Sunteți pe pagina 1din 7

390 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO.

1, JANUARY 2005

Evaluation of Line Voltage Drop in Presence


of Unbalance, Harmonics, and Interharmonics:
Theory and Applications
Sonia Leva, Member, IEEE, Adriano P. Morando, and Dario Zaninelli, Senior Member, IEEE

Abstract—This paper deals with the line voltage drop calcula-


tion in presence of disturbances in the electric network, like un-
balance, harmonic, and interharmonic components. The Park ap-
proach permits to define a calculation expression with a structure
very close to the classical one typically employed in case of bal-
anced systems and also permits to underline the role of the imag-
inary power that quantifies in one term only the effects of distur-
bances on the voltage drop. In order to text the effectiveness of the
proposed methodology, two applications on real industrial plants
are presented in the second part of the paper. The comparison with Fig. 1. Three-phase line with physical symmetry.
the classical theory and calculation made by using commercial soft-
ware gives rise to interesting comments and discussion on the pro-
posed approach. introduction of some simplifying hypotheses can bring to wrong
results neglecting some disturbance’s contributions.
Index Terms—Harmonics, interharmonics, park transforma-
In a previous paper the Authors introduced the Park transfor-
tion, unbalance, voltage drop, zero-sequence components.
mation for taking into account the simultaneous contributions
of harmonic and negative sequence components in the voltage
I. INTRODUCTION drop [4]. In particular, the analysis in terms of the Park vector
confirms the single-phase nature of the Park variables and high-
T HE VOLTAGE drop is one of the most important quan-
tities in the characterization of transmission and distribu-
tion electric power systems. In fact it represents in a certain way
lights the role of the Park imaginary power. This last quantity
appears to be a generalization of the reactive power concept to
the indicator of the effectiveness of the connection between the any operating condition as far as the voltage drop is considered
loads and the generation centres. The voltage drop control is also [5].
an essential task both for the stability and the economy of the The theoretical approach presented in [4] did not consider
power system and its calculation, even with the introduction of the simultaneous presence of interharmonics and zero-sequence
simplified procedures and approximations, is fundamental for instantaneous components. These latter are very important for
power system analysis [1]. taking into account phenomena related to interharmonic com-
The voltage drop calculation, in case of ac sinusoidal systems, ponents (i.e., flicker) and in case of low voltage three-phase
had rise with the phasor algebra, then, it was extended from the four-wire distribution systems where unbalances or third order
single-phase case to the three-phase balanced systems. After- harmonics are present in the network.
wards, the formulation of the symmetrical component’s theory, Considering in this way the most common steady-state dis-
starting by Stokvis [2], posed the problem of an extension to turbances present in power systems, the present paper permits
dissymmetrical sinusoidal case. Nowadays, the presence of har- to carry out compatible models for representing the distribu-
monics and interharmonics in power systems points out the need tion systems in any possible perturbation due to disturbances
of a new formulation of voltage drop expression [3], that gener- or faults.
alizes the former phasorial one but, in same time, takes into the The results obtained taking as reference to real industrial
account the contributions (instantaneous and average) of har- plant show the role of the instantaneous power components
monics, interharmonics, and unbalances. (real and imaginary by Park and real by zero-sequence) on
In fact, in presence of unbalances or/and distortions the ac- the line voltage drop and permit a formalism very close to the
curacy of the voltage drop calculation becomes burden and the one used for single-phase equivalent systems in the case of
balanced and non polluted circuits.

II. PROPOSED APPROACH


Manuscript received April 11, 2003; revised October 2, 2003. Paper no.
TPWRD-00170-2003. In the most general case, the time-domain equations for a
The authors are with the Electrical Engineering Department of the three-phase distribution line (see Fig. 1) are differential equa-
Politecnico di Milano, Milano, Italy (e-mail: sonia.leva@polimi.it;
adriano.morando@polimi.it; dario.zaninelli@polimi.it). tions. For the purposes of this work, they can be more clearly
Digital Object Identifier 10.1109/TPWRD.2004.837830 written in term of Heaviside operator [6], [7] , so the
0885-8977/$20.00 © 2005 IEEE
LEVA et al.: EVALUATION OF LINE VOLTAGE DROP IN PRESENCE OF UNBALANCE, HARMONICS, AND INTERHARMONICS 391

