Sunteți pe pagina 1din 35

Aweer Gas Turbine Power Station 'H' (Phase II) Part 2

SIEMENS Operating Manual (Overall Plant)


Section 5.1
Description of Systems

Gas Turbine MB

Chapter 1: System Descriptions

Chapter 2: P&I Diagrams

Chapter 3: Requirements for Operation

Issue resp.
prepared by/
Rev. Date Modifications prepared by reviewed by released by
reviewed by
(pages)

PG E8C3 PG E8C3
a 2006-05-12 preliminary 1)
H. Wolf / C. Koch P. Koch

sgd. C. Koch sgd. P. Koch 2)

red marked
"as built"

finalized

1) organisational unit/name printed 2) signature

Transmittal, reproduction, dissemination and/or editing of this document as well as


utilization of its contents and communication thereof to others without express
For internal use only authorization are prohibited. Offenders will be held liable for payment of damages. All
rights created by patent grant or registration of a utility model or design patent are
reserved.
Aweer Gas Turbine Power Station 'H' (Phase II) Part 2
SIEMENS Operating Manual (Overall Plant)
Section 5.1
Gas Turbine MB
Revision a

Chapter 1: System Descriptions

List of System Descriptions


3.1-2601-0585/1-3 UNID: Rev.: 0705E MBA Gas Turbine Instrumentation
3.1-4966-9020/1-2 UNID: 453012902 Rev.: 0403E MBA Drainage System

3.1-4411-9022/1-2 UNID: 453009339 Rev.: 0800E MBA Blowoff System


3.1-2603-0526/1-3 UNID: 453012926 Rev.: 0403E MBA Combustion Chamber
Instrumentation
CNE/121/2004-B-21-M-M-50620A UNID: 453012896 Rev.: a MBA Advanced Compressor
Cleaning System (ACCS)

This document is subject to the restrictions set forth on the first or title page.
Gas Turbine Measuring and Supervisory Equipment
Description Gas Turbine Instrumentation

Refer also to: bearing; alarms are annunciated and/or gas turbine
protection functions triggered if certain limits are violated.
Setting of Temperature Limits Signals from these transmitters are used by a
at the Turbine Outlet 3.1-0118 processor module to calculate the effective vibration
List of Control Settings 3.1-2020 velocity, which is then output as current signals that
P+I Diagram, Gas Turbine 3.1-2600 undergo further processing in the I&C system. Casing
List of Measuring Instruments 3.1-2620 vibration is registered using two equivalent channels. If at
Equipment List 3.1-2640 least one of the two channels indicates that the limit
List of Electrical Loads 3.1-2630 Y.LAGER.M is exceeded, the alarm “… BEARING
Blowoff System 3.1-4411 VIBRATION WARNING” is annunciated. If any channel
indicates that the higher limit Y.LAGER.S is violated, the
Settings, limits, and measuring ranges of the devices gas turbine trips and is shut down and the alarm
referred to here are given in the List of Measuring “TRIGGERING BY … BEARING VIBRATION” is
Instruments, Equipment List, and List of Control Settings annunciated.
(SREL).

Shaft Vibration Measurement


Preliminary Remarks
Shaft vibration measurement has the task of detecting
Gas turbine instrumentation, valves, and equipment rapid motion of the shaft relative to its centerline.
content is not permitted without express written authority.

rights created by patent grant or registration of a utility model


Offenders will be liable for damages. All rights, including
The reproduction, transmission or use of this document or its

units, with the exception of such items associated with


Shaft vibration is measured at the turbine bearing by
other auxiliary systems, are indicated in the P+ID referred
vibration pickups MBD11CY111 and MBD11CY112 and at
to above.
the compressor bearing by vibration pickups MBD12CY111
and MBD12CY112. In each case, two pickups are mounted
Speed Measurement 45 degrees from the vertical at the same axial position
along the turbine shaft. This arrangement permits the
The speed of the turbine-generator is measured by the
transducers to measure the vibration vector as a function of
six speed pickups MBA10CS101 to MBA10CS106. Slots
time. Any shaft vibrations occurring are displayed and
or design, are reserved.

are machined in the intermediate shaft near the


recorded.
compressor bearing. The magnetic field sensors located
around the circumference of this region generate a pulse Keyphasor® MBA10CY101 determines the phase
each time the land between two adjacent slots passes by. angle of vibration. The Keyphasor is a pickup, analogous to
As the shaft rotates, the magnetic field sensors generate the speed transmitters, which generates one pulse per
impulses, the frequency of which is equal to the product of revolution of the shaft, namely at that instant when a slot
the number of slots and rotational shaft speed. machined in the turbine shaft passes by.

These impulses are used for speed protection after


further processing in two redundant speed monitoring Bearing Temperature Measurement
systems, each comprising three channels. Every channel
The compressor end of the GT shaft is equipped with a
of each speed monitoring system is set to the limit
journal bearing and thrust bearings for both directions. A
S.TURB.72. If at least two channels of one or both speed
journal bearing supports the turbine end of the rotor.
monitoring systems indicate that this limit has been
violated, speed is impermissibly high, the gas turbine trips An insufficient supply of lube oil, overloading, excessive
and is shut down. oil temperatures, or foreign matter can damage these
bearings. Bearing metal temperature is measured to permit
The speed monitoring system forwards the output
prompt detection of impending damage. Impending
signals of instruments MBA10CS101 to MBA10CS103 to
damage to bearings is generally indicated by elevated
the gas turbine controller. The gas turbine controller uses
bearing temperature. Two triple-element thermocouples
these impulses to generate a speed signal that is
are installed at each end of the two thrust bearings, namely
forwarded to the I&C system.
the end facing the turbine and the end facing the generator.
Triplex thermocouples MBD12CT102A/B/C (generator end)
Casing Vibration Measurement and MBD12CT104A/B/C (turbine end) are used to measure
Class: RESTRICTED

bearing temperature; triplex thermocouples


Casing vibrations are measured by vibration pickups
MBD12CT103A/B/C (generator end) and
MBD11CY101 and MBD11CY102 at the turbine bearing
and MBD12CY101 and MBD12CY102 at the compressor

Siemens AG 3.1-2601-0585/1
Power Generation MBA/MBD 0705E
Gas Turbine Measuring and Supervisory Equipment
Description Gas Turbine Instrumentation

MBD12CT105A/B/C (turbine end) each serve as backups Compressor Outlet Pressure and
and their leads end on a sub-distribution board. Temperature
Triple-element thermocouples are installed at the
Compressor outlet pressure (MBA12CP101, MBA12-
journal bearings (MBD12CT101A/B/C, MBD12CT106A/B/C
CP102) is required for monitoring the relative combustion
at the compressor end and MBD11CT101A/B/C and
chamber pressure and for the purge water system.
MBD11CT102A/B/C at the turbine end).
Compressor outlet temperature (MBA12CT101,
The alarm “BEARING TEMPERATURE HIGH” is
MBA12CT102) has an influence on burner temperature
annunciated if one-of-three logic indicates that bearing
monitoring.
temperature exceeds T.LAGER.M at the compressor
bearing or turbine bearing. The compressor outlet pressure and temperature
readings are forwarded to the operation and monitoring
If 2-of-3 logic indicates that the temperature of the
system for display purposes.
compressor or turbine bearing exceeds the higher limit
T.LAGER.S, trip is triggered and the GT shut down.
Turbine Cooling Air Pressure
Air Temperature Upstream of Differential pressure indicator MBA21CP501 measures
Compressor the drop in pressure between the compressor outlet and
the cooling air chamber at turbine vane row 1. A change in
An average compressor inlet temperature is required
this pressure drop with otherwise identical operating
content is not permitted without express written authority.

rights created by patent grant or registration of a utility model


Offenders will be liable for damages. All rights, including
The reproduction, transmission or use of this document or its

for calculating the corrected turbine outlet temperature


conditions indicates a fault in the turbine cooling system.
(TOTC) used for temperature limit control and turbine outlet
temperature protection.
Resistance thermometers MBA11CT101, MBA11- Turbine Outlet Temperature
CT102, and MBA11CT103 measure the compressor inlet Six dual-element thermocouples are distributed around
temperature. the circumference of the turbine outlet. Exhaust
Resistance thermometer MBA11CT104 is used in temperature is measured by dual-element thermocouples
addition for acceptance measurements. These MBA22CT102 to MBA22CT104 for the left combustion
or design, are reserved.

