Documente Academic
Documente Profesional
Documente Cultură
1,January 1992
INSULATION THERMAL LIFE CONSIDERATIONS
FOR TRANSFORMER LOADING GUIDES
W. J. McNutt, Fellow, IEEE
Berkshire Transformer Consultants, Inc.
Pittsfield. MA
0885-8977/91/$3.0001992
IEEE
393
Pyrolysis (Heat) (1)
Heat in the extreme will result in char- A and B are empirical constants, and T is
ring of the fibers, but at lesser levels i t temperature in degrees Kelvin. This form of
contributes to the breakdown of individual relationship is frequently referred to as an
monomers in the cellulose chain. A solid Arrhenius reaction rate equation. It indi-
residue is formed and gases are liberated, cates that the perunit change in a property
namely water vapor, carbon monoxide, carbon is equal to the rate constant multiplied by
dioxide, and hydrogen. Again DP is reduced. the time interval over which the change takes
place. Dakin demonstrated that his own aging
There is an obvious consequence of this data and other published aging data of that
discussion. Since the agents which accel- time, including Montsinger's data, would f i t
erate cellulose degradation have been iden- this relationship.
tified, their levels should be minimized in
operating transformers to extend useful life. Montsinger resisted Dakin's proposal, but
That is the purpose of modern oil preserva- the general technical community in the U.S.
tion systems which seek to prevent entry of accepted i t , and continuing work within AIEE
oxygen and water. This is accomplished by committees referenced i t and applied it. In
sealing the tank with an inert gas blanket a 1953 paper (13). Sumner et al. showed that
over the oil to accomodate oil expansion or the aging rate curves for different residual
by utilizing a membrane in a conservator oil strength end points had the same slope. Much
expansion tank. Heat is the remaining accel- later, Head et a1.(14) found in their inves-
erating agent which must be left to the tigations of oil-immersed cable paper that
control of operating personnel. the rate slopes (the B constant) were essen-
tially the same not only for the degradation
INSULATION AGING RATE of the various mechanical characteristics
(tensile strength, burst strength, elongation
For at least 75 years i t has been recog- at rupture), but also for change in degree of
nized that thermal aging of cellulose trans- polymerization and gas evolution. Other
former insulation deteriorates its mechanical modern investigators (16.17) have found sim-
properties. In a 1930 paper (9), V. M. Mont- ilarly close agreement between rates of gas
singer published aging data taken in 1916 on evolution and changes in mechanical proper-
yellow varnished cambric, the insulation used ties and DP.
in transformers in that era. The data showed
a gradual reduction of tensile strength over Since there appears to be general agree-
time at temperature, with an accelerating ment that Dakin's (or Arrhenius's) chemical
rate of reduction as temperature increased. reaction rate equation is appropriate for
F. M. Clark published similar data for linen measuring thermal degradation of transformer
paper in 1935 (10) which showed the same insulation, whether by change in mechanical
gradual loss of tensile strength, and also properties, change in DP, or gas evolution,
showed that other mechanical properties i t is reasonable to search for a single rate
(stretch, burst, and tear) deteriorated in a slope which might be applicable for all forms
like fashion, but tensile strength was most
sensitive to aging effects if a 50% retention
o f characteristic was used as an end point
criterion. Thermal aging test results for
modern transformer insulation papers yield
similar patterns of strength reduction with
time at temperature. (See Figure 2.)
Montsinger (9) made an observation about
the aging rate of cellulose versus tempera-
ture which has found wide favor. He proposed
a simple rule-of-thumb that the rate of de-
terioration of mechanical properties doubles
for each 5-10" C increase in temperature. He
recognized that this doubling factor was not
constant at all aging temperatures, but
people tend to remember i t as a constant
factor. In the vicinity of 100-110" C , he
found the aging rate to double for each 6" C
increase in temperature, but at 120" C and
higher a temperature increase of 8" C was
required to double the aging rate. The
simple 6" C doubling rule is still used in
IEC loading guides today.(4)
A more significant advance in defining
aging rates was made by Dakin in 1948.(12)
He observed that the changes taking place in
cellulose insulation as i t thermally ages are
0 10 20 30 40 50 €4 70 80
the result of chemical react ions, and,
Days at 160 "C
therefor, the rate of change of any measured
physical property might be expressed in the
form of a reaction rate constant, KO. Figure 2: Tensile Strength Reduction as a
a Result of Aging at 160°C.
