Documente Academic
Documente Profesional
Documente Cultură
Installation
Operation
Maintenance
L80 IM 025 E
Foreword
These Installation, Operation, and Maintenance They do not contain the full service procedures
instructions are given as a guide to good practice in the necessary for the continued successful operation of this
installation, start-up, operation, and periodic equipment. The services of a qualified service
maintenance by the user of UCM-CLD modules. technician should be employed, through the medium of
a maintenance contract with a reputable service
company.
Warranty
Warranty is based on the general terms and conditions Damage due to misuse, lack of maintenance, or failure
of the manufacturer. The warranty is void if the to comply with the manufacturer's instructions, is not
equipment is modified or repaired without the written covered by the warranty obligation.
approval of the constructor, if the operating limits are
exceeded, or if either the control system or the
electrical wiring is modified.
Reception
On arrival, inspect the unit before signing the delivery registered letter of protest to the carrier within 7 days
note. Specify any damage on the delivery note, and of delivery and notify the local sales office.
send a registered letter of protest to the last carrier of Units are shipped with the refrigerant operating or
the goods within 72 hours of delivery. Notify the local holding charge, and should be examined with an
sales office at the same time. electronic leak detector to determine the hermetic
The unit should be totally inspected within 7 days of integrity of the unit. The refrigerant charge is not
delivery. If any concealed damage is discovered, send a included in the standard Warranty Cover.
General information
About this manual
Cautions appear at appropriate places in this The manufacturer assumes no liability for installations
instruction manual. Your personal safety and the or servicing performed by unqualified personnel.
proper operation of this machine require that you
follow them carefully.
2
Index
Foreword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Reception . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Diagnostics
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Default description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Unit operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Compressor operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Maintenance contract . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
3
Principles of operation of the module UCM-CLD
Alarm
ADAPTIVE CONTROL™
General information
This regulation assembly is composed of 6 electronic - CSR (Communication and Setpoint Reset): control of
modules which have each their own 115V power the serial communication, unit external setpoints, and
supply and communicate with each other via a serial ice-making mode (optional module).
link. Each module has a set of functions which are - Local CLD (Local Clear Language Display): operator’s
associated to make the unit regulation. interface located in the unit: front panel (software
Each module has the following name linked to its version and number displayed at power-up).
functions. - Remote LCD (Remote Clear Language Display):
- MCSP (Motor Compressor Start and Protection): operator’s interface located up to 1500 m from the
safety, protection and control of the helical-rotary unit at the operator’s, and which can communicate
compressor as well as all associated components. with up to four units of the same type (optional
- CPM (Chiller Protection and Management): safety, module).
protection, and control of the chiller. - TCI IV, IPCB (Tracer Communication Interface 4,
- EXV (Electronic Expansion Valve): control of both Inter-Processor Communication Buffer): protection of
electrical expansion valves. the unit internal communication bus from the external
interferences existing in the unit (optional module,
compulsory when using a remote CLD, and which
must be factory-mounted).
4
Figure 2: Control and regulation panel mounted on helical-rotary units equipped with UCM-CLD
Menu keys
- Chiller Report menu
- Custom Report menu
- Refrigerant menu
- Compressor menu
5
Description of the operation
The whole information is gathered in various menus Previous key
according to the location of the sensor and/or the Pressing the Previous key allows the operator to
function performed. scroll up to the previous information in the current
menu. All the display items are looped, so it is
Chiller report menu possible to scroll from the first item to the last one.
This menu gathers the information relating to the liquid
chiller (reading only). Active setpoints and their origins, Next key
chilled water, air temperature, current draws, are found Pressing the Next key allows the operator to scroll
in this menu. down to the next information in the current menu. All
the display items are looped, so it is possible to scroll
Custom report menu from the last item to the first one.
This menu is peculiar because originally it does not
include any information at all. However, the operator + key
can build his own menu which is comprised of read- If this information displayed is a read-only item,
only information, by simply pressing the + key when in pressing the + key will add it to the operator’s menu.
other menus. To remove information from this menu, if the information can be modified, the value is
simply press the - key when displayed. increased by 1. Pressing the key for longer than 1
second will increase the value of 1 every .25 seconds.
