Documente Academic
Documente Profesional
Documente Cultură
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including Conditions of Contract and
Division 1 Specification Sections, apply to this Section.
0.2 SUMMARY
A. This Section includes diesel-drive, horizontal fire pumps for building fire-suppression
systems and the following:
0.3 DEFINITIONS
A. Fire Pump: Horizontal-type fire pump used to supply water at rated capacity and total head
required for fire-suppression service.
B. Fire-Pump Unit: Assembly with fire pump, driver, controller, and related accessories.
E. Split-Case Fire Pump: Axially split-case, horizontal fire pump with its housing split parallel
to shaft.
B. Pump, Equipment, Accessory, and Piping Pressure Rating: 1200 kPa minimum working-
pressure rating, unless higher rating is indicated.
0.5 SUBMITTALS
A. Product Data: Include rated capacities; certified pump performance curves with each
selection point indicated; shipping, installed, and operating weights; furnished specialties;
and accessories for each fire-pump and pressure-maintenance-pump unit and flow-
measuring system.
B. Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loads,
required clearances, methods of field assembly, components, and location and size of each
field connection for each fire-pump and pressure-maintenance-pump unit.
1. Wiring Diagrams: Detail wiring for power, signal, and control systems and
differentiate between manufacturer-installed and field-installed wiring.
2. Shop Drawings may be incorporated into other Division 13 fire-suppression piping
system Shop Drawings.
D. Field Test Reports: As specified in "Field Quality Control" Article in Part 3 of this Section,
Indicate and interpret test results for compliance with performance requirements.
G. Comply with NFPA 20, "Centrifugal Fire Pumps," for fire pumps, drivers, controllers,
accessories, and installation.
A. Preparation for Shipping: After assembling and testing fire pumps and pressure-
maintenance pumps, protect flanges and exposed machined metal surfaces, pipe openings,
and nozzles.
B. Retain shipping flange protective covers and protective coatings during storage.
C. Protect bearings and couplings against damage from sand, grit, or other foreign matter.
PART 2 - PRODUCTS
1. Characteristics: Capable of furnishing not less than 150 percent of rated capacity at
not less than 65 percent of total rated head. Shutoff head is limited to 140 percent of
total rated head.
2. Casing: Axially split cast iron with suction and discharge flanges machined to
ASME B16.1, Class 125 dimensions, unless Class 250 flanges are indicated.
3. Impeller: Cast bronze of construction to match fire pump, statically and dynamically
balanced, and keyed to shaft.
4. Wear Rings: Replaceable, bronze.
5. Shaft and Sleeve: Steel shaft with bronze sleeve.
6. Shaft Bearings: Grease-lubricated ball bearings in cast-iron housing.
7. Seals: Stuffing box with minimum of 4 rings of graphite-impregnated braided yarn
and bronze packing gland.
8. Coupling: Flexible and capable of absorbing torsional vibration and shaft
misalignment. Include metal coupling guard.
9. Driver: Diesel engine.
10. Finish: Manufacturer's standard red paint applied to factory-assembled and -tested
units before shipping.
11. Nameplates: Complete with capacities, characteristics, and other pertinent data.
8. Dual Batteries: Lead-acid-storage type, with 100 percent standby reserve capacity.
9. Fuel System: According to NFPA 20.
10. Fuel Storage Tank: Size indicated, but not less than required by NFPA 20. Include
floor legs, direct-reading level gage, and secondary containment tank with capacity at
least equal to fuel storage tank.
11. Exhaust System: ASTM A 53, Type E or S, Schedule 40, black steel pipe;
ASME B16.9, weld-type pipe fittings; ASME B16.5, steel flanges; and
ASME B16.21, nonmetallic gaskets. Fabricate double-wall, ventilated thimble from
steel pipe.
1. Controls, devices, alarms, functions, and operations listed in NFPA 20 as required for
drivers and controller types used, and specific items listed for each controller type.
2. Nameplate: Complete with capacity, characteristics, approvals and listings, and other
pertinent data.