measurements are also used to calculate the compressor chamber and by MBA22CT106 to MBA22CT108 for the
mass flow. right combustion chamber.
One element of each thermocouple is used for
Pressure Upstream of Compressor temperature control, the other for protection functions and
display.
Pressure transducer MBA11CP101 measures the
The turbine exhaust temperature is used in conjunction
subatmospheric pressure in the compressor intake duct
with the compressor inlet temperature and speed to
and forwards this information to the operation and
calculate the corrected outlet temperature TOTC. Because
monitoring system and other systems.
the temperature in the exhaust diffuser is not constant
around the circumference, limits are defined for each
Compressor Surge Detection thermocouple individually. Further details on this are given
in document 3.1-0118, Setting of Temperature Limits at the
Data acquisition for compressor surge detection and Turbine Outlet”.
compressor surge protection is performed by the triple-
redundant differential pressure switches MBA11CP001, The pretrip alarm “TURBINE OUTLET TEMPERATURE
MBA11CP002, and MBA11CP003. Compressor surge 1-3 (or 4-6) WARNING” is annunciated if one of the
protection is enabled above the limit S.TURB.15. following situations occurs in a given group of temperature
measurements:
Gas turbine trip is triggered if the readings of two of
a) No thermocouple is defective and two thermocouple
these three pressure switches exceed the set limit. Trip readings exceed TT.ATK.M…
causes shutoff of all fuel systems by closing the respective
b) One thermocouple is defective and one thermocouple
emergency stop valves. The alarm “COMPRESSOR reading exceeds TT.ATK.M…
SURGE PROTECTION RESPONSE” is annunciated when c) Two thermocouples are defective and one
the compressor surge protection system responds.
Class: RESTRICTED

thermocouple reading exceeds TT.ATK.M…

Trip is triggered if one of the following situations occurs


in one of the groups of temperature measurements:

Siemens AG 3.1-2601-0585/2
Power Generation MBA/MBD 0705E
Gas Turbine Measuring and Supervisory Equipment
Description Gas Turbine Instrumentation

a) No thermocouple is defective and two thermocouple flow, turbine outlet (exhaust) temperature decreases when
readings exceed TT.ATK.S… the vanes are opened and vice versa. If the flow of fuel and
b) One thermocouple is defective and one thermocouple air are simultaneously increased or decreased, a constant
reading exceeds TT.ATK.S… turbine outlet temperature can be maintained. Because the
c) Two thermocouples are defective and one fuel-air ratio is also held nearly constant in this case, the
thermocouple reading exceeds TT.ATK.S… premix burners, which are inherently only operable with a
narrow fuel-air ratio range, can be used over a wider range
Compressor IGV Pitch Adjustment of conditions.
The pitch of the inlet guide vanes is adjusted in
The gas turbine compressor is equipped with one row
response to TOTC using actuator MBA11AS001, thus
of variable-pitch inlet guide vanes. The flow of air through
setting the pitch of the compressor inlet guide vanes
the compressor and gas turbine is controlled by adjusting
accordingly. Position transmitter MBA11CG101 measures
the pitch of the compressor inlet guide vanes within a
the pitch of the IGVs which is then displayed.
defined permissible range. As the inlet guide vanes are
opened, the air flow through the gas turbine increases; it
decreases when they are closed. Given a constant fuel
content is not permitted without express written authority.

rights created by patent grant or registration of a utility model


Offenders will be liable for damages. All rights, including
The reproduction, transmission or use of this document or its

or design, are reserved. Class: RESTRICTED

Siemens AG 3.1-2601-0585/3
Power Generation MBA/MBD 0705E
Gas Turbine Auxiliary Equipment
Description Drainage System

Refer also to: Configuration


List of Control Settings (SREL) 3.1-2020 Used cleaning fluid is drained off at the following
List of Measuring Instruments 3.1-2620 locations:
List of Electrical Loads 3.1-2630
Equipment List 3.1-2640
Wet Cleaning System for Compressor Blading 3.1-4962 No. Gas Turbine Location
P+I Diagram, Drainage System 3.1-4969 1 Compressor stage 5
2 Compressor stage 10
Settings, limits and measuring ranges of the devices 3 Compressor outlet
listed here are given in the List of Measuring Instruments, 4 Sight glass, left combustion chamber
Equipment List and List of Control Settings (SREL). This 5 Sight glass, right combustion chamber
description only gives guideline values. 6 Inner casing
7 Turbine stage 3
8 Turbine outlet
Functions 9 Blowoff line, left
Cleaning fluid sprayed into the compressor or turbine 10 Blowoff line, right
during the cleaning operation collects at several locations 11 Combustion chamber outer shell, left
in the gas turbine (cf. Section 3.1-4962). This fluid is 12 Combustion chamber outer shell, right
removed via the drainage system before the gas turbine is
The reproduction, transmission or use of this document or its
content is not permitted without express written authority.
Offenders will be liable for damages. All rights, including
rights created by patent grant or registration of a utility model

restarted. These locations are connected by pipes to header


MBA18BB001. The shutoff valves in these lines must be
opened to drain the used cleaning fluid and then closed
Danger! after completion of the draining process. A separate shutoff
Risk of scalding! The cleaning and valve is not provided for each of the locations listed above;
subsequent draining of the compressor drainage pipes from locations with identical operating
are manual operations, i.e. the associated pressures are connected with one another upstream of the
valves must be actuated by hand. It is shutoff valve.
absolutely imperative that all the valves
or design, are reserved.

Used cleaning fluid must be routed from header


opened during the draining operation are
MBA18BB001 via connection 30A and a hose line to a
closed once draining has been completed.
disposal tank, which must be supplied locally. The header
If this is not done, hot air which can scald
only has a small volume and therefore cannot function as a
persons or damage equipment will escape
collecting vessel. Shutoff valve MBA18AA262 at the end of
from the drainage piping. In addition,
the hose must always be open. When draining used
crosscurrent flow may occur between the
cleaning fluid, this valve may only be closed long enough to
individual gas turbine drain connections.
allow changeover from a full disposal tank to an empty one.
The header is equipped with a venting nozzle. If shutoff
In the case of gas turbines operated on liquid fuel (fuel valve MBA18AA262 at the end of the hose remains closed
oil), some fuel oil may collect at the lowest points of the for too long while draining, used cleaning fluid emerges
combustion chambers and casing after a failed start. The from the venting nozzle.
appropriate (solenoid-type) shutoff valves are automatically During cleaning of the compressor, some of the
opened following a failed start to drain off this fuel oil. cleaning fluid flows to the lowest point of the casing,
Furthermore, these solenoid valves are open when the GT located upstream of the compressor, which is not indicated
is at standstill to allow any fuel oil that has ingressed as a in the P+ID. This lowest point, which is just below the
result of a fault to drain off. The valves are closed when the turbine building floor, is connected to the disposal tank by a
GT is started up. duct cast into the foundation. The operator must ensure
that this connection is closed when the GT is in operation.
Otherwise the subatmospheric pressure in the intake
structure would draw unfiltered air through this duct.
When the gas turbine is started up with liquid fuel (fuel
oil), this fuel is injected into the combustion chambers
Class: RESTRICTED

during the ignition phase. If the flames do not ignite


immediately or if they go out due to a fault, fuel oil may
condense on the combustion chamber walls and collect at

Siemens AG 3.1-4966-9020/1
Power Generation 0403E
Gas Turbine Auxiliary Equipment
Description Drainage System

the lowest points. Uncombusted fuel oil is drained off at the ignition current is switched on. This actuates these two
following locations: valves to their “drain oil” setting: A–C open; B closed.
When flames have formed in the combustion chambers,
No Gas Turbine Location MBA18AA001 and MBA18AA002 are deenergized and
. thus actuated to their “drain water” setting.
3 Compressor outlet During operation, these solenoid valves remain in their
4 Sight glass, left combustion chamber “drain water” setting.
5 Sight glass, right combustion chamber If no flames form in the combustion chambers a short
6 Inner casing time after ignition and injection of fuel oil, the start has
11 Combustion chamber outer shell, left failed. In this case, solenoid valves MBA18AA001 and
12 Combustion chamber outer shell, right MBA18AA002 remain energized, i.e. in their “drain oil”
setting. Solenoid valve MBA18AA003 is energized when
The above locations are drained via two separate speed drops below S.TURB.21. All the solenoid valves are
headers. The fluid is routed either via 3-way solenoid now in their “drain oil” setting and the fuel oil flows through
valves MBA18AA001 and MBA18AA002 to header connection 111A into the used oil disposal tank.
MBA18BB001 or via solenoid valve MBA18AA003 to a As the solenoid valve MBA18AA003 is only opened at
drain pipe. The fuel oil must be routed from connection relatively low speed, the pressure at the locations where
111A into a disposal tank for used oil (supplied locally). fuel oil can collect is not particularly high; this ensures that
This tank must have provision for continuous venting since the flow velocity of the fuel oil and air into the used oil
The reproduction, transmission or use of this document or its
content is not permitted without express written authority.
Offenders will be liable for damages. All rights, including
rights created by patent grant or registration of a utility model

air can also escape at connection 111A. disposal tank is not excessive.
The GT is ready for restarting after all four valves have
Functional Principle of the Fuel Oil Drain been left open a defined period of time (sufficient for
drainage of the fuel oil). These solenoid valves are
All solenoid valves are energized when the turbine is
equipped with limit switches.
not running (including turning gear operation). They are
thus in the “drain oil” setting: If there were no failed starts, solenoid valve
MBA18AA003 would never be actuated. There would
−= MBA18AA001 and MBA18AA002: A–C open; B closed;
or design, are reserved.

