Documente Academic
Documente Profesional
Documente Cultură
net/publication/311988058
CITATIONS READS
5 829
3 authors:
Xing Shi
Southeast University (China)
58 PUBLICATIONS 522 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
2019 Researcher Links Workshop on Investigation of the Impact of Occupant Behavior on Building Performance in the UK and China View project
All content following this page was uploaded by Da Yan on 09 April 2018.
1
7 School of Architecture, Southeast University, Nanjing, Jiangsu Province, 210096,
8 China
2
10 School of Architecture, Tsinghua University, Beijing 100084, China
11
*
12 Corresponding author. E-mail address: zhou-x06@seu.edu.cn (X. Zhou)
13
14
1
1 Comparative research on different air-conditioning systems
3 Abstract
4 There are generally two types of air-conditioning (AC) systems, namely, centralized
5 and decentralized AC systems. This study focuses on three actual engineering projects
8 analyzed. In addition, the key elements that lead to different building energy
11 residential buildings, at the point where the centralized feature of the system meets the
12 decentralized feature of users’ load, the problems of high energy consumption and low
14 Keywords
16 research
17 1 Introduction
19 type air conditioner has been used in a majority of residential buildings in China for a
21 buildings, and they are approved and supported by specific government policies
2
1 (Zhang et al. 2009). In some opinions, centralized AC systems reflect an advanced
2 and efficient way of energy usage. They consume less energy with better service;
4 buildings should take the centralized AC systems into consideration (Aste et al. 2013).
5 One of the main advantages of centralized AC systems is that they can satisfy the
6 cooling requirements for multiple buildings at the same time (Chow et al. 2004(b)). In
7 addition, they have the advantage of employing refrigeration equipment with large
8 capacity and high efficiency. Compared to split AC systems, the power required by
9 the equipment is lower (Chow et al. 2004(c); Shimoda et al. 2008; Soederman 2007;
10 Jordi et al. 2013). Moreover, for the usage of renewable energy sources, like
12 cooling systems are simpler and less expensive (Rezaie and Rosen 2012; Chow et al.
13 2004(a)). From an energy usage point of view and considering urban landscape,
18 control method, the cooling energy supplied by the AC system would be reduced
20 decentralized AC systems, which means that the total energy consumption would not
21 include the consumption of fans or pumps. Therefore, from the above analysis on
3
1 system types, both centralized and decentralized AC systems have their own
2 advantages. From the comparison, it can be concluded that the centralized and
4 As Figure 1 shows, many studies (Li and Jiang 2009; Hu et al. 2004; Ren et al. 2003;
5 Long et al. 2003; Wu 2005; Chen et al. 2008; Ma et al. 2007; Li 2012; Building
6 Energy Research Center in Tsinghua University 2013; Sun 2006) have been
10 general. The largest difference between the energy consumption of the two systems
12
13 Figure 1. Comparison of annual energy consumption for decentralized and centralized AC
14 systems in residential buildings
15 Thus, the theoretical analyses of district cooling systems differ greatly from the actual
16 operating experience in many cases, and some important factors that lead to the large
18 have been ignored. In order to analyze the reason for the energy differences between
4
1 different types of centralized AC systems were considered in this study. The
3 discussed, and the key elements influencing the energy consumption differences
4 between centralized and decentralized AC systems in the case studies are explored.
5 2 Methodology
6 The basic information of the three actual cases is graphically explained in Figure 2.
7 Centralized AC systems are applied in all the three cases; however, the levels of
9 AC systems can be considered as three heat transfer segments, namely (1) the heat
10 transfer process between AC terminals and indoor environment, (2) the chilled water
11 heat distribution process between refrigerating machines and AC terminals, and (3)
12 the cooling water heat distribution process between refrigerating machines and the
13 cooling side. In the segment of the heat transfer process between the AC terminals and
14 indoor environment, users in case 1 cannot adjust the AC terminals; however, in case
15 2 and case 3, users can turn on or turn off the AC terminals according to their
16 requirements. In the segment of the chilled water heat distribution process between
17 the refrigerating machines and AC terminals, in case 1 and case 2, all cooling energy
18 consumptions are centralized to the cold site and processed by a unified refrigeration
19 equipment with large capacity, while in case 3, household heat pump systems are
20 applied, and the heat pumps are distributed in each family. Because of different types
5
1 different. In case 1 and case 2, the chilled water is supplied uniformly from
3 distribution process. In the segment of the cooling water heat distribution process
4 between refrigerating machines and the cooling side, all three cases use underground
5 water as the cooling source, and the cooling water is collected together for heat
7 underground cooling source and the heat pump in each household. Thus, the three
14 of chilled water and cooling water; users can adjust the AC terminals.
