Documente Academic
Documente Profesional
Documente Cultură
Gas Turbine MB
Issue resp.
prepared by/
Rev. Date Modifications prepared by reviewed by released by
reviewed by
(pages)
PG E8C3 PG E8C3
a 2006-05-12 preliminary 1)
H. Wolf / C. Koch P. Koch
red marked
"as built"
finalized
This document is subject to the restrictions set forth on the first or title page.
Gas Turbine Measuring and Supervisory Equipment
Description Gas Turbine Instrumentation
Refer also to: bearing; alarms are annunciated and/or gas turbine
protection functions triggered if certain limits are violated.
Setting of Temperature Limits Signals from these transmitters are used by a
at the Turbine Outlet 3.1-0118 processor module to calculate the effective vibration
List of Control Settings 3.1-2020 velocity, which is then output as current signals that
P+I Diagram, Gas Turbine 3.1-2600 undergo further processing in the I&C system. Casing
List of Measuring Instruments 3.1-2620 vibration is registered using two equivalent channels. If at
Equipment List 3.1-2640 least one of the two channels indicates that the limit
List of Electrical Loads 3.1-2630 Y.LAGER.M is exceeded, the alarm “… BEARING
Blowoff System 3.1-4411 VIBRATION WARNING” is annunciated. If any channel
indicates that the higher limit Y.LAGER.S is violated, the
Settings, limits, and measuring ranges of the devices gas turbine trips and is shut down and the alarm
referred to here are given in the List of Measuring “TRIGGERING BY … BEARING VIBRATION” is
Instruments, Equipment List, and List of Control Settings annunciated.
(SREL).
Siemens AG 3.1-2601-0585/1
Power Generation MBA/MBD 0705E
Gas Turbine Measuring and Supervisory Equipment
Description Gas Turbine Instrumentation
MBD12CT105A/B/C (turbine end) each serve as backups Compressor Outlet Pressure and
and their leads end on a sub-distribution board. Temperature
Triple-element thermocouples are installed at the
Compressor outlet pressure (MBA12CP101, MBA12-
journal bearings (MBD12CT101A/B/C, MBD12CT106A/B/C
CP102) is required for monitoring the relative combustion
at the compressor end and MBD11CT101A/B/C and
chamber pressure and for the purge water system.
MBD11CT102A/B/C at the turbine end).
Compressor outlet temperature (MBA12CT101,
The alarm “BEARING TEMPERATURE HIGH” is
MBA12CT102) has an influence on burner temperature
annunciated if one-of-three logic indicates that bearing
monitoring.
temperature exceeds T.LAGER.M at the compressor
bearing or turbine bearing. The compressor outlet pressure and temperature
readings are forwarded to the operation and monitoring
If 2-of-3 logic indicates that the temperature of the
system for display purposes.
compressor or turbine bearing exceeds the higher limit
T.LAGER.S, trip is triggered and the GT shut down.
Turbine Cooling Air Pressure
Air Temperature Upstream of Differential pressure indicator MBA21CP501 measures
Compressor the drop in pressure between the compressor outlet and
the cooling air chamber at turbine vane row 1. A change in
An average compressor inlet temperature is required
this pressure drop with otherwise identical operating
content is not permitted without express written authority.
measurements are also used to calculate the compressor chamber and by MBA22CT106 to MBA22CT108 for the
mass flow. right combustion chamber.
One element of each thermocouple is used for
Pressure Upstream of Compressor temperature control, the other for protection functions and
display.
Pressure transducer MBA11CP101 measures the
The turbine exhaust temperature is used in conjunction
subatmospheric pressure in the compressor intake duct
with the compressor inlet temperature and speed to
and forwards this information to the operation and
calculate the corrected outlet temperature TOTC. Because
monitoring system and other systems.
the temperature in the exhaust diffuser is not constant
around the circumference, limits are defined for each
Compressor Surge Detection thermocouple individually. Further details on this are given
in document 3.1-0118, Setting of Temperature Limits at the
Data acquisition for compressor surge detection and Turbine Outlet”.
compressor surge protection is performed by the triple-
redundant differential pressure switches MBA11CP001, The pretrip alarm “TURBINE OUTLET TEMPERATURE
MBA11CP002, and MBA11CP003. Compressor surge 1-3 (or 4-6) WARNING” is annunciated if one of the
protection is enabled above the limit S.TURB.15. following situations occurs in a given group of temperature
measurements:
Gas turbine trip is triggered if the readings of two of
a) No thermocouple is defective and two thermocouple
these three pressure switches exceed the set limit. Trip readings exceed TT.ATK.M…
causes shutoff of all fuel systems by closing the respective
b) One thermocouple is defective and one thermocouple
emergency stop valves. The alarm “COMPRESSOR reading exceeds TT.ATK.M…
SURGE PROTECTION RESPONSE” is annunciated when c) Two thermocouples are defective and one
the compressor surge protection system responds.
