Sunteți pe pagina 1din 28

UCM-CLD

Operating and control


principles

Installation
Operation
Maintenance

UCM-CLD – Operating and control principles of the electronic module


TRANE ADAPTIVE CONTROL™ used on helical-rotary units equipped with
CHHN and CHHB compressors.

L80 IM 025 E
Foreword
These Installation, Operation, and Maintenance They do not contain the full service procedures
instructions are given as a guide to good practice in the necessary for the continued successful operation of this
installation, start-up, operation, and periodic equipment. The services of a qualified service
maintenance by the user of UCM-CLD modules. technician should be employed, through the medium of
a maintenance contract with a reputable service
company.

Warranty
Warranty is based on the general terms and conditions Damage due to misuse, lack of maintenance, or failure
of the manufacturer. The warranty is void if the to comply with the manufacturer's instructions, is not
equipment is modified or repaired without the written covered by the warranty obligation.
approval of the constructor, if the operating limits are
exceeded, or if either the control system or the
electrical wiring is modified.

Reception
On arrival, inspect the unit before signing the delivery registered letter of protest to the carrier within 7 days
note. Specify any damage on the delivery note, and of delivery and notify the local sales office.
send a registered letter of protest to the last carrier of Units are shipped with the refrigerant operating or
the goods within 72 hours of delivery. Notify the local holding charge, and should be examined with an
sales office at the same time. electronic leak detector to determine the hermetic
The unit should be totally inspected within 7 days of integrity of the unit. The refrigerant charge is not
delivery. If any concealed damage is discovered, send a included in the standard Warranty Cover.

General information
About this manual
Cautions appear at appropriate places in this The manufacturer assumes no liability for installations
instruction manual. Your personal safety and the or servicing performed by unqualified personnel.
proper operation of this machine require that you
follow them carefully.

© American Standard Inc. 2000

2
Index
Foreword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Reception . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

Principles of operation of the UCM-CLD module


General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Operator’s interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

Description of the operation


Chiller report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Refrigerant report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Compressor report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Operator’s settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Service settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Service tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

Diagnostics
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Default description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Unit operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Compressor operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Maintenance contract . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28

3
Principles of operation of the module UCM-CLD

Figure 1: Operator’s interface

Alarm

Custom Chiller Refrigerant Compressor


Select Report Group
Report Report Report Report

Operator Service Service Diagnostics


Select Setting Group
Settings Settings Tests

Previous Enter Auto

Next Cancel Stop

ADAPTIVE CONTROL™

General information

This regulation assembly is composed of 6 electronic - CSR (Communication and Setpoint Reset): control of
modules which have each their own 115V power the serial communication, unit external setpoints, and
supply and communicate with each other via a serial ice-making mode (optional module).
link. Each module has a set of functions which are - Local CLD (Local Clear Language Display): operator’s
associated to make the unit regulation. interface located in the unit: front panel (software
Each module has the following name linked to its version and number displayed at power-up).
functions. - Remote LCD (Remote Clear Language Display):
- MCSP (Motor Compressor Start and Protection): operator’s interface located up to 1500 m from the
safety, protection and control of the helical-rotary unit at the operator’s, and which can communicate
compressor as well as all associated components. with up to four units of the same type (optional
- CPM (Chiller Protection and Management): safety, module).
protection, and control of the chiller. - TCI IV, IPCB (Tracer Communication Interface 4,
- EXV (Electronic Expansion Valve): control of both Inter-Processor Communication Buffer): protection of
electrical expansion valves. the unit internal communication bus from the external
interferences existing in the unit (optional module,
compulsory when using a remote CLD, and which
must be factory-mounted).

4
Figure 2: Control and regulation panel mounted on helical-rotary units equipped with UCM-CLD

Operator’s interface (Figure 1) - Operator settings menu


- Service settings menu
Digital display - Service test menu
The display of control regulation and operating - Diagnostics menu
parameters, as well as diagnostic and error messages, These 8 keys allow to access each of these menus.
is made on a two-line 40-character liquid crystal
display. Control keys
When powering-up the system, the display is not lit - + key
and the message “Self-test in progress” is displayed in - - key
order to make sure the display operates properly. - Previous key
The screen allows to display: - Next key
- The error codes. - Enter key
- The settings of the various setpoints. - Cancel key
- The specified temperature and pressure values. - Auto key
- The status of operating parameters and various - Stop key
options. These 8 keys allow the operator to move within the
various menus and to modify their parameters.
Keyboard
A 16-key touch pad allows the operator to move within Remark: All the menus and setpoints cannot be
the various menus and to modify their parameters and accessed by the chillers operator; Service Settings
setpoints. and Service Test menus are protected by a password
The keys are divided into two groups. and are reserved for Trane engineers.