15 It is difficult to get direct access to all three types of actual projects; therefore, we
16 seek assistance from other researchers. Case 1 (Li 2012) and case 3 (Sun 2006) have
17 been analyzed in previous studies, and the details of energy data are sufficient for our
19 to obtain the primary data for our study. The data collection procedure for each case
20 study is as follows:
6
1 the community and the electricity consumption of the AC equipment (like
3 2. Case 2: An AC unit metering system that records the on/off state and the daily
4 run time of the fan coil unit (FCU) was installed in the community. The
7 each building, supply and return water temperatures for each building, chiller
8 flow rates, chiller supply and return water temperatures, and electrical power
9 to the chillers and pumps) were recorded every 10 min in the district cooling
10 system from July to September 2011. The energy consumption and system
14 of chiller and pumps. Moreover, the supply and return water temperatures of
16 In the following discussions, the energy consumption of each segment and the reason
7
Electricity
input
Heat Pump
Users
5 2.1 Case 1: centralized chillers and distribution system; users cannot adjust
6 terminals
8 residential buildings in the community, and the total building area is 114,000 m2. The
9 community includes 1200 households, while the occupancy ratio is approximately 90%
12 community adopt ceiling panel radiation and displacement ventilation systems to meet
14 units are chosen as cooling source. Variable speed pumps are employed on the
8
1 cooling-water and chilled-water sides. The design cooling load of the ceiling panel
2 radiation system is 1757 kW, and two heat pumps are installed with unit number
3 control.
5 The chilled water collects the cooling consumption at the users’ side together and
6 brings it to the heat pumps to obtain the unified management. On the users’ side, the
7 cooling utility is charged by area. Each space in the buildings, including the corridors,
9 temperature and humidity standard, in order to keep the comfort requirement (24 °C
10 dry-bulb temperature) in every room all the time. Therefore, the service concept in
11 this community is centralized AC control. However, under this type of control mode,
12 the adjustability of the indoor environment by the users is considerably limited. For
13 example, in this community, users cannot open the windows to get fresh air, and the
Electricity
input
Heat Pump
Users
9
1 Under this type of service, the energy consumption of the AC system in this
6 electricity consumption is 4.3 kWh/m2 (Long et al. 2003). Owing to the similarity of
7 the climate in Jiangsu and Shanghai, it is considered that the energy consumptions of
8 the split AC systems in the two districts are similar. From the comparison, the
10 approximately five times of that in the split AC system in the similar district.
11
20
(kWh/m2)
6.5
15
10
4.3
13.4
5
0
Case 1 Split AC system
12
13 Figure 4. Electricity consumption of AC system in case 1
14
15 Through the analysis of the measurements and survey results, it is found that the main
16 reason for the high AC consumption in this community is that under this type of
10
1 system, namely, the non-adjustable feature for users, the AC operation mode is full
2 time and full space. Under this type of operation mode, the operating time and space
3 of the AC system under full load is considerably higher than that of the split AC
4 system. Under the centralized AC system in case 1, the product of the service area and
6 the split AC system is adopted, the product of the service area and service time is
7 approximately 684,000 m2·h, which is only 25% of that in case 1 (Building Energy
8 Research Center in Tsinghua University 2013). The efficiency of the heat pump
9 equipment itself is high, and the average COP in the cooling season is 4.4. However,
10 with the large requirement of cooling consumption in the terminal sides, the
11 electricity consumption of the heat pump itself is approximately two times of that in
13 Compared with split AC systems, the centralized AC system includes the electricity
14 consumption of water pumps and fans. According to the system operation records
15 from May 2009 to September 2009, the monthly electricity consumption of chillers,
16 water pumps, and fresh air units (FAU) is calculated as shown in Figure 5. The
17 proportion of electricity consumption for water pumps and fans in each month ranges
18 from 30% to 60%, which is approximately 0.5 to 1.4 times of the chiller consumption.