Class: RESTRICTED
Siemens AG 3.1-2601-0585/2
Power Generation MBA/MBD 0705E
Gas Turbine Measuring and Supervisory Equipment
Description Gas Turbine Instrumentation
a) No thermocouple is defective and two thermocouple flow, turbine outlet (exhaust) temperature decreases when
readings exceed TT.ATK.S… the vanes are opened and vice versa. If the flow of fuel and
b) One thermocouple is defective and one thermocouple air are simultaneously increased or decreased, a constant
reading exceeds TT.ATK.S… turbine outlet temperature can be maintained. Because the
c) Two thermocouples are defective and one fuel-air ratio is also held nearly constant in this case, the
thermocouple reading exceeds TT.ATK.S… premix burners, which are inherently only operable with a
narrow fuel-air ratio range, can be used over a wider range
Compressor IGV Pitch Adjustment of conditions.
The pitch of the inlet guide vanes is adjusted in
The gas turbine compressor is equipped with one row
response to TOTC using actuator MBA11AS001, thus
of variable-pitch inlet guide vanes. The flow of air through
setting the pitch of the compressor inlet guide vanes
the compressor and gas turbine is controlled by adjusting
accordingly. Position transmitter MBA11CG101 measures
the pitch of the compressor inlet guide vanes within a
the pitch of the IGVs which is then displayed.
defined permissible range. As the inlet guide vanes are
opened, the air flow through the gas turbine increases; it
decreases when they are closed. Given a constant fuel
content is not permitted without express written authority.
Siemens AG 3.1-2601-0585/3
Power Generation MBA/MBD 0705E
Gas Turbine Auxiliary Equipment
Description Drainage System
Siemens AG 3.1-4966-9020/1
Power Generation 0403E
Gas Turbine Auxiliary Equipment
Description Drainage System
the lowest points. Uncombusted fuel oil is drained off at the ignition current is switched on. This actuates these two
following locations: valves to their “drain oil” setting: A–C open; B closed.
When flames have formed in the combustion chambers,
No Gas Turbine Location MBA18AA001 and MBA18AA002 are deenergized and
. thus actuated to their “drain water” setting.
3 Compressor outlet During operation, these solenoid valves remain in their
4 Sight glass, left combustion chamber “drain water” setting.
5 Sight glass, right combustion chamber If no flames form in the combustion chambers a short
6 Inner casing time after ignition and injection of fuel oil, the start has
11 Combustion chamber outer shell, left failed. In this case, solenoid valves MBA18AA001 and
12 Combustion chamber outer shell, right MBA18AA002 remain energized, i.e. in their “drain oil”
setting. Solenoid valve MBA18AA003 is energized when
The above locations are drained via two separate speed drops below S.TURB.21. All the solenoid valves are
headers. The fluid is routed either via 3-way solenoid now in their “drain oil” setting and the fuel oil flows through
valves MBA18AA001 and MBA18AA002 to header connection 111A into the used oil disposal tank.
MBA18BB001 or via solenoid valve MBA18AA003 to a As the solenoid valve MBA18AA003 is only opened at
drain pipe. The fuel oil must be routed from connection relatively low speed, the pressure at the locations where
111A into a disposal tank for used oil (supplied locally). fuel oil can collect is not particularly high; this ensures that
This tank must have provision for continuous venting since the flow velocity of the fuel oil and air into the used oil
The reproduction, transmission or use of this document or its
content is not permitted without express written authority.
Offenders will be liable for damages. All rights, including
rights created by patent grant or registration of a utility model
air can also escape at connection 111A. disposal tank is not excessive.
The GT is ready for restarting after all four valves have
Functional Principle of the Fuel Oil Drain been left open a defined period of time (sufficient for
drainage of the fuel oil). These solenoid valves are
All solenoid valves are energized when the turbine is
equipped with limit switches.
not running (including turning gear operation). They are
thus in the “drain oil” setting: If there were no failed starts, solenoid valve
MBA18AA003 would never be actuated. There would
−= MBA18AA001 and MBA18AA002: A–C open; B closed;
or design, are reserved.