3. Controller Sensing Pipes: Fabricate pipe and fittings according to NFPA 20 with
nonferrous-metal sensing piping, DN15, with globe valves for testing controller
mechanism from system to pump controller as indicated. Include bronze check valve
with 2.4-mm orifice in clapper or ground-face union with noncorrosive diaphragm
having 2.4-mm orifice.
4. Interface Panel: Factory supplied interface panel to communicate and transmit data
between the pump controller and BMS. All required data as from pumps as specified
to be transmitted to BMS. Interface panel to be capable for communication with the
specified BMS system.
A. Description: UL 218 and NFPA 20; listed for diesel-drive, fire-pump service. Include the
following:
1. Enclosure: UL 508 and UL 50, Type 2, wall-mounting type for field electrical
wiring.
A. Match fire-pump suction and discharge ratings as required for fire-pump capacity rating.
Include the following:
a. A completely separate pressure sensing line shall be provided for each fire
pump and for the jockey pump. The sensing line shall be arranged in
DIESEL-DRIVE, HORIZONTAL FIRE PUMPS 13922 - Page 6/11
STD-SPC-DCA(A1)-ME-DCA REV A
<Project Title>
accordance with Figure A-7-5.2.1. of NFPA 20. The sensing line shall be 15
mm H58 brass tubing complying with ASTM B 135M.
b. The sensing line shall be equipped with 2 restrictive orifice unions each.
Restricted orifice unions shall be ground-face unions with brass restricted
diaphragms drilled for a 2.4 mm. Restricted orifice unions shall be mounted in
the horizontal position, not less than 1.5 m apart on the sensing line.
c. 2 test connections shall be provided for each sensing line. Test connections
shall consist of 2 brass 15 mm globe valves and 8 mm gage connection tee
arranged per NFPA 20. One of the test connections shall be equipped with a 0
to 1380 kPa water oil-filled gage.
d. Sensing line shall be connected to the pump discharge piping between the
discharge piping control valve and the check valve.
A. Description: Factory-assembled and -wired remote panel complying with UL 508 and
requirements in NFPA 20. Include audible and visible alarms matching controller type.
1. Engine running.
2. Main switch off or in manual position.
3. Engine trouble.
4. Low-water alarm.
5. Low fuel.
0.12 BATTERIES:
A. Batteries for diesel engine driver shall be sealed lead calcium batteries. Batteries shall be
mounted in a steel rack with non-corrosive, non-conductive base, not less than 300 mm
above the floor.
A. Factory Tests: Hydrostatically test and test run fire pumps before shipping. Test at 150
percent of shutoff head plus suction head, but not less than 1725 kPa. Produce certified test
curves showing head capacity and brake horsepower of each pump.
0.14 GROUT
PART 3 - EXECUTION
0.1 EXAMINATION
A. Examine areas, equipment foundations, and conditions, with the Installer present, for
compliance with requirements for installation and other conditions affecting fire-pump
performance.
1. Proceed with installation only after unsatisfactory conditions have been corrected.
A. Install concrete bases of dimensions indicated, or otherwise required, for fire pumps,
pressure-maintenance pumps, and controllers. Refer to Division 3 Section "Cast-in-Place
Concrete" and Division 15 Section "Basic Mechanical Materials and Methods."
0.3 INSTALLATION
B. Install pumps and controllers to provide access for periodic maintenance, including removal
of drivers, impellers, couplings, and accessories.
1. Support pump baseplate on rectangular metal blocks and shims or on metal wedges
having small taper, at points near foundation bolts to provide 19 to 38 mm gap
between pump base and foundation for grouting.
2. Adjust metal supports or wedges until pump and driver shafts are level. Check
coupling faces and pump suction and discharge flanges to verify that they are level
and plumb.
D. Install suction and discharge piping equal to or greater than diameter of fire-pump nozzles.
E. Install valves that are the same size as piping connecting fire pumps, bypasses, test headers,
and other piping systems.
G. Support pumps and piping separately so weight of piping does not rest on pumps.
H. Install piping accessories, hangers and supports, anchors, valves, meters and gages, and
equipment supports.