therefore be a risk that this valve could jam when


−= MBA18AA003: open. attempting to actuate it to the “drain oil” setting after a
failed start. For this reason the valve is energized during
All three of these valves are deenergized prior to every shutdown when GT speed drops below S.TURB.21.
startup.
During startup, MBA18AA003 remains closed.
MBA18AA001 and MBA18AA002 are energized when the
Class: RESTRICTED

Siemens AG 3.1-4966-9020/2
Power Generation 0403E
Gas Turbine Safety and Protective Equipment
Description Blowoff System

Refer also to: blowoff valves are brought into the positions "OPEN" and
"CLOSED" by pneumatic actuators.
List of Control Settings (SREL) 3.1-2020
P+I Diagram, Gas Turbine 3.1-2600
Gas Turbine Instrumentation 3.1-2601 Extraction C stage Blowoff valve KKS
List of Measuring Instruments 3.1-2620 Ea1 5 1.1 MBA41AA051
List of Electrical Loads 3.1-2630
Equipment List 3.1-2640 Ea1 5 1.2 MBA41AA052
P+I Diagram, Blowoff Equipment 3.1-4410 Ea2 10 2 MBA42AA051
Wet Cleaning System for Compressor Blading 3.1-4962
P+I Diagram, Compressor Washing System 3.1-4967
Drainage System 3.1-4966 Because the blowoff lines located at the bottom act as
P+I Diagram, Water Drainage 3.1-4969 siphons due to their position, drain lines are connected at
Compressor Washing System 3.4-4962
the lowest points of these lines. Any water which may have
accumulated here during compressor washing can be
Settings, limits and measuring ranges of the items of
drained off via these lines (cf. 3.1-4966, 3.1-4962, and 3.4-
equipment listed here are given in the List of Measuring
4962).
Instruments, the Equipment List and the List of Control
Settings (SREL). The values stated in this description are
only given as examples. Compressed Air Supply
The compressed air used as the working medium for
rights created by patent grant or registration of a utility
Offenders will be liable for damages. All rights, including
its content is not permitted without express written authority.
The reproduction, transmission or use of this document or

Function the blowoff valve dual-plenum pneumatic actuators is


extracted from the receiver MBA40BB001. The receiver
The axial compressor of the gas turbine is designed to
ensures that sufficient control air is available for each
run at the rated speed of the turbine generator. At speeds
switching operation. It is filled with air extracted from the
in a certain range below rated speed, the front stages of
compressor discharge via the filter MBA40AT001. Check
the compressor would be so highly loaded
valve MBA40AA201 prevents compressed air from flowing
aerodynamically that air flows would separate at the
from the receiver back into the gas turbine when
model or design, are reserved.

compressor blading surface due to excessive deceleration.


compressor pressure drops.
As a result, the overloaded compressor stages are no
longer capable of generating the necessary increase in Any condensation which forms is drained off by
pressure, the compressor surges and the flow of air automatic drains trap MBA40AA203. The upstream orifice
becomes unstable. The breakdown of flow patterns results MBA40BP001 prevents excessive drops in receiver
in periodic reverse flow, which is characterized outwardly pressure in the event of an automatic drains trap leak. A
by pronounced, periodic fluctuations in the pressure at the vent line is connected from the automatic drains trap to the
final compressor stage together with severe vibration of boost pressure side. Shutoff valve MBA40AA401 must be
the turbine generator and pulsating noise synchronous kept open during operation of the gas turbine. It is only
with the pressure fluctuations. This subjects the permissible to close this valve for performing maintenance.
compressor blades to both high alternating bending If the blowoff valves are to be actuated for service
stresses and high temperatures. reasons during standstill of the gas turbine, the receiver
When this surge-critical speed range is reached, air is must be charged with compressed air from another source
bled from certain stages of the compressor, reliably through shutoff valve MBA40AA251. In such situations,
preventing compressor surging. ensure that the receiver is not charged to above its
operating pressure (compressor discharge pressure).

System Configuration
Valve Actuation
Two blowoff lines are provided on the compressor
casing from the extraction points designated Ea1 and one All valves are brought into the "OPEN" and "CLOSED"
from the extraction point designated Ea2 for bleeding positions by a pneumatic piston which is pressurized from
compressor air. The blowoff lines open into the exhaust both sides.
gas duct downstream of the gas turbine. As a result, the Actuation of the butterfly valves by the solenoid valves
exhaust silencer simultaneously functions as a silencer for is explained below with reference to valve MBA41AA052.
the blowoff air. Each blowoff line is provided with a butterfly To open the valve, solenoid valves MBA41AA052A and
Class: RESTRICTED

valve which is opened when air is to be blown off. These MBA41AA052B are first deenergized. This causes air to
flow from the receiver through solenoid valve

Siemens AG 3.1-4411-9022/1
Energieerzeugung KWU MBA 0800E
Gas Turbine Safety and Protective Equipment
Description Blowoff System

MBA41AA052A (3 – 2 open; 1 closed) to one of the piston As speed again increases, the blowoff valves are
plenums. At the same time, the other piston plenum is closed as in the gas turbine startup procedure.
vented via solenoid valve MBA41AA052B (2 – 3 open; 1 − Shutdown:
closed). When the valve is to be closed, the solenoid
When shutting down the gas turbine, all blowoff valves
valves are switched, reversing the pressures in the two
are opened simultaneously when the emergency stop
piston plenums.
valves reach their closed position.
Because two butterfly valves (MBA41AA051 and
− GT trip:
MBA41AA052) must be vented via solenoid valve
MBA41AA052B, solenoid valve MBA41AA052C is also In the event that the gas turbine trips, all blowoff valves
opened. This increases the opening rate of these two are opened immediately as it is now certain that the
butterfly valves. axial compressor will pass through the unfavorable
speed range.
Limit switches are provided on all butterfly valves for
monitoring limit positions. − Compressor Washing:
It may be necessary to open blowoff valves 1.1 and 1.2
after compressor washing. A subloop control function is
Open-loop Control provided to ensure that the butterfly valves are opened
Opening and closing of the blowoff valves is controlled and closed in the correct sequence. The details of this
automatically as appropriate to operating conditions. procedure are given in Section 3.4-4962.
− Startup with natural gas or fuel oil: − Protection functions:
rights created by patent grant or registration of a utility
Offenders will be liable for damages. All rights, including
its content is not permitted without express written authority.
The reproduction, transmission or use of this document or

At the onset of startup, all blowoff valves are open. − If any of the blowoff valves is not open during gas
They are sequentially closed as of appr. 76 % rated turbine startup, the start is aborted.
speed. This minimizes the associated sudden changes − A pretrip alarm is annunciated if any of the blowoff
in temperature and output. valves opens during power operation or cannot be
− Power Operation: closed during runup. Other automatic action is not
The blowoff valves always remain closed during power taken.
model or design, are reserved.

operation. − An alarm is annunciated if one blowoff valve is not in its


− Speed drop: "OPEN" position at any speed in the surge-critical
range (e.g. 8 to 95 % rated speed). The surge
Blowoff valves 1.1. and 1.2 are opened if speed drops
protection monitor trips the gas turbine if this condition
below the minimum permissible operating speed (e.g.
causes compressor surging (cf. 3.1-2601).
95 % rated speed) during power operation.
Class: RESTRICTED

Siemens AG 3.1-4411-9022/2
Energieerzeugung KWU MBA 0800E
Gas Turbine Measuring and Supervisory Equipment
Description Combustion Chamber Instrumentation

Refer also to: The following functions are derived from this for control
and monitoring of the GT:
List of Control Settings (SREL) 3.1-2020
P+I Diagram, Gas Turbine 3.1-2600
P+I Diagram, Combustion Chamber 3.1-2602
Natural Gas and Fuel Oil Operation
List of Measuring Instruments 3.1-2620 −= If the gas turbine is running in premix mode and the
Equipment List 3.1-2640 relative pressure drop ∆pCCrel in one combustion
chamber declines to or below PP.BK.01 for more than 5
Settings, limits and measuring ranges of the items of seconds, the GT must be changed over to diffusion
equipment listed here are given in the List of Measuring mode.
Instruments and List of Control Settings (SREL). This
−= Changeover from diffusion mode to premix mode may
description only gives guideline values.
only be enabled if the relative combustion chamber
pressure drop is above limit PP.BK.01 at the onset of
Function the planned changeover. At a ∆pCCrel >PP.BK.01 either
premix or diffusion mode is permitted.
The tasks of the measuring instruments associated with
the combustion chamber system are described in this −= If the relative combustion chamber pressure drop
Section. These measuring instruments are used to detect remains below limit PP.BK.01 for more than five
the pressure drop across the combustion chamber, seconds at speeds above the turbine speed
combustion process instabilities (known as humming), and S.TURB.70, the individual alarm “Relative combustion
chamber pressure drop <MIN” and the group alarm
The reproduction, transmission or use of this document or its
content is not permitted without express written authority.
Offenders will be liable for damages. All rights, including
rights created by patent grant or registration of a utility model

flame out.
“Hybrid burner fault” are annunciated.