Siemens AG 3.1-4966-9020/2
Power Generation 0403E
Gas Turbine Safety and Protective Equipment
Description Blowoff System
Refer also to: blowoff valves are brought into the positions "OPEN" and
"CLOSED" by pneumatic actuators.
List of Control Settings (SREL) 3.1-2020
P+I Diagram, Gas Turbine 3.1-2600
Gas Turbine Instrumentation 3.1-2601 Extraction C stage Blowoff valve KKS
List of Measuring Instruments 3.1-2620 Ea1 5 1.1 MBA41AA051
List of Electrical Loads 3.1-2630
Equipment List 3.1-2640 Ea1 5 1.2 MBA41AA052
P+I Diagram, Blowoff Equipment 3.1-4410 Ea2 10 2 MBA42AA051
Wet Cleaning System for Compressor Blading 3.1-4962
P+I Diagram, Compressor Washing System 3.1-4967
Drainage System 3.1-4966 Because the blowoff lines located at the bottom act as
P+I Diagram, Water Drainage 3.1-4969 siphons due to their position, drain lines are connected at
Compressor Washing System 3.4-4962
the lowest points of these lines. Any water which may have
accumulated here during compressor washing can be
Settings, limits and measuring ranges of the items of
drained off via these lines (cf. 3.1-4966, 3.1-4962, and 3.4-
equipment listed here are given in the List of Measuring
4962).
Instruments, the Equipment List and the List of Control
Settings (SREL). The values stated in this description are
only given as examples. Compressed Air Supply
The compressed air used as the working medium for
rights created by patent grant or registration of a utility
Offenders will be liable for damages. All rights, including
its content is not permitted without express written authority.
The reproduction, transmission or use of this document or
System Configuration
Valve Actuation
Two blowoff lines are provided on the compressor
casing from the extraction points designated Ea1 and one All valves are brought into the "OPEN" and "CLOSED"
from the extraction point designated Ea2 for bleeding positions by a pneumatic piston which is pressurized from
compressor air. The blowoff lines open into the exhaust both sides.
gas duct downstream of the gas turbine. As a result, the Actuation of the butterfly valves by the solenoid valves
exhaust silencer simultaneously functions as a silencer for is explained below with reference to valve MBA41AA052.
the blowoff air. Each blowoff line is provided with a butterfly To open the valve, solenoid valves MBA41AA052A and
Class: RESTRICTED
valve which is opened when air is to be blown off. These MBA41AA052B are first deenergized. This causes air to
flow from the receiver through solenoid valve
Siemens AG 3.1-4411-9022/1
Energieerzeugung KWU MBA 0800E
Gas Turbine Safety and Protective Equipment
Description Blowoff System
MBA41AA052A (3 – 2 open; 1 closed) to one of the piston As speed again increases, the blowoff valves are
plenums. At the same time, the other piston plenum is closed as in the gas turbine startup procedure.
vented via solenoid valve MBA41AA052B (2 – 3 open; 1 − Shutdown:
closed). When the valve is to be closed, the solenoid
When shutting down the gas turbine, all blowoff valves
valves are switched, reversing the pressures in the two
are opened simultaneously when the emergency stop
piston plenums.
valves reach their closed position.
Because two butterfly valves (MBA41AA051 and
− GT trip:
MBA41AA052) must be vented via solenoid valve
MBA41AA052B, solenoid valve MBA41AA052C is also In the event that the gas turbine trips, all blowoff valves
opened. This increases the opening rate of these two are opened immediately as it is now certain that the
butterfly valves. axial compressor will pass through the unfavorable
speed range.
Limit switches are provided on all butterfly valves for
monitoring limit positions. − Compressor Washing:
It may be necessary to open blowoff valves 1.1 and 1.2
after compressor washing. A subloop control function is
Open-loop Control provided to ensure that the butterfly valves are opened
Opening and closing of the blowoff valves is controlled and closed in the correct sequence. The details of this
automatically as appropriate to operating conditions. procedure are given in Section 3.4-4962.
− Startup with natural gas or fuel oil: − Protection functions:
rights created by patent grant or registration of a utility
Offenders will be liable for damages. All rights, including
its content is not permitted without express written authority.
