Documente Academic
Documente Profesional
Documente Cultură
Renewable Energy
journal homepage: www.elsevier.com/locate/renene
a r t i c l e i n f o a b s t r a c t
Article history: The energy and exergy flow for a space heating systems of a typical residential building of natural
Received 2 May 2009 ventilation system with different heat generation plants have been modeled and compared. The aim of
Accepted 5 October 2009 this comparison is to demonstrate which system leads to an efficient conversion and supply of energy/
Available online 31 October 2009
exergy within a building system.
The analysis of a fossil plant heating system has been done with a typical building simulation software
Keywords:
IDA–ICE. A zone model of a building with natural ventilation is considered and heat is being supplied by
Ground source heat pump system
condensing boiler. The same zone model is applied for other cases of building heating systems where
Air source heat pump system
Conventional system power generation plants are considered as ground and air source heat pumps at different operating
Energy analysis conditions. Since there is no inbuilt simulation model for heat pumps in IDA–ICE, different COP curves of
Exergy analysis the earlier studies of heat pumps are taken into account for the evaluation of the heat pump input and
output energy.
The outcome of the energy and exergy flow analysis revealed that the ground source heat pump
heating system is better than air source heat pump or conventional heating system. The realistic
and efficient system in this study ‘‘ground source heat pump with condenser inlet temperature 30 C and
varying evaporator inlet temperature’’ has roughly 25% less demand of absolute primary energy and
exergy whereas about 50% high overall primary coefficient of performance and overall primary exergy
efficiency than base case (conventional system). The consequence of low absolute energy and exergy
demands and high efficiencies lead to a sustainable building heating system.
Ó 2009 Elsevier Ltd. All rights reserved.
1. Introduction ground coupled heat pump over air source heat pump that has
extreme low outside temperatures at severe weather conditions and
The use of energy in the building sector for heating and cooling is lead to high operational energy consumption. Capital cost of GCHPs
nearly one third of the total energy consumed in the world [16]. As is 30–50% more expensive than air source heat pumps, which is
there is growing concern in the use of fossil fuels that is being a major hurdle in gaining overwhelming demand despite having
depleted soon and because of the sustainability issue, an alternative several advantages. Nevertheless, the annual operation cost is less
source of energy must be found to meet energy supply of high making the unit justifiable over the life time operation [12]. As heat
energy consumption sector. The building sector is one of the pumps are advantageous from the energy, environment and
prominent sectors, which could save