Dividing the contribution due to the Park vector and the one
associated to the zero-sequence, the (5) becomes

(6)

The voltage drop in a four-wire three-phase distribution line is


composed by two terms. The first one depends on the instanta-
neous positive and negative sequences through the Park vector;
the second one represents the contribution of the instantaneous
zero-sequence.
With reference to Fig. 2, it follows:

Fig. 2. Park representation of a two-port network for three-phase short line.

line impedance vector z, written in terms of this operator, be-


comes . Therefore, the time-domain equations for the line
in Fig. 1 are:
(7)
(1)
By applying to the first term of (6) the geometrical approach
By applying the Park transformation (see Appendix), the fol- typical of the sinusoidal case in terms of Park vector [4], [5],
lowing relationships can be obtained: and observing that , the following ex-
1) Park Vector: pression is obtained:

(2)

(8)
These equations are the Park equations describing the two-port
network shown in Fig. 2(a). They differ from those describing
This result can be extended to the second term of (6), taking into
a single-phase line under sinusoidal conditions because of the
account the usual value of the ratio between the impedance of
presence of the dynamic term .
the distribution system and that of the load. This is in accordance
2) Zero-Sequence Component:
with the results obtained by the Authors in different examples
and applications [4], [5]. Then, we have
(3)
(9)
These equations describe the two-port network shown in
Fig. 2(b).
On the point of view of energy flow, it is possible to affirm that
By applying Park transformation, it is possible to extend the
the voltage drop expressed by (6) depends on the real and
classical definitions adopted for the sinusoidal case to the non-
imaginary power in terms of Park vectors, and depends
sinusoidal three-phase one by substituting the sinusoidal phase
on the power as concerns the instantaneous zero-sequence
quantities with the instantaneous Park quantities. Considering
component. The result confirms once again the important role
the rms three-phase instantaneous voltage the relevant per unit
played by the imaginary power where, considering a four-wire
three-phase voltage drop, expressed in term of Park quantities
system, the contribution due to the zero-sequence power
(see Appendix), can be written as
must be added.
Equations (6), (8), (9) allow the voltage drop calculation in
(4) presence of zero-sequence components in the power line. In this
way it is possible to take into account harmonics, interharmonics
Representing the difference between rms output and input in- and all sequence components that can occur in case of distribu-
stantaneous voltages by using Taylor Series approximation [5], tion lines with earth conductor.
we obtain Equations (6), (8), (9) are valid under any conditions. They
can be applied to many systems operation, as for example the
presence of static converters and nonlinear loads, and at steady
(5)
state or transient conditions.
392 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 1, JANUARY 2005

III. EFFECT OF HARMONICS AND UNBALANCES ON THE Applying (11) to the formula (6), it is possible to obtain for
VOLTAGE DROP the two different terms (8), (9) respectively:
The definition of the role performed by harmonics and
sequence components present in the network becomes very
important on the application point of view. Equations (6), (8),
(9) can be reconsidered in order to clarify the dependence of
, and on the harmonic (12)
and sequence components.
The first term of (6), represented as in (8), is already deeply
The unbalanced sinusoidal case is of particular interest. In
investigated in [4] with the only difference of the zero-sequence
these conditions the presence of contributions associated to
voltage contribution at the denominator. Instead, the
positive-, negative- and zero-sequence components brings to
second term of (6), represented as in (9), concerns the contri-
the following:
bution of the zero-sequence component and will be developed
in the following.
Under the hypothesis of periodic steady-state, it is convenient
to apply the Fourier series analysis. In this way, for each har- (13)
monic it is possible to use the theory related to sinusoidal system
and counter-rotating vectors. This procedure brings to the fol- Equation (13) represents a generalization of the voltage drop
lowing expressions shown in (10), at the bottom of the page. The classical expression typically used in case of positive sequence
results obtained can be discussed as follows: component only. In fact, the reactive power associated to pos-
— the formal unification of the effects associated to har- itive-, negative- and zero-sequence components ( , and
monics and sequence components on the voltage drop, , respectively) appears.
already shown in [4] for the instantaneous positive and
negative sequences, extends to the zero sequence one IV. EFFECT OF INTERHARMONICS ON THE VOLTAGE DROP
due to the presence of the earth conductor; It is particularly interesting the case in which interharmonics
— also the zero sequence contribution to the voltage drop are present in the power systems. In this case the general formu-
presents a pulsating component, giving evidence of lations (6), (8), (9) are still valid. Also the equations developed
zero-sequence component additional contribution with concerning the periodic conditions are valid when frequency,
respect to the sinusoidal, positive sequence, balanced harmonic order and time period are referred to the basic quan-
three-phase case. tities (i.e., the ones associated to the basic frequency of the cor-
respondent waveform) instead of the network frequency (50 or
A. Voltage Drop Average Value 60 Hz).
Starting from the above general expression (6) of the voltage In this case the Park quantities become:
drop in time domain, it is possible to evaluate the following
average value with reference to the interval

