MAN B&W Diesel A/S 1 (2)

INTERFACE BETWEEN MANB&W ALPHA LUB.SYSTEM AND VESSEL SYSTEMS

We have from MAN B&W supplied the alpha lubrication system which can be regarded as
one big block of different items.
This system has to interface with the ships governor/safety and alarm systems in order to
work. As MAN B&W do not know the specific governor system on the different vessels, we
require a specialist from the governor maker to be present during the retro-fit, in case the
safety system and/or alarm system is of different make than the governor system, a
specialist from the maker of these systems will be required as well.

This has to be arranged by owners.

The interface consists of the following items:

We will from our side supply the alarm system with 6 new alarms for which we will need
available channels as well as cable termination points.

We will from our side supply the safety system with one engine slow down signal for which
we need cable termination points.
From the safety system we require two separate engine stop signals.
From the safety system we require one signal for engine ahead/astern.

From the governor system we require one signal for cylinder lubrication in Load Change
Dependent mode.

The LCD signal is not absolutely vital as we can obtain the same feature internally in alpha
lubrication system. But it is much preferred that the signal is made available.

All signals are digital.

All these changes in governor system normally require the system to re-configured by
specialist.

Please see the enclosed Alpha lubricator interface specification which must be handed over
to governor/alarm and safety system specialist.

Best regards
MAN B&W Diesel A/S

D:\USERDATA\Alpha Lubricator\Instruction\Interface.doc 2004-06-01


Tom Ballegaard
MAN B&W Diesel A/S 2 (2)

Alpha lubricator - Interface specification.


Electrical interface between Alpha Lubricator Control Unit (ALCU) and existing systems.

All contact inputs to the ALCU must be potential free.

Power supply
Voltage Breaker Comment
Control system 24 V DC 2 separate16 A, Voltage to be constant up to 1.5 x IN.
(2 supplies) characteristic C Cable quadrate: 1.5 for 0 – 25 m
breakers supplied from 2.5 for 25 – 70 m
same UPS 4.0 for 70 – 150 m
Booster pump 3 x 380 / 2 separate Voltage according to pump station
station 440 V 10 A, characteristic C specification
(2 supplies) breakers

Interface to alarm system


Alarm text Type Input / output Comment
Alpha lub. Common NC Output from ALCU
Alarm
Alpha lub.MCU NC Output from ALCU
No delay required in alarm system.
Power fail
It is very important that there is no
Alphalub. BCU in NC Output from ALCU
OFF delay, whereas a small ON
Control
delay can be accepted, but no delay
Alpha lub.BCU NC Output from ALCU
is preferred
Power fail
Alpha lub. MCU Fail NC Output from ALCU
Alpha lub.BCU Fail NC Output from ALCU

Interface to safety system


Text Type Input / output Comment
BCU Stop NO Input to ALCU To be closed in stop
Ahead / Astern NO Input to ALCU To be closed in Astern
Slow Down from NO Output from ALCU Open in normal condition.
Alpha lub.
MCU Stop NO Input to ALCU To be closed in stop
BCU Stop and MCU Stop must be 2 separate isolated contacts.

Interface to governor system


Text Type Input / output Comment
LCD Input NO Input to ALCU Standard.
Telegraph pos. 4– Input to ALCU Only used if the LCD output cannot
20 Isolated and powered be supplied from the governor
mA from ALCU system

Interface to auxiliary blowers


Text Type Input / output Comment
Pre lubrication NO Input to ALCU To be activated at Aux. blower start