Refrigerant report menu A logical stop prevents an adjustment higher than the
This menu gathers the information, read-only, relating maximum value; a message is displayed to indicate
to the refrigerant. Refrigerant pressures and this status.
temperatures at various points of the refrigerant circuit
can be found in this menu. - key
If the information displayed is a read-only item,
Compressor report menu pressing the - key will remove it from the operator’s
This menu gathers the information, read-only, relating menu. If the information can be modified, the value is
to the compressor. Voltages and amps, hour and start increased by 1. Pressing the key for longer than 1
counters, as well as oil temperature (GP compressor second will increase the value of 1 every .25 seconds.
only) can be found in this menu. A logical stop prevents an adjustment higher than the
maximum value; a message is displayed to indicate
Operator settings menu this status.
This menu comprises all the particular setpoints and
operating modes existing in the unit and which are Enter key
accessible by the usual operator of the chiller. In Pressing this key allows the validation of a value after
addition, the following can be programmed: chilled it has been modified by pressing the + or - key.
water pump operation, temperature resets, ice-making
operation, and low ambient limit. Cancel key
Pressing this key allows the cancellation of a value
Service settings menu after it has been modified by pressing the + or - key
This menu has three access levels. The first one and to come back to the original value.
contains information which can be adjusted by the
customer such as the unit voltage, the validation of Auto key
over/under voltage protection, the display language, Pressing this key (green) allows the unit to come back
and the programmable relay function of the units. The in auto mode if it was previously placed in stop mode
keyboard can also be locked if the relating function is with the stop key. The unit cannot be forced into auto
validated. A second level contains the setpoints mode if it has been stopped by an external contact or
adjusted by the service engineer to adapt the operation the serial link. When the unit is stopped by the remote
of the unit to a particular site, such as the address of interface (Remote CLD), the local “auto” mode order
the serial link, the water and refrigerant limit is prioritary.
parameters, and so forth. The third level contains the
configuration and protection information: number of Stop key
circuits, compressors and fans, compressor amps and Pressing this key (red) allows the unit to go into stop
expansion valve settings. mode. In every case, and wherever the origin (except
a local stop), the stop order and stop status have
Service tests menu priority over a run order. The stop generated is a soft
This menu allows the operator to perform some tests stop, meaning the unit unloads before stopping.
when the unit is in operation or during the initial start-
up of the unit: expansion valve test, circuit locking, or
pump-out.
Diagnostics menu
This menu contains all the information on the current
faults or faults that occurred in the past. It allows the
possibility to reset a manual reset fault or to erase the
historic list of faults.
6
Chiller report
Chiller Chiller report: status, water temperatures and setpoints
report “Press (Next) (Previous) to continue”
Next
Unit model
(service setting menu)
all others RTXA
Next
Active ice termination setpoint XXX C
Evaporator entering water temperature XXX.X C
Next
Next
Fan control
(Service Setting Menu)
Disable Enable
Next
Condenser entering water temperature XXX.X C
Condenser leaving water temperature XXX.X C
Next
7
Refrigerant report
Refrigerant Refrigerant temperature and pressure report
report “Press (Next) (Previous) to continue”
Next
Cooling Next
Heating
Defrosting Circuit 1 evaporator refrigerant pressure XXX bar
Heat to Defrost Circuit 1 condenser refrigerant pressure XXX bar
Defrost to Heat
Cool to Heat Next
Heat to Cool
Circuit 1 compressor suction refrigerant temperature XXX.X C
Circuit 1 saturated evaporator refrigerant temperature XXX.X C
Next
Next
Next
Next
Next
Next
8
Compressor report
Compressor Compressor report: Mode, Hours, Starts, Rated load amps
report “Press (Next) (Previous) to continue”
Next
Compressors on A, B, C, D, NONE
Circuits locked out Circuit 1, Circuit 2, NONE
Next
Next
Next
Next
9
Operator settings
Operator Chiller operation settings and setpoints
settings “Press (Next) (previous) to continue”
Next
Next
10
Default = ON. Manual override of chilled water
pump off delay Chilled water pump [ON, AUTO]
AUTO = activates the “Chilled water pump off “Press (+) (-) to change setting”
delay”
Next
[MINUTES] Chilled water pump off delay [MINUTES]
Default = 10 minutes “Press (+) (-) to change setting”
Select = 1 minute to 30 minutes
The time period that the chilled water pump will Next
run, once the stop signal is given to the chiller.
