Documente Academic
Documente Profesional
Documente Cultură
1, JANUARY 2005
Dividing the contribution due to the Park vector and the one
associated to the zero-sequence, the (5) becomes
(6)
(2)
(8)
These equations are the Park equations describing the two-port
network shown in Fig. 2(a). They differ from those describing
This result can be extended to the second term of (6), taking into
a single-phase line under sinusoidal conditions because of the
account the usual value of the ratio between the impedance of
presence of the dynamic term .
the distribution system and that of the load. This is in accordance
2) Zero-Sequence Component:
with the results obtained by the Authors in different examples
and applications [4], [5]. Then, we have
(3)
(9)
These equations describe the two-port network shown in
Fig. 2(b).
On the point of view of energy flow, it is possible to affirm that
By applying Park transformation, it is possible to extend the
the voltage drop expressed by (6) depends on the real and
classical definitions adopted for the sinusoidal case to the non-
imaginary power in terms of Park vectors, and depends
sinusoidal three-phase one by substituting the sinusoidal phase
on the power as concerns the instantaneous zero-sequence
quantities with the instantaneous Park quantities. Considering
component. The result confirms once again the important role
the rms three-phase instantaneous voltage the relevant per unit
played by the imaginary power where, considering a four-wire
three-phase voltage drop, expressed in term of Park quantities
system, the contribution due to the zero-sequence power
(see Appendix), can be written as
must be added.
Equations (6), (8), (9) allow the voltage drop calculation in
(4) presence of zero-sequence components in the power line. In this
way it is possible to take into account harmonics, interharmonics
Representing the difference between rms output and input in- and all sequence components that can occur in case of distribu-
stantaneous voltages by using Taylor Series approximation [5], tion lines with earth conductor.
we obtain Equations (6), (8), (9) are valid under any conditions. They
can be applied to many systems operation, as for example the
presence of static converters and nonlinear loads, and at steady
(5)
state or transient conditions.
392 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 1, JANUARY 2005
III. EFFECT OF HARMONICS AND UNBALANCES ON THE Applying (11) to the formula (6), it is possible to obtain for
VOLTAGE DROP the two different terms (8), (9) respectively:
The definition of the role performed by harmonics and
sequence components present in the network becomes very
important on the application point of view. Equations (6), (8),
(9) can be reconsidered in order to clarify the dependence of
, and on the harmonic (12)
and sequence components.
The first term of (6), represented as in (8), is already deeply
The unbalanced sinusoidal case is of particular interest. In
investigated in [4] with the only difference of the zero-sequence
these conditions the presence of contributions associated to
voltage contribution at the denominator. Instead, the
positive-, negative- and zero-sequence components brings to
second term of (6), represented as in (9), concerns the contri-
the following:
bution of the zero-sequence component and will be developed
in the following.
Under the hypothesis of periodic steady-state, it is convenient
to apply the Fourier series analysis. In this way, for each har- (13)
monic it is possible to use the theory related to sinusoidal system
and counter-rotating vectors. This procedure brings to the fol- Equation (13) represents a generalization of the voltage drop
lowing expressions shown in (10), at the bottom of the page. The classical expression typically used in case of positive sequence
results obtained can be discussed as follows: component only. In fact, the reactive power associated to pos-
— the formal unification of the effects associated to har- itive-, negative- and zero-sequence components ( , and
monics and sequence components on the voltage drop, , respectively) appears.
already shown in [4] for the instantaneous positive and
negative sequences, extends to the zero sequence one IV. EFFECT OF INTERHARMONICS ON THE VOLTAGE DROP
due to the presence of the earth conductor; It is particularly interesting the case in which interharmonics
— also the zero sequence contribution to the voltage drop are present in the power systems. In this case the general formu-
presents a pulsating component, giving evidence of lations (6), (8), (9) are still valid. Also the equations developed
zero-sequence component additional contribution with concerning the periodic conditions are valid when frequency,
respect to the sinusoidal, positive sequence, balanced harmonic order and time period are referred to the basic quan-
three-phase case. tities (i.e., the ones associated to the basic frequency of the cor-
respondent waveform) instead of the network frequency (50 or
A. Voltage Drop Average Value 60 Hz).
Starting from the above general expression (6) of the voltage In this case the Park quantities become:
drop in time domain, it is possible to evaluate the following
average value with reference to the interval
(11)
(10)
LEVA et al.: EVALUATION OF LINE VOLTAGE DROP IN PRESENCE OF UNBALANCE, HARMONICS, AND INTERHARMONICS 393
Fig. 3. Schematic diagram of railway motor drive system of the train ETR470.
TABLE I
NOMINAL DATA OF THE RAILWAY MOTOR DRIVE SYSTEM OF TRAIN ETR470
where
• is the Fourier’s basic frequency (it is the greatest
common divisor of all the frequencies components in the
signal);
• is the harmonic order referred to ;
• is the period associated to the basic frequency.
Furthermore, the relation between these latter quantities and the
ones related to the network frequency is
(15) Fig. 4. Case 1. (a) Voltage drop waveform. The solid line represents the voltage
drop given by (4), the dashed line represents the voltage drop given by the
proposed relationship (8), the dotted line represents the classical voltage drop
and the point-dashed line represents the voltage drop given by a commercial
V. STUDIED CASES software. (b) Imaginary power waveform.
TABLE II
DATA OF THE INDUSTRIAL SYSTEM CONSIDERED IN THE CASE 2
Fig. 6. Case 2. (a) Voltage drop waveform. The solid line represents the voltage
TABLE III drop given by (4), the dashed line represents the voltage drop given by the
SUBHARMONIC AND INTERHARMONIC CURRENTS PRODUCED BY proposed relationship (8), the dotted line represents the classical voltage drop
INDUCTION MOTORS and the point-dashed line represents the voltage drop given by a commercial
software. (b) Imaginary power waveform.