Pressure Drop across the Combustion Dual-Fuel Operation


Chamber Because dual-fuel operation is only used with the
Over time, the gas turbine can sustain wear (for natural gas and fuel oil diffusion burners, no control
example increased gaps in the combustion chamber hot measures are necessary if pressure drops below the lower
gas casing), a possible consequence of which is a decline limit PP.BK.01. Individual and group alarms are triggered
or design, are reserved.

in the amount of air reaching the burners due to increased by criteria identical to those in effect during operation on
gap losses. This in turn can jeopardize stable premix natural gas or fuel oil alone.
combustion.
The relative combustion chamber pressure drop can
Monitoring of Measuring Points
generally be considered an indication of the flow of primary If measuring points MBA12CP101 or MBM11-
air through the burners. It is dependent on the combustion CP103/MBM21CP103 indicate positive or negative
chamber geometry, but particularly in the upper output violation of limits the individual alarm “Relative combustion
range is virtually independent of the momentary GT output. chamber pressure drop measurement faulted” and the
The relative combustion chamber pressure drop changes group alarm “Transmitter fault” are annunciated. Rapid
as a result of wear or damage to burner or combustion changeover from premix mode to diffusion mode is not
chamber parts (changes in geometry, changes in flow path performed. If a measuring point fault is not rectified after
cross-section). Long-term monitoring of the relative approximately 24 hours, the changeover from premix to
combustion chamber pressure drop is performed to diffusion mode is made and a corresponding interlock
evaluate the condition of the combustion chambers. activated that prevents changeover back to premix mode.
The differential pressure across each combustion The enable for changeover to premix mode is immediately
chamber ∆pCC is measured using differential pressure deactivated, however, if the positive or negative measuring
transducers MBM11CP103 and MBM21CP103; the range violation is detected.
compressor outlet pressure pCII is measured using
pressure transducer MBA12CP101. This pressure Flame Monitoring
transducer is depicted in the P+ID “Gas Turbine” (3.1-
2600). Signals from these instruments are used to Fuel must never be fed to the gas turbine combustion
calculate the relative combustion chamber pressure drop chambers for an impermissibly long period without
(in percent): combustion taking place. The purpose of flame monitoring
Class: RESTRICTED

is to determine whether the fuel in each combustion


chamber is in fact burning, i.e. whether flames are present.
∆pCC rel. = (∆pCC/pCII) * 100 %
If this is not the case, the supply of fuel is interrupted.

Siemens AG 3.1-2603-0526/1
Power Generation 0403E
Gas Turbine Measuring and Supervisory Equipment
Description Combustion Chamber Instrumentation

Two flame monitoring systems per combustion Actuation of the IGVs and changeover from DM to PM
chamber (MBM11CR101/102 and MBM21CR101/102) are are not blocked. Rapid changeover from premix mode to
provided for monitoring combustion flames. The radiant diffusion mode is not performed.
energy emitted by the flames (UV to IR range) is detected If the measure described in the foregoing is not
and these signals processed for further use. sufficient to eliminate combustion chamber humming, the
At least one flame monitor in each combustion chamber load setpoint of the gas turbine is abruptly reduced by the
must signal “Flame on”. If the readings of the two flame increment E.LEIST.12 if violation of limit P.BRUMM.04
monitors of one combustion chamber do not coincide, the persists for at least 3 seconds.
individual alarm “Flame monitor faulted” is annunciated. Actuation of the IGVs and changeover from DM to PM
Individual alarms are delayed for time K.FLAMM.01 to are not blocked. Pilot control of the IGVs remains active.
prevent premature control action. During the gas turbine Rapid changeover from premix mode to diffusion mode is
startup phase, flame monitor conditions may briefly deviate not performed.
from one another.
FO DM or FO/NG Dual-Fuel Operation
Monitoring of Humming P.BRUMM.04 is not used in these operating modes.
Gas turbines equipped with hybrid burners may If limit P.BRUMM.03 is exceeded for at least two
experience combustion instabilities manifested as seconds the gas turbine load setpoint is continuously
elevated-amplitude combustion chamber pressure decreased at the normal gradient until limit P.BRUMM.03 is
The reproduction, transmission or use of this document or its
content is not permitted without express written authority.
Offenders will be liable for damages. All rights, including
rights created by patent grant or registration of a utility model

fluctuations; this phenomenon is also known as humming no longer violated. A fault alarm is annunciated in such
and has a typical frequency range. Humming must be cases.
promptly detected and eliminated to prevent a further Actuation of the IGVs and changeover from DM to PM
increase in pressure fluctuation amplitudes and possible are not blocked. Pilot control of the IGVs remains active.
consequential damage to components of the gas turbine.
Humming is detected by measuring the amplitudes of Burner Temperature Monitoring in
combustion chamber pressure fluctuations using the two
dynamic pressure sensors MBM11CP102 and
Premix Mode
or design, are reserved.

MBM21CP102 and evaluating their output signals that lie in Rapid output fluctuations during operation in premix
a defined frequency range. modecaused, for example, by rapid pressure fluctuations
Monitoring of humming is only activated when the gas in the natural gas or fuel oil suppliedmay result in the
turbine is running in the speed range intended for extended formation of flames in the diagonal swirler section of the
operation. Monitoring is also blocked during changeover premix burners. Changeover back to diffusion mode must
from DM to PM and vice versa with natural gas. be made in such cases. For this reason burner
temperatures are monitored by two thermocouples per
NG DM/PM or FO PM burner (MBM12CT101 to MBM12CT116 and
MBM22CT101 to MBM22CT116). Temperature is
The limits P.BRUMM.03 and P.BRUMM.04 are
measured at the axial swirler. Faults to individual
stipulated for the effective value of combustion chamber
measuring points do not result in restricted availability.
pressure oscillations; the respective measures to eliminate
Burner temperature monitoring is only required for
combustion chamber humming are triggered if they are
operation on natural gas or fuel oil in premix mode.
exceeded. Triggering occurs if one of the two
Monitoring is not performed in diffusion mode on either
measurements indicates that a limit has been exceeded
natural gas or fuel oil or in dual-fuel mode (with NG + FO).
when monitoring of humming is active. A fault alarm is
annunciated in such cases. Differential temperatures are calculated from the mean
compressor outlet temperature and the temperatures at the
If limit P.BRUMM.03 is exceeded for at least two
axial swirlers. If a differential temperature exceeds limit
seconds the gas turbine load setpoint is continuously
TT.BRENNER.M01 for a period of at least one second, a
decreased at the normal gradient until limit P.BRUMM.03 is
separate individual alarm “Burner (xx) temperature >MAX”
no longer violated or P.BRUMM.04 responds. Control
is annunciated for each affected burner.
action in response to signal P.BRUMM.03 is delayed by the
time K.BRUMM.11 to ensure that load is reduced by a If a differential temperature exceeds the setting
TT.BRENNER.U01 for a period of at least 1 second during
Class: RESTRICTED

sufficient magnitude.
operation in diffusion mode, changeover from diffusion to
premix mode is blocked and the individual alarm “PM

Siemens AG 3.1-2603-0526/2
Power Generation 0403E
Gas Turbine Measuring and Supervisory Equipment
Description Combustion Chamber Instrumentation

blocked” is annunciated. This interlock is deactivated when channels and the individual alarm “Burner temperature
the differential temperature drops below monitoring faulted” is annunciated. After the third channel
TT.BRENNER.U01. fault occurs, rapid changeover from premix to diffusion
If a differential temperature exceeds limit mode is initiated and the individual alarms “Burner
TT.BRENNER.U01 for a period of at least 1 second in temperature monitoring faulted” and “PM blocked” are
premix mode, rapid changeover from premix to diffusion annunciated. The machine cannot be returned to premix
mode is initiated and the individual alarms “Premix mode mode until these channel faults have been rectified. If one
blocked” and “Burner temperature monitoring response” of the axial swirler temperature monitoring channels is
are annunciated. The changeover command is faulted, the invalid reading is excluded from processing and
documented and blocks a change back to premix mode. the individual alarm “Burner temperature monitoring
faulted” is annunciated. If both thermocouples of a given
Changeover from diffusion mode back to premix mode
burner are defective, rapid changeover from premix to
is possible when the corresponding enable criteria have
diffusion mode is initiated and the individual alarm “PM
been met. If limit TT.BRENNER.U01 is exceeded a second
blocked” is annunciated. The machine cannot be returned
time during operation in premix mode, changeover is made
to premix mode until these channel faults have been
to diffusion mode, an interlock prevents resumption of
rectified.
premix mode and the individual alarms “Burner
temperature monitoring response”, “PM blocked”, and
“Perform burner inspection” are annunciated. Operation in Burners
diffusion mode or dual-fuel mode (NG + FO) is still
The reproduction, transmission or use of this document or its
content is not permitted without express written authority.
Offenders will be liable for damages. All rights, including
rights created by patent grant or registration of a utility model

