Digital inputs.
Pulsed input
Water meters
Fertiliser meters
Analogue inputs.
Continuous signal
EC
pH
Radiation (sunlight).
TYPES OF DOSING UNITS AND THEIR SELECTION
Control Types
Inputs and outputs – levels of sophistication
Digital outputs.
Electric command
Time based controller
Garden / landscape irrigation controller
Simple filter flushing timer
Digital inputs.
Pulsed input Increasing level of sophistication
Advanced filter flushing controller
Irrigation by volume
Analogue inputs.
Continuous signal
Highest level
Fertigation – EC pH
Irrigation based on radiation, temperature, RH.
TYPES OF DOSING UNITS AND THEIR SELECTION
Fertiliser Dosing Types
Two main methods
Batch
No Specific concentration
Continuous
Proportional dosing
EC pH monitoring
EC pH control.
TYPES OF DOSING UNITS AND THEIR SELECTION
Fertiliser Dosing Types
Two main methods
Batch
Only in soil
Mainly in the open field: not greenhouses
Fixed concentration - Direct proportional. Flow-on-flow. Fixed litres fertiliser per m³ irrigation
water.
Dosing Unit
Dosing channel
TYPES OF DOSING UNITS AND THEIR SELECTION
Fertiliser Dosing Channel
Dosing channel key
components
TYPES OF DOSING UNITS AND THEIR SELECTION
Fertiliser Dosing Channel
Dosing channel key
components
Venturi
TYPES OF DOSING UNITS AND THEIR SELECTION
Fertiliser Dosing Channel
Dosing channel key
components
Venturi
Solenoid valve
TYPES OF DOSING UNITS AND THEIR SELECTION
Fertiliser Dosing Channel
Dosing channel key
components
Venturi
Solenoid valve
Manual throttle valve
TYPES OF DOSING UNITS AND THEIR SELECTION
Fertiliser Dosing Channel
Dosing channel key
components
Venturi
Solenoid valve
Manual throttle valve
Visual flow meter.
TYPES OF DOSING UNITS AND THEIR SELECTION
Fertiliser Dosing Channel
Venturi
One flow rate
(Measured in litres / hour).
Fertiliser in
TYPES OF DOSING UNITS AND THEIR SELECTION
Fertiliser Dosing Channel
Solenoid valve
De-energised (at rest)
Closed
TYPES OF DOSING UNITS AND THEIR SELECTION
Fertiliser Dosing Channel
Solenoid valve
Energised
Open
TYPES OF DOSING UNITS AND THEIR SELECTION
Fertiliser Dosing Channel
Solenoid valve
Either
Fully closed
Fully open
Solenoid
Either
Open
Closed
Either
Flow
No flow
Either
Fertiliser
No fertiliser
TYPES OF DOSING UNITS AND THEIR SELECTION
Fertiliser Dosing Channel
Dosing channel example
Required flow rate of fertiliser solution into the irrigation system = 100 ℓ/h
80%
Venturi flow rate = 125 ℓ/h
If the solenoid remains open for a 1 h period, 125 ℓ will pass = Too much
Overshoot
Too high
Target EC
EC Too low
Time
TYPES OF DOSING UNITS AND THEIR SELECTION
Fertiliser Dosing Channel
Venturi and solenoid
Ratio - venturi flow rate : irrigation flow rate (dependant / linked)
Achieved by opening and closing dosing channel
Target EC
TYPES OF DOSING UNITS AND THEIR SELECTION
Fertiliser Dosing Channel
Dosing unit must reach target EC
Target EC
Mixing EC
Thorough
Reached quickly
Function of
Controller software (firmware)
Dosing unit design
TYPES OF DOSING UNITS AND THEIR SELECTION
Fertiliser Dosing Units
Hydraulic proportional injection unit
Three levels
Proportional dosing.
Proportional dosing with EC pH monitoring. Increasing level of sophistication
EC pH control.
TYPES OF DOSING UNITS AND THEIR SELECTION
Fertiliser Dosing Units
Open mixing tank
EC pH control.