Menu keys
- Chiller Report menu
- Custom Report menu
- Refrigerant menu
- Compressor menu

5
Description of the operation
The whole information is gathered in various menus Previous key
according to the location of the sensor and/or the Pressing the Previous key allows the operator to
function performed. scroll up to the previous information in the current
menu. All the display items are looped, so it is
Chiller report menu possible to scroll from the first item to the last one.
This menu gathers the information relating to the liquid
chiller (reading only). Active setpoints and their origins, Next key
chilled water, air temperature, current draws, are found Pressing the Next key allows the operator to scroll
in this menu. down to the next information in the current menu. All
the display items are looped, so it is possible to scroll
Custom report menu from the last item to the first one.
This menu is peculiar because originally it does not
include any information at all. However, the operator + key
can build his own menu which is comprised of read- If this information displayed is a read-only item,
only information, by simply pressing the + key when in pressing the + key will add it to the operator’s menu.
other menus. To remove information from this menu, if the information can be modified, the value is
simply press the - key when displayed. increased by 1. Pressing the key for longer than 1
second will increase the value of 1 every .25 seconds.
Refrigerant report menu A logical stop prevents an adjustment higher than the
This menu gathers the information, read-only, relating maximum value; a message is displayed to indicate
to the refrigerant. Refrigerant pressures and this status.
temperatures at various points of the refrigerant circuit
can be found in this menu. - key
If the information displayed is a read-only item,
Compressor report menu pressing the - key will remove it from the operator’s
This menu gathers the information, read-only, relating menu. If the information can be modified, the value is
to the compressor. Voltages and amps, hour and start increased by 1. Pressing the key for longer than 1
counters, as well as oil temperature (GP compressor second will increase the value of 1 every .25 seconds.
only) can be found in this menu. A logical stop prevents an adjustment higher than the
maximum value; a message is displayed to indicate
Operator settings menu this status.
This menu comprises all the particular setpoints and
operating modes existing in the unit and which are Enter key
accessible by the usual operator of the chiller. In Pressing this key allows the validation of a value after
addition, the following can be programmed: chilled it has been modified by pressing the + or - key.
water pump operation, temperature resets, ice-making
operation, and low ambient limit. Cancel key
Pressing this key allows the cancellation of a value
Service settings menu after it has been modified by pressing the + or - key
This menu has three access levels. The first one and to come back to the original value.
contains information which can be adjusted by the
customer such as the unit voltage, the validation of Auto key
over/under voltage protection, the display language, Pressing this key (green) allows the unit to come back
and the programmable relay function of the units. The in auto mode if it was previously placed in stop mode
keyboard can also be locked if the relating function is with the stop key. The unit cannot be forced into auto
validated. A second level contains the setpoints mode if it has been stopped by an external contact or
adjusted by the service engineer to adapt the operation the serial link. When the unit is stopped by the remote
of the unit to a particular site, such as the address of interface (Remote CLD), the local “auto” mode order
the serial link, the water and refrigerant limit is prioritary.
parameters, and so forth. The third level contains the
configuration and protection information: number of Stop key
circuits, compressors and fans, compressor amps and Pressing this key (red) allows the unit to go into stop
expansion valve settings. mode. In every case, and wherever the origin (except
a local stop), the stop order and stop status have
Service tests menu priority over a run order. The stop generated is a soft
This menu allows the operator to perform some tests stop, meaning the unit unloads before stopping.
when the unit is in operation or during the initial start-
up of the unit: expansion valve test, circuit locking, or
pump-out.

Diagnostics menu
This menu contains all the information on the current
faults or faults that occurred in the past. It allows the
possibility to reset a manual reset fault or to erase the
historic list of faults.

6
Chiller report
Chiller Chiller report: status, water temperatures and setpoints
report “Press (Next) (Previous) to continue”

Next

Unit model
(service setting menu)
all others RTXA

[operating mode] will be one of Mode: [OPERATING MODE]


Reset Request setpoint source: [SETPOINT SOURCE]
Stopped by Local Display
Stopped by Remote Display
Stopped by Tracer
Stopped by External Source Chiller Mode: [OPERATING MODE]
Auto Request setpoint source: [SETPOINT SOURCE]
Waiting, Restart Inhibit
Starting
Running Heat Mode: [OPERATING MODE]
Running, Current Limit Request setpoint source: [SETPOINT SOURCE]
Running, Condenser Limit
Running, Evaporator Limit Next
Stopping
Making ice Compressors on A, B, C, D, NONE
ice-making complete Circuits locked out CIRCUIT 1, CIRCUIT 2, NONE
Low ambient temperature lockout
Electronic expansion valve test Next
Manufacturing test
Service pumpdown [Operating mode]
Making ice,
ice-making complete All others

Next
Active ice termination setpoint XXX C
Evaporator entering water temperature XXX.X C

Active chilled water setpoint XXX C


Evaporator leaving water temperature XXX.X C

Active hot water setpoint XXX C


Leaving water temperature XXX.X C

Next

Evaporator entering water temperature XXX.X C


Evaporator leaving water temperature XXX.X C

Next

Fan control
(Service Setting Menu)
Disable Enable

Next
Condenser entering water temperature XXX.X C
Condenser leaving water temperature XXX.X C

Water heat recovery entering water temperature XXX.X C


Water heat recovery leaving water temperature XXX.X C

Next

Active current limit setpoint XXX %


* Dashes will be displayed if the sensor is open Chiller % Rated load amps XXX %
or shorted and neither outdoor air reset or
low ambient lockout is enabled. Next

** Dashes will be displayed if the zone * Outdoor air temperature XXX.X C


temperature sensor is open or shorted or ** Zone temperature XXX.X C
zone reset is disabled.
Next

7
Refrigerant report
Refrigerant Refrigerant temperature and pressure report
report “Press (Next) (Previous) to continue”

Next

All others RTXA

The possible replacement to Circuit 1 Circuit Mode: [Circuit mode]