Front panel current limit setpoint XXX %
Default = 120%
“Press (+) (-) to change setting”
Select = 40% to 120%
Next
Next
Next
Next
11
Default = Disable
Select = Return water Chilled water reset type [TYPE]
Zone “Press (+) (-) to change setting”
Outdoor air
Next
Return water
Zone
Outdoor air Disable
Default = -3°C
Select = -7 to -1°C Panel ice termination setpoint XXX F
“Press (+) (-) to change setting”
Next
12
Service settings Service Service settings, enable and units
settings “Press (Next) (Previous) to continue”
Next
Next
Next
Depress either Enter or Next
Enter
Next
Next
Default = Disable
External circuit lockout [Disable/Enable]
“Press (+) (-) to change setting”
Next
Next
13
Service tests Service
Service tests: pumpdown, electronic expansion valve,
compressor, lockout
tests “Press (Next) (Previous) to continue”
Next
Is there a compressor C ?
Yes No
Next
Is there a compressor D ?
Yes No
Next
Next
Is there a compressor C ?
Yes No
Next
14
Is there a compressor D ?
Yes No
Next
15
Diagnostics
If there are no diagnostic messages, the selected menu If more than one diagnostic is present, only the highest
item will be displayed continuously. If the diagnostics priority active diagnostic will be explained in detail. For
key is pressed and there are no active diagnostics, the example, if the diagnostics occur in the following order
readout on the display will be: before the operator returns - IFW, MMR, CMR - the
display will read:
NO ACTIVE DIAGNOSTICS PRESENT *** A machine shutdown has occurred ! ***
When a system malfunction occurs, one of the because the MMR has the highest priority. However, as
following appropriate diagnostic messages will be the operator moves through the diagnostic menu to the
displayed: “Last diagnostic,” the [Diagnostic description] will
show the CMR diagnostic as well as the IFW. If the
*** A machine shutdown has occurred ! *** “Next” key is pressed, the display will show all the
other active and historic diagnostics.
A machine shutdown occurred
The active diagnostic priorities, listed from highest to
but has cleared “press (Next)” lowest are:
*** A circuit shutdown has occurred ! *** Machine shutdown - manual reset (MMR)
Machine shutdown - automatic reset (MAR)
A circuit shutdown occurred Circuit shutdown - manual reset (CMR)
Circuit shutdown - automatic reset (CAR)
but has cleared “press (Next)” Informational warning (IFW)
*** Informational warning *** The following flowchart shows the display readouts
found under the diagnostics menu. By following the
An informational warning occurred steps shown in the flowchart, a brief description of the
diagnostic can be viewed. Use the Next key to enter the
but has cleared “press (Next)” main diagnostic menu, where the diagnostic can be
cleared.
When a circuit shutdown - manual reset (CMR) or a
machine shutdown - manual reset (MMR) occurs, the
red LED to the right of the display will flash. Otherwise
this alarm LED is de-energized.
16
Diagnostics Diagnostics No
Diagnostic present
Yes
Other
Type of diagnostic
MMR/MAR Active
Note:
MMR: Machine shutdown manual reset. *** A machine shutdown has occurred ! ***
“Press (Next) for diagnostic info”
MAR: Machine shutdown automatic reset.
CMR: Circuit shutdown manual reset. Next
CAR: Circuit shutdown automatic reset.
MAR
IFW: Informational warning. Type of machine shutdown
MMR
[Diagnostic description]
Latched fault - manual reset required
Next
Enter
Next
Press Enter or Next
Enter
[DIAGNOSTIC DESCRIPTION]
Active fault - May clear automatically
Next
Other
Type of diagnostic
MAR inactive
Next
17
Note:
MMR: Machine shutdown manual reset.
MAR: Machine shutdown automatic reset.
CMR: Circuit shutdown manual reset. Other
CAR: Circuit shutdown automatic reset. Type of diagnostic
IFW: Informational warning.
CMR/ CAR active
Next
CAR
Type of circuit shutdown
CMR
Next
Circuit 1
Press (Enter) to
reset circuit 1 diagnostics
Next Enter
Press (Enter) to
reset circuit 2 diagnostics
Next Enter
Next
Other
Type of diagnostic
CAR inactive
Next
IFW inactive
Type of diagnostic
IFW active
Next
18
An informational warning occurred
but has cleared “Press (Next)”
Next
Next
No
Are there diagnostics
in history ?