The reproduction, transmission or use of this document or
At the onset of startup, all blowoff valves are open. − If any of the blowoff valves is not open during gas
They are sequentially closed as of appr. 76 % rated turbine startup, the start is aborted.
speed. This minimizes the associated sudden changes − A pretrip alarm is annunciated if any of the blowoff
in temperature and output. valves opens during power operation or cannot be
− Power Operation: closed during runup. Other automatic action is not
The blowoff valves always remain closed during power taken.
model or design, are reserved.
Siemens AG 3.1-4411-9022/2
Energieerzeugung KWU MBA 0800E
Gas Turbine Measuring and Supervisory Equipment
Description Combustion Chamber Instrumentation
Refer also to: The following functions are derived from this for control
and monitoring of the GT:
List of Control Settings (SREL) 3.1-2020
P+I Diagram, Gas Turbine 3.1-2600
P+I Diagram, Combustion Chamber 3.1-2602
Natural Gas and Fuel Oil Operation
List of Measuring Instruments 3.1-2620 −= If the gas turbine is running in premix mode and the
Equipment List 3.1-2640 relative pressure drop ∆pCCrel in one combustion
chamber declines to or below PP.BK.01 for more than 5
Settings, limits and measuring ranges of the items of seconds, the GT must be changed over to diffusion
equipment listed here are given in the List of Measuring mode.
Instruments and List of Control Settings (SREL). This
−= Changeover from diffusion mode to premix mode may
description only gives guideline values.
only be enabled if the relative combustion chamber
pressure drop is above limit PP.BK.01 at the onset of
Function the planned changeover. At a ∆pCCrel >PP.BK.01 either
premix or diffusion mode is permitted.
The tasks of the measuring instruments associated with
the combustion chamber system are described in this −= If the relative combustion chamber pressure drop
Section. These measuring instruments are used to detect remains below limit PP.BK.01 for more than five
the pressure drop across the combustion chamber, seconds at speeds above the turbine speed
combustion process instabilities (known as humming), and S.TURB.70, the individual alarm “Relative combustion
chamber pressure drop <MIN” and the group alarm
The reproduction, transmission or use of this document or its
content is not permitted without express written authority.
Offenders will be liable for damages. All rights, including
rights created by patent grant or registration of a utility model
flame out.
“Hybrid burner fault” are annunciated.
in the amount of air reaching the burners due to increased by criteria identical to those in effect during operation on
gap losses. This in turn can jeopardize stable premix natural gas or fuel oil alone.
combustion.
The relative combustion chamber pressure drop can
Monitoring of Measuring Points
generally be considered an indication of the flow of primary If measuring points MBA12CP101 or MBM11-
air through the burners. It is dependent on the combustion CP103/MBM21CP103 indicate positive or negative
chamber geometry, but particularly in the upper output violation of limits the individual alarm “Relative combustion
range is virtually independent of the momentary GT output. chamber pressure drop measurement faulted” and the
The relative combustion chamber pressure drop changes group alarm “Transmitter fault” are annunciated. Rapid
as a result of wear or damage to burner or combustion changeover from premix mode to diffusion mode is not
chamber parts (changes in geometry, changes in flow path performed. If a measuring point fault is not rectified after
cross-section). Long-term monitoring of the relative approximately 24 hours, the changeover from premix to
combustion chamber pressure drop is performed to diffusion mode is made and a corresponding interlock
evaluate the condition of the combustion chambers. activated that prevents changeover back to premix mode.
The differential pressure across each combustion The enable for changeover to premix mode is immediately
chamber ∆pCC is measured using differential pressure deactivated, however, if the positive or negative measuring
transducers MBM11CP103 and MBM21CP103; the range violation is detected.
compressor outlet pressure pCII is measured using
pressure transducer MBA12CP101. This pressure Flame Monitoring
transducer is depicted in the P+ID “Gas Turbine” (3.1-
2600). Signals from these instruments are used to Fuel must never be fed to the gas turbine combustion
calculate the relative combustion chamber pressure drop chambers for an impermissibly long period without
(in percent): combustion taking place. The purpose of flame monitoring
Class: RESTRICTED
Siemens AG 3.1-2603-0526/1
Power Generation 0403E
Gas Turbine Measuring and Supervisory Equipment
Description Combustion Chamber Instrumentation
Two flame monitoring systems per combustion Actuation of the IGVs and changeover from DM to PM
chamber (MBM11CR101/102 and MBM21CR101/102) are are not blocked. Rapid changeover from premix mode to
provided for monitoring combustion flames. The radiant diffusion mode is not performed.