The burners shown in the P+ID are not described in


permissible. This interlock is not deactivated until the GT is
greater detail in this section. Their descriptions are given in
shut down.
the corresponding manual Sections pertaining to fuel.
Compressor outlet temperature measurement channels
identified as defective are excluded from processing; mean
values are calculated using the non-faulted measurement
or design, are reserved. Class: RESTRICTED

Siemens AG 3.1-2603-0526/3
Power Generation 0403E
A 18.08.2005 Complete Revision Lübbers Merz Vogt
C.C. CHKD AT
REV No. DATE REVISION DESCRIPTION PREP. CHKD APPYD.
CHKD. SITE

CONTRACTOR SUB CONTRACTOR

SIEMENS PG
CONTRACTOR: DWG. No SUB CONTRACTOR DWG. No

VAE266-XS00-MBA-357401
CONTRACT JOB. No TITLE

System Description Advance Compressor Cleaning


CNE/121/2004
System (ACCS)
PKZ/PC UA/DCC UNID
VAE266 XS00 453012896
NAME DATE SIZE SCALE SHEETS OF

FIRST ISSUE

PREPARED Merz 05-01-31


CHECKED Pürzer 05-01-31 KKS No.

APPROVED Pfuff 05-01-31


CHECKED AT
MBA
SITE
DRAWING No. REV No. ISSUE SCOPE

CNE/121/2004-B-21-M-M-50620A A

Weitergabe sowie Vervielfältigung, Verbreitung und/oder Bearbeitung dieses Dokumentes, Verwertung und
Siemens Mitteilung seines Inhaltes sind verboten, soweit nicht ausdrücklich gestattet. Zuwiderhandlungen verpflichten
zu Schadenersatz. Alle Rechte für den Fall der Patenterteilung, Gebrauchsmuster- oder
Geschmacksmustereintragung vorbehalten.
Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents
and communication thereof to others without express authorization are prohibited. Offenders will be held
liable for payment of damages. All rights created by patent grant or registration of a utility model or design
patent are reserved.
CoverSheet_SYSDESC_ACCS.doc
Projekt/Anlage: VAE266

System - Beschreibung
Project/Plant:

Description

System Weiterentwickeltes Verdichterreinigungssystem MBA30 Seiten/Pages: ...4......


Anlagen/Appendices: ...--......
Advanced Compressor Cleaning System (ACCS) MBA30

UNID
VAE266 XS00 MBA-357401 453012896
Proj.-Kennz./Proj. Code UA/Doc. Inhaltskennzeichen/Contents Code

Zugehörige Systemschaltpläne/ Handhabung: RESTRIKTIV


Related P & I Diagrams: Handling: RESTRICTED

P&I DIAGRAM VAE266-XG02-MBA-357401 UNID 453168951

freigegeben durch/released by
In- Erstellung bzw.
dex Datum Änderungen (Seiten) Dienststelle bearbeitet durch geprüft durch intern extern
Date Office prepared by reviewed by Internal external
Rev. Issue resp.
Modifications (Pages).

Complete Revision
A 18.08.05 G133 J. Lübbers A. Merz A. Vogt 1)

2)

1) Name in Druckbuchstaben/Name in block letters


2) Unterschrift/Signature

Siemens AG .Power Generation G133


File: SysDescACCS_a .doc
H30-K5560-X-X-400 07.93 B Deckblatt
Projekt/Anlage: Kapitel/Chapter
VAE266 Seite/Page
Beschreibung Project/Plant:
System-
Description System MBA30 Index/Revision A

Inhalt/Contents
Seite/Page
1 Allgemeines 1

1. General 1

2 Aufbau des System 1

2. System Configuration 1

3. Reinigungsmodi 1

3. Cleaning Modes 1
3.1 ON-Line Reinigung 2
3.1 On-line Cleaning 2
3.2 OFF-Line Reinigung 2
3.2 Off-line Cleaning 2
4. Düsensystem 3

4. Nozzle System 3

5 Verdichterreinigungspackage 3

5. Compressor Cleaning Package 3

6. Druckluftsystem 4

6. Compressed Air System 4

Siemens AG Power Generation G133


File: SysDescACCS_a .doc
H30-K6056-X-X-7400 02.92 B mit Grafikrahmen
Projekt/Anlage: Kapitel/Chapter
VAE266 Seite/Page
Beschreibung Project/Plant:
-1-
System-
Description System MBA30 Index/Revision A

1 Allgemeines 1. General
Beim Betrieb einer Gasturbine kommt es trotz During operation of a gas turbine, soiling of
sorgfältiger Filterung der Ansaugluft zu einer blading occurs despite thorough filtration of
Verschmutzung der Beschaufelung, vor allem the intake air; such soiling occurs particularly
beim Verdichter. in the compressor section.
Verschmutzte Schaufeln führen zu weniger Blading deposits reduce output and the effi-
Leistung und verschlechtern den ciency of the gas turbine. Performing a com-
Wirkungsgrad der Gasturbine. Durch eine pressor cleaning operation removes deposits
Verdichterreinigung werden from the compressor airfoils and restores lost
Verschmutzungen der Verdichterschaufeln gas turbine output.
entfernt, und Leistung der Gasturbine
zurückgewonnen.

2 Aufbau des Systems 2. System Configuration


Für die Durchführung einer Verdichterwäsche Two systems are required for performing
sind zwei Systeme nötig: ein Düsensystem (s. compressor washing: a nozzle system (cf. 4)
4), welches Reinigungsflüssigkeit in den that injects cleaning fluid into the intake duct
Ansaugkanal der Gasturbine eindüst, und ein of the gas turbine and a compressor cleaning
Verdichterreinigungspackage (s. 5) mit Hilfe package (cf. 5) that is used to mix and supply
dessen die Reinigungsflüssigkeit voll the cleaning fluid to the nozzle system in a
automatisch angesetzt und dem Düsensystem fully automatic process.
zugeführt wird.
Das Package wird durch eine lokale SPS ge- The package is controlled by a local PLC.
steuert, von der ein Signalaustausch zur A data link connects the control unit of the
Leittechnik des Kraftwerks besteht. package to the power plant I&C system. This
Damit kann dieses von der Warte aus bedient makes it possible to perform remote control
werden. actions from there.

3 Reinigungsmodi 3. Cleaning Modes


Die Reinigung des Gasturbinenverdichters ist Cleaning of the gas turbine compressor is
sowohl während des Nennbetriebes (ON-line), possible both during rated plant operation
als auch bei Betrieb der Maschine mit Anfahr- (on-line cleaning) and during operation with
umrichterbetrieb (OFF-line) möglich. the Startup Frequency Converter (off-line).

Beide Reinigungsverfahren nutzen das Both cleaning operations use the same noz-
gleiche Düsensystem, unterscheiden sich zle system but differ in terms of their effec-
aber in der Wirksamkeit, in der tiveness, the procedure followed, and the
Vorgehensweise und bei der zum Einsatz cleaning fluid that is injected. Corresponding
kommenden Reinigungsflüssigkeit. Die data for the composition of this medium are
Zusammensetzung dieses Mediums ist stored in the control unit of the compressor
entsprechend in der Steuerung des cleaning package.
Verdichterreinigungspackage hinterlegt.

Detaillierte Beschreibungen beider Reini- Detailed description of both cleaning modes


gungsvorgänge sind in den Dokumentations- are contained in the documentation of the
unterlagen des Verdichterreinigungssystems compressor cleaning system.
enthalten.