(11)

This calculation is justified by the importance of the voltage rms


value on the load supply and distribution system operation. (14)

(10)
LEVA et al.: EVALUATION OF LINE VOLTAGE DROP IN PRESENCE OF UNBALANCE, HARMONICS, AND INTERHARMONICS 393

Fig. 3. Schematic diagram of railway motor drive system of the train ETR470.

TABLE I
NOMINAL DATA OF THE RAILWAY MOTOR DRIVE SYSTEM OF TRAIN ETR470

where
• is the Fourier’s basic frequency (it is the greatest
common divisor of all the frequencies components in the
signal);
• is the harmonic order referred to ;
• is the period associated to the basic frequency.
Furthermore, the relation between these latter quantities and the
ones related to the network frequency is

(15) Fig. 4. Case 1. (a) Voltage drop waveform. The solid line represents the voltage
drop given by (4), the dashed line represents the voltage drop given by the
proposed relationship (8), the dotted line represents the classical voltage drop
and the point-dashed line represents the voltage drop given by a commercial
V. STUDIED CASES software. (b) Imaginary power waveform.

Two industrial applications are here considered for testing the


above reported theory. . In addition Fig. 4(a) reports as
Case 1: This selected system refers to a three-phase motor comparison the voltage drop evaluated by means of a
drive used for traction purpose. The schematic diagram of this simulation performed with commercial software for harmonic
DC supplied railway system is reported in Fig. 3 while the rel- analysis [8]. The p.u. voltage drop valuated as mean value of
evant nominal data are summarized in Table I. This data refer the proposed formula (8) is 0.0158, while the p.u. voltage drop
to the high-speed train ETR470 in operation in some European calculated with the classical formulation is 0.0155 and the one
countries. The calculation of the voltage drop is very important resulting from the commercial software is 0.0160.
in this case because the motor torque depends on the squared Fig. 4(b) shows the imaginary Park power waveform.
rms voltage applied to the stator winding. The knowledge of Comments on the results will be report at the end of the sec-
the voltage drop permits to determine the control strategy of the tion together with those relevant to case 2.
drive. The application of the above reported theory to the eval- Case 2: The second power plant considered is to industrial
uation of the line voltage drop is made in the case of a steady power system reported in Fig. 5. The electric supply is provided
state operation condition when the train runs at 100 km/h with at 132 kV busbar (A) with a short circuit level of 4115 MVA.
a six step motor voltage supply impressed by the inverter drive. Two kV transformers, and , connect through the
In particular, the presented method that relates the voltage drop bars the busbar B supplying a MV distribution network. Useful
to the imaginary Park power permits to introduce control action data concerning transformers, bars and the two feeders,
that can compensate the voltage drop during the motor drive op- and , are reported in Table II.
eration. A three phase static controlled converter , with 2.5 MW
Fig. 4(a) shows the voltage drop waveforms evaluated demand and power factor of 0.7, is supplied from busbar B. A
by means of the usual definition (4) by the proposed re- power factor correction device rated 1.92 MVAr is also
lationship (5), (8), (9) and with the classical formulation connected at the same busbar. From , a 1 MW rated three-
394 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 1, JANUARY 2005

Fig. 5. Layout of the industrial system taken for the case 2.