energy emitted by the flames (UV to IR range) is detected If the measure described in the foregoing is not
and these signals processed for further use. sufficient to eliminate combustion chamber humming, the
At least one flame monitor in each combustion chamber load setpoint of the gas turbine is abruptly reduced by the
must signal “Flame on”. If the readings of the two flame increment E.LEIST.12 if violation of limit P.BRUMM.04
monitors of one combustion chamber do not coincide, the persists for at least 3 seconds.
individual alarm “Flame monitor faulted” is annunciated. Actuation of the IGVs and changeover from DM to PM
Individual alarms are delayed for time K.FLAMM.01 to are not blocked. Pilot control of the IGVs remains active.
prevent premature control action. During the gas turbine Rapid changeover from premix mode to diffusion mode is
startup phase, flame monitor conditions may briefly deviate not performed.
from one another.
FO DM or FO/NG Dual-Fuel Operation
Monitoring of Humming P.BRUMM.04 is not used in these operating modes.
Gas turbines equipped with hybrid burners may If limit P.BRUMM.03 is exceeded for at least two
experience combustion instabilities manifested as seconds the gas turbine load setpoint is continuously
elevated-amplitude combustion chamber pressure decreased at the normal gradient until limit P.BRUMM.03 is
The reproduction, transmission or use of this document or its
content is not permitted without express written authority.
Offenders will be liable for damages. All rights, including
rights created by patent grant or registration of a utility model
fluctuations; this phenomenon is also known as humming no longer violated. A fault alarm is annunciated in such
and has a typical frequency range. Humming must be cases.
promptly detected and eliminated to prevent a further Actuation of the IGVs and changeover from DM to PM
increase in pressure fluctuation amplitudes and possible are not blocked. Pilot control of the IGVs remains active.
consequential damage to components of the gas turbine.
Humming is detected by measuring the amplitudes of Burner Temperature Monitoring in
combustion chamber pressure fluctuations using the two
dynamic pressure sensors MBM11CP102 and
Premix Mode
or design, are reserved.
MBM21CP102 and evaluating their output signals that lie in Rapid output fluctuations during operation in premix
a defined frequency range. modecaused, for example, by rapid pressure fluctuations
Monitoring of humming is only activated when the gas in the natural gas or fuel oil suppliedmay result in the
turbine is running in the speed range intended for extended formation of flames in the diagonal swirler section of the
operation. Monitoring is also blocked during changeover premix burners. Changeover back to diffusion mode must
from DM to PM and vice versa with natural gas. be made in such cases. For this reason burner
temperatures are monitored by two thermocouples per
NG DM/PM or FO PM burner (MBM12CT101 to MBM12CT116 and
MBM22CT101 to MBM22CT116). Temperature is
The limits P.BRUMM.03 and P.BRUMM.04 are
measured at the axial swirler. Faults to individual
stipulated for the effective value of combustion chamber
measuring points do not result in restricted availability.
pressure oscillations; the respective measures to eliminate
Burner temperature monitoring is only required for
combustion chamber humming are triggered if they are
operation on natural gas or fuel oil in premix mode.
exceeded. Triggering occurs if one of the two
Monitoring is not performed in diffusion mode on either
measurements indicates that a limit has been exceeded
natural gas or fuel oil or in dual-fuel mode (with NG + FO).
when monitoring of humming is active. A fault alarm is
annunciated in such cases. Differential temperatures are calculated from the mean
compressor outlet temperature and the temperatures at the
If limit P.BRUMM.03 is exceeded for at least two
axial swirlers. If a differential temperature exceeds limit
seconds the gas turbine load setpoint is continuously
TT.BRENNER.M01 for a period of at least one second, a
decreased at the normal gradient until limit P.BRUMM.03 is
separate individual alarm “Burner (xx) temperature >MAX”
no longer violated or P.BRUMM.04 responds. Control
is annunciated for each affected burner.
action in response to signal P.BRUMM.03 is delayed by the
time K.BRUMM.11 to ensure that load is reduced by a If a differential temperature exceeds the setting
TT.BRENNER.U01 for a period of at least 1 second during
Class: RESTRICTED
sufficient magnitude.