Cooling Next
Heating
Defrosting Circuit 1 evaporator refrigerant pressure XXX bar
Heat to Defrost Circuit 1 condenser refrigerant pressure XXX bar
Defrost to Heat
Cool to Heat Next
Heat to Cool
Circuit 1 compressor suction refrigerant temperature XXX.X C
Circuit 1 saturated evaporator refrigerant temperature XXX.X C

Next

Circuit 1 saturated condenser refrigerant temperature XXX.X C

Next

All others RTXA

Circuit 2 Circuit Mode: [Circuit mode]

Next

Circuit 2 evaporator refrigerant pressure XXX bar


Circuit 2 condenser refrigerant pressure XXX bar

Next

Circuit 2 compressor suction refrigerant temperature XXX.X C


Circuit 2 saturated evaporator refrigerant temperature XXX.X C

Next

Circuit 2 saturated condenser refrigerant temperature XXX.X C

Next

8
Compressor report
Compressor Compressor report: Mode, Hours, Starts, Rated load amps
report “Press (Next) (Previous) to continue”

Next

Compressors on A, B, C, D, NONE
Circuits locked out Circuit 1, Circuit 2, NONE

Next

% line volts XXX %

Next

* Display will change according to compressor * Compressor A mode [MODE]


reviewing
Compressor A mode
Compressor B mode Next
Compressor C mode
Compressor D mode
Compressor A % Rated load amps, average XXX %
[MODE] Compressor A % Rated load amps, high phase XXX %
Stopped
Locked out Next
Waiting for restart inhibit time
Starting Tonnage of unit
Running 130-400 Tons 70-125 Tons
Run-condenser limit
Run-evaporator limit
Run-current limit
Stopping Compressor A entering oil temperature XXX C
Service pumpdown

Next

Compressor A starts XXXXX


Compressor A running hours XXXXX

Next

After review of last compressor Compressor B, C, D

9
Operator settings
Operator Chiller operation settings and setpoints
settings “Press (Next) (previous) to continue”

Next

[SOURCE] Setpoint source [SOURCE]


Local “Press (+) (-) to change setting”
Tracer
Next

All others RTXA


Default = 6.7°C
Select = - 17.8 to 18.3°C
* If “Limited by cutout setpoint, (+) to change” is
Front panel chilled water setpoint XXX C
displayed, refer to the section on “Leaving water
“Press (+) (-) to change setting”
temperature cutout” and “Low refrigerant
temperature cutout.”
Next

Default = Disable External chilled water setpoint [Disable/Enable]


“Press (+) (-) to change setting”

Next

Default = 5.5 °C Design delta temperature setpoint XXX C


Select = -16 to +2°C “Press (+) (-) to change setting”
This is difference between the entering and
leaving chilled water temperature.

Front Panel Chilled Water Setpoint XXX C


“Press (+) (-) to change setting”

Front Panel Hot Water Setpoint XXX C


“Press (+) (-) to change setting”

External Chilled Water Setpoint [Disable/Enable]


“Press (+) (-) to change setting”

External Hot Water Setpoint [Disable/Enable]


“Press (+) (-) to change setting”

Cooling Design Delta Temperature Setpoint XXX C


“Press (+) (-) to change setting”

Heating Design Delta Temperature Setpoint XXX C


“Press (+) (-) to change setting”

Default = 1.1°C Differential to start setpoint XXX C


Select = 16.6 to 1.1°C “Press (+) (-) to change setting”
The temperature which is added the chilled water
setpoint, at which the chiller will start. Next

10
Default = ON. Manual override of chilled water
pump off delay Chilled water pump [ON, AUTO]
AUTO = activates the “Chilled water pump off “Press (+) (-) to change setting”
delay”
Next
[MINUTES] Chilled water pump off delay [MINUTES]
Default = 10 minutes “Press (+) (-) to change setting”
Select = 1 minute to 30 minutes
The time period that the chilled water pump will Next
run, once the stop signal is given to the chiller.
Front panel current limit setpoint XXX %
Default = 120%
“Press (+) (-) to change setting”
Select = 40% to 120%
Next

Default = Disable External current limit setpoint [Disable/Enable]


“Press (+) (-) to change setting”

Next

Default = Disable Low ambient lockout [Disable/Enable]


“Press (+) (-) to change setting

Next

Low ambient lockout


(Operator settings menu)
Enable Disable

Default = -6.6°C Low ambient lockout setpoint XXX C


Select: -28°C to 16°C “Press (+) (-) to change setting

Next

11
Default = Disable
Select = Return water Chilled water reset type [TYPE]
Zone “Press (+) (-) to change setting”
Outdoor air
Next

Type of chilled water reset selected above

Return water
Zone
Outdoor air Disable

[TYPE] [TYPE] type, reset ratio XXX %


Return water ”Press (+) (-) to change setting”
Default = 50%
Range = 10% to 120% Next
Zone
Default = 100%
Range = 50% to 300%
Outdoor
Default = 10%
Range = -80% to 80%

[TYPE] [TYPE] type, start reset setpoint XXX C


Return: “Press (+) (-) to change setting”
Default = 2,7°C
Range = 0° to 11°C Next
Zone
Default = 25°C
Range = 10 to 55°C
Outdoor
Default = 32°C
Range = 10 to 55°C

[TYPE] [TYPE] type, max reset setpoint


Return water “Press (+) (-) to change setting”
Default = 2,7°C
Range = 0° to 11°C Next
Zone
Default = -15°C
Range = 0° to 11°C
Outdoor
Default = 2,7°C
Range = 0° to 11°C
Ice machine control [Disable/Enable]
Default = Disable “Press (+) (-) to change setting”