393
E
has been examined by several investigators,
including Fabre (5) and Lampe (18). The
usual experiment is to compare aging rates
for a sealed system and for a system with
free access to oxygen. Through such experi-
ments Fabre found an aging acceleration fac-
tor of 2.5, while Lampe found a factor of 1 0 .
In any case, i t is clear that the presence of
o io m 30 40 yl 60 70 BO 9 0 1 0 0 oxygen has a very negative effect. Again,
Days at 160 "C these facts give utilities good incentive to
emplby an oil preservation system which
Figure 3 : Degree of Polymerization Reduction maintains a low oxygen content in the opera-
as a Result of Aging at 160OC. ting transformer.
which the transformer insulation integrity Some experience with in-service aging of
can be prejudiced by normally experienced transformer insulation is available in the
levels of mechanical and dielectric stresses. published literature in terms of residual DP
Since the critical physical condition can not after many Years of operation. A summary of
be precisely defined in terms of a specific that information is given in Table 11. It is
DP level at present, i t could prove useful to my understanding that all of the insulation
Zstablish a profile of DP versus age in the materials were non-thermally upgraded and in
general operating transformer population by no case was the degraded insulation a cause
testing insulation samples from transformers of failure.
whose service life is terminated for any
reason. Some data of this type is already Table I1
available in the published literature, as Degree of Polymerization Data
will be discussed later. From Service-Aaed Transformers
When the loading guide insulation life In Service
measurement is applied to estimate the effect MVA Service Years Dp
of certain loading conditions on the func-
tional life of operating transformers, i t 3.3 1922 31 189
must be remembered that the end point life 6.1 1923 36 150
was established with controlled levels of 6 1925 34 218
moisture and oxygen in the insulation system 6 1928 31 179
under test. Those levels may not be main- 6 1928 31 192
*tained in operating transformers throughout 0.9 1929 30 116
their lifetime. For that reason, a relative 1.5 1932 21 139
life consumption calculation would be more 8 1935 24 300
appropriate than an absolute life consumption 38 1935 24 110
calculation, as will be proposed later. At 64 1945 14 877
the same time, i t is important to be aware of 15 1938 23 125
the effect of the two controllable variables, 16 -- 14 190
water and oxygen, on thermal deterioration of 3.8 -- 10 460
cellulose. 3 1942 41 53
2 1958 31 105
Fabre and Pichon ( 5 ) stated a very sim- 2 1949 40 iao
ple rule for the effect of water, namely that 5 1964 25 304
the rate of thermal deterioration of paper is
directly proportional to its water content. Note: Where information on date of samp1 e
Data given by Shroff and Stannet (6) support measurement was not available i t was assumed
that rule. To the extent that the moisture that the sample was taken the year before the
content of the insulation in the hottest spot paper was written.