20 contributing part in the AC system and is a major factor in the high AC consumption
11
1
Electricity consumption
6
5
(kWh/m2) 4
3
2
1
0
2009.5 2009.6 2009.7 2009.8 2009.9
2
7 The electricity consumption for each part of the centralized AC system in case 1 is
8 listed in Table 1. The efficiency of the entire AC system is equal to the users’ cooling
9 consumption divided by the sum of the electricity consumption of the heat pumps and
10 water pumps. Through calculation, we can obtain the system efficiency of this AC
11 system in case 1, which is 3.0. This value is higher than the typical efficiency of split
12 AC systems (2.5). However, in case 1, the operation mode is full time and full space,
13 and the AC terminals are non-adjustable. The actual cooling consumption of users in
14 this residential community is more than five times of that with the split AC systems in
15 the same district. Under high cooling requirement, the electricity consumption of the
12
1 centralized AC system operation in case 1 is significantly higher than that of split
2 systems, and the distribution system consumes approximately 33% of the total
3 electricity consumption. With the two affecting elements, notwithstanding the high
4 efficiency of heat pump itself and the entire AC system, the electricity consumption of
5 the AC system in case 1 is approximately five times of the consumption when split
8 2.2 Case 2: centralized chillers and distribution system, users can adjust
9 terminals
11 area of 27,944 m2 with a habitable floor area of 41,200 m2. There are 12 buildings
12 with 294 households in the community, and each building has five floors. The
13 occupancy rate is 75%. Two screw water source heat pump units with cooling
14 capacities of 1463 kW and 542 kW, separately, are taken as the central AC equipment.
15 The pumps in the water system are constant-speed—the pumps include two
16 circulating pumps and two submersible pumps. The submersible pumps are working
17 under the water to pumps the water up. The list of main equipment is presented in
18 Table 2. The FCUs are taken as AC terminals with no control on the waterside. In this
19 community, users are charged for the cooling consumption according to the operation
20 situation of the FCU terminals, i.e., the cost of cooling consumption is based on the
21 measured operating hours of fan coils under high, middle, and low speeds. When the
13
1 AC terminal is closed, there would be no cooling fees.
6 Figure 6. However, in case 2, the AC terminals are the FCUs, and users can choose
7 different speeds of the fan to adjust the indoor environment according to their
9 some rooms. Therefore, the adjustability of this type of AC terminals is very similar to
10 that of the split AC system. As previously mentioned, in this community, the charging
11 method is based on the operating hours of the AC terminals, which encourages the
12 users to turn off the AC when not required. However, for the centralized refrigerating
13 machines and the constant-flow operation mode of the chilled-water system, the
14
Electricity
input
Heat Pump
Users
4 In case 2, the measured result of the users’ cooling consumption during the cooling
5 season is 7.5 kWh/m2. Under the air-conditioning system in case 2, the adjustability of
6 the AC terminal is similar to that of the split AC system; thus, it is assumed that the
7 cooling consumptions in the two types of AC systems are similar. Through simulation,
8 it can be calculated that if the totally centralized AC system (like the full-time and
9 full-space operation mode in case 1) is applied for the community in case 2, the
11 times of the actual existing cooling consumption. Therefore, when users can adjust the
14 It is supposed that when the split AC system is applied in this residential community,
15 the cooling consumption is the same as the actual cooling consumption in case 2.
16 Using the average COP of split AC systems as 2.5, then, we can calculate that when
15
1 the split AC system is adopted, the electricity consumption of the AC system is 3.0
2 kWh/m2. This result is compared with the actual situation, as shown in Figure 7, and it
3 can be observed that the electricity consumption of the AC system in case 2 is more
Chillers Pumps
8
Eletricity consumption
6 3.2
(kWh/m2)
4
3.0
2 4.4
0
Case 2 Split AC system
5
8 Figure 8 shows the service time proportion of the FCU terminals, which is equal to
9 the total operating time in each household divided by the total number of FCUs in the
10 community and the operation hours of the heat pump. The operation data of the
11 household FCUs are obtained from the household cooling consumption meter system.