Default = -3°C
Select = -7 to -1°C Panel ice termination setpoint XXX F
“Press (+) (-) to change setting”

Next

12
Service settings Service Service settings, enable and units
settings “Press (Next) (Previous) to continue”

Next

Status of keypad/display lock feature


(Service setting menu)
Enable Disable

“Press (Enter) to lock display and keypad”


password will be required to unlock

Next
Next
Depress either Enter or Next

Enter

* ***DISPLAY AND KEYPAD ARE LOCKED ***


* If the keypad is locked and a diagnostic occurs, *** ENTER PASSWORD TO UNLOCK ***
the alarm light will flash if applicable but the
diagnostic screen will not be displayed until the ** Previous Enter
keypad is unlocked.

** Once the keypad is locked the “PREVIOUS” and


“ENTER” key need to be pressed simultaneously Display will return to
to unlock the keypad. “Chiller operating mode”
under chiller report

Default = Disable Under/Over voltage protection [Disable/Enable]


The optional under/over voltage transformer is “Press (+) (-) to change setting”
needed for this feature.
Next

Default = 460 Unit line voltage [VOLT] V


Selections = 200, 220, 230, 346, 380, 415, 460, 500, “Press (+) (-) to change setting”
575.
Next

Default = 120 seconds Restart inhibit time XXX SEC


select = 30 to 120 seconds “Press (+) (-) to change setting”
The time period between power-up or stop and the
initiation of the compressor start sequence, when Next
there is a call for cooling.
Balanced compressor start and hours [Disable/Enable]
Default = Disable “Press (+) (-) to change setting”

Next

[UNITS] Display units [UNITS]


SI “Press (+) (-) to change setting”
English
Next

[LANGUAGE] Language [LANGUAGE]


English / Français / Espanol / Nippon / Italiano / “Press (+) (-) to change setting”
Deutsch / Nederlands
Next

Default = 1 ** Programmable relay setup XX


Select = 1 to 12 “Press (+) (-) to change setting”

Next
Default = Disable
External circuit lockout [Disable/Enable]
“Press (+) (-) to change setting”

Next

*** Password required for further access


“Please enter password”

Next

13
Service tests Service
Service tests: pumpdown, electronic expansion valve,
compressor, lockout
tests “Press (Next) (Previous) to continue”

Next

Default = Disable Service pumpdown, compressor A [Disable/Enable]


Must be manually enabled by sevice personnel “Press (+) (-) to change setting”
from the UCM. The unit must be in STOP/RESET
and can be performed only once for every power- Next
up of the UCM. Restart inhibit will be prepositioned
and the compressor selected will start and run for Is there a compressor B ?
one minute. Manual closing of the liquid line angle Yes No
valve will be required.

Service pumpdown, compressor B [Disable/Enable]


“Press (+) (-) to change setting”
Default = Disable
Next

Is there a compressor C ?
Yes No

Service pumpdown, compressor C [Disable/Enable]


Default = Disable “Press (+) (-) to change setting”

Next

Is there a compressor D ?
Yes No

Service pumpdown, compressor D [Disable/Enable]


Default = Disable “Press (+) (-) to change setting”

Next

Default = Disable Electronic expansion valve test, circuit 1


Electronic expansion valve test will be initiated “Press (+) (-) to change setting”
when the unit is in STOP/RESET and Electronic
expansion valve test is set to enable. The mode will Next
automatically be reset to disable upon completion
of the test. Electronic expansion valve test, circuit 2
“Press (+) (-) to change setting”
Default = Disable
Next

Compressor test, compressor A [Disable/Enable]


Default = Disable “Press (+) (-) to change setting”
Allows service personnel to override the lead/lag
function and start the compressor of concern. After Next
the compressor starts, the display will
automatically return to “D.” Is there a compressor B ?
Yes No

Compressor test, compressor B [Disable/Enable]


Default = Disable “Press (+) (-) to change setting”

Next

Is there a compressor C ?
Yes No

Compressor test, compressor C [Disable/Enable]


Default = Disable “Press (+) (-) to change setting”

Next

14
Is there a compressor D ?
Yes No

Compressor test, compressor D [Disable/Enable]


“Press (+) (-) to change setting”
Default = Disable
Next

Default = UNLOCK Circuit lockout, circuit 1 [UNLOCK/LOCKOUT]


If the setting is changed to “LOCKOUT,” the circuit “Press (+) (-) to change setting”
will become non-operational. The setting must be
manually changed to “UNLOCK” to regain Next
operation of the circuit.
Circuit lockout, circuit 2 [UNLOCK/LOCKOUT]
Default = UNLOCK “Press (+) (-) to change setting”

Next

15
Diagnostics
If there are no diagnostic messages, the selected menu If more than one diagnostic is present, only the highest
item will be displayed continuously. If the diagnostics priority active diagnostic will be explained in detail. For
key is pressed and there are no active diagnostics, the example, if the diagnostics occur in the following order
readout on the display will be: before the operator returns - IFW, MMR, CMR - the
display will read:
NO ACTIVE DIAGNOSTICS PRESENT *** A machine shutdown has occurred ! ***

