212 124 165 97
ACS800-104-0175-3 -0175-3 R7i 224 272 406 161 159 261 153 203 119
ACS800-104-0260-3+E205 -0260-3+E205 R8i 284 344 471 204 202 331 194 258 151
ACS800-104-0320-3+E205 -0320-3+E205 R8i 378 458 627 272 269 440 258 343 201
ACS800-104-0390-3+E205 -0390-3+E205 R8i 473 573 784 340 336 550 323 429 252
ACS800-104-0510-3+E205 -0510-3+E205 R8i 630 764 1046 453 448 733 430 571 335
ACS800-104-0770-3+E205 -0390-3+E205 2×R8i 945 1146 1568 679 672 1100 646 857 503
ACS800-104-1030-3+E205 -0510-3+E205 2×R8i 1235 1497 2049 888 879 1437 844 1120 657
ACS800-104-1540-3+E205 -0510-3+E205 3×R8i 1833 2223 3042 1318 1304 2134 1252 1662 976
ACS800-104-2050-3+E205 -0510-3+E205 4×R8i 2419 2933 4015 1739 1722 2816 1653 2194 1288
500 V
ACS800-104-0175-5 -0175-5 R7i 180 218 327 156 154 210 148 163 115
ACS800-104-0215-5 -0215-5 R7i 220 267 399 191 189 256 181 200 141
ACS800-104-0320-5+E205 -0320-5+E205 R8i 270 327 475 234 231 314 222 245 173
ACS800-104-0400-5+E205 -0400-5+E205 R8i 360 436 633 312 309 419 296 327 231
ACS800-104-0460-5+E205 -0460-5+E205 R8i 450 546 792 390 386 524 370 408 289
ACS800-104-0610-5+E205 -0610-5+E205 R8i 600 727 1056 520 514 698 494 544 385
ACS800-104-0910-5+E205 -0460-5+E205 2×R8i 900 1091 1584 779 772 1048 741 816 577
ACS800-104-1210-5+E205 -0610-5+E205 2×R8i 1176 1426 2069 1018 1008 1369 968 1067 754
ACS800-104-1820-5+E205 -0610-5+E205 3×R8i 1746 2117 3072 1512 1497 2032 1437 1584 1120
ACS800-104-2430-5+E205 -0610-5+E205 4×R8i 2304 2794 4054 1995 1975 2682 1896 2090 1478
690 V
ACS800-104-0175-7 -0175-7 R7i 119 144 216 142 141 139 135 108 105
ACS800-104-0215-7 -0215-7 R7i 135 164 245 161 160 157 153 122 119
ACS800-104-0260-7+E205 -0260-7+E205 R8i 180 218 327 215 213 210 204 163 159
ACS800-104-0400-7+E205 -0400-7+E205 R8i 250 303 453 299 296 291 284 227 221
ACS800-104-0440-7+E205 -0440-7+E205 R8i 300 364 544 359 355 349 341 272 266
ACS800-104-0580-7+E205 -0580-7+E205 R8i 400 485 726 478 473 466 454 363 354
ACS800-104-0870-7+E205 -0440-7+E205 2×R8i 600 727 1088 717 710 698 682 544 531
ACS800-104-1160-7+E205 -0580-7+E205 2×R8i 784 951 1422 937 928 913 890 711 694
ACS800-104-1740-7+E205 -0580-7+E205 3×R8i 1164 1411 2111 1391 1377 1355 1322 1056 1030
ACS800-104-2320-7+E205 -0580-7+E205 4×R8i 1536 1862 2786 1836 1817 1788 1745 1393 1359
00184674.xls / G
Nominal ratings
Icont.max continuous rms input (AC) or output (DC) current. No overload capability at 40°C.
Imax maximum output current. Available for 10 s at start, otherwise as long as allowed by module temperature.
Pcont.max nominal output power
Light overload use (10% overload capability) ratings
IN continuous rms current. 10% overload is allowed for one minute every 5 minutes.
PN output power in light overload use
Heavy-duty use (50% overload capability) ratings
Ihd continuous rms current. 50% overload is allowed for one minute every 5 minutes.
Phd output power in heavy duty-use
Derating
The load capacity (current and power) decreases if the installation site altitude exceeds 1000 metres
(3300 ft), or if the ambient temperature exceeds 40 °C (104 °F).