12 The results show that nearly 80 households did not open the FCU terminals during the
13 observation period, and more than 1/3 of the users indicated the use of FCU terminal
14 service time at less than 10%. The calculation showed that the average proportion of
15 the FCU terminal service time of this residential community during the entire cooling
16
60%
50%
Open Rate of FCU
40%
30%
20%
10%
0%
1 21 41 61 81 101 121 141 161 181 201 221 241 261 281
Users
1
2 Figure 8. Proportion of FCU terminal service time from July 1 to 20, 2011
4 Under this AC terminal operation mode, the contemporary usage ratio of the AC is
5 low, which resulted in a low load ratio of the entire residential community. With the
6 small load ratio, the efficiency of the entire AC system is extremely low. The system
7 efficiency in case 2, which is equal to the total cooling consumption divided by the
8 total electricity consumption, is approximately 1 (7.5/7.6). The main reasons for this
10
12 mode in this residential community, the load ratio of the entire system is
13 relatively low. Only few users have high cooling load requirements, while
15 the time, only few fan coils would operate in the AC system. However, the water
17
1 system has a constant flow rate— the water system would work under a
2 situation with large water flow rate and small differences between the supply
3 and return water temperature. As Figure 9 shows, during the entire cooling
4 season, the chilled-water temperature difference between the supply and return
7 consumption of the water pumps can account for 42% of the total electricity
8 consumption.
9 2. On the other hand, because of the low cooling load requirement in the community,
10 the heat pumps work under low load ratio for a long time. The COP of the heat
11 pumps is considerably lower than the rated value of 6.4. During the entire
12 cooling season, the average COP of the heat pumps is only 1.7, and the system
13 efficiency of the entire AC system is only 1. However, even if the COP of the
14 heat pump can reach the rated value of 6.4, the system efficiency can only
17 concluded that the electricity consumption of the water pumps is the main factor
18 that limits the increase of the system efficiency of the entire AC system.
18
Distribution of T differences beween supply and return side
Temperature differences(℃) 1.8
1.6
1.4
1.2
1.0
0.8
0.6
0.4
0.2
0.0
1# 2# 3# 4# 5# 6# 7# 8# 9# 10# 11# 12#
1
2 Figure 9. Chilled-water temperature differences between supply and return side of each building
4 In conclusion, through the analysis of case 2, when users have the ability to control
5 the AC terminals, the cooling consumption from the users’ side would reduce greatly
6 compared with the centralized AC system in case 1. Influenced by the system type,
8 consumption of the water pumps. With the constant flow rate operating mode of the
9 water system, the electricity consumption of the water pumps becomes the main
10 contributor to the total AC consumption and is also the main reason for the low
11 system efficiency.
15 buildings in the community, and the total cooling area is 70,000 m2. The community
16 includes 368 households. The distributed water loop heat pump system is adopted as
19
1 the AC system,and the design cooling load is 64 W/m2. As shown in Figure 10, the
3 decentralized heat pump system. The underground water is lifted by a deep-well pump.
4 After heat exchange, cooling water is supplied to the heat pump in each household
5 through the loop pipe network. The heat pump is distributed in each household. In
6 order to satisfy the cooling requirement, the circulating pumps operate 24 h a day
7 continuously under a constant flow rate. The cooling water pump and water collection
Distribution of
cooling water
Cooling water pump Centralized
Heat
exchanger
Water collection
pump
9
10 Figure 10. System diagram of case 3
11
12 An all-air system is taken as the AC terminal in this community. Air ducts are
20
1 installed in each room, and there is no control valve in the air inlet. Therefore, when
2 there is a cooling requirement in a room, all rooms in the household would be cooled.
3 In contrast with the two cases above, the heat pump is set in each household in case 3,
4 and the heat pump can be turned on or off according to the requirement. Thus, the
5 operation mode is part time, full space. In case 3, the AC system still has a centralized
6 feature, i.e., the cooling water circulates uniformly, and the AC terminals in each
7 household are controlled uniformly. Users will pay for the electricity consumption of
8 heat pumps and a portion of other consumptions is charge based on the area of the
9 household.