When a system malfunction occurs, one of the because the MMR has the highest priority. However, as
following appropriate diagnostic messages will be the operator moves through the diagnostic menu to the
displayed: “Last diagnostic,” the [Diagnostic description] will
show the CMR diagnostic as well as the IFW. If the
*** A machine shutdown has occurred ! *** “Next” key is pressed, the display will show all the
other active and historic diagnostics.
A machine shutdown occurred
The active diagnostic priorities, listed from highest to
but has cleared “press (Next)” lowest are:

*** A circuit shutdown has occurred ! *** Machine shutdown - manual reset (MMR)
Machine shutdown - automatic reset (MAR)
A circuit shutdown occurred Circuit shutdown - manual reset (CMR)
Circuit shutdown - automatic reset (CAR)
but has cleared “press (Next)” Informational warning (IFW)

*** Informational warning *** The following flowchart shows the display readouts
found under the diagnostics menu. By following the
An informational warning occurred steps shown in the flowchart, a brief description of the
diagnostic can be viewed. Use the Next key to enter the
but has cleared “press (Next)” main diagnostic menu, where the diagnostic can be
cleared.
When a circuit shutdown - manual reset (CMR) or a
machine shutdown - manual reset (MMR) occurs, the
red LED to the right of the display will flash. Otherwise
this alarm LED is de-energized.

16
Diagnostics Diagnostics No
Diagnostic present

Yes
Other
Type of diagnostic

MMR/MAR Active
Note:
MMR: Machine shutdown manual reset. *** A machine shutdown has occurred ! ***
“Press (Next) for diagnostic info”
MAR: Machine shutdown automatic reset.
CMR: Circuit shutdown manual reset. Next
CAR: Circuit shutdown automatic reset.
MAR
IFW: Informational warning. Type of machine shutdown

MMR

[Diagnostic description]
Latched fault - manual reset required

Next

All others RTXA

Mode at fault: [OPERATING MODE]


Compressors running at fault: [A, B, C, D]

[Unit operating mode] [Unit operating mode] [Operating mode]


Compressors running at fault: [A, B, C, D]
Cooling Mode
Heating Mode Next
Defrost Mode
Press (Enter) to reset control
and clear all active diagnostics

Enter

Next
Press Enter or Next

Enter

Machine will unload if loaded


and display will automatically
return to “MODE” in the chiller report

[DIAGNOSTIC DESCRIPTION]
Active fault - May clear automatically

Next

All others RTXA

Mode at fault: [Operating mode]


Compressors running at fault: [A, B, C, D]

[Unit operating mode] [Operating mode]


Compressors running at fault: [A, B, C, D]

Other
Type of diagnostic

MAR inactive

*** A circuit shutdown has occurred ! ***


Press (Next) for diagnostic information”

Next

17
Note:
MMR: Machine shutdown manual reset.
MAR: Machine shutdown automatic reset.
CMR: Circuit shutdown manual reset. Other
CAR: Circuit shutdown automatic reset. Type of diagnostic
IFW: Informational warning.
CMR/ CAR active

Latched fault - manual reset required


“Press (Next) for more”

Next
CAR
Type of circuit shutdown

CMR

Latched fault - manual reset required


“Press (Next) for more”

Next

Did diagnostic occur Circuit 2


on Circuit 1 or Circuit 2?

Circuit 1

Press (Enter) to
reset circuit 1 diagnostics

Next Enter

Reset Circuit 1 diagnostic

Press (Enter) to
reset circuit 2 diagnostics

Next Enter

Reset Circuit 2 diagnostic

Active fault - can clear automatically


“Press (Next) for more”

Next
Other
Type of diagnostic

CAR inactive

A circuit shutdown occurred


but has cleared “Press (Next)”

Next
IFW inactive
Type of diagnostic

IFW active

*** Informational warning ***


“Press (Next) for diagnostic info”

Next

18
An informational warning occurred
but has cleared “Press (Next)”

Next

No active diagnostics present


“Press (Next) (Previous) to continue”

Next
No
Are there diagnostics
in history ?

Yes

Diagnostic status report follows


“Press (Next) (Previous) to continue”

Next

Last diagnostic:
[DIAGNOSTIC DESCRIPTION]

Next
Next

[DIAGNOSTIC DESCRIPTION]
[DIAGNOSTIC TYPE]

No historic diagnostics present


“Press (Next) (Previous) to continue”

Next

Press (Enter) to
clear diagnostic history

Next

Press (Enter) to
reset circuit 1 diagnostics

Next

Press (Enter) to
reset circuit 2 diagnostics

Next

Press (Enter) to reset control


and clear all active diagnostics

Next
Next
Press Enter or Next

Enter

Machine will unload if loaded and


display will automatically return to
“MODE” in the chiller report.

19
Defaults description
Fault 87
Check External Chilled Water Setpoint: IFW - Value out of range

Fault 89
Check External Current Limit Setpoint: IFW - Value out of range

Fault 8A
Chilled Water Flow (Entering Water Temperature): MMR 1) Entering water temperature
< leaving water temperature
2) No water flow
3) Defective Evaporator sensor
Fault 8E
Evaporator Entering Water Temperature Sensor: MMR - Defective sensor

Fault 8F
Condenser Refrigerant Temperature Sensor - Circuit 1: MMR - Defective sensor

Fault 90
Condenser Refrigerant Temperature Sensor - Circuit 2: MMR - Defective sensor

Fault 93
Evaporator Refrigerant Temperature Sensor - Circuit 1: MMR - Defective sensor

Fault 94
Evaporator Refrigerant Temperature Sensor - Circuit 2: MMR - Defective sensor