Yes
Next
Last diagnostic:
[DIAGNOSTIC DESCRIPTION]
Next
Next
[DIAGNOSTIC DESCRIPTION]
[DIAGNOSTIC TYPE]
Next
Press (Enter) to
clear diagnostic history
Next
Press (Enter) to
reset circuit 1 diagnostics
Next
Press (Enter) to
reset circuit 2 diagnostics
Next
Next
Next
Press Enter or Next
Enter
19
Defaults description
Fault 87
Check External Chilled Water Setpoint: IFW - Value out of range
Fault 89
Check External Current Limit Setpoint: IFW - Value out of range
Fault 8A
Chilled Water Flow (Entering Water Temperature): MMR 1) Entering water temperature
< leaving water temperature
2) No water flow
3) Defective Evaporator sensor
Fault 8E
Evaporator Entering Water Temperature Sensor: MMR - Defective sensor
Fault 8F
Condenser Refrigerant Temperature Sensor - Circuit 1: MMR - Defective sensor
Fault 90
Condenser Refrigerant Temperature Sensor - Circuit 2: MMR - Defective sensor
Fault 93
Evaporator Refrigerant Temperature Sensor - Circuit 1: MMR - Defective sensor
Fault 94
Evaporator Refrigerant Temperature Sensor - Circuit 2: MMR - Defective sensor
Fault 9A
Condenser Entering Water Temperature Sensor: IFW - Defective sensor
Fault 9b
Condenser Leaving Water Temperature Sensor: IFW - Defective sensor
Fault A0
Zone Temperature Sensor: IFW - Defective sensor
Fault A1
Outdoor Air Temperature Sensor: IFW - Defective sensor
Fault Ab
Evaporator Leaving Water Temperature Sensor: MMR - Defective sensor
Fault b5
Low Pressure Cutout - Circuit 1: CMR - Low pressure switch open
Fault b6
Low Pressure Cutout - Circuit 2: CMR - Low pressure switch open
Fault bA
Overload trip - Compressor A: CMR - Current exceeded
Fault bb
Overload Trip - Compressor B: CMR - Current exceeded
Fault bC
Overload trip - Compressor C: CMR - Current exceeded
Fault bd
Overload trip - Compressor D: CMR - Current exceeded
Fault bE
High Pressure Cutout - Compressor C: CMR - High pressure too high
Fault bF
High Pressure Cutout - Compressor D: CMR - High pressure too high
20
Fault C5
Low Chilled Water Temperature (Unit Off): IFW - Antifreeze protection
Fault C6
Low Chilled Water Temperature (Unit On): MAR - Antifreeze protection
Fault CA
Contactor - Compressor A: MMR - Welded compressor contactor
Fault Cb
Contactor - Compressor B: MMR - Welded compressor contactor
Fault CC
Contactor - Compressor C: MMR - Welded compressor contactor
Fault Cd
Contactor - Compressor D: MMR - Welded compressor contactor
Fault d7
Over Voltage: MAR - Voltage 10% > nominal
Fault d8
Under Voltage: MAR - Voltage 10% < nominal
Fault Ed
Chilled Water Flow Interlock: MAR - Flow switch open more than 6 seconds
Fault F5
High Pressure Cutout - Compressor A: MMR - High pressure too high
Fault F6
High Pressure Cutout - Compressor B: MMR - High pressure too high
Fault Fd
Emergency Stop Input: MMR - Emergency stop input open
Fault 180
Starter Transition - Compressor A: CMR 1) Transition proof signal not received
2) Proof input shunted
Fault 181
Starter Transition - Compressor B: CMR 1) Transition proof signal not received
2) Proof input shunted
Fault 182
Starter Transition - Compressor C: CMR 1) Transition proof signal not received
2) Proof input shunted
Fault 183
Starter Transition - Compressor D: CMR 1) Transition proof signal not received
2) Proof input shunted
Fault 184
Phase Reversal - Compressor A: CMR - Phase reversed
Fault 185:
Phase reversal - Compressor B CMR - Phase reversed
Fault 186
Phase reversal - Compressor C: CMR - Phase reversed
Fault 187