operation in diffusion mode, changeover from diffusion to
premix mode is blocked and the individual alarm “PM
Siemens AG 3.1-2603-0526/2
Power Generation 0403E
Gas Turbine Measuring and Supervisory Equipment
Description Combustion Chamber Instrumentation
blocked” is annunciated. This interlock is deactivated when channels and the individual alarm “Burner temperature
the differential temperature drops below monitoring faulted” is annunciated. After the third channel
TT.BRENNER.U01. fault occurs, rapid changeover from premix to diffusion
If a differential temperature exceeds limit mode is initiated and the individual alarms “Burner
TT.BRENNER.U01 for a period of at least 1 second in temperature monitoring faulted” and “PM blocked” are
premix mode, rapid changeover from premix to diffusion annunciated. The machine cannot be returned to premix
mode is initiated and the individual alarms “Premix mode mode until these channel faults have been rectified. If one
blocked” and “Burner temperature monitoring response” of the axial swirler temperature monitoring channels is
are annunciated. The changeover command is faulted, the invalid reading is excluded from processing and
documented and blocks a change back to premix mode. the individual alarm “Burner temperature monitoring
faulted” is annunciated. If both thermocouples of a given
Changeover from diffusion mode back to premix mode
burner are defective, rapid changeover from premix to
is possible when the corresponding enable criteria have
diffusion mode is initiated and the individual alarm “PM
been met. If limit TT.BRENNER.U01 is exceeded a second
blocked” is annunciated. The machine cannot be returned
time during operation in premix mode, changeover is made
to premix mode until these channel faults have been
to diffusion mode, an interlock prevents resumption of
rectified.
premix mode and the individual alarms “Burner
temperature monitoring response”, “PM blocked”, and
“Perform burner inspection” are annunciated. Operation in Burners
diffusion mode or dual-fuel mode (NG + FO) is still
The reproduction, transmission or use of this document or its
content is not permitted without express written authority.
Offenders will be liable for damages. All rights, including
rights created by patent grant or registration of a utility model
Siemens AG 3.1-2603-0526/3
Power Generation 0403E
A 18.08.2005 Complete Revision Lübbers Merz Vogt
C.C. CHKD AT
REV No. DATE REVISION DESCRIPTION PREP. CHKD APPYD.
CHKD. SITE
SIEMENS PG
CONTRACTOR: DWG. No SUB CONTRACTOR DWG. No
VAE266-XS00-MBA-357401
CONTRACT JOB. No TITLE
FIRST ISSUE
CNE/121/2004-B-21-M-M-50620A A
Weitergabe sowie Vervielfältigung, Verbreitung und/oder Bearbeitung dieses Dokumentes, Verwertung und
Siemens Mitteilung seines Inhaltes sind verboten, soweit nicht ausdrücklich gestattet. Zuwiderhandlungen verpflichten
zu Schadenersatz. Alle Rechte für den Fall der Patenterteilung, Gebrauchsmuster- oder
Geschmacksmustereintragung vorbehalten.
Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents
and communication thereof to others without express authorization are prohibited. Offenders will be held
liable for payment of damages. All rights created by patent grant or registration of a utility model or design
patent are reserved.
CoverSheet_SYSDESC_ACCS.doc
Projekt/Anlage: VAE266
System - Beschreibung
Project/Plant:
Description
UNID
VAE266 XS00 MBA-357401 453012896
Proj.-Kennz./Proj. Code UA/Doc. Inhaltskennzeichen/Contents Code
freigegeben durch/released by
In- Erstellung bzw.
dex Datum Änderungen (Seiten) Dienststelle bearbeitet durch geprüft durch intern extern
Date Office prepared by reviewed by Internal external
Rev. Issue resp.
Modifications (Pages).
Complete Revision
A 18.08.05 G133 J. Lübbers A. Merz A. Vogt 1)
2)
Inhalt/Contents
Seite/Page
1 Allgemeines 1
1. General 1
2. System Configuration 1
3. Reinigungsmodi 1
3. Cleaning Modes 1
3.1 ON-Line Reinigung 2
3.1 On-line Cleaning 2
3.2 OFF-Line Reinigung 2
3.2 Off-line Cleaning 2
4. Düsensystem 3
4. Nozzle System 3
5 Verdichterreinigungspackage 3
6. Druckluftsystem 4
1 Allgemeines 1. General
Beim Betrieb einer Gasturbine kommt es trotz During operation of a gas turbine, soiling of
sorgfältiger Filterung der Ansaugluft zu einer blading occurs despite thorough filtration of
Verschmutzung der Beschaufelung, vor allem the intake air; such soiling occurs particularly
beim Verdichter. in the compressor section.
Verschmutzte Schaufeln führen zu weniger Blading deposits reduce output and the effi-
Leistung und verschlechtern den ciency of the gas turbine. Performing a com-
Wirkungsgrad der Gasturbine. Durch eine pressor cleaning operation removes deposits
Verdichterreinigung werden from the compressor airfoils and restores lost
Verschmutzungen der Verdichterschaufeln gas turbine output.
entfernt, und Leistung der Gasturbine
zurückgewonnen.