I. Refer to Division 15 Section "Basic Mechanical Materials and Methods" for basic piping
installation and joint construction.
J. Install water supply and drain piping for diesel-engine heat exchangers. Extend drain piping
from heat exchangers to point of disposition.
K. Install exhaust system piping for diesel engines. Extend to point of termination outside
structure. Install pipe and fittings with welded joints, and components having flanged
connections with gasketed joints.
L. Install condensate drain piping for diesel-engine exhaust system. Extend drain piping from
low points of exhaust system to condensate traps and to point of disposition.
M. Install flow meters and sensors where indicated. Install flow-measuring system components
and make connections according to manufacturer's written instructions.
N. Electrical Wiring: Install electrical devices furnished by equipment manufacturers but not
specified to be factory mounted. Furnish copies of manufacturers' wiring diagram
Submittals to the electrical Installer.
0.4 ALIGNMENT
A. Align fire-pump and driver shafts after complete unit has been leveled on foundation, grout
has set, and foundation bolts have been tightened.
B. After alignment is correct, tighten foundation bolts evenly but not too firmly. Fill baseplate
completely with grout, with metal blocks and shims or wedges in place. Tighten foundation
bolts after grout has hardened. Check alignment and make required corrections.
1. Adjust alignment of pump and driver shafts for angular and parallel alignment by one
method in HI 1.1-1.5, Section 1.4, "Installation, Operation and Maintenance."
2. Alignment Tolerances: Comply with manufacturer's written instructions.
0.5 CONNECTIONS
1. Install piping adjacent to fire and pressure-maintenance pumps to allow service and
maintenance.
2. Connect water supply to fire and pressure-maintenance pumps.
3. Connect fire-pump and pressure-maintenance-pump discharge piping to building fire-
suppression piping.
4. Connect relief-valve discharge to point of disposal.
5. Connect cooling-system water supply and drain piping to diesel-engine heat
exchangers.
6. Connect exhaust system piping to diesel engines.
C. Connect fire-pump controllers to building fire alarm system. Refer to Division 13 Section
"Fire Alarm."
F. Ground equipment.
1. Leak Test: After installation, charge system and test for leaks. Repair leaks and
retest until no leaks exist.
2. Check suction line connections for tightness so no air gets into pump.
3. Operational Test: After electrical circuitry has been energized, start units to confirm
proper motor rotation and unit operation. Remove malfunctioning units, replace with
new units, and retest.
4. Test and adjust controls and safeties. Replace damaged and malfunctioning controls
and equipment.
5. Furnish fire hoses in number, size, and length required to reach storm drain or other
acceptable location to dispose of fire-pump test water. Fire hoses are for field-
acceptance tests only and are not property of the Employer.
6. Final Checks before Startup: Perform the following preventive-maintenance
operations and checks:
a. Install coolant in cooling system. Fill closed-loop cooling system with potable
water and add rust inhibitor.
b. Install coolant in cooling system. Fill closed-loop cooling system with solution
of 50 percent potable water and 50 percent ethylene glycol permanent
antifreeze. Add rust inhibitor if not in antifreeze.
c. Prime pump by opening suction valve and closing drains, and prepare pump for
operation.
d. Open sealing liquid supply valves if pump is so fitted.
e. Start engine.
f. Open discharge valve slowly.
g. Observe leakage from stuffing boxes and adjust sealing liquid valve for proper
flow to ensure lubrication of packing. Do not tighten gland immediately but let
packing run in before reducing leakage through stuffing boxes.
h. Check general mechanical operation of pump and driver.
B. Perform field tests for each fire-pump unit and system piping when installation is complete.
Comply with operating instructions and procedures in NFPA 20 to demonstrate compliance
with requirements. Where possible, field correct malfunctioning equipment, then retest to
demonstrate compliance. Replace equipment that cannot be satisfactorily corrected or that
does not perform as indicated, then retest to demonstrate compliance. Verify that each fire-
pump unit performs as indicated. Report test results in writing.
0.7 DEMONSTRATION