TABLE II
DATA OF THE INDUSTRIAL SYSTEM CONSIDERED IN THE CASE 2

Fig. 6. Case 2. (a) Voltage drop waveform. The solid line represents the voltage
TABLE III drop given by (4), the dashed line represents the voltage drop given by the
SUBHARMONIC AND INTERHARMONIC CURRENTS PRODUCED BY proposed relationship (8), the dotted line represents the classical voltage drop
INDUCTION MOTORS and the point-dashed line represents the voltage drop given by a commercial
software. (b) Imaginary power waveform.

(5), (8), (9) and with the classical formulation . In addition


Figs. 6(a), 4(a) reports as comparison the voltage drop
evaluated by means of a simulation performed with commercial
software for harmonic analysis [8]. The p.u. voltage drop valu-
ated as mean value of the proposed formula (8) is 0.0074, while
the p.u. voltage drop calculated with the classical formulation
is 0.0075 and the one resulting from the commercial software
is 0.0074. These values are very low in consideration to the fact
phase rectifier equipped with 5th and 7th har- that power plant presents reactive power and harmonic compen-
monic current tuned arm filters is supplied. At busbar two sation devices (see Fig. 5). In any case the proposed method of
large induction motors, and , respectively 1 MW and 0.4 evaluation shows that the instantaneous voltage drop can reach
MW rated, as well as a 0.48 kVAr power factor correc- highest values, up to 0.012.
tion equipment, are connected. Table III summarizes the sub- Fig. 6(b) shows the imaginary Park power waveform.
harmonic and interharmonic currents produced by the motors Comments on the Results: The simulation processes on the
and and flowing in the line . above described real cases of existing power systems give rise
Fig. 4(a) shows the voltage drop waveforms evaluated by to the following comments and discussion.
means of the usual definition (4) by the proposed relationship The diagrams reported in Figs. 4, and 6 show that:
LEVA et al.: EVALUATION OF LINE VOLTAGE DROP IN PRESENCE OF UNBALANCE, HARMONICS, AND INTERHARMONICS 395

1) The comparison of the diagrams in Figs. 4(a) and 6(a) The proposed transformation does not consider the coupling
proves that the proposed algorithm, based on the Park ap- between the sequences due to the physical asymmetries present
proach, is correct, since the voltage drop diagram is the in the real life on transmission lines or feeders.
same as that computed using (4). Then, the proposed for-
mula (8) can be used for directly evaluating the correct
value of the voltage drop in case of unbalanced and dis- APPENDIX
torted systems. PARK TRANSFORMATION APPROACH
2) The exam of the diagrams in Figs. 4(a) and 6(a) confirms
If the following Park transformation [2], [3] is employed:
the implication typical of classical theory: the classical
voltage drop is close to the mean value of the Park voltage
drop if the system is linear and the zero-sequence compo-
nent is nil.
3) The diagrams of the Park imaginary power show that this (A.1)
quantity has fairly the same waveform as the instanta-
neous voltage drop, and hence give evidence of the role
of this quantity that is completely disregarded by the clas- Equation (1) can be expressed by means of variables.
sical theory. Then, the Park vectors are defined as
Furthermore a comparison is made with the results obtained by
means of commercial software on power system harmonics [8].
The simulation with this software brings to the point-dashed
lines in Figs. 4(a) and 6(a). These results are very close to the
mean value of voltage drop as seen by Park approach, but they (A.2)
do not consider the voltage drop time variation.
In the end, the investigation performed on the two cases where . The zero-sequence component is expressed
shows that: as
— as regards the line design, where the mean value of the
voltage drop is taken as reference parameter, the pro- (A.3)
posed method for evaluating the voltage drop confirms
the validity of the classical theory and of the commer-
cial simulation tool; The formal time-domain generalization of the rms three-phase
— as regards the dynamic control for power compensa- value under sinusoidal condition can be written in the following
tion and stability regulation, the proposed method is form:
the only one that can simply identify the instantaneous
voltage drop variation with formula that recall in some
way the classical formulation.
(A.4)