area of an operating transformer differs
from the controlled moisture condition of the Although the type of oil preservation was
insulation in a sealed aging cell, typically usually not identified for most of the above
0,2%-0.3% water by weight, the aging rate transformers, their age and the fact that
396
they are European and South American would 1. New "Transformer Insulation Life" Curve
imply that the oil preservation was open
conservator. It is known thst the last four Introduce a "Transformer Insulation Life"
units had open conservators and high moisture curve which relates per unit life to conduc-
contents, in the order of 5%. As a conse- tor hot spot temperature as shown in Figure
quence, all of the DP values are low compared 4. This curve has the form:
to what might be expected from relatively
oxygen free transformers in the U.S. Per U n i t L i f e = 9.80 >: 10-18 e15clCQ/T (2)
I can give two examples of as yet unpub- The reference life of 1.0 per unit occurs for
lished U . S . data, both of which came from operation at llO°C, the hottest-spot basis of
transformers with inert gas cushion oil rating temperature for a 65°C average winding
preservation. The first transformer in rise insulation system. 1 . 0 per unit life
service for 6 1 years on the New England for a 55°C average winding rise insulation
Electric system had a residual DP of 1 2 4 . system would occur for operation at a refer-
Inner wraps of paper close to the conductor ence temperature of 95°C. Aging is acceler-
were brittle, but were held in place by a ated at temperatures higher than the refer-
varnish dip which impregnated the outer wraps ence and is decelerated at temperatures lower
of paper. Insulation from the second trans- than the reference in accordance with equa-
former had a residual DP of 3 1 4 after 55 tion ( 2 ) . Since the same cellulose insula-
years of service on the Rochester Gas & tion materials are applied in power and dis-
Electric system. At this level of DP the tribution transformers, the same relative
paper was not extremely brittle and still life equation should be used.
appeared usable. In my opinion, the better
DP levels versus age for these two trans- This approach is similar to that taken in
formers are the result of lower levels of the IEC loading guide ( 4 ) . It isolates tem-
oxygen and moisture within the insulation perature as the principal variable which
s yst em. influences thermal life and eliminates the
effects of other variables affecting absolute
In a separate effort to evaluate func- life which may vary from one transformer to
tional life of transformer insulation, EPRI another or one application to another. Those
sponsored programs by General Electric and secondary variables, including moisture con-
Westinghouse in the 1 9 7 8 - 1 9 8 2 time period, tent of the cellulose, oxygen content of the
the results of which can be found in refer- oil, life end-point criterion, etc., would
ences 2 1 , 2 2 , and 2 3 . Both programs involved influence the choice of a projected value of
thermal aging of model disk windings while absolute life.
periodically subjecting them to short-circuit
and dielectric end point tests. In the 2. Life ConsumDtion Calculation
General Electric program ( 2 2 , 2 3 1 models were
cyclically aged at 180" C for 6 2 0 hours The procedure for calculating life con-
without failure. This represents 6 . 2 times sumption during operation under varying load
the reference ANSI life. After this degree conditions should be described in a loading
of aging the models were dielectrically guide modified as described above. Such a
tested to breakdown and it was found that the calculation can be made by accumlat ing rela-
mean breakdown strength was only reduced by tive life consumed over a 2 4 hour period
1 0 % compared to models with new insulation. an aging acceleration factor, "A",
The insulation wraps next to the conductor
I
were noticeably darkened and embrittled, but 10
the less affected outer wraps provided mech-
anical support to keep them intact.
Winding models in the Westinghouse pro-
gram ( 2 1 ) were aged at 1 8 0 " C and 2 0 0 " C.
Four 1 8 0 " C models survived end point tests 1.o
at 8 6 4 hours ( 8 . 6 4 times the reference ANSI
life), but failed tests after 1 7 2 8 hours.
Two models aged at 2 0 0 " C survived end point
tests after 3 4 2 hours and one survived for
2 6 9 hours. These times represent 15.3 and 0.1
1 2 . 0 times the reference ANSI life. Paper at
the top of the winding was very dark in color
and had been mechanically ruptured by short-
circuit stresses in some cases. The conclu-
sion from the two programs was that 5 0 % ten-
sile strength is a very conservative criter- 0.01
ion for end of functional life.
PROPOSALS FOR LOADING GUIDE REVISION
180 :
The material presented to this point
reveals some opportunities for improving the
realism of insulation life treatment in the
existing loading guides, leading me to make Hottest Spot Temperature - "C
the following proposals:
Figure 4 : "Transformer Insulation Life" VS
Temperature.
