Visión General

Digital output sensors as well as actuators driven by digital signals are very popular in the industry. One can find a digital
output sensor for practically any type of variable (temperature, flow, pressure, speed and more) with their digital output
signal represented in multiple formats. In this document we first classify Digital Output Sensors based on their output
signal and circuit interface, and then point out the critical parameters that should be taken into account when selecting a
Digital I/O Module1 for your application.

Contenido

1. Introduction to Digital Output Sensors


2. Classification of Digital Output Sensor Based on:
3. Characteristic of the Signal Driving the Sensor Output
4. Sinking vs. Sourcing Outputs
5. 2-Wire and 3-Wire Sensors
6. Electronic Component Used to Implement the Sensor’s Output
7. Selecting the Right Industrial Digital I/O Module for Your Digital Output Sensors
8. Example of Digital Output Sensors

Introduction to Digital Output Sensors

Digital Output Sensor is a sensor that will produce only two values in its output, either On or Off, as opposed to an
Analog Output Sensor which produces a continuously varying output value over its entire range. The simplest example
of a digital sensor is the touch switch. A typical touch switch is an open circuit with infinite resistance when it is not
pressed and a short circuit with zero resistance when it is pressed.

Whenever interfacing the digital output sensor it is important to take into account some key factors that will determine
the compatibility of the sensor with the data acquisition device. Throughout this document we will present these key
factors and provide an easy way to select the appropriated data acquisition device for your application.
Hola Alvaro Antonio Gaitán (Usuario equivocado.)

Classification of Digital Output Sensor Based on:

Digital Output Sensors can be classified based on the following parameters:

1. Characteristic of the Signal Driving the Sensor’s Output

2. Sinking vs. Sourcing Outputs

3. 2-Wire and 3-Wire Sensors

4. Electronic Component Used to Implement the Sensor’s Output

Characteristic of the Signal Driving the Sensor Output

Technological development has brought a variety of complex digital output sensors to the market. Nowadays, you can
find sensors that produce trains of transitions between the On and Off state, with these types of sensors the frequency
characteristic or even the shape of the pulse trains convey the sensor’s measurement, making it possible to implement
continuous measurement.

Figure 1 shows a classification of digital output sensors based on signal characteristics driving its output. As can be
seen in the chart, 45 % of the digital output sensors are based on the on-off state of the digital line, 35 % of the sensors
are based on the frequency of the signal and 12 % as based on the duty cycle of the output frequency 2.

http://zone.ni.com/devzone/cda/tut/p/id/3090 28/01/2011
Choosing the Right Industrial Digital I/O Module for Your Digital Output Sensor - De... Page 2 of 7

[+] Ampliar Imagen

Figure 1 – Digital Output Sensors – Characteristic Conveying Measurement2

The signal characteristic conveying the sensor’s measurement is the first parameter to be considered when selecting an
industrial digital I/O module. This is important to decide whether you need counters on your digital I/O module.

Browse industrial static DIO devices

Browse counter/timer devices

Sinking vs. Sourcing Outputs

Sinking and Sourcing are terms used to define the control of direct current flow in a load.

Sinking Device: provides a path for the current to ground and is not responsible for powering the device. Terms used
to describe sinking devices include NPN, Open Collector, Normally High, and IEC Negative Logic.
Sourcing Device: A sourcing device provides the power or a positive potential. Sourcing devices 'push' the current
through the load. Terms used to describe sourcing devices include PNP, Open Emitter, Normally Low, and IEC Positive
Logic.

The concept of Sourcing and Sinking is independent of the component (ex.: transistor, mechanical relay and etc...) that
implements the operation. This concept applies to any DC circuitry; the component that is implementing the circuitry may
vary.

[+] Ampliar Imagen


Figure 2 - Sinking Output Sensors.

http://zone.ni.com/devzone/cda/tut/p/id/3090 28/01/2011
Choosing the Right Industrial Digital I/O Module for Your Digital Output Sensor - De... Page 3 of 7

[+] Ampliar Imagen


Figure 3 - Sourcing Output Sensors.
2-Wire and 3-Wire Sensors

The third type classification is important in order to define the relationship between current and voltage in the sensor’s
On state and Off state. A sensor can be classified as a 2-wire or 3-wire device as follows:

2-Wire Sensors: They are connected in series with the device that is acquiring the data.

Figure 4 – 2 Wire Sensors

When the sensor is not activated, it must draw a minimum operating current normally referred to as off-state leakage
current, which in some cases are also called by the sensors manufacturers as residual current. This current is
necessary in order to keep the sensor electronics working. The residual current is not a problem if the sensor is
connected directly to another load other then the data acquisition device, for example in industrial environment is not
unusual to have these 2-wire sensors directly connected to motors and similar devices, which have a low impedance.