Phase reversal - Compressor D: CMR - Phase reversed
Fault 190
Low Superheat - Circuit 1: CMR - Superheat < 1°C during more than
1333°C x seconds
21
Fault 191
Low Superheat - Circuit 2: CMR - Superheat < 1°C during more than 1333°C x seconds
Fault 194
Low Evaporator Refrigerant Temperature. - Circuit 1: CMR - Refrigerant temperature < setpoint during more than
30°C x seconds
Fault 195
Low Evaporator Refrigerant Temperature. - Circuit 2: CMR - Refrigerant temperature < setpoint during more than
30°C x seconds
Fault 198
Low Oil Flow - Compressor A: CMR - Oil flow switch open during more than 20 seconds
Fault 199
Low Oil Flow - Compressor B: CMR - Oil flow switch open during more than 20 seconds
Fault 19A
low Oil Flow - Compressor C: CMR - Oil flow switch open during more than 20 seconds
Fault 19b
Low Oil Flow - Compressor D: CMR - Oil flow switch open during more than 20 seconds
Fault 19C
Phase Loss - Compressor A: CMR - Loss of 1 or more phases
Fault 19d
Phase Loss - Compressor B: CMR - Loss of 1 or more phases
Fault 19E
Phase Loss - Compressor C: CMR - Loss of 1 or more phases
Fault 19F
Phase Loss - Compressor D: CMR - Loss of 1 or more phases
Fault 1A0
Power Loss - Compressor A: CAR - Loss of all three phases in operation
Fault 1A1
Power Loss - Compressor B: CAR - Loss of all three phases in operation
Fault 1A2
Power Loss - Compressor C: CAR - Loss of all three phases in operation
Fault 1A3
Power Loss - Compressor D: CAR - Loss of all three phases in operation
Fault 1A4
Tracer Communication Loss: IFW - Loss of external information
Fault 1A5
Oil Flow Control - Compressor A: CMR - Problem on oil circuit
Fault 1A6
Oil Flow Control - Compressor B: CMR - Problem on oil circuit
Fault 1A7
Oil Flow Control - Compressor C: CMR - Problem on oil circuit
Fault 1A8
Oil Flow Control - Compressor D: CMR - Problem on oil circuit
Fault 1A9
Electronic expansion valve Electric Drive Circuit
- Refrigerant Circuit 1: CMR 1) Electronic expansion valve wiring
2) Defective UCM
3) Defective Electronic expansion valve
4) Defective Electronic expansion valve relay
22
Fault 1AA
Electronic expansion valve Electric Drive Circuit
- Refrigerant Circuit 2: CMR 1) Electronic expansion valve wiring
2) Defective UCM
3) Defective Electronic expansion valve
4) Defective Electronic expansion valve relay
Fault 1Ad
Memory Error Type I: IFW - Non Volatile Random Access Memory [NOVRAM}
problem, unit is placed on default setting operating
Fault 1AE
Low Differential Pressure - Circuit 1: CMR - Delta P< 2,8bar during more than 2 minutes
Fault 1AF
Low Differential Pressure - Circuit 2: CMR - Delta P< 2,8bar during more than 2 minutes
Fault 1b2
Severe Phase Unbalance - Compressor A: CMR - Phase imbalance >30%, check current transformer
and unit power supply
Fault 1b3
Severe Phase Unbalance - Compressor B: CMR - Phase imbalance >30%, check current transformer
and unit power supply
Fault 1b4
Severe Phase Unbalance - Compressor C: CMR - Phase imbalance >30%, check current transformer
and unit power supply
Fault 1b5
Severe Phase Unbalance - Compressor D: CMR - Phase imbalance >30%, check current transformer
and unit power supply
Fault 1b6
Compressor Overload Setting - Compressor A: IFW - Check setting of compressor overload
Fault 1b7
Compressor Overload Setting - Compressor B: IFW - Check setting of compressor overload
Fault 1b8
Compressor Overload Setting - Compressor C: IFW - Check setting of compressor overload