Fault 9A
Condenser Entering Water Temperature Sensor: IFW - Defective sensor

Fault 9b
Condenser Leaving Water Temperature Sensor: IFW - Defective sensor

Fault A0
Zone Temperature Sensor: IFW - Defective sensor

Fault A1
Outdoor Air Temperature Sensor: IFW - Defective sensor

Fault Ab
Evaporator Leaving Water Temperature Sensor: MMR - Defective sensor

Fault b5
Low Pressure Cutout - Circuit 1: CMR - Low pressure switch open

Fault b6
Low Pressure Cutout - Circuit 2: CMR - Low pressure switch open

Fault bA
Overload trip - Compressor A: CMR - Current exceeded

Fault bb
Overload Trip - Compressor B: CMR - Current exceeded

Fault bC
Overload trip - Compressor C: CMR - Current exceeded

Fault bd
Overload trip - Compressor D: CMR - Current exceeded

Fault bE
High Pressure Cutout - Compressor C: CMR - High pressure too high

Fault bF
High Pressure Cutout - Compressor D: CMR - High pressure too high

20
Fault C5
Low Chilled Water Temperature (Unit Off): IFW - Antifreeze protection

Fault C6
Low Chilled Water Temperature (Unit On): MAR - Antifreeze protection

Fault CA
Contactor - Compressor A: MMR - Welded compressor contactor

Fault Cb
Contactor - Compressor B: MMR - Welded compressor contactor

Fault CC
Contactor - Compressor C: MMR - Welded compressor contactor

Fault Cd
Contactor - Compressor D: MMR - Welded compressor contactor

Fault d7
Over Voltage: MAR - Voltage 10% > nominal

Fault d8
Under Voltage: MAR - Voltage 10% < nominal

Fault Ed
Chilled Water Flow Interlock: MAR - Flow switch open more than 6 seconds

Fault F5
High Pressure Cutout - Compressor A: MMR - High pressure too high

Fault F6
High Pressure Cutout - Compressor B: MMR - High pressure too high

Fault Fd
Emergency Stop Input: MMR - Emergency stop input open

Fault 180
Starter Transition - Compressor A: CMR 1) Transition proof signal not received
2) Proof input shunted

Fault 181
Starter Transition - Compressor B: CMR 1) Transition proof signal not received
2) Proof input shunted

Fault 182
Starter Transition - Compressor C: CMR 1) Transition proof signal not received
2) Proof input shunted

Fault 183
Starter Transition - Compressor D: CMR 1) Transition proof signal not received
2) Proof input shunted

Fault 184
Phase Reversal - Compressor A: CMR - Phase reversed

Fault 185:
Phase reversal - Compressor B CMR - Phase reversed

Fault 186
Phase reversal - Compressor C: CMR - Phase reversed

Fault 187
Phase reversal - Compressor D: CMR - Phase reversed

Fault 190
Low Superheat - Circuit 1: CMR - Superheat < 1°C during more than
1333°C x seconds

21
Fault 191
Low Superheat - Circuit 2: CMR - Superheat < 1°C during more than 1333°C x seconds

Fault 194
Low Evaporator Refrigerant Temperature. - Circuit 1: CMR - Refrigerant temperature < setpoint during more than
30°C x seconds

Fault 195
Low Evaporator Refrigerant Temperature. - Circuit 2: CMR - Refrigerant temperature < setpoint during more than
30°C x seconds

Fault 198
Low Oil Flow - Compressor A: CMR - Oil flow switch open during more than 20 seconds

Fault 199
Low Oil Flow - Compressor B: CMR - Oil flow switch open during more than 20 seconds

Fault 19A
low Oil Flow - Compressor C: CMR - Oil flow switch open during more than 20 seconds

Fault 19b
Low Oil Flow - Compressor D: CMR - Oil flow switch open during more than 20 seconds

Fault 19C
Phase Loss - Compressor A: CMR - Loss of 1 or more phases

Fault 19d
Phase Loss - Compressor B: CMR - Loss of 1 or more phases

Fault 19E
Phase Loss - Compressor C: CMR - Loss of 1 or more phases

Fault 19F
Phase Loss - Compressor D: CMR - Loss of 1 or more phases

Fault 1A0
Power Loss - Compressor A: CAR - Loss of all three phases in operation

Fault 1A1
Power Loss - Compressor B: CAR - Loss of all three phases in operation

Fault 1A2
Power Loss - Compressor C: CAR - Loss of all three phases in operation

Fault 1A3
Power Loss - Compressor D: CAR - Loss of all three phases in operation

Fault 1A4
Tracer Communication Loss: IFW - Loss of external information

Fault 1A5
Oil Flow Control - Compressor A: CMR - Problem on oil circuit

Fault 1A6
Oil Flow Control - Compressor B: CMR - Problem on oil circuit

Fault 1A7
Oil Flow Control - Compressor C: CMR - Problem on oil circuit

Fault 1A8
Oil Flow Control - Compressor D: CMR - Problem on oil circuit

Fault 1A9
Electronic expansion valve Electric Drive Circuit
- Refrigerant Circuit 1: CMR 1) Electronic expansion valve wiring
2) Defective UCM
3) Defective Electronic expansion valve
4) Defective Electronic expansion valve relay