Beide Reinigungsverfahren nutzen das Both cleaning operations use the same noz-
gleiche Düsensystem, unterscheiden sich zle system but differ in terms of their effec-
aber in der Wirksamkeit, in der tiveness, the procedure followed, and the
Vorgehensweise und bei der zum Einsatz cleaning fluid that is injected. Corresponding
kommenden Reinigungsflüssigkeit. Die data for the composition of this medium are
Zusammensetzung dieses Mediums ist stored in the control unit of the compressor
entsprechend in der Steuerung des cleaning package.
Verdichterreinigungspackage hinterlegt.
Im Reinigungsbetrieb fördert die Pumpe During the cleaning operation the pump for-
dieses Reinigungsmedium mit einem wards the cleaning medium at a pressure of
Überdruck von min. 6 bar über eine fest at least 6bar(g) through a permanently-
installierte Rohrleitung in das Düsensystem installed pipe to the nozzle system of the GT.
der Gasturbine.
This document is subject to the restrictions set forth on the first or title page.
Aweer Gas Turbine Power Station 'H' (Phase II) Part 2
SIEMENS Operating Manual (Overall Plant)
Section 5.1
Gas Turbine MB
Revision a
This document is subject to the restrictions set forth on the first or title page.
Aweer Gas Turbine Power Station 'H' (Phase II) Part 2
Revision a
Table of Contents
1 Manual Valve Position List ................................................................................. 2
1.1 Gas Turbine – 41MBA .........................................................................................................2
1.2 Compressor Cleaning – 41MBA ..........................................................................................2
1.3 Combustion Chamber – 41MBM .........................................................................................3
2 Operational Readiness......................................................................................... 4
2.1 Checks on Site.....................................................................................................................4
2.2 Checks on OM-System ........................................................................................................4
This document is subject to the restrictions set forth on the first or title page.
Aweer Gas Turbine Power Station 'H' (Phase II) Part 2
Revision a
1
The KKS identifiers prefixed with "41" have to be adapted for the other gas turbines by changing the identifiers
prefix to "42" or "43".
2
This valve may only be closed during change-over of the drains disposal tank.
This document is subject to the restrictions set forth on the first or title page.
Aweer Gas Turbine Power Station 'H' (Phase II) Part 2
Revision a
This document is subject to the restrictions set forth on the first or title page.
Aweer Gas Turbine Power Station 'H' (Phase II) Part 2
Revision a
2 Operational Readiness3
2.1 Checks on Site
MANUAL VALVES ACCORDING TO POSITION LIST SET 41MBA
41MBM
3
The KKS identifiers prefixed with "41" have to be adapted for the other gas turbines by changing the identifiers
prefix to "42" or "43".
This document is subject to the restrictions set forth on the first or title page.
Aweer Gas Turbine Power Station 'H' (Phase II) Part 2
Revision a
Enabling Criteria
41MYB01 EC001
RELEASE MEMORY FOR START STEP 58 SET
&
4
The KKS identifiers prefixed with "41" have to be adapted for the other gas turbines by changing the identifiers
prefix to "42" or "43".
This document is subject to the restrictions set forth on the first or title page.
Aweer Gas Turbine Power Station 'H' (Phase II) Part 2
Revision a
5
42CHB00 EU001 ZV01
PROT CUB PWR SUPPLY FAULT
At first it is checked that the start-up frequency converter is in normal start mode.
The subgroup controls "SGC NATURAL GAS" – 41MBP01 EC001 and "SGC FUEL OIL" – 41MBN01 EC001 are
switched on (set to automatic mode) and the lube oil system is started up by activating the start-up program of the
subgroup control "SGC LUB OIL/TRN SYST" – 41MBV01 EC001.
The air dryer of the gas turbine compressor (41MBA10 AT001) is switched off and the memory "COMPR AIR S/O"
– 41MBL20 EE010 is activated. The IGV controller (41MBY10 DT040) is switched on.
The hydraulic oil system is started up by switching on the preselected hydraulic pump (41MBX02 AP001/002) via
the subloop control "SLC PRESSURE KEEPING" - 41MBX00 EE010. If pressure build-up is delayed, the standby
pump is switched on additionally.
5
This release criteria from the protection cubicle of another unit is only applicable for unit 41.