10 Researchers have obtained the average electricity consumption of the split AC system
12 Beijing (Li 2006). The electricity consumption of the AC system in the residential
14 shown in Figure 11. Considering the average COP of the split AC system as 2.5, the
17 kWh/m2. Therefore, under this type of system, the cooling consumption is higher than
18 that of the split AC system. The main reason for this is that under the split AC system,
19 the usage mode is part time and part space, while in case 3, which is influenced by the
21
10
Electricity consumption
1.2 Chillers
8 Cooling circulating pumps
(kWh/m2)
3.6 Water collection pumps
6
4
3.1
2 4.6
0
Case 3 Split AC system
1
2 Figure 11. Electricity consumption of AC system in case 3
4 During the entire cooling season, the average COP of the heat pumps is 2.9, which is
5 higher than the split AC system. However, in case 3, all the water pumps are turned on
6 for the entire day, irrespective of the number of heat pumps under operation. Only the
7 circulating pumps have an electricity consumption of 3.7 kWh/m2. Table 3 shows the
8 average result of the temperature measurement during the entire cooling season. From
9 the measured result of cooling water temperature differences, it can be observed that
10 the water system is under a situation with large water flow rate and small differences
11 between the supply and return water temperatures as shown in Table 3. Under this
12 operating situation, the consumption by the water pumps becomes the main
13 composition of the total electricity consumption, which can be observed in Figure 11.
17
22
1 Table 3. Cooling water temperature differences between supply and return side
3 In conclusion, case 3 shows that under a cooling supply mode of part time and full
4 space, the cooling requirement of users would be less than that of the total centralized
5 AC system (case 1); however, it is higher than the cooling consumption under the part
6 time and part space service mode. In case 3, the system adopts a decentralized heat
7 pump, which ensures that the heat pumps can work under a high load ratio; therefore,
8 the operating performance of the heat pumps is improved. However, the cooling water
9 system is centralized, and the electricity consumption of the cooling water distributed
10 system becomes the main part of the total consumption. The electricity consumption
11 of the cooling water pumps is approximately 51% of the total electricity consumption
12 of the AC system.
13
15 The three case studies discussed above all adopt centralized AC systems; however,
16 they are different in the users’ ability to control the AC terminals, type of refrigeration
17 equipment, and form of distribution system. Taking the three cases together and
23
1 applicability of centralized AC systems in residential buildings. For the differences in
2 thermal load, service area, room temperature, etc., it is not appropriate to compare the
3 energy consumption of the three cases directly. Therefore, in this study, we focus on
4 the characteristics of each case, and only the ratios of each energy consumption part
5 are compared.
Transport
Transport Electricity
coefficient of COP of heat System
coefficient of consumption
cooling pumps efficiency
chilled water kWh/m2
water
Case 1 29.0 4.4 14.8 3.0 21.9
Case 2 7.0 1.7 5.0 1.0 7.6
Case 3 3.7 2.9 - 1.4 9.4
10
11 The composition of the electrical and cooling consumption in the three cases are listed
12 in Table 4, and Table 5 lists the energy efficiency of each segment. The calculation
13 method of energy efficiency is based on the requirement in the Chinese standard for
24
1 “economic operation of AC control system.” The COP is equal to the cooling
2 consumption divided by the electricity consumption of the heat pumps; the transport
3 coefficient of chilled water (TCchw) is equal to the cooling consumption divided by the
5 cooling water (TCcdp) is equal to the cooling consumption divided by the electricity
6 consumption of cooling water pumps; the system efficiency is equal to the cooling
7 consumption divided by the sum of the electricity consumption of heat pumps and
8 water pumps. The electricity consumption is the sum of the consumptions of all
9 components (cooling water pumps, chilled-water pumps, and heat pumps). Through
10 the comparison and analysis, the main conclusions from the three study cases are as
11 follows:
13 terminals according to the operation of split AC system. The cooling load would
15 In cold and extremely cold areas, the cooling and heating loads in residential
16 buildings have different characteristics. During the heating season, the heating load is
17 mainly influenced by the outdoor climate; thus, the heating loads of different users are
18 synchronous. However, during the cooling season, the internal heat gain becomes the
21 Apartment is the main building type in Chinese residential buildings. The main
25
1 features of the operation mode in apartments are: 1) the occupancy situation differs
4 With these features, if users could control the AC terminals freely, they would operate
5 the AC part time and part space, and the operation mode results in the load feature of
7 Through the comparison, we can find that in totally centralized AC systems, the full
8 time and full space indoor environment control service (case 1) results in the highest
10 times of that in the situation where the AC terminals can be controlled freely (case 2).