22
Fault 1AA
Electronic expansion valve Electric Drive Circuit
- Refrigerant Circuit 2: CMR 1) Electronic expansion valve wiring
2) Defective UCM
3) Defective Electronic expansion valve
4) Defective Electronic expansion valve relay
Fault 1Ad
Memory Error Type I: IFW - Non Volatile Random Access Memory [NOVRAM}
problem, unit is placed on default setting operating
Fault 1AE
Low Differential Pressure - Circuit 1: CMR - Delta P< 2,8bar during more than 2 minutes

Fault 1AF
Low Differential Pressure - Circuit 2: CMR - Delta P< 2,8bar during more than 2 minutes

Fault 1b2
Severe Phase Unbalance - Compressor A: CMR - Phase imbalance >30%, check current transformer
and unit power supply

Fault 1b3
Severe Phase Unbalance - Compressor B: CMR - Phase imbalance >30%, check current transformer
and unit power supply

Fault 1b4
Severe Phase Unbalance - Compressor C: CMR - Phase imbalance >30%, check current transformer
and unit power supply

Fault 1b5
Severe Phase Unbalance - Compressor D: CMR - Phase imbalance >30%, check current transformer
and unit power supply

Fault 1b6
Compressor Overload Setting - Compressor A: IFW - Check setting of compressor overload

Fault 1b7
Compressor Overload Setting - Compressor B: IFW - Check setting of compressor overload

Fault 1b8
Compressor Overload Setting - Compressor C: IFW - Check setting of compressor overload

Fault 1b9
Compressor Overload Setting - Compressor D: IFW - Check setting of compressor overload

Fault 1bA
Phase Unbalance - Compressor A: CMR - Phase imbalance >15%

Fault 1bb
Phase Unbalance - Compressor B: CMR - Phase imbalance >15%

Fault 1bC
Phase Unbalance - Compressor C: CMR - Phase imbalance >15%

Fault 1bd
Phase Unbalance - Compressor D: CMR - Phase imbalance >15%

Fault 1bE
Winding Temperature - Compressor A: CMR - Winding temperature > 105°C

Fault 1bF
Winding Temperature - Compressor B: CMR - Winding temperature > 105°C

Fault 1C0
Winding Temperature - Compressor C: CMR - Winding temperature > 105°C

Fault 1C1
Winding Temperature - Compressor D: CMR - Winding temperature > 105°C

23
Fault 1C6
High Differential Pressure - Circuit 1: CMR - LB/High pressure differential > 24,5 bar

Fault 1C7
High Differential Pressure - Circuit 2: CMR - LB/High pressure differential > 24,5 bar

Fault 1d1
Memory Error Type II: IFW - RAM error

Fault 1d2
Memory Error Type III: IFW - RAM error

Fault 1d3
Compressor Suction Temperature Sensor - Circuit 1: CMR - Defective sensor

Fault 1d4
Compressor Suction Temperature Sensor - Circuit 2: CMR - Defective sensor

Fault 1d7
Phase Reversal Protection Lost - Compressor A: CMR - Phase reversal protection not operative

Fault 1d8
Phase Reversal Protection Lost - Compressor B: CMR - Phase reversal protection not operative

Fault 1d9
Phase Reversal Protection Lost - Compressor C: CMR - Phase reversal protection not operative

Fault 1dA
Phase Reversal Protection Lost - Compressor D: CMR - Phase reversal protection not operative

Fault 1db
Slaved Electronic expansion valve
Electronic Drive Circuit - Refrigerant Circuit 1: CMR - Electronic expansion valve electric drive defective

Fault 1dC
Slaved Electronic expansion valve
Electronic Drive Circuit - Refrigerant Circuit 2: CMR - Electronic expansion valve electric drive defective

Fault 1dd
High Oil Temperature - Compressor A: CMR - Oil temperature > 77°C

Fault 1dE
High Oil Temperature - Compressor B: CMR - Oil temperature > 77°C

Fault 1dF
High Oil Temperature - Compressor C: CMR - Oil temperature > 77°C

Fault 1E0
High Oil Temperature - Compressor D: CMR - Oil temperature > 77°C

Fault 1E1
Oil System Fault - Compressor A: CMR - Oil temperature < condenser saturated temperature
during more than 30 minutes

Fault 1E2
Oil System Fault - Compressor B: CMR - Oil temperature < condenser saturated temperature
during more than 30 minutes

Fault 1E3
Oil System Fault - Compressor C: CMR - Oil temperature < condenser saturated temperature
during more than 30 minutes

Fault 1E4
Oil System Fault - Compressor D: CMR - Oil temperature < condenser saturated temperature
during more than 30 minutes

Fault 1E5
Entering Oil Temperature Sensor - Compressor A: CMR - Defective sensor

24
Fault 1E6
Entering Oil Temperature Sensor - Compressor B: CMR - Defective sensor

Fault 1E7
Entering Oil Temperature Sensor - Compressor C: CMR - Defective sensor

Fault 1E8
Entering Oil Temperature Sensor - Compressor D: CMR - Defective sensor

Fault 2A1
Condenser Fan Variable Speed Drive Fault - Circuit 1: IFW - Defective fan speed controller after 5 attempts

Fault 2A2
Condenser Fan Variable Speed Drive Fault - Circuit 2: IFW - Defective fan speed controller after 5 attempts

Note:
MMR: Machine shutdown manual reset.
MAR: Machine shutdown automatic reset.
CMR: Circuit shutdown manual reset.
CAR: Circuit shutdown automatic reset.
IFW: Informational warning.