Residual current is a problem for the system if the sensor requires a residual current higher then what the digital I/O
module has been designed to sustain. In this case the digital I/O module might incorrectly detect an On state because
the current being drawn is higher then it expects to provide. Most 2-wire sensors in the industry have an off-state
leakage current or residual current no higher then 1.7 mA.

Similar to the Off state, there is also a minimum current required to sustain the On state of a sensor, called the
minimum holding current. Typically this current ranges from 3 mA to 20 mA. The sensor will not operate correctly if the
digital I/O module cannot sink or source this current.

3-wire Sensors: 3-wire sensors derive their power from a excitation terminal and not directly through the digital output
line, they are also called by some manufacturers as line-powered sensors.

http://zone.ni.com/devzone/cda/tut/p/id/3090 28/01/2011
Choosing the Right Industrial Digital I/O Module for Your Digital Output Sensor - De... Page 4 of 7

Figure 5 – 3-wire Sensors

The operating current these devices pull from the digital I/O module is called burden current and it is typically in the
neighborhood of 20 mA. Important to notice this current is provided by the excitation terminal.

Electronic Component Used to Implement the Sensor’s Output

There are three electronic components that typically drive the output of a signal output sensor:

Mechanical Relay;
Transistor;
Bilateral FET Devices:

Mechanical Relay: A Mechanical relay is an electromechanical device that closes contacts to complete a circuit or
opens contacts to interrupt a circuit. It is a device that can handle current load at high voltages.

Since they are relatively slow devices when compared against solid state relays, they are normally used by sensors
where the state of the line is the characteristic of the signal driving output. These devices are subject to contact wear
and resistance build up. Their contact life depends on the load current as well as the frequency of operation. They can
sometimes produce erratic results due to contact bounce when connected to counters and digital I/O modules.

Transistor: is a solid-state device designed to control DC current. Transistors are most commonly found in low DC
powered sensors as the output switch. There are two types of transistors - NPN and PNP.

Figure 6 shows a NPN (Current Sink) Open Collector Transistor

Figure 6 – Sensor NPN Output.

Bilateral FET Device: Many photosensors in the market have an output implemented in an architecture called bilateral
FET output which can be seen in Figure 7. This architecture has many advantages but the most important one is the fact
that interfaces directly to TTL and CMOS circuits, additionally they show:

Low off-state leakage current;


Fast response time;

FET stands for Field Effect Transistor and is supposed to become the most popular output for digital output sensors
because of its operating characteristics, being near to the ideal model.

http://zone.ni.com/devzone/cda/tut/p/id/3090 28/01/2011
Choosing the Right Industrial Digital I/O Module for Your Digital Output Sensor - De... Page 5 of 7

Figure 7 - Sensor with Bilateral FET Device Output


Selecting the Right Industrial Digital I/O Module for Your Digital Output Sensors

In order to select the Digital I/O module one should answer the three following questions:

What is the characteristic of the digital signal that conveys the sensosurement? This has been discussed in the
section on "Characteristic of the Signal Driving the Sensor’s Output" in this document.

Based on this answer make reference to Table-A to check the group of Digital I/O modules that would be appropriate for
your application.

Is the sensor output a sinking or sourcing output?

Table-A again provide a classification of the NI boards based on sinking and sourcing capabilities, so if your sensor has
a sinking output you want to select a board with a sourcing input and vice-versa.

What is the component that implements the output of my device?

At this point might need to consider the off-state leakage current as well as the minimum holding current for On
state.

Compare specs of the sensors with the specs of the data acquisition devices in Table-B in order to select the most
appropriate device for your sensor. Besides the voltage levels, one should still observe the two important following
conditions which are sometimes overlooked:

1. Off-State leakage current (sensor) < Maximum Input Current at Low State (Board)
2. Minimum holding current (sensor) < Maximum Input Current at High State (Board)

Timed-Based
Sensors Digital I/O Module
NI Board On-Off (State) Type of Isolation # Channels
(Frequency, Duty- Input Type
Cycle, etc.)
NI 6601 — √ Sinking — 4 CTR
NI 6602/6608 — √ Sinking — 8 CTR
NI 6624 — √ Sinking Ch-Ch 8 CTR
NI 6501 √ √* Sinking/Sourcing — 24 DIO 1 CTR
NI 6509 √ — Sinking/Sourcing — 96 DIO
NI 6514 √ — Sourcing Bank 32 DI 32 DO
NI 6515 √ — Sinking Bank 32 DI 32 DO
NI 6518 √ — Sourcing Bank 16 DI 16 DO
NI 6519 √ — Sinking Bank 16 DI 16 DO
NI 6520/6521 √ — Sinking/Sourcing Ch-Ch 8 DI 8 DO
NI 6525 √ √* Sinking/Sourcing Ch-Ch 8 DI 8 DO 1 CTR
NI 6528 √ — Sinking/Sourcing Ch-Ch 24 DI 24 DO