Siemens AG Power Generation G133


File: SysDescACCS_a .doc
H30-K6056-X-X-7400 02.92 B mit Grafikrahmen
Projekt/Anlage: Kapitel/Chapter
VAE266 Seite/Page
Beschreibung Project/Plant:
-2-
System-
Description System MBA30 Index/Revision A

3.1 ON-Line Reinigung 3.1 On-line Cleaning


Für eine Verdichterreinigung während des Performance of compressor cleaning during
Betriebes sind einige Betriebsparameter der plant operation requires consideration of sev-
Gasturbine zu berücksichtigen. Zum Beispiel eral gas turbine operating parameters. For
muss die Leistung der Gasturbine geringfügig instance the gas turbine output has to be re-
von der Nennleistung abgesenkt werden. duced slightly from base load.
ON-line Reinigung kann mit reinem Deionat On-line cleaning can employ either straight
oder auch mit Reinigerzusatz durchgeführt demineralized water or demineralized water
werden. Die Reinigungsflüssigkeit, welche to which a cleaning agent has been added.
vom Package nach Vorgabe zur Verfügung The cleaning fluid supplied by the package as
gestellt wird, wird über den Düsenring (s. 4) in required for cleaning is injected via the nozzle
den Luftansaugkanal der Gasturbine ring (cf. 4) into the gas turbine intake duct.
eingedüst. Nach Beendigung des The GT can be returned to operation at full
Reinigungsvorganges kann die Gasturbine load after completion of the cleaning opera-
wieder auf Volllast hochgefahren werden. tion.
Der Zeitaufwand liegt zwischen 5 und 10 Time required ranges between 5 and 10 min-
Minuten. Es wird empfohlen eine ON-line utes. It is recommended that on-line cleaning
Reinigung täglich durchzuführen und je nach be performed daily and, depending on how
Verschmutzungszunahme regelmäßig auch fast deposits build up, that an approved
Reinigerzusatz zu verwenden. cleaning agent is also used regularly.
Die ON-line Wäsche dient dazu die Intervalle On-line cleaning is intended to extend the
zwischen den OFF-line Wäschen sinnvoll zu intervals between off-line cleaning operations
verlängern, um Stillstandzeiten zu verringern. within reasonable limits and thus to avoid
plant outages.

3.2 OFF-Line Reinigung 3.2 Off-line Cleaning


Durch die OFF-line Wäsche lässt sich die Off-line cleaning makes it possible to nearly
Leistung der Gasturbine nahezu wieder auf restore gas turbine output to the levels indi-
die Leistung entsprechend der Alterungskurve cated by the aging curve.
anheben.
Dazu wird im ersten von vier Schritten die This involves shutting down the gas turbine in
Gasturbine heruntergefahren und zum Ab- the first of four steps and rotating its shaft for
kühlen mittels Dreheinrichtung gedreht. Im cooling with the turning gear. In the second
zweiten Schritt „Einweichen“ wird dann die step “soaking” the premixed cleaning fluid is
angesetzte Reinigungsflüssigkeit über den injected via the nozzlering (cf. 4). Therefor the
Düsenring (s. 4) eingespritzt. Dafür wird die turbine is accelerated to cleaning speed by
Gasturbine mittels Anfahrumrichter auf startup frequency converter. The soaking
Waschdrehzahl beschleunigt. Wenn alle phase follows when all internal parts have
Maschinenteile benetzt sind, folgt eine been wetted.
Einweichzeit.
Der Ablauf des nächsten Schrittes „Spülen“ ist Except for demineralized water being injected
analog zum Einweichen, mit dem Unterschied, the procedure of the following step “flushing”
dass reines Deionat eingedüst wird. Nach is analogous to soaking. After the off-line
erfolgter Off-line Reinigung kann die Gastur- cleaning has been concluded, the gas turbine
bine entweder wieder in Betrieb genommen, can be returned to commercial operation, or
oder nach einer abschließenden Trocknungs- shut down after a drying phase.
phase stillgesetzt werden.
Der Zeitaufwand liegt insgesamt bei 8 bis 10 A total of 8 to 10 hours are required.
Stunden.

Siemens AG Power Generation G133


File: SysDescACCS_a .doc
H30-K6056-X-X-7400 02.92 B mit Grafikrahmen
Projekt/Anlage: Kapitel/Chapter
VAE266 Seite/Page
Beschreibung Project/Plant:
-3-
System-
Description System MBA30 Index/Revision A

4 Düsensystem 4. Nozzle System


Das Düsensystem zur Verdichterreinigung The nozzle system used for compressor
einschließlich der Verrohrung und Armaturen cleaning, including piping and fittings up to
bis zur Wand des Ansaughauses gehören the wall of the intake structure, is part of the
zum Lieferumfang des Luftansaugsystems. air intake system scope of supply.
Es besteht aus einer Ringleitung auf der eine It comprises a ring line onto which a defined
bestimmte Anzahl von langgezogenen number of long conical spray pattern nozzles
Kegelstrahldüsen MBA30BN001 geschweißt (MBA30BN001) are welded. This ring line is
ist. Sie befindet sich im Luftansaugkanal um mounted in the air intake duct concentric to
den Innenkonus vor dem Verdichtereintritt. and upstream of the inner compressor inlet
Diese Düsen zerstäuben das cone. These nozzles atomize the cleaning
Reinigungsmedium und bringen die feinen medium and spray fine droplets well into the
Tröpfchen tief in den Luftstrom ein. flow of air.
Es ist nicht nötig, dass die Fluidpartikeln direkt It is not necessary for the fluid particels to
die Verdichterschaufeln erreichen, die reach the compressor airfoils directly, the flow
vorbeiströmenden Ansaugluft reißt die of intake air entrains the fluid drops into the
Tröpfchen mit in den Gasturbinenverdichter. gas turbine compressor.

5 Verdichterreinigungspackage 5. Compressor Cleaning Package


Zur Versorgung der Düsen für die The compressor cleaning package is required
Verdichterwäsche mit Reinigungsflüssigkeit to supply the cleaning fluid used for compres-
wird das Verdichterwaschpackage benötigt. sor washing to the nozzles.
Es ist im wesentlichen eine It essentially comprises a pressure boost sta-
Druckerhöhungsstation mit den tion and associated components. The pack-
dazugehörigen Komponenten. Das Package age is mounted on a frame constructed of
ist auf einen Profilrahmen montiert und in der steel sections that is installed at a fixed loca-
nächsten Umgebung zur Gasturbine fest tion in the immediate vicinity of the gas tur-
installiert. Bis zu drei Turbinen können von bine. Up to three gas turbines can be sup-
einem Package mit Reinigungsflüssigkeit plied with cleaning fluid from one such pack-
versorgt werden. age.
Die wichtigsten Komponenten auf dem The most important components of the com-
Verdichterwaschpackage sind eine pressor cleaning package are centrifugal
Förderpumpe MBA30AP001 für das pump MBA30AP001 that forwards the clean-
Reinigungsmediums, sowie Vorratsbehälter ing medium and storage tanks for demineral-
für Deionat MBA31BB001 und ized water MBA31BB001 and MBA32BB001
Reinigungsmittel MBA32BB001. Das Deionat for cleaning agent. Demineralized water is
wird über einen Anschluss an das vorhandene filled into the tank from the demineralized wa-
VE-Wasserleitungsnetz, und das ter system, the cleaning agent is added to the
Reinigungsmittel mittels Fasspumpe aus dem cleaning package tank from a storage tank
Vorratstank nachgefüllt. Das Reinigungsmittel using a drum pump. Cleaning agent is auto-
wird durch eine Dosierpumpe MBA32AP001 matically supplied by dosing pump
automatisch zudosiert und mit dem Deionat MBA32AP001 and homogeneously mixed
homogenisiert. with demineralized water.

Im Reinigungsbetrieb fördert die Pumpe During the cleaning operation the pump for-
dieses Reinigungsmedium mit einem wards the cleaning medium at a pressure of
Überdruck von min. 6 bar über eine fest at least 6bar(g) through a permanently-
installierte Rohrleitung in das Düsensystem installed pipe to the nozzle system of the GT.
der Gasturbine.

Siemens AG Power Generation G133


File: SysDescACCS_a .doc
H30-K6056-X-X-7400 02.92 B mit Grafikrahmen
Projekt/Anlage: Kapitel/Chapter
VAE266 Seite/Page
Beschreibung Project/Plant:
-4-
System-
Description System MBA30 Index/Revision A

6 Druckluftsystem 6. Compressed Air System


Das Verdichterreinigungspackage ist zudem Furthermore, the compressor cleaning pack-
mit einem Druckluftsystem ausgerüstet. age is equipped with a compressed air sys-
Dieses dient zum Einen der Steuerung tem. The latter is used on the one hand to
wesentlicher Armaturen des Package, und supply the main valves of the package and on
zum Anderen wird damit nach Ende eines the other to blow out any cleaning fluid re-
Reinigungsschrittes die noch in den maining in system piping when a cleaning
Rohrleitungen befindliche step has been completed. This prevents
Reinigungsflüssigkeit ausgeblasen. Damit wird separation of the cleaning medium in these
vermieden, dass sich zwischen den lines during breaks between intermittent
Betriebszeiten des Package das package operation; after separation water
Reinigungsmedium in den Leitungen could either freeze directly or form ice crystals
entmischt und direkt gefriert oder erst beim the next time the package is used, which
nächsten Einsatz Vereisung und damit could then cause damage to the gas turbine.
möglichen Schaden an der Gasturbine
verursacht.
Gespeist wird das System von dem örtlich The system is supplied from the compressed
vorhandenen Druckluftnetz oder optional von air network that is installed locally, or option-
einem beigestelltem Kompressor. ally from a supplied compressor.