Communication failures

Fault 410
Loss of Local Display Panel Communication

Fault 412
Chiller Module to Option Module Communication Failure

Fault 413
Chiller Module to Electronic expansion valve Module Communication Failure

Fault 414
Chiller Module to Compressor A Module Communication Failure

Fault 415
Chiller Module to Compressor B Module Communication Failure

Fault 416
Chiller Module Compressor C Module Communication Failure

Fault 417
Chiller Module to Compressor D Module Communication Failure

Fault 418
Chiller Module to Slaved Electronic expansion valve Module Communication Failure

Fault 431
Electronic expansion valve Module to Chiller Module Communication Failure

Fault 434
Electronic expansion valve Module to Compressor A Module Communication Failure

Fault 435
Electronic expansion valve Module to Compressor B Module Communication Failure

Fault 436
Electronic expansion valve Module to Compressor C Module Communication Failure

Fault 437
Electronic expansion valve Module to Compressor D Module Communication Failure

Fault 441
Compressor A Module to Chiller Module Communication Failure

Fault 443
Compressor A Module to Electronic expansion valve Module Communication Failure

25
Fault 445
Compressor A Module to Compressor B Module Communication Failure

Fault 451
Compressor B Module to chiller Module Communication Failure

Fault 453
Compressor B Module to Electronic expansion valve Module Communication Failure

Fault 454
Compressor B Module to Compressor A Module Communication Failure

Fault 461
Compressor C Module to Chiller Module Communication Failure

Fault 463
Compressor C Module to Electronic expansion valve Module Communication Failure

Fault 467
Compressor C Module to Compressor D Module Communication Failure

Fault 471
Compressor D Module to Chiller Module Communication Failure

Fault 473
Compressor D Module to Electronic expansion valve Module Communication Failure

Fault 476
Compressor D Module to Compressor C Module Communication Failure

Fault 481
Slaved Electronic expansion valve Module to Chiller Module Communication Failure

Fault 483
Slaved Electronic expansion valve Module to Electronic expansion valve Module Communication Failure

Fault 484
Slaved Electronic expansion valve Module to Compressor A Module Communication Failure

Fault 485
Slaved Electronic expansion valve Module to Compressor B Module Communication Failure

Fault 486
Slaved Electronic expansion valve Module to Compressor C Module Communication Failure

Fault 487
Slaved Electronic expansion valve Module to Compressor D Module Communication Failure

Unit operating mode

Mode A00
Stopped

Mode A01, A02


Auto

Mode A17
Service Pump down

Mode A70
Waiting, Restart Inhibit

Mode A72
Starting

Mode A74
Running

26
Mode A75
Running, Current Limit

Mode A76
Running, Condenser Limit

Mode A77
Running, Evaporator Limit

Mode A7E
Stopping

Mode A88
Reset

Mode A100
Stopped by Source

Mode A101
Ice Making Complete

Mode A118
Electronic expansion valve Test

Mode A174
Making Ice

Mode A175
Making Ice, Condenser Limit

Mode A177
Making Ice, Evaporator Limit

Mode A200
Low Ambient Temperature Lockout

Mode A234
Manufacturing Test
Stopped By Tracer
Stopped By Remote Display

Compressor operating mode


Mode 00
Stopped

Mode 16
Locked Out

Mode 17
Service Pumpdown

Mode 70
Restart Inhibited

Mode 72
Starting

Mode 74
Running

Mode 75
Run - Current Limit

Mode 76
Run - Condenser Limit

Mode 77
Run - Evaporator Limit

Mode 7E
Stopping

27
Maintenance contract
It is strongly recommended that you sign a possibility that serious damage will occur. Finally,
maintenance contract with your local Service Agency. regular maintenance helps ensure the maximum
This contract provides regular maintenance of your operating life of your equipment. Failure to follow
intallation by a specialist in our equipment. Regular these installation and maintenance instructions may
maintenance helps ensure that any malfunction is affect your warranty.
detected and corrected quickly and minimizes the

Training
The equipment described in this manual is the result of maintenance technicians a better knowledge of the
many years of research and continuous development. equipment they are using, or that is under their charge.
To assist you in obtaining the best use of it, and Emphasis is particularly given to the importance of
maintaining it in perfect operating condition over a periodic checks on the unit operating parameters as
long period of time, the manufacturer has available a well as on preventive maintenance, which can reduce
refrigeration and air conditioning service school. The the cost of owning the unit by helping avoid serious
principal aim of this is to give operators and and costly breakdown.

This publication is a general guide to install, use and properly maintain our products. The information
given may be different from the specification for a particular country or for a specific order. In this
event, please refer to your nearest office.
All rights reserved. No part of this publication may be reproduced or transmitted in any form or by
any means without the written authorization of the manufacturer.

Literature Order Number L80 IM 025 E


Date July 2000
Supersedes L80 IM 025 E - 1297
Stocking Location La Crosse
The Trane Company
An American Standard Company Since The Trane Company has a policy of continuous product improvement, it reserves the right to
www.trane.com change design and specifications without notice.
For more information contact Société Trane – Société Anonyme au capital de 41500 000 F – Siege Social: 1 rue des Amériques – 88190
Your local sales office or Golbey – France – Siret 306 050 188-00011 – RSC Epinal B 306 050 188
e-mail us at comfort@trane.com Numéro d’identification taxe intracommunanutaire: FR 83 3060501888

S-ar putea să vă placă și