Table - A
(* The USB-6501 and USB-6525 have one event counter)

Voltage Input Current Input


Maximum
Input Logic Low Voltage Input Logic High Voltage Max Input
NI Board Max Input Switching
(VIL) (HIL) Current
Current (low) Capacity
Min Max Min Max (high)
Supply +0.3
NI 6601 -0.3 VDC 0.8 VDC 2 VDC -10 µA 200 µA 4 mA
VDC
Supply +0.3
NI 6602/6608 -0.3 VDC 0.8 VDC 2 VDC -10 µA 200 µA 4 mA
VDC
NI 6624 — 0.8 VDC 3.2 VDC 48 VDC 0.1 mA 10 mA 200 mA
NI 6501 -0.3 VDC 0.8 VDC 2 VDC 5.8 VDC — — ±8 mA
NI 6509 0 VDC 0.8 VDC 2 VDC VCC -91.0 µA 91.0 µA ±24 mA
NI 6514 0 VDC ±4 VDC ±11 VDC ±30 VDC 4.5 mA/line 12.5 mA/line 350 mA
NI 6515 0 VDC ±4 VDC ±11 VDC ±30 VDC 4.5 mA/line 12.5 mA/line 500 mA
NI 6518 0 VDC ±4 VDC ±11 VDC ±30 VDC 4.5 mA/line 12.5 mA/line 350 mA
NI 6519 0 VDC ±4 VDC ±11 VDC ±30 VDC 4.5 mA/line 12.5 mA/line 500 mA

http://zone.ni.com/devzone/cda/tut/p/id/3090 28/01/2011
Choosing the Right Industrial Digital I/O Module for Your Digital Output Sensor - De... Page 6 of 7

4.5 12.5
NI 6520/6521 0 VDC ±4 VDC ±11 VDC ±30 VDC 2A
mA/channel mA/channel
3.0 3.0
NI 6525 -60 VDC 1 VDC 3.2 VDC 60 VDC 500 mA
mA/channel mA/channel
NI 6528 -60 VDC 1 VDC 3.2 VDC 60 VDC 1.5 mA 2 mA 150 mA

Table - B

Example of Digital Output Sensors

Type of Measurement: Flow Measurement


Manufacturer: Gems Sensors
Digital Output type: Frequency

[+] Ampliar Imagen

Type of Measurement: Acceleration (ADXL202, ±2 g Dual Axis Accelerometer)


Manufacturer: Analog Devices
Digital Output Type: Duty-Cycle (TTL, CMOS compatible)

Type of Measurement: Position Switch (Mechanical Relay)


Manufacturer: Schmersal
Digital Output Type: ON-OFF output.

http://zone.ni.com/devzone/cda/tut/p/id/3090 28/01/2011
Choosing the Right Industrial Digital I/O Module for Your Digital Output Sensor - De... Page 7 of 7

Other Manufacturers of Digital Output Sensors include

· Omega
· Omron
· Encoder Products Co.
· US. Sensors
· Sensotec
· Watlow
· PCB Piezotronics
· Weed Instrument
· Measurement Specialities
· Celesco
· Endevco
· Macro Sensors
· Transducer Techniques Inc.

1
Throughout this document 'Digital I/O Module' is used to describe the data acquisition device that is connected to the
Digital Output Sensor.

2
Kirianaki, Yurish, Shpak, Deynega. Data Acquisition and Signal Processing for Smart Sensors, 2002 [ISBN 0-470-
84317-9].
Related Links:
Buy Digital I/O Modules for Your Sensor
Data Acquisition Hardware Selection

Comentarios del Lector | Enviar un comentario »

Legal
Este tutorial (este "tutorial") fue desarrollado por National Instruments (“NI“). Aunque el soporte técnico para este
tutorial sea proporcionado por National instruments, el contenido de este tutorial puede no estar completamente
verificado y probado y NI no garantiza su calidad, ni que NI continuará proporcionando soporte a este contenido en
cada nueva revisión de productos y controladores relacionados. ESTE TUTORIAL ES PROPORCIONADO "COMO ES"
SIN GARANTÍA DE NINGUN TIPO Y SUJETO A CIERTAS RESTRICCIONES QUE SE EXPONEN EN LOS
TÉRMINOS DE USO EN NI.COM (http://ni.com/legal/termsofuse/unitedstates/us/).

Mi Perfil | RSS | Privacidad | Aviso Legal | Comuníquese con NI © 2011 National Instruments Corporation. All rights reserved. | Enviar esta página