Siemens AG Power Generation G133


File: SysDescACCS_a .doc
H30-K6056-X-X-7400 02.92 B mit Grafikrahmen
Aweer Gas Turbine Power Station 'H' (Phase II) Part 2
SIEMENS Operating Manual (Overall Plant)
Section 5.1
Gas Turbine MB
Revision a

Chapter 2: P&I Diagrams

List of P & I Diagrams


800585-MBA9B-001-A01 UNID: 452979169 Rev.: f MBA, MBD Gas Turbine
800585-MBA9E-001-A01 UNID: 452979190 Rev.: i MBA Drainage

800585-MBA9A-001-A01 UNID: 452979077 Rev.: d MBA Blow Off System


800585-MBM9A-001-A01 UNID: 452979220 Rev.: d MBM;MBP Combustion Chamber
Measuring Devices
CNE/121/2004-B-21-M-R-50610 UNID: 453168951 Rev.: e MBA Advanced Compressor
Cleaning System (ACCS)

This document is subject to the restrictions set forth on the first or title page.
Aweer Gas Turbine Power Station 'H' (Phase II) Part 2
SIEMENS Operating Manual (Overall Plant)
Section 5.1
Gas Turbine MB
Revision a

Chapter 3: Requirements for Operation

This document is subject to the restrictions set forth on the first or title page.
Aweer Gas Turbine Power Station 'H' (Phase II) Part 2

SIEMENS Operating Manual (Overall Plant) Section 5.1

Gas Turbine MB Page 1/9

Revision a

Table of Contents
1 Manual Valve Position List ................................................................................. 2
1.1 Gas Turbine – 41MBA .........................................................................................................2
1.2 Compressor Cleaning – 41MBA ..........................................................................................2
1.3 Combustion Chamber – 41MBM .........................................................................................3

2 Operational Readiness......................................................................................... 4
2.1 Checks on Site.....................................................................................................................4
2.2 Checks on OM-System ........................................................................................................4

3 Open Loop Controls ............................................................................................ 5


3.1 "SGC GAS TURBINE" – 41MYB01 EC001 .........................................................................5
3.1.1 Start-up Procedure ..............................................................................................................................5
3.1.2 Shutdown Procedure...........................................................................................................................8

This document is subject to the restrictions set forth on the first or title page.
Aweer Gas Turbine Power Station 'H' (Phase II) Part 2

SIEMENS Operating Manual (Overall Plant) Section 5.1

Gas Turbine MB Page 2/9

Revision a

1 Manual Valve Position List 1


1.1 Gas Turbine – 41MBA
SHUT-OFF VALVE OPEN 41MBA11 AA301 ‰
SHUT-OFF VALVE OPEN 41MBA11 AA341 ‰
SHUT-OFF VALVE OPEN 41MBA11 AA342 ‰
SHUT-OFF VALVE OPEN 41MBA11 AA343 ‰
SHUT-OFF VALVE OPEN 41MBA11 AA371 ‰
SHUT-OFF VALVE OPEN 41MBA11 AA372 ‰
SHUT-OFF VALVE OPEN 41MBA11 AA373 ‰

SHUT-OFF COCK CLOSED 41MBA11 AA401 ‰


SHUT-OFF COCK CLOSED 41MBA11 AA402 ‰

SHUT-OFF VALVE OPEN 41MBA12 AA301 ‰


SHUT-OFF VALVE OPEN 41MBA12 AA302 ‰
SHUT-OFF VALVE CLOSED 41MBA12 AA321 ‰

SHUT-OFF COCK CLOSED 41MBA12 AA401 ‰

DRAIN, CENTRE CASING CLOSED 41MBA18 AA253 ‰


DRAIN, CENTRE CASING CLOSED 41MBA18 AA254 ‰
DRAIN, CENTRE CASING CLOSED 41MBA18 AA255 ‰
DRAIN, EXHAUST CASING CLOSED 41MBA18 AA256 ‰
DRAIN, CENTRE CASING CLOSED 41MBA18 AA257 ‰
DRAIN, COMB. CHAMBER CLOSED 41MBA18 AA258 ‰
DRAIN, BLOW-OFF PIPING CLOSED 41MBA18 AA261 ‰
DRAIN, MBA18BB001 OPEN2 41MBA18 AA262 ‰

SHUT-OFF VALVE OPEN 41MBA21 AA341 ‰


SHUT-OFF VALVE OPEN 41MBA21 AA371 ‰

SHUT-OFF VALVE CLOSED 41MBA21 AA401 ‰

SHUT-OFF VALVE CLOSED 41MBA40 AA251 ‰


SHUT-OFF VALVE OPEN 41MBA40 AA401 ‰

1.2 Compressor Cleaning – 41MBA


SHUT-OFF VALVE OPEN 41MBA30 AA251 ‰
SHUT-OFF VALVE OPEN 41MBA30 AA301 ‰

1
The KKS identifiers prefixed with "41" have to be adapted for the other gas turbines by changing the identifiers
prefix to "42" or "43".
2
This valve may only be closed during change-over of the drains disposal tank.

This document is subject to the restrictions set forth on the first or title page.
Aweer Gas Turbine Power Station 'H' (Phase II) Part 2

SIEMENS Operating Manual (Overall Plant) Section 5.1

Gas Turbine MB Page 3/9

Revision a

SHUT-OFF VALVE OPEN 41MBA31 AA301 ‰


SHUT-OFF VALVE OPEN 41MBA31 AA311 ‰
DRAIN VALVE MIXTURE TANK CLOSED 41MBA31 AA??? ‰

SHUT-OFF VALVE OPEN 41MBA32 AA251 ‰


SHUT-OFF VALVE OPEN 41MBA32 AA301 ‰
DRAIN VALVE CLEANER TANK CLOSED 41MBA32 AA??? ‰

SHUT-OFF VALVE OPEN 41MBA34 AA301 ‰


SHUT-OFF VALVE OPEN 41MBA34 AA302 ‰

1.3 Combustion Chamber – 41MBM

SHUT-OFF VALVE OPEN 41MBM11 AA342 ‰


SHUT-OFF VALVE OPEN 41MBM11 AA372 ‰

SHUT-OFF VALVE CLOSED 41MBM11 AA401 ‰


SHUT-OFF COCK CLOSED 41MBM11 AA402 ‰

SHUT-OFF VALVE OPEN 41MBM21 AA342 ‰


SHUT-OFF VALVE OPEN 41MBM21 AA372 ‰

SHUT-OFF VALVE CLOSED 41MBM21 AA401 ‰


SHUT-OFF VALVE CLOSED 41MBM21 AA402 ‰

This document is subject to the restrictions set forth on the first or title page.
Aweer Gas Turbine Power Station 'H' (Phase II) Part 2

SIEMENS Operating Manual (Overall Plant) Section 5.1

Gas Turbine MB Page 4/9

Revision a

2 Operational Readiness3
2.1 Checks on Site
MANUAL VALVES ACCORDING TO POSITION LIST SET 41MBA ‰
41MBM ‰

DISPOSAL TANK D/STR 41MBA18 AA262 READY/DRAINED ‰


DISPOSAL SYSTEM D/STR 41MBA18 AA003 READY ‰

2.2 Checks on OM-System


SGC GAS TURBINE CB S/D 41MYB01 EC001 ‰
SGC GAS TURBINE RDY F SR 41MYB01 EC001 ‰

ANTI COND HEAT COMPR ON 41MBA10 AT001 ‰

FO DRAIN VALVE 1 OPEN 41MBA18 AA001 ‰


FO DRAIN VALVE 2 OPEN 41MBA18 AA002 ‰
FO DRAIN VALVE 3 OPEN 41MBA18 AA003 ‰

COMPR BLOWOFFS 1.1/2 OPEN 41MBA41 AA050 ‰


COMPR BLOWOFF 2 OPEN 41MBA42 AA051 ‰

The blowoff valves are opened during shutdown of


the gas turbine. If one blowoff valve is still in the
closed position, e.g. due to a fault, the blowoff valve
has to be opened with auxiliary compressed air via
the shutoff valve 41MBA40 AA251.
The reason for the opening failure has to be deter-
mined and rectified before start-up.
The gas turbine systems 41MBA / 41MBM are ready for the
start-up of the unit.

3
The KKS identifiers prefixed with "41" have to be adapted for the other gas turbines by changing the identifiers
prefix to "42" or "43".

This document is subject to the restrictions set forth on the first or title page.
Aweer Gas Turbine Power Station 'H' (Phase II) Part 2

SIEMENS Operating Manual (Overall Plant) Section 5.1

Gas Turbine MB Page 5/9

Revision a

3 Open Loop Controls 4


3.1 "SGC GAS TURBINE" – 41MYB01 EC001
The subgroup control "SGC GAS TURBINE" – 41MYB01 EC001 controls the open loop controls of the gas turbine
and the gas turbine related subgroup controls during start-up and shutdown of the gas turbine.