that is invariant with the axis choice. The axis can be fixed,
VI. CONCLUSION
, or rotating at speed .
In the present paper the problem of voltage drop calculation
in three-phase, four-wire distribution lines is pointed out and
REFERENCES
deeply investigated with reference to dynamic state, in which
unbalances, harmonics and interharmonics are taken into [1] B. Weedy, Electric Power Systems, 3rd ed, New York: Wiley, 1990.
[2] L. G. Stokvis and C. Lavanchy, “Diagramme de la chute de tension
account. The use of Park transformation permits the expres- dans un conducteur de ligne triphasée de tension moyenne. Cas général
sion—in a separate form and generalizing the results of the d’un système déséquilibré géométriquement et électriquement,” Revue
classical theory—of the contribution due to the three different Gènèrale de l’Electricité, vol. 13, pp. 3–5, 1923.
[3] J. Arrilaga, D. A. Bradley, and P. S. Bodger, Power System Har-
instantaneous sequences. In particular, the positive, negative, monics. New York: Wiley, 1985, p. 116.
and zero-sequence components are associated in terms of power [4] S. Leva, A. P. Morando, and D. Zaninelli, “A new formulation of line
quality and energy flow to the classical Park power. voltage drop in unbalanced and distorted systems,” in Proc. IEEE Int.
Conf. Harmonics Quality of Power, vol. 2, Orlando, FL, Oct. 1–4, 2000,
After the presentation of the theoretical development of the pp. 751–756.
proposed method, the paper presents the application to real cases [5] A. Ferrero, S. Leva, and A. P. Morando, “About the role of the park
of industrial plants, where a comparison is also made both with imaginary power on the three-phase line voltage drop,” ETEP Eur. Trans.
Electr. Power 10, no. 5, pp. 287–296, 2000.
the classical voltage drop formulation and the one of the most [6] K. Kupfmuller, Einführung in die theoretische Elektrotecnik, Heidel-
common commercial software on power system harmonics. The berg, Germany: Springer Verlag, 1968, p. 623.
results of these applications and comparisons validate this new [7] K. Simonyi, Foundations of Electrical Engineering. Oxford, U.K.:
Pergamon, 1963, p. 385.
approach based on Park theory and show its strength in case of [8] Harmflow+, Harmonic Simulation and Analysis Tools, Feb. 1995.
power systems dynamic studies. EPRI/Electrotek, version 2.0, Knoxville, TN.
396 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 1, JANUARY 2005

Sonia Leva (M’01) received the M.S. and Ph.D. de- Dario Zaninelli (SM’96) received the Ph.D. degree
grees in electrical engineering from the Politecnico in electrical engineering from the Politecnico di Mi-
di Milano,” Milano, Italy, in 1997 and 2001, respec- lano, Milano, Italy, in 1989.
tively. Currently, he is Professor in the Electrical Engi-
Currently, she is Assistant Professor of Eletrotec- neering Department of the Politecnico di Milano. His
nica in the Electrical Engineering Department at the areas of research include power system harmonics
Politecnico di Milano. Her research interests include and power system analysis.
electromagnetic compatibility, power quality, and the Dr. Zaninelli is a member of AEI and of the Italian
foundation of electromagnetic theory of electric net- National Research Council (C.N.R.) Group of Elec-
work. trical Power Systems.

Adriano Paolo Morando received the M.S. degree


in electrical engineering from the Politecnico di Mi-
lano, Milano, Italy.
Currently, he is Associate Professor of Elettrotec-
nica in the Electrical Engineering Department of
the Politecnico di Milano. From 1984 to 1989,
he was with ASEA Brown Boveri, Milano, Italy,
where he was concerned with ac drives for electrical
traction. His current research interests include
electromagnetic compatibility, the power quality,
and the foundation of electromagnetic (EM) theory
of electric networks.

S-ar putea să vă placă și