11 The service mode is one of the most important factors affecting the differences in
13 times higher than that in case 2 and case 3. In case 1, no matter what the cooling
15 standard of comfort, i.e., the full time and full space indoor environment control mode.
16 In case 3, the household centralized AC system is adopted, and the service mode is
17 part time and full space. In this case, the cooling consumption is 13.2 kWh/m2, which
18 is lower than that in case 1. In case 2, the control of AC terminals is similar to that in
19 split AC systems, and users can control the AC terminals according to their
20 requirements. Under this type of control mode, influenced by the lifestyle, most
21 residents in China would select the part time and part space operating mode.
26
1 Therefore, the cooling consumption in case 2 is lower compared to that in case 1 and
2 case 3. For example, the bedroom in a household will only be occupied during 30% of
3 the day, and the residents would like to close the air conditioner after they fall asleep.
4 Thus, the time when the air conditioner is opened in the bedroom is only
5 approximately 20% of the day. However, the same bedroom in case 1 would be air
6 conditioned all day long; therefore, the cooling consumption would be considerably
7 higher than the actual requirement. Under this type of service mode, the factor of
8 service time and space is almost five times of that in split AC systems.
13 In case 2 and case 3, the control of AC terminals possesses the feature of that in split
19 consumption in case 2 and case 3. From Table 5, it can be observed that the transport
20 coefficient of chilled water and cooling water cannot exceed 10. In case 3, the
21 transport coefficient of chilled water is only 3.7. According to the stipulation in the
27
1 Chinese standard for “economic operation of air-conditioning control system,” when
2 the annual working condition is evaluated, the lower limit value for TCchw and TCcdp is
3 30 and 25, respectively. Therefore, in case 2 and case 3, the transport coefficients of
5 As mentioned above, in case 2 and case 3, the cooling consumptions do not differ
7 in the distribution systems continuously operate for 24 h; thus, most of the time, the
9 during the cooling season, the circulating pump electricity consumption alone is 3.2
10 kWh/m2, and this value is equal to the average electricity consumption of the split AC
11 system in summer in that area. Case 3 can explain the phenomenon further. In case 3,
12 only the cooling water is circulating in the system. With the ability to control the AC
13 terminals, residents will take the control mode of part time and part space; thus, the
14 operating time of the heat pumps will be reduced considerably. From the results in
15 case 3, the electricity consumption of heat pumps and terminal equipment is only 48%,
16 and the electricity consumption of cooling water pumps is more than half of the total
17 consumption.
18 If electric on/off valves are installed in the users’ side, and the water pumps use
19 frequency conversion control in case 2 and case 3, then the water temperature
20 differences of the chilled-water system can be increased, and this can reduce the
28
1 However, with desynchrony and low load ratio feature of the cooling load in
2 residential buildings, the energy consumption of the distribution system will still be a
4 the statistical result of each household’s AC terminal operating time frequency on July
5 4. Majority of users’ operation ratio of FCU terminals is within 10%, and only a few
6 users’ operation ratio reaches 60%. Under this situation, the most ideal control mode
7 of the water system is that many circulating pumps are installed using parallel
8 operation control, and the operation number and frequency of the water pumps are
10 engineering cases, in general, the number of pumps would be two to three. Therefore,
11 when the AC terminal operation ratio is low, the water pump operating point would
12 have a serious deviation that will result in high consumption and low efficiency of the
13 distribution system. Meanwhile, the chillers also limit the reduction of the energy
15 three chillers at most, and each chiller has a minimum flow restriction. Therefore, the
16 flow rate of the distribution system cannot be reduced considerably under low load
17 ratio. Consequently, the system will inevitably operate under a situation with large
18 water flow rate and small differences between the supply and return water
19 temperatures.
29
1 situation where the cooling consumption is extremely low and unevenly distributed
2 among different households (as Figure 8 shows). Other pumping systems, like
5 Therefore, from the above analysis, the main reason for the low system efficiency is
6 that the cooling load in residential buildings has the feature of desynchrony and low
7 load ratio, and this feature considerably differs from that in public buildings. During
8 the design phase, the engineering load calculation method usually focuses on the peak
9 load for equipment sizing, while load diversity is rarely considered. In addition, even
10 when the hourly cooling load is calculated, the internal load and schedule of each
11 household are the same; thus, the disparity due to desynchrony and low load ratio
13
60%
Operation time frequency
50%
40%
30%
20%
10%
0%
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Open ratio
14
15 Figure 12. Statistical result of operating time frequency of FUC terminal on July 4 in case 2
16
17 3. In residential buildings, the sections where the centralized feature meets the
30
1 decentralized feature frequently present high energy consumption characteristics.