3.1.1 Start-up Procedure


The start-up program of the "SGC GAS TURBINE" – 41MYB01 EC001 is activated manually via the OM system.

Enabling Criteria

41MYB01 EC001
RELEASE MEMORY FOR START STEP 58 SET

41MKA70 EU010 ZV02


COLD GAS GEN PROT RELS

41MBA18 EU002 ZV03


FO DRAIN VALVES SR RELS

41SAM30 EE001 ZV02


GT ENCL VENT CTRL ON DLYD

41MBN00 EU001 ZV02


FO S/O SYSTEM CLOSED

41MBP00 EU001 ZV02


NG S/O SYSTEM CLOSED

41MBY10 DU090 XM13


GT CONTROLLER OK

41CHA00 EU001 ZV01


PROT CUB PWR SUPPLY FAULT

41CHB00 EU001 ZV01


PROT CUB PWR SUPPLY FAULT

41BYY00 EU001 ZV01


UNIT SWITCHGEARS FAULT

41MBJ01 DE003 XG03


START UP FREQ CONV BLOCKED

41MKC01 DE003 XG03


EXCITATION EQUIPMENT BLOCKED

41MYB01 EZ100 ZV01


GT PROTECTION FAILURE

&

4
The KKS identifiers prefixed with "41" have to be adapted for the other gas turbines by changing the identifiers
prefix to "42" or "43".

This document is subject to the restrictions set forth on the first or title page.
Aweer Gas Turbine Power Station 'H' (Phase II) Part 2

SIEMENS Operating Manual (Overall Plant) Section 5.1

Gas Turbine MB Page 6/9

Revision a

41MBV41 EU001 ZV02


COOLING TURNING SR RELS

41MBV10 EU001 ZV01


TEMP LUB OIL TANK > MIN

41MYB01 EZ001 ZV10


GT TRIP CIRCUIT RELS SGC

41MBN82 EU001 ZV02


FO PO FLUSHING CLOSED

41MKA11 CL021 XG51


L LIQ GEN CSG TE < MAX

41MKA11 CL022 XG51


L LIQ GEN CSG < MAX

41MKA11 CL041 XG51


L LIQ GEN CSG EE < MAX

41MKA11 CL042 XG51


L LIQ GEN CSG < MAX

5
42CHB00 EU001 ZV01
PROT CUB PWR SUPPLY FAULT

Preparation for Gas Turbine Start-up (S01-07)

At first it is checked that the start-up frequency converter is in normal start mode.

The subgroup controls "SGC NATURAL GAS" – 41MBP01 EC001 and "SGC FUEL OIL" – 41MBN01 EC001 are
switched on (set to automatic mode) and the lube oil system is started up by activating the start-up program of the
subgroup control "SGC LUB OIL/TRN SYST" – 41MBV01 EC001.

The air dryer of the gas turbine compressor (41MBA10 AT001) is switched off and the memory "COMPR AIR S/O"
– 41MBL20 EE010 is activated. The IGV controller (41MBY10 DT040) is switched on.

The hydraulic oil system is started up by switching on the preselected hydraulic pump (41MBX02 AP001/002) via
the subloop control "SLC PRESSURE KEEPING" - 41MBX00 EE010. If pressure build-up is delayed, the standby
pump is switched on additionally.

5
This release criteria from the protection cubicle of another unit is only applicable for unit 41.

This document is subject to the restrictions set forth on the first or title page.
Aweer Gas Turbine Power Station 'H' (Phase II) Part 2

SIEMENS Operating Manual (Overall Plant) Section 5.1

Gas Turbine MB Page 7/9

Revision a

The fuel oil drain valves 1-3 (41MBA18 AA001/ AA002/ AA003) are closed.

The generator forced cooling system is activated by switching on the subloop controls "SLC GEN GLG PUMPS" -
41MPR10 EE010 and "SLC GEN CLG FANS" - 41MPR30 EE010.

The automated bus bar transfer for the LV switchgears 41BFE/BME is enabled by switching on the subloop control
"LV CHANGE-OVER" - 41BFE00 EE010.

The subloop control for the generator air dryer 41MKA05 EE001 is switched on. The generator voltage controller is
switched to automatic mode and the synchronizing selectors of the generator circuit breaker, HV unit circuit break-
er and unit auxiliary circuit breaker are set to "not selected".

It is ensured that the blow-off valves (41MBA41 AA051/052, 41MBA42 AA051) are opened.

The start-up frequency converter is prepared for start-up of the gas turbine.

Start-up of the Selected Fuel System (S08)

Dependent on the fuel preselection, the start-up program of the subgroup control "SGC FUEL OIL" – 41MBN01
EC001 or "SGC NATURAL GAS" – 41MBP01 EC001 is activated.

The "SGC FUEL OIL" – 41MBN01 EC001 or "SGC NATURAL GAS" – 41MBP01 EC001 accelerate the gas tur-
bine up to a speed of > 15.0 s-1.

Monitoring Run-up of the Gas Turbine to Nominal Speed (S09-10)

The gas turbine is accelerated further. At a turbine speed > 38.6 s-1 the start-up frequency converter is switched off
and the external isolator for the SFC is opened. The combustion accelerates the gas turbine further up to nominal
speed.

Synchronising of the Generator to the Grid and Load Increase (S11-16)

Now the excitation unit is switched on and the selection of the generator circuit breaker is set to "automatic" mode.
The synchronising system is activated, the auto-paralleling device is switched on and the gas turbine is synchro-
nised to the grid at the generator circuit breaker.

This document is subject to the restrictions set forth on the first or title page.
Aweer Gas Turbine Power Station 'H' (Phase II) Part 2

SIEMENS Operating Manual (Overall Plant) Section 5.1

Gas Turbine MB Page 8/9

Revision a

3.1.2 Shutdown Procedure


The shutdown program of the "SGC GAS TURBINE" – 41MYB01 EC001 is activated manually via the OM system.

Enabling Criteria

No enabling criteria available.

Unloading GT and Disconnecting Generator from Grid (S51-55)

The start-up frequency converter is switched off (in the event of a failed start). The subgroup control "SGC GAS
TURBINE" – 41MYB01 EC001 unloads the gas turbine to a load < 8 MW.

If the gas turbine is running in premix mode, selection of the shutdown program and unloading of the gas turbine
results in automatic switch-over to diffusion mode.

The gas turbine is unloaded further until the active power has dropped below 1.5 MW. Now the generator circuit
breaker (41BAC01 GS001) is opened. When the gas turbine is disconnected from the grid, the excitation unit is
switched off.

Shutdown of the Fuel System (S56)

Dependent on the fuel selection, the shutdown program of the subgroup control "SGC FUEL OIL" – 41MBN01
EC001 or "SGC NATURAL GAS" – 41MBP01 EC001 is activated and gas turbine trip is initiated.

GT Running Down (S57-58)

When the subgroup control "SGC FUEL OIL" – 41MBN01 EC001 has reached step 55 or the "SGC NATURAL
GAS" – 41MBP01 EC001 has reached step 53, the subgroup control "SGC GAS TURBINE" – 41MYB01 EC001
observes the further coast-down of the gas turbine.

When the gas turbine has reached a speed < 12.5 s-1, the fuel oil drain valves 1-3 (41MBA18 AA001/002/003) are
opened for draining unburned fuel oil in case of a failed start.

When the turbine speed has fallen below 7.6 s-1, the "SGC GAS TURBINE" – 41MYB01 EC001 proceeds to step
58 and is released for start-up again..

This document is subject to the restrictions set forth on the first or title page.
Aweer Gas Turbine Power Station 'H' (Phase II) Part 2

SIEMENS Operating Manual (Overall Plant) Section 5.1

Gas Turbine MB Page 9/9

Revision a

Starting Turning Operation (S59-62)

When the turbine speed is < 3.0 s-1, the generator forced cooling system is de-activated by switching off the
subloop controls "SLC GEN GLG PUMPS" - 41MPR10 EE010 and "SLC GEN CLG FANS" - 41MPR30 EE010.

The hydraulic oil system is shut down by switching off the hydraulic pumps (41MBX02 AP001/002).

The subloop control for the generator air dryer (41MKA05 EE001) is switched on. The shutdown program of the
subgroup control "SGC LUB OIL/TRN SYST" – 41MBV01 EC001 is activated. As the gas turbine slows down to
turning speed, the lube oil / turning gear system takes over the task of cooling down the gas turbine.

On receiving the corresponding feedback signals, the subgroup control "SGC GAS TURBINE" – 41MYB01 EC001
reaches the last step.

This document is subject to the restrictions set forth on the first or title page.

S-ar putea să vă placă și