391
derived from equation (2). This factor can Table I11
be written in terms of a natural logarithm: "Insulation Life" __
__ Definitions
In A = 15,000/383 - 15,00O/T (3) Insul. Oxygen Life
Bas i s
-~ Water* Leve 1 Hours
"A" has a value greater than 1.0 for any time
increment when T is greater than 383°K 50% Tensile 0.5% Low 65,020
(110°C) and has a value less than 1.0 for any 1.0% Low 32,510
time increment when T is less than 383°K. 2.0% Low 16,255
Thus, for normal loading at nameplate rating 0.5% High 26,000
with a 0.5 load factor and a 20°C ambient 1.0% High 13,000
temperature, the hottest-spot temperature is 2.0% High 6,500
always less than 110°C and life consumed per 20% Tensile 0.5% Low 152,000
day may be only 30%-40% of a reference day's 1.0% Low 76,000
life. This corresponds to .011%-.015% loss 2.0% Low 38,000
of life per day by the present ANSI/IEEE 0.5% High 60,800
C57.92 life definition. On the other hand, 1.0% High 30,400
for a short-time emergency, with operation up 2.0% High 15,200
to 180°C conductor hottest-spot temperature 200 D.P. 0.5% Low 158,000
for a fraction of an hour, the aging accel- 1.0% Low 79,000
eration would be very great and life consumed 2.0% Low 39,500
in one day might be 8 reference day's life. 0.5% High 63,200
For rare occurrences, such an accelerated 1.0% High 31,600
life consumption could be found acceptable. 2.0% High 15,800
7
399
DISCUSSION ing us how to better assess the condition of the cellulose insulation system
when actual sampling of the paper is not possible. Mr. McNutt indicated
that transformer aging is not a uniform process. Changes in equipment and
MALCOLM V. THADEN system conditions, along with variations in thermal, moisture, and oxygen
Potomac Electric Power Company gradients within a transformer will all cause changes in the rate of insula-
1900 Pennsylvania Ave. N. w. tion aging. Doble is now involved in a study of the DP of in-service trans-
Washington, D. C. 20068
formers that includes collecting as much historical data as can be obtained.
Our instructions to those who might supply us with samples for testing are
Percent loss of life ( M F ) per day has to obtain paper from the top, middle, and bottom of both the high- and
been a useful parameter in establishing one low- voltage windings, as well as from one of the leads for each winding
of the limits to the calculations for when they are of the paper-wrapped type. There are at least two important
determining loading beyond nameplate. The reasons for taking samples from the winding bushing leads. The first is to
concept, however, of percent M F per day can see if some correlation exists between the data obtained for the leads and
be confusing to the typical user, since one that obtained for the windings of the same transformer. The second reason
must understand the meaning of a day as used is that it is easier (and less damaging) to obtain both outer wrap and inner
in this context, and the significance of the wrap samples of the leads. This allows for comparison of the paper most
percent value is not as meaningful as an exposed to the oil (outer wrap) and therefore higher oxygen and water
absolute or per unit value. content, with that which is subject to greater thermal stress (inner wrap).
The only test of this nature performed to date revealed that the outer wrap
For example, to understand the impact of
a MF/day value, such as .0369%, one must was the most aged with a DP value of 597 versus 696 for the inner wrap.
recognize that under the current loading Such differences may give us clues to the relative importance of the factors
guides a 65OC transformer continuously influencing the aging process. DP Measurements were made in accordance
operated at a llO°C hot spot has a calculated with IEC Publication 450.
life of 65,013 hours or 2709 days. .0369% of
2709 days is one day of this life. As
proposed by this paper, this day of life An example of differences between transformers can be seen by the DP
would be one per unit. Utility engineers are distribution given in Figure 1 which shows considerable variation in the
comfortable with per unit systems and paper aging.
quantifying life in terms of this reference
day should be readily understood. Cumulating
loss of life should also be simplified by Sample Location Transf. A Transf. B
summing the multiples of the per unit day
over time. Low-Voltage Winding Top 206: 318: 232 1015
Middle 975
per unit system would also provide the
A
Bottom 895
user with the flexibility to make changes in
the definition of absolute insulation life,
which may change as industry data is gathered Interwinding Insulation 875
and analyzed. High-Voltage Winding Top 910: 924 9 60
Middle 1025
Adoption of a per unit system and a new Bottom 1040
life curve that more accurately reflects the
observed life of power transformers should be Lead (Low Voltage) 635
a significant step toward the goal of being Lead (High Voltage) 854
able to evaluate remaining transformer life.