2 From the above analysis, the cooling requirement in residential buildings has the
3 feature of part time and part space. This feature is in conflict with the inherent
7 In case 1, the AC terminals cannot be adjusted, and this is in conflict with the
8 decentralized feature of the cooling load on the users’ side. This contradiction leads to
10 in case 1.
11 In case 2, the AC terminals are adjustable; however, the water system has a constant
12 flow rate, which is in conflict with the users’ decentralized cooling load. Particularly,
13 in case 2, the heat distribution process of chilled water between the refrigerating
15 makes the distribution and consumption of chilled-water pumps the main reason for
16 high energy consumption. From Table 5, the transport coefficient of chilled water in
17 case 2 is only 5, which is significantly below the standard limit value of 30. The
19 operating condition of chillers and cooling water systems, resulting in low system
20 efficiency.
21 In case 3, the household heat pump system is adopted; therefore, the heat pumps and
31
1 the indoor heat transfer can be taken in entirety and possess the decentralized feature.
2 However, the cooling water system has a constant flow rate. Consequently, this
3 contradiction makes the electricity consumption of the cooling water pumps as the
4 main component of the total consumption. Comparing case 2 and case 3, where both
5 heat pumps are adopted, the electricity of the cooling water pumps in case 2 is only 20%
6 of the total consumption, while the consumption of the cooling water system in case 3
7 is 51%.
8 Therefore, through the comparison of the three cases, when a centralized AC system
13 Therefore, from the comparison, it can be concluded that the AC usage mode,
14 distribution system, and adjustability greatly influence the operation of the centralized
15 AC system. Particularly in residential buildings where the cooling load has the feature
16 of desynchrony and low load ratio, it is difficult to predict during the design phase the
17 correct sizing, control method, and pumping method that fit all types of situations.
18 This would be an extremely difficult task and would require a detailed analysis.
19 However, it should be noted that other elements, like architectural characteristics and
20 climate would also influence the performance of the AC system. More research must
32
1 consumption and system efficiency in the near future.
3 4 Conclusion
4 The data from the three cases are analyzed and discussed in this study and the
10 2. The inherent load feature of desynchrony and low load ratio would influence
12 3. The design scheme should improve the system operation efficiency on the
14
15 Acknowledgements
16 This work was supported by the Key Projects in the National Science & Technology
17 Pillar Program during the 13th Five-year Plan Period (No. 2016YFC0700102) and
19
20 References
21 Aste N, Adhikari RS, Manfren M (2013). Cost optimal analysis of heat pump
33
1 technology adoption in residential reference buildings. Renewable energy, 60:
2 615-624
3 Building Energy Research Center in Tsinghua University (2013). 2013 annual report
5 (in Chinese)
6 Chen SQ, Li NP, Guan J, Xie YQ, Sun FM, et al (2008). A statistical method to
13 Chow TT, Fong KF, Chan ALS (2004c). Energy modeling of district cooling system
15 Hu PF, Jiang ZN, Leng YH, Xiang CW (2004). Investigation of thermal environment
16 and energy consumption for Hubei residences. Heating ventilation & Air
34
1 use behavior and energy consumption in China. PhD Thesis, School of architecture in
4 buildings in China’s urban areas. Heating ventilation & Air Conditioning, 39(5):
6 Long WD, Zhong T, Zhang BH (2003). Situation and trends of residential building
10 Ma BQ, Yan ZF, Gui ZG, Tan W, He JC (2007). Investigation and analysis on summer
13 Ren J, Meng QL, Liu Y, Yang SR (2003). Analysis and research about AC energy
16 Rezaie B, Rosen MA (2012). District heating and cooling: Review of technology and
19 of district heating and cooling system by simulation considering design and operation
35
1 networks in urban regions. Applied thermal engineering, 27(16):2665-2676
2 Sun F (2006). Research of ground water-source heat pump air conditioning system.
7 Zhang WJ, Huai LL, Liu JL (2009). Comparison analysis of energy consumption
12
36