Temperature derating
In the temperature range +40°C (+104°F) to +50 °C (+122°F) the rated output current is decreased 1 %
for every additional 1 °C (1.8°F). The output current is calculated by multiplying the current given in the
rating table by the derating factor.
Example If the ambient temperature is +50°C (+122°F), the derating factor is 100% - 1 % · 10°C =
90 % or 0.90. The output current is then 0.90 · I or 0.90 · I . °C
N hd
Note: Icont.max rating is not allowed above 40°C (104°F).
Altitude derating
In altitudes from 1000 to 4000 m (3300 to 13123 ft) above sea level, the derating is 1% for every 100 m
(328 ft). For a more accurate derating, use the DriveSize PC tool. If the installation site is higher than
2000 m (6600 ft) above sea level, please contact your local ABB distributor or office for further
information.
AC and DC fuses
Note 1: Larger fuses must not be used.
Note 2: Fuses from other manufacturers can be used if they meet the ratings.
Note 3: The recommended fuses are for branch circuit protection per NEC as
required for the UL approval.
Module type DC fuse information AC fuse information
Bussman type Qty Bussman type In Qty
400 V
ACS800-104-0145-3 170M3819 2 170M3817 315 3
ACS800-104-0175-3 170M6810 2 170M5808 400 3
ACS800-104-0260-3 170M6810 2 170M5809 450 3
ACS800-104-0320-3 170M8545 2 170M6810 630 3
ACS800-104-0390-3 170M8552 2 170M8545 800 3
ACS800-104-0510-3 170M8547 2 170M6814 1000 3
ACS800-104-0770-3 170M8552 4 170M6419 1600 3
ACS800-104-1030-3 170M8547 4 170M6421 2000 3
ACS800-104-1540-3 170M8547 6 170M6419 1600 6
ACS800-104-2050-3 170M8547 8 170M6421 2000 6
500 V
ACS800-104-0175-5 170M3819 2 170M3817 315 3
ACS800-104-0215-5 170M6810 2 170M5808 400 3
ACS800-104-0320-5 170M6810 2 170M5809 450 3
ACS800-104-0400-5 170M8545 2 170M6810 630 3
ACS800-104-0460-5 170M8552 2 170M8545 800 3
ACS800-104-0610-5 170M8547 2 170M6814 1000 3
ACS800-104-0910-5 170M8552 4 170M6419 1600 3
ACS800-104-1210-5 170M8547 4 170M6421 2000 3
ACS800-104-1820-5 170M8547 6 170M6419 1600 6
ACS800-104-2430-5 170M8547 8 170M6421 2000 6
690 V
ACS800-104-0175-5 170M6301 2 170M3816 250 3
ACS800-104-0215-5 170M6303 2 170M3817 315 3
ACS800-104-0260-7 170M8643 2 170M3817 315 3
ACS800-104-0400-7 170M8645 2 170M5809 450 3
ACS800-104-0440-7 170M8646 2 170M5809 450 3
ACS800-104-0580-7 170M8647 2 170M6810 630 3
ACS800-104-0870-7 170M8646 4 170M6414 1000 3
ACS800-104-1160-7 170M8647 4 170M6416 1250 3
ACS800-104-1740-7 170M8647 6 170M6414 1000 6
ACS800-104-2320-7 170M8647 8 170M6416 1250 6
00184674.xls / G
1)
Noise for the complete IGBT supply unit including the LCL filter(s)
2) Dimensions for single module only.