Fault 1b9
Compressor Overload Setting - Compressor D: IFW - Check setting of compressor overload
Fault 1bA
Phase Unbalance - Compressor A: CMR - Phase imbalance >15%
Fault 1bb
Phase Unbalance - Compressor B: CMR - Phase imbalance >15%
Fault 1bC
Phase Unbalance - Compressor C: CMR - Phase imbalance >15%
Fault 1bd
Phase Unbalance - Compressor D: CMR - Phase imbalance >15%
Fault 1bE
Winding Temperature - Compressor A: CMR - Winding temperature > 105°C
Fault 1bF
Winding Temperature - Compressor B: CMR - Winding temperature > 105°C
Fault 1C0
Winding Temperature - Compressor C: CMR - Winding temperature > 105°C
Fault 1C1
Winding Temperature - Compressor D: CMR - Winding temperature > 105°C
23
Fault 1C6
High Differential Pressure - Circuit 1: CMR - LB/High pressure differential > 24,5 bar
Fault 1C7
High Differential Pressure - Circuit 2: CMR - LB/High pressure differential > 24,5 bar
Fault 1d1
Memory Error Type II: IFW - RAM error
Fault 1d2
Memory Error Type III: IFW - RAM error
Fault 1d3
Compressor Suction Temperature Sensor - Circuit 1: CMR - Defective sensor
Fault 1d4
Compressor Suction Temperature Sensor - Circuit 2: CMR - Defective sensor
Fault 1d7
Phase Reversal Protection Lost - Compressor A: CMR - Phase reversal protection not operative
Fault 1d8
Phase Reversal Protection Lost - Compressor B: CMR - Phase reversal protection not operative
Fault 1d9
Phase Reversal Protection Lost - Compressor C: CMR - Phase reversal protection not operative
Fault 1dA
Phase Reversal Protection Lost - Compressor D: CMR - Phase reversal protection not operative
Fault 1db
Slaved Electronic expansion valve
Electronic Drive Circuit - Refrigerant Circuit 1: CMR - Electronic expansion valve electric drive defective
Fault 1dC
Slaved Electronic expansion valve
Electronic Drive Circuit - Refrigerant Circuit 2: CMR - Electronic expansion valve electric drive defective
Fault 1dd
High Oil Temperature - Compressor A: CMR - Oil temperature > 77°C
Fault 1dE
High Oil Temperature - Compressor B: CMR - Oil temperature > 77°C
Fault 1dF
High Oil Temperature - Compressor C: CMR - Oil temperature > 77°C
Fault 1E0
High Oil Temperature - Compressor D: CMR - Oil temperature > 77°C
Fault 1E1
Oil System Fault - Compressor A: CMR - Oil temperature < condenser saturated temperature
during more than 30 minutes
Fault 1E2
Oil System Fault - Compressor B: CMR - Oil temperature < condenser saturated temperature
during more than 30 minutes
Fault 1E3
Oil System Fault - Compressor C: CMR - Oil temperature < condenser saturated temperature
during more than 30 minutes
Fault 1E4
Oil System Fault - Compressor D: CMR - Oil temperature < condenser saturated temperature
during more than 30 minutes
Fault 1E5
Entering Oil Temperature Sensor - Compressor A: CMR - Defective sensor
24
Fault 1E6
Entering Oil Temperature Sensor - Compressor B: CMR - Defective sensor
Fault 1E7
Entering Oil Temperature Sensor - Compressor C: CMR - Defective sensor
Fault 1E8
Entering Oil Temperature Sensor - Compressor D: CMR - Defective sensor
Fault 2A1
Condenser Fan Variable Speed Drive Fault - Circuit 1: IFW - Defective fan speed controller after 5 attempts
Fault 2A2
Condenser Fan Variable Speed Drive Fault - Circuit 2: IFW - Defective fan speed controller after 5 attempts
Note:
MMR: Machine shutdown manual reset.
MAR: Machine shutdown automatic reset.
CMR: Circuit shutdown manual reset.
CAR: Circuit shutdown automatic reset.
IFW: Informational warning.