This document is subject to the restrictions set forth on the first or title page.
Aweer Gas Turbine Power Station 'H' (Phase II) Part 2
Revision a
The fuel oil drain valves 1-3 (41MBA18 AA001/ AA002/ AA003) are closed.
The generator forced cooling system is activated by switching on the subloop controls "SLC GEN GLG PUMPS" -
41MPR10 EE010 and "SLC GEN CLG FANS" - 41MPR30 EE010.
The automated bus bar transfer for the LV switchgears 41BFE/BME is enabled by switching on the subloop control
"LV CHANGE-OVER" - 41BFE00 EE010.
The subloop control for the generator air dryer 41MKA05 EE001 is switched on. The generator voltage controller is
switched to automatic mode and the synchronizing selectors of the generator circuit breaker, HV unit circuit break-
er and unit auxiliary circuit breaker are set to "not selected".
It is ensured that the blow-off valves (41MBA41 AA051/052, 41MBA42 AA051) are opened.
The start-up frequency converter is prepared for start-up of the gas turbine.
Dependent on the fuel preselection, the start-up program of the subgroup control "SGC FUEL OIL" – 41MBN01
EC001 or "SGC NATURAL GAS" – 41MBP01 EC001 is activated.
The "SGC FUEL OIL" – 41MBN01 EC001 or "SGC NATURAL GAS" – 41MBP01 EC001 accelerate the gas tur-
bine up to a speed of > 15.0 s-1.
The gas turbine is accelerated further. At a turbine speed > 38.6 s-1 the start-up frequency converter is switched off
and the external isolator for the SFC is opened. The combustion accelerates the gas turbine further up to nominal
speed.
Now the excitation unit is switched on and the selection of the generator circuit breaker is set to "automatic" mode.
The synchronising system is activated, the auto-paralleling device is switched on and the gas turbine is synchro-
nised to the grid at the generator circuit breaker.
This document is subject to the restrictions set forth on the first or title page.
Aweer Gas Turbine Power Station 'H' (Phase II) Part 2
Revision a
Enabling Criteria
The start-up frequency converter is switched off (in the event of a failed start). The subgroup control "SGC GAS
TURBINE" – 41MYB01 EC001 unloads the gas turbine to a load < 8 MW.
If the gas turbine is running in premix mode, selection of the shutdown program and unloading of the gas turbine
results in automatic switch-over to diffusion mode.
The gas turbine is unloaded further until the active power has dropped below 1.5 MW. Now the generator circuit
breaker (41BAC01 GS001) is opened. When the gas turbine is disconnected from the grid, the excitation unit is
switched off.
Dependent on the fuel selection, the shutdown program of the subgroup control "SGC FUEL OIL" – 41MBN01
EC001 or "SGC NATURAL GAS" – 41MBP01 EC001 is activated and gas turbine trip is initiated.
When the subgroup control "SGC FUEL OIL" – 41MBN01 EC001 has reached step 55 or the "SGC NATURAL
GAS" – 41MBP01 EC001 has reached step 53, the subgroup control "SGC GAS TURBINE" – 41MYB01 EC001
observes the further coast-down of the gas turbine.
When the gas turbine has reached a speed < 12.5 s-1, the fuel oil drain valves 1-3 (41MBA18 AA001/002/003) are
opened for draining unburned fuel oil in case of a failed start.
When the turbine speed has fallen below 7.6 s-1, the "SGC GAS TURBINE" – 41MYB01 EC001 proceeds to step
58 and is released for start-up again..
This document is subject to the restrictions set forth on the first or title page.
Aweer Gas Turbine Power Station 'H' (Phase II) Part 2
Revision a
When the turbine speed is < 3.0 s-1, the generator forced cooling system is de-activated by switching off the
subloop controls "SLC GEN GLG PUMPS" - 41MPR10 EE010 and "SLC GEN CLG FANS" - 41MPR30 EE010.
The hydraulic oil system is shut down by switching off the hydraulic pumps (41MBX02 AP001/002).
The subloop control for the generator air dryer (41MKA05 EE001) is switched on. The shutdown program of the
subgroup control "SGC LUB OIL/TRN SYST" – 41MBV01 EC001 is activated. As the gas turbine slows down to
turning speed, the lube oil / turning gear system takes over the task of cooling down the gas turbine.
On receiving the corresponding feedback signals, the subgroup control "SGC GAS TURBINE" – 41MYB01 EC001
reaches the last step.
This document is subject to the restrictions set forth on the first or title page.