TYPES OF DOSING UNITS AND THEIR SELECTION
Fertiliser Dosing Units
Bypass units
PSV PRV
EC pH control
Mainline Mixing
chamber
Mixing chamber.
Booster pH pH
Dosing Unit Pump
EC EC
C
1 2 3 4 5
TYPES OF DOSING UNITS AND THEIR SELECTION
fertiliser Dosing Units System Inlet System Outlet
Mixing
Inline units chamber
PSV PRV
Limited to flow constrains, as
pH pH
mainline runs through the unit.
EC pH control EC EC
Booster
Mainline Pump
C
1 2 3 4 5
Dosing Unit
TYPES OF DOSING UNITS AND THEIR SELECTION
Control Cycle
The control cycle
EC/pH control
TYPES OF DOSING UNITS AND THEIR SELECTION
Control Cycle
The control cycle
TYPES OF DOSING UNITS AND THEIR SELECTION
Control Cycle
Dosing unit design
By pass with mixing chamber
Water
downstream -
to the unit
Mixing chamber
Some water
from the
Pump mainline is
pH
EC pumped through
the dosing unit
TYPES OF DOSING UNITS AND THEIR SELECTION
Control Cycle
Dosing unit design
Open mixing tank
Pump
Venturis pH pH
Solenoid valves EC EC
TYPES OF DOSING UNITS AND THEIR SELECTION
Control Cycle
Dosing method Channel open time % Irrigation pulse Control cycle time
(minutes) (seconds)
Min % Max %
Proportional EC pH control 60 80 Less than 30 6 to 12
Flow-on-flow with EC pH 40 80 More than 30 9 to 18
monitoring
Flow-on-flow 40 80 More than 30 9 to 18
Batch Spread, Bulk or by Time 10 80 More than 120 n/a
Mixing
chamber
Main line
pH
Pump EC
TYPES OF DOSING UNITS AND THEIR SELECTION
Control Cycle
Never exceed a maximum opening time of 80%
Required flow rate of fertiliser into the solution is 100 litres per
hour.
Channel manually chocked to a flow rate of 100 litres / hour.
Solenoid must be open for 80% of the time. – This case 100%
80%
If the injection falls behind and needs to inject 110 litres / hour to
catch up, it will never catch up .
It needs the 20% cushion to catch up.
Do not use a 125 litre / hour venturi if the required dosing rate
is 125 litres / hour.
P
TYPES OF DOSING UNITS AND THEIR SELECTION
Irrigation Flow Rates
Irrigation flow rates can vary by not more than 25% at
one time.
Irrigation flow rate to first block = 20 m³/h
Dosing rate = 10 ℓ fertiliser / 1 m³ irrigation water
Dosing rate into the control cycle = 200 ℓ/h
Venturi flow rate for 80% opening time = 200 ℓ/h / 80% = 250 ℓ/h
Throttle set to 250 ℓ/h
Method of dosing
Ability to cope within the open / closing times of the dosing channel
Batch
Proportional
Flow-on-flow
EC pH control.
TYPES OF DOSING UNITS AND THEIR SELECTION
Example – Selection sheet extract
DOSING UNIT DOSING CHANNELS IRRIGATION SYSTEM
Compensation Channel
Dosing rate (ℓ fert/m3 water)
open) open)
Qty
Q
Model
minimum calibration and % maximum calibration and % open (m3/h) with channel 80% open on
open time time maximum calibration. (Note 1)
At what pressure?
Let’s say 4.5Bar.
TYPES OF DOSING UNITS AND THEIR SELECTION
Example
Scenario requirements:
Flow Rate: 100m3/h @4.5Bar
Tank 1 (Acid) 3 litre per 1m3/h
Thus: 100 x 3 = 300 ℓ/h
300 ℓ/h /80% = 375 ℓ/h
Compensation Channel
Dosing rate (ℓ fert/m3 water)
open) open)
Qty
Q
8
Model
minimum calibration and % maximum calibration and % open (m3/h) with channel 80% open on
open time time maximum calibration. (Note 1)