Minimum effective area of air Minimum effective area of air Max. pressure
inlet 2) outlet 2) drop of
Nominal air
IGBT supply Frame cabinet at
flow 1) with Luftfilter/ with Luftfilter/
module type size unfiltered unfiltered nominal air
airTex G150 airTex G150
flow 2)
m3/h (ft3/min) cm2 (in2) cm2 (in2) cm2 (in2) cm2 (in2) Pa
400 V
ACS800-104-0145-3 R7i 800 (470) 960 (150) 1920 (295) 1536 (240) 3072 (475) 150
ACS800-104-0175-3 R7i 800 (470) 960 (150) 1920 (295) 1536 (240) 3072 (475) 150
ACS800-104-0260-3 1×R8i 1280 (750) 960 (150) 1920 (295) 1536 (240) 3072 (475) 150
ACS800-104-0320-3 1×R8i 1280 (750) 960 (150) 1920 (295) 1536 (240) 3072 (475) 150
ACS800-104-0390-3 1×R8i 1280 (750) 960 (150) 1920 (295) 1536 (240) 3072 (475) 150
ACS800-104-0510-3 1×R8i 1280 (750) 960 (150) 1920 (295) 1536 (240) 3072 (475) 150
ACS800-104-0770-3 2×R8i 2560 (1510) 1440 (225) 2280 (355) 2304 (355) 4608 (715) 180
ACS800-104-1030-3 2×R8i 2560 (1510) 1440 (225) 2280 (355) 2304 (355) 4608 (715) 180
ACS800-104-1540-3 3×R8i 3840 (2260) 1920 (295) 3840 (595) 3072 (475) 6144 (950) 180
ACS800-104-2050-3 4×R8i 5120 (3010) 2880 (445) 5700 (885) 4608 (715) 9216 (1430) 180
500 V
ACS800-104-0175-5 R7i 800 (470) 960 (150) 1920 (295) 1536 (240) 3072 (475) 150
ACS800-104-0215-5 R7i 800 (470) 960 (150) 1920 (295) 1536 (240) 3072 (475) 150
ACS800-104-0320-5 1×R8i 1280 (750) 960 (150) 1920 (295) 1536 (240) 3072 (475) 150
ACS800-104-0400-5 1×R8i 1280 (750) 960 (150) 1920 (295) 1536 (240) 3072 (475) 150
ACS800-104-0460-5 1×R8i 1280 (750) 960 (150) 1920 (295) 1536 (240) 3072 (475) 150
ACS800-104-0610-5 1×R8i 1280 (750) 960 (150) 1920 (295) 1536 (240) 3072 (475) 150
ACS800-104-0910-5 2×R8i 2560 (1510) 1440 (225) 2280 (355) 2304 (355) 4608 (715) 180
ACS800-104-1210-5 2×R8i 2560 (1510) 1440 (225) 2280 (355) 2304 (355) 4608 (715) 180
ACS800-104-1820-5 3×R8i 3840 (2260) 1920 (295) 3840 (595) 3072 (475) 6144 (950) 180
ACS800-104-2430-5 4×R8i 5120 (3010) 2880 (445) 5700 (885) 4608 (715) 9216 (1430) 180
690 V
ACS800-104-0175-7 R7i 800 (470) 960 (150) 1920 (295) 1536 (240) 3072 (475) 150
ACS800-104-0215-7 R7i 800 (470) 960 (150) 1920 (295) 1536 (240) 3072 (475) 150
ACS800-104-0260-7 1×R8i 1280 (750) 960 (150) 1920 (295) 1536 (240) 3072 (475) 150
ACS800-104-0320-7 1×R8i 1280 (750) 960 (150) 1920 (295) 1536 (240) 3072 (475) 150
ACS800-104-0400-7 1×R8i 1280 (750) 960 (150) 1920 (295) 1536 (240) 3072 (475) 150
ACS800-104-0440-7 1×R8i 1280 (750) 960 (150) 1920 (295) 1536 (240) 3072 (475) 150
ACS800-104-0580-7 1×R8i 1280 (750) 960 (150) 1920 (295) 1536 (240) 3072 (475) 180
ACS800-104-0870-7 2×R8i 2560 (1510) 1440 (225) 2280 (355) 2304 (355) 4608 (715) 180
ACS800-104-1160-7 2×R8i 2560 (1510) 1440 (225) 2280 (355) 2304 (355) 4608 (715) 180
ACS800-104-1740-7 3×R8i 3840 (2260) 1920 (295) 3840 (595) 3072 (475) 6144 (950) 180
ACS800-104-2320-7 4×R8i 5120 (3010) 2880 (445) 5700 (885) 4608 (715) 9216 (1430) 150
1) Valid for the converter module. For the LCL filter figures, see section LCL filter dimensions, weight and air flow.
2) Valid for the IGBT Supply Unit including converter module(s) and LCL filter(s).
