Technical Information

Grid Connection
Influence of the grid conditions in terms of connected power
of PV inverters

Content
Some properties of a PV inverter grid connection can cause the grid voltage at the inverter to increase and
exceed the permissible operating range if the feed power is high. If this occurs, SMA grid guard, an
independent disconnection device integrated into the inverter, will safely disconnect the inverter from the grid.
The switch-off limits for this are determined by the technical connection requirements in the country of
installation.
The technical information provided below explains what requirements must be met to prevent the device from
switching off due to a voltage overshoot at the AC connection.

Netzanschluss-UEN083010 Version 1.0 1/4


Technical Information Estimating the maximum possible feed power

1  Estimating the maximum possible feed power


For the initial estimate of how much power can be fed to a phase conductor of the main power grid, the
following information is needed:
• Grid voltage at the grid connection point (without feed power),
• Grid impedance at the terminal of the inverter,
• Applicable conditions regarding inverter-based grid monitoring in the country of installation.
The grid voltage and grid impedance must be determined through measurements performed at the installation
site.
Note that a measurement of the grid impedence will only represent a spot value. Under real-world conditions,
grid impedance is not static, but subject to constant changes (e.g., connection of loads, grid expansion, etc.).

Switch-off condition in German grids (DIN VDE 0126-1-1)


The average grid voltage (UAC) at the inverter as measured over a period of 10 minutes is limited to a
maximum of 253 V in Germany according to DIN VDE 0126-1-1. If the inverter records that the 10-minute
average exceeds this voltage limit, or if the 260 V limit is temporarily exceeded, it will switch off immediately.
The inverter will display a grid error message if this occurs.

Estimating a general switch-off condition at 253 V


The following diagram shows the feed power situations based on the grid voltage as measured without feed
power. A maximum possible feed power per phase (x axis) is obtained for the respective curves depending
on the grid impedance (y axis). The switch-off condition in this case is 253 V. (The diagram does not include
the 10-minute average value combined with a fast cut-off at 260 V that is required in Germany. The result is
therefore somewhat lower than the output that is actually possible.)

SMA Solar Technology AG 2/4


Technical Information Estimating the maximum possible feed power

Grid impedance [Ohm]

Output [kW] per phase

Example:
Possible feed power per phase depending on grid impedance at UACmax = 253 V.
• The grid voltage without mains supply is 230 V
• The grid impedance at the terminal is 0.7 Ohms
• Switch-off criterium at UACmax = 253 V
Grid impedance [Ohm]

Output [kW] per phase

The power as read on the x axis is approximately 8.3 kW per phase. To install a higher output per phase
without causing disconnections due to excessive AC voltage, the connection requirements must be optimized
for the inverter, e.g., by:
• Using cables with larger conductor cross-sections,
• Using shorter cable routes,
• Modifying the switch-off criteria of the inverter.

SMA Solar Technology AG 3/4


Technical Information Switch-off criteria for countries other than Germany

2  Switch-off criteria for countries other than


Germany
The switch-off criteria for the target country of the inverter are pre-stored in a parameter set. These criteria are
based on knowledge of the target land of your supplier or the deployment location as indicated during order
placement.
You can change the switch-off parameters using a personnal access code. The access code can be requested
from the SMA Service Line after having obtained the express consent of the local grid operator.