1) The comparison of the diagrams in Figs. 4(a) and 6(a) The proposed transformation does not consider the coupling
proves that the proposed algorithm, based on the Park ap- between the sequences due to the physical asymmetries present
proach, is correct, since the voltage drop diagram is the in the real life on transmission lines or feeders.
same as that computed using (4). Then, the proposed for-
mula (8) can be used for directly evaluating the correct
value of the voltage drop in case of unbalanced and dis- APPENDIX
torted systems. PARK TRANSFORMATION APPROACH
2) The exam of the diagrams in Figs. 4(a) and 6(a) confirms
If the following Park transformation [2], [3] is employed:
the implication typical of classical theory: the classical
voltage drop is close to the mean value of the Park voltage
drop if the system is linear and the zero-sequence compo-
nent is nil.
3) The diagrams of the Park imaginary power show that this (A.1)
quantity has fairly the same waveform as the instanta-
neous voltage drop, and hence give evidence of the role
of this quantity that is completely disregarded by the clas- Equation (1) can be expressed by means of variables.
sical theory. Then, the Park vectors are defined as
Furthermore a comparison is made with the results obtained by
means of commercial software on power system harmonics [8].
The simulation with this software brings to the point-dashed
lines in Figs. 4(a) and 6(a). These results are very close to the
mean value of voltage drop as seen by Park approach, but they (A.2)
do not consider the voltage drop time variation.
In the end, the investigation performed on the two cases where . The zero-sequence component is expressed
shows that: as
— as regards the line design, where the mean value of the
voltage drop is taken as reference parameter, the pro- (A.3)
posed method for evaluating the voltage drop confirms
the validity of the classical theory and of the commer-
cial simulation tool; The formal time-domain generalization of the rms three-phase
— as regards the dynamic control for power compensa- value under sinusoidal condition can be written in the following
tion and stability regulation, the proposed method is form:
the only one that can simply identify the instantaneous
voltage drop variation with formula that recall in some
way the classical formulation.
(A.4)
that is invariant with the axis choice. The axis can be fixed,
VI. CONCLUSION
, or rotating at speed .
In the present paper the problem of voltage drop calculation
in three-phase, four-wire distribution lines is pointed out and
REFERENCES
deeply investigated with reference to dynamic state, in which
unbalances, harmonics and interharmonics are taken into [1] B. Weedy, Electric Power Systems, 3rd ed, New York: Wiley, 1990.
[2] L. G. Stokvis and C. Lavanchy, “Diagramme de la chute de tension
account. The use of Park transformation permits the expres- dans un conducteur de ligne triphasée de tension moyenne. Cas général
sion—in a separate form and generalizing the results of the d’un système déséquilibré géométriquement et électriquement,” Revue
classical theory—of the contribution due to the three different Gènèrale de l’Electricité, vol. 13, pp. 3–5, 1923.
[3] J. Arrilaga, D. A. Bradley, and P. S. Bodger, Power System Har-
instantaneous sequences. In particular, the positive, negative, monics. New York: Wiley, 1985, p. 116.
and zero-sequence components are associated in terms of power [4] S. Leva, A. P. Morando, and D. Zaninelli, “A new formulation of line
quality and energy flow to the classical Park power. voltage drop in unbalanced and distorted systems,” in Proc. IEEE Int.
Conf. Harmonics Quality of Power, vol. 2, Orlando, FL, Oct. 1–4, 2000,
After the presentation of the theoretical development of the pp. 751–756.
proposed method, the paper presents the application to real cases [5] A. Ferrero, S. Leva, and A. P. Morando, “About the role of the park
of industrial plants, where a comparison is also made both with imaginary power on the three-phase line voltage drop,” ETEP Eur. Trans.
Electr. Power 10, no. 5, pp. 287–296, 2000.
the classical voltage drop formulation and the one of the most [6] K. Kupfmuller, Einführung in die theoretische Elektrotecnik, Heidel-
common commercial software on power system harmonics. The berg, Germany: Springer Verlag, 1968, p. 623.
results of these applications and comparisons validate this new [7] K. Simonyi, Foundations of Electrical Engineering. Oxford, U.K.:
Pergamon, 1963, p. 385.
approach based on Park theory and show its strength in case of [8] Harmflow+, Harmonic Simulation and Analysis Tools, Feb. 1995.
power systems dynamic studies. EPRI/Electrotek, version 2.0, Knoxville, TN.
396 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 1, JANUARY 2005
Sonia Leva (M’01) received the M.S. and Ph.D. de- Dario Zaninelli (SM’96) received the Ph.D. degree
grees in electrical engineering from the Politecnico in electrical engineering from the Politecnico di Mi-
di Milano,” Milano, Italy, in 1997 and 2001, respec- lano, Milano, Italy, in 1989.
tively. Currently, he is Professor in the Electrical Engi-
Currently, she is Assistant Professor of Eletrotec- neering Department of the Politecnico di Milano. His
nica in the Electrical Engineering Department at the areas of research include power system harmonics
Politecnico di Milano. Her research interests include and power system analysis.
electromagnetic compatibility, power quality, and the Dr. Zaninelli is a member of AEI and of the Italian
foundation of electromagnetic theory of electric net- National Research Council (C.N.R.) Group of Elec-
work. trical Power Systems.