Communication failures
Fault 410
Loss of Local Display Panel Communication
Fault 412
Chiller Module to Option Module Communication Failure
Fault 413
Chiller Module to Electronic expansion valve Module Communication Failure
Fault 414
Chiller Module to Compressor A Module Communication Failure
Fault 415
Chiller Module to Compressor B Module Communication Failure
Fault 416
Chiller Module Compressor C Module Communication Failure
Fault 417
Chiller Module to Compressor D Module Communication Failure
Fault 418
Chiller Module to Slaved Electronic expansion valve Module Communication Failure
Fault 431
Electronic expansion valve Module to Chiller Module Communication Failure
Fault 434
Electronic expansion valve Module to Compressor A Module Communication Failure
Fault 435
Electronic expansion valve Module to Compressor B Module Communication Failure
Fault 436
Electronic expansion valve Module to Compressor C Module Communication Failure
Fault 437
Electronic expansion valve Module to Compressor D Module Communication Failure
Fault 441
Compressor A Module to Chiller Module Communication Failure
Fault 443
Compressor A Module to Electronic expansion valve Module Communication Failure
25
Fault 445
Compressor A Module to Compressor B Module Communication Failure
Fault 451
Compressor B Module to chiller Module Communication Failure
Fault 453
Compressor B Module to Electronic expansion valve Module Communication Failure
Fault 454
Compressor B Module to Compressor A Module Communication Failure
Fault 461
Compressor C Module to Chiller Module Communication Failure
Fault 463
Compressor C Module to Electronic expansion valve Module Communication Failure
Fault 467
Compressor C Module to Compressor D Module Communication Failure
Fault 471
Compressor D Module to Chiller Module Communication Failure
Fault 473
Compressor D Module to Electronic expansion valve Module Communication Failure
Fault 476
Compressor D Module to Compressor C Module Communication Failure
Fault 481
Slaved Electronic expansion valve Module to Chiller Module Communication Failure
Fault 483
Slaved Electronic expansion valve Module to Electronic expansion valve Module Communication Failure
Fault 484
Slaved Electronic expansion valve Module to Compressor A Module Communication Failure
Fault 485
Slaved Electronic expansion valve Module to Compressor B Module Communication Failure
Fault 486
Slaved Electronic expansion valve Module to Compressor C Module Communication Failure
Fault 487
Slaved Electronic expansion valve Module to Compressor D Module Communication Failure
Mode A00
Stopped
Mode A17
Service Pump down
Mode A70
Waiting, Restart Inhibit
Mode A72
Starting
Mode A74
Running
26
Mode A75
Running, Current Limit
Mode A76
Running, Condenser Limit
Mode A77
Running, Evaporator Limit
Mode A7E
Stopping
Mode A88
Reset
Mode A100
Stopped by Source
Mode A101
Ice Making Complete
Mode A118
Electronic expansion valve Test
Mode A174
Making Ice
Mode A175
Making Ice, Condenser Limit
Mode A177
Making Ice, Evaporator Limit
Mode A200
Low Ambient Temperature Lockout
Mode A234
Manufacturing Test
Stopped By Tracer
Stopped By Remote Display
Mode 16
Locked Out
Mode 17
Service Pumpdown
Mode 70
Restart Inhibited
Mode 72
Starting
Mode 74
Running
Mode 75
Run - Current Limit
Mode 76
Run - Condenser Limit
Mode 77
Run - Evaporator Limit
Mode 7E
Stopping
27
Maintenance contract
It is strongly recommended that you sign a possibility that serious damage will occur. Finally,
maintenance contract with your local Service Agency. regular maintenance helps ensure the maximum
This contract provides regular maintenance of your operating life of your equipment. Failure to follow
intallation by a specialist in our equipment. Regular these installation and maintenance instructions may
maintenance helps ensure that any malfunction is affect your warranty.
detected and corrected quickly and minimizes the
Training
The equipment described in this manual is the result of maintenance technicians a better knowledge of the
many years of research and continuous development. equipment they are using, or that is under their charge.
To assist you in obtaining the best use of it, and Emphasis is particularly given to the importance of
maintaining it in perfect operating condition over a periodic checks on the unit operating parameters as
long period of time, the manufacturer has available a well as on preventive maintenance, which can reduce
refrigeration and air conditioning service school. The the cost of owning the unit by helping avoid serious
principal aim of this is to give operators and and costly breakdown.
This publication is a general guide to install, use and properly maintain our products. The information
given may be different from the specification for a particular country or for a specific order. In this
event, please refer to your nearest office.
All rights reserved. No part of this publication may be reproduced or transmitted in any form or by
any means without the written authorization of the manufacturer.