CAS 1: DN 200 FD
REFOULEMENT STATION DE SURPRESSION (SP) VERS REGARD (R1) EN FONTE DUCTILE
Long Q Q Ø.ext DN s. int J unit Jt Jt J total V HMT Côte SP Côte R1 Côte piézo Côte piézo Pression
Tronçon lineaire singulière amont; SP aval;R1 résiduel
(ml) (l/s) M3/S (mm) m (m2) (mm/m) (m) (m) (m) (m/s) m m m (mce) (mce) mce
SP - Regard
50,000 48.61 0.049 222 FD 0.200 0.031 0.010 500 50 550 1.55 275 248.04 268.27 523 -27 -295
R1
CAS 2: DN 250 FD
REFOULEMENT STATION DE SURPRESSION (SP) VERS REGARD (R1) EN FONTE DUCTILE
Jt Jt Côte piézo Côte piézo Pression
Long Q Q Ø.ext DN s. int J unit lineaire singulière J total V HMT Côte SP Côte R1 amont; SP aval;R1 résiduel
Tronçon
(ml) (l/s) M3/S (mm) m (m2) (mm/m) (m) (m) (m) (m/s) m m m (mce) (mce) mce
SP - Regard
50,000 48.61 0.049 274 FD 0.250 0.049 0.004 175 18 193 0.99 275 248.04 268.27 523 331 62
R1
Page 1 sur 2
548.04
CAS2: Refoulement DN250 Fonte Ductile
528.04
508.04
488.04
468.04
448.04 H=193 m
428.04
408.04
388.04
368.04
348.04
328.04
308.04
Pr=62 m
288.04
268.04
248.04
228.04
PK0+000 ligne piézometrique TN Ligne statique PK50+000
Page 2 sur 2
Pr= Pression résiduel
CAS1: La perte de charge est très importante 550m, Pr est né gative(cas1 est impossible). CAS2: La perte de charge est normal 193m, Pr=62m