Cable terminals
DC and AC terminal sizes and tightening torques are given below.
R7i
M12
M12 (busbars or cable to quick connector)
R8i Tightening torque: 50 Nm (37 lbf.ft)
Tightening torque: 50 Nm (37 lbf.ft)
Max. intrusion into module: 20 mm (0.8”).
2
I 50
In nth harmonic component
THD = ∑ n
2 IN IN nominal current
THD = Total Harmonic Distortion (THD). The voltage THD depends on the short-circuit
ratio (Rsc). The spectrum of the distortion also contains interharmonics.
Rsc = Isc/IN
Isc= short-circuit current at point of common coupling (PCC)
IN= IGBT supply unit nominal current
Output connection
Voltage 510…560 V DC for 400 V units
510…675 V DC for 500 V units
710…930 V DC for 690 V units
Switching frequency 3 kHz (average)
Degree of protection
IP00
Ambient conditions
The drive is to be used in a heated, indoor controlled environment.
Operation Storage Transportation
installed for stationary use in the protective package in the protective package
Installation site altitude 0 to 4000 m (13123 ft) above - -
sea level [above 1000 m
(3281 ft), see Derating on
page 58].
Air temperature 0 to +50°C (32 to 122°F). No -40 to +70°C (-40 to +158 °F) -40 to +70°C (-40 to +158 °F)
frost allowed. See Derating
on page 58.
Relative humidity 5 to 95% Max. 95% Max. 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the presence of
corrosive gases.
Contamination levels No conductive dust allowed.
(IEC 60721-3-3, IEC 60721-3- Boards without coating: Boards without coating: Boards without coating:
2, IEC 60721-3-1) Chemical gases: Class 3C1 Chemical gases: Class 1C2 Chemical gases: Class 2C2
Solid particles: Class 3S2 Solid particles: Class 1S3 Solid particles: Class 2S2
Boards with coating: Boards with coating: Boards with coating:
Chemical gases: Class 3C2 Chemical gases: Class 1C2 Chemical gases: Class 2C2
Solid particles: Class 3S2 Solid particles: Class 1S3 Solid particles: Class 2S2
Atmospheric pressure 70 to 106 kPa 70 to 106 kPa 60 to 106 kPa
0.7 to 1.05 atmospheres 0.7 to 1.05 atmospheres 0.6 to 1.05 atmospheres
Vibration (IEC 60068-2) Max. 1 mm (0.04 in.) Max. 1 mm (0.04 in.) Max. 3.5 mm (0.14 in.)
(5 to 13.2 Hz), (5 to 13.2 Hz), (2 to 9 Hz),
max. 7 m/s2 (23 ft/s2) max. 7 m/s2 (23 ft/s2) max. 15 m/s2 (49 ft/s2)
(13.2 to 100 Hz) sinusoidal (13.2 to 100 Hz) sinusoidal (9 to 200 Hz) sinusoidal
Shock (IEC 60068-2-29) Not allowed Max. 100 m/s2 (330 ft./s2), Max. 100 m/s2 (330 ft./s2),
11 ms 11 ms
Free fall Not allowed 250 mm (10 in.) for weight 250 mm (10 in.) for weight
under 100 kg (220 lb) under 100 kg (220 lb)
100 mm (4 in.) for weight 100 mm (4 in.) for weight
over 100 kg (220 lb) over 100 kg (220 lb)
Materials
Module • PC/ABS 2.5 mm, colour NCS 1502-Y (RAL 90021 / PMS 420 C) Colour NCS 1502-Y
(RAL 90021 / PMS 420 C),
• hot-dip zinc coated steel sheet 1.5 to 2.5 mm, thickness of coating 20 micrometres
Busbars Tin plated copper (AC and DC busbars), or silver plated copper (quick connector and the
module counterpart)
Packaging Frame of wood or plywood with PE-LD wrapping and PP or steel bands.
Disposal The drive contains raw materials that should be recycled to preserve energy and natural
resources. The package materials are environmentally compatible and recyclable. All
metal parts can be recycled. The plastic parts can either be recycled or burned under
controlled circumstances, according to local regulations. Most recyclable parts are marked
with recycling marks.
If recycling is not feasible, all parts excluding electrolytic capacitors and printed circuit
boards can be landfilled. The DC capacitors (C1-1 to C1-x) contain electrolyte and the
printed circuit boards contain lead, both of which will be classified as hazardous waste
within the EU. They must be removed and handled according to local regulations.
For further information on environmental aspects and more detailed recycling instructions,
please contact your local ABB distributor.
Applicable standards
See ACS800 Multidrive and ACS800 Multidrive Modules Planning the Electrical
Installation [3AFE64783742 (English)].
Markings
See ACS800 Multidrive and ACS800 Multidrive Modules Planning the Electrical
Installation [3AFE64783742 (English)].
Analogue outputs
Two programmable current outputs: 0 (4) to 20 mA, RL < 700 ohm
Resolution 0.1% (10 bit)
Inaccuracy ± 1% (Full Scale Range) at 25 °C (77 °F). Temperature coefficient: ± 200 ppm/°C
(± 111 ppm/°F) max.
Digital inputs
With six programmable digital inputs (common ground: 24 VDC, -15% to +20%).
Group isolated, can be divided in two isolated groups (see Isolation and grounding
diagram below).
Thermistor input: 5 mA, < 1.5 kohm “1” (normal temperature), > 4 kohm “0”
(high temperature), open circuit “0” (high temperature).
Internal supply for digital inputs (+24 VDC): short circuit proof. An external 24 VDC
supply can be used instead of the internal supply.
Isolation test voltage 500 VAC, 1 min
Logical thresholds < 8 VDC “0”, > 12 VDC “1”
Input current DI1 to DI 5: 10 mA, DI6: 5 mA
Filtering time constant 1 ms
Relay outputs
Three programmable relay outputs
Switching capacity 8 A at 24 VDC or 250 VAC, 0.4 A at 120 VDC
Minimum continuous current 5 mA rms at 24 VDC
Maximum continuous current 2 A rms
Isolation test voltage 4 kVAC, 1 minute
The terminals on the RMIO board as well as on the optional modules attachable to the board fulfil the Protective Extra
Low Voltage (PELV) requirements stated in EN 50178 provided that the external circuits connected to the terminals also
fulfil the requirements.
9 AO1+
10 AO1-
11 AO2+
12 AO2-
X22
1 DI1
2 DI2
3 DI3
4 DI4
Jumper J1 settings:
9 DGND1
Boards
Un Un f In Imax
Type
V DC V AC Hz A A
APBU-44 24 – – 0.2 –
NPBU-42 24 – – 0.2 0.235
RDCU-02 24 – – 0.25 1.2
Cooling fans
Un f In Istart
Frame size Type
V AC Hz A A
50 0.7 1.4
R2E225-BD92-12 230
R7i 60 0.7 1.4
R2E225-BD40-21 115 60 1.8 3.6
400 50 1.3 2.6
R8i D2D160-BE02-11
320 60 1.8 3.6
Un f In Istart
Filter type Type
V AC Hz A A
ALCL-04-5 R2E190-AE77-50 230 50 0.26 0.52
ALCL-05-5 R2E190-AE77-50 230 50 0.26 0.52
ALCL-04-7 R2E190-AE77-50 230 50 0.26 0.52
ALCL-05-7 R2E190-AE77-50 230 50 0.26 0.52
400 50 1.3 2.6
ALCL_2x_xx D2D160-BE02-11
320 60 1.8 3.6
230 50 0.78 1.6
ALCL_1x_xx R2E225-PD-92-12
230 60 1.12 2.2
US patents
This product is protected by one or more of the following US patents
4,920,306 5,301,085 5,463,302 5,521,483 5,532,568 5,589,754
5,654,624 5,799,805 5,940,286 5,942,874 5,952,613 6,094,364
6,147,887 6,175,256 6,184,740 6,195,274 6,229,356 6,252,436
6,265,724 6,305,464 6,313,599 6,316,896 6,335,607 6,370,049
6,396,236 6,448,735 6,498,452 6,552,510 6,597,148 6,741,059
6,774,758 6,844,794 6,856,502 6,859,374 6,922,883 6,940,253
6,934,169 6,956,352 6,958,923 D 503,931
3AFE68233810 Rev B / EN
EFFECTIVE: 60.12.2005