Grid Connection
Influence of the grid conditions in terms of connected power
of PV inverters
Content
Some properties of a PV inverter grid connection can cause the grid voltage at the inverter to increase and
exceed the permissible operating range if the feed power is high. If this occurs, SMA grid guard, an
independent disconnection device integrated into the inverter, will safely disconnect the inverter from the grid.
The switch-off limits for this are determined by the technical connection requirements in the country of
installation.
The technical information provided below explains what requirements must be met to prevent the device from
switching off due to a voltage overshoot at the AC connection.
Example:
Possible feed power per phase depending on grid impedance at UACmax = 253 V.
• The grid voltage without mains supply is 230 V
• The grid impedance at the terminal is 0.7 Ohms
• Switch-off criterium at UACmax = 253 V
Grid impedance [Ohm]
The power as read on the x axis is approximately 8.3 kW per phase. To install a higher output per phase
without causing disconnections due to excessive AC voltage, the connection requirements must be optimized
for the inverter, e.g., by:
• Using cables with larger conductor cross-sections,
• Using shorter cable routes,
• Modifying the switch-off criteria of the inverter.