FIGURE 1
M a n u s c r i p t r e c e i v e d August 26, 1991. Average Degree Of Polymerization Of Paper Samples
It should be noted that the types of paper for the high- and low-voltage
winding in Transformer A were different. Upon further investigation into
S. H. Osborn, Jr. and P. J. Griffin (Doble Engineering Co.Watertown, the history of Transformer A the following was revealed:
MA). The information and ideas presented in Mr. McNutt’s extremely 1) The transformer was manufactured in 1951 and failed in 1978.
timely paper allow a better understanding and appreciation of that nebu-
lous phrase that we casually use - transformer insulation life. While the 2) The high-voltage winding and interwinding insulation was re-
impetus for this paper was directly related to the present Transformer placed in 1979.
Loading Guides promulgated by ANSI/IEEE, Mr. McNutt’s tutorial mate-
rial on the origin of the present formulas and rules relating to transformer 3) The low-voltage winding recently failed.
insulation aging rates is must reading for everyone concerned with deter-
mining the remaining life of aging transformers. The guidelines established Although there is no information as to insulation tests performed on the
for estimating insulation life affect manufacturers’ designs, utility loading low voltage winding in the late 1970’s when the HV winding was replaced,
practices, and expectations for replacement. Accurate estimation of insu- present data and operating history suggests that both windings should have
lation integrity may affect practical considerations, such as whether an old- been replaced in 1979. Further, if only the lead samples were used to as-
er transformer can be moved while retaining its electrical and mechanical sess the condition of the overall insulation in Transformer A or B, the
properties in a reliable condition. evaluation would be misleading. Transformer B was a 1982 RTE unit which
also failed in service in the past year. Clearly the more information that can
be obtained about the transformer history, the better the analysis and un-
In his paper, the author presents some data on the degree of polymeriza- derstanding of aging of the cellulose insulation.
tion (DP) of paper samples from service-aged transformers from different
sources. The results of these DP tests emphasize that besides thermal In just the last few months there has been considerably more interest in
stress, two other critical factors in reducing transformer insulation life are performing the DP tests on in-service and failed transformers. Samples
moisture and oxygen. When there is an excess of either (or both) the DP from over ten transformers have been tested and many more are expected
results will be reduced. Correlating DP with thermal stress and reliable this year. It is hoped that this experience will aid in our understanding of
measurements of water and oxygen content, could prove helpful in teach- transformer insulation life, and provide important empirical information
400
for the deliberations currently under way on revisions to the transformer Table A
loading guides. Camparlaon Between Service and
Calculated Life of Tranoformere
Manuscript received August 2 3 , 1991.
UNlT DP SERVICE WATER CALCULATED LIFE IN
NQ * YEARS CONT. YEARS IF OPERATING
OF AT THE FOLLOWING
Since I have been personally involved in 4 245 14 4 51.0 26.2 13.7 7.3
obtaining paper samples from power 5 12.7
transformers and voltage regulators for the 282 14 2 87.6 45.0 23.5
past five years to assess their solid
insulation aging, I had the opportunity to 6 304 23 2 81.1 41.7 21.8 11.7
analyze how the criteria proposed by Mr. 7 35.3 10.1 9.5 5.1
WcNutt correlated with such an information. 33 8 41 4
The transformers on CPFL’s system have 8 444 9 3 30.5 15.7 8.2 4.4
a 55% average winding rise insulation 9.4
system and are free-breathing. For this 9 448 9 5 18.3 4.9 2.6
type of insulation system, equation (2)
becomes : 10 500 22 2 39.2 20.2 10.5 5.7
x lo-.*’
Per Unit Life = 1.985 e*s*e*/l (1)
* DP of paper samples collected from the
PU Life = 1.00 for T = 368 K (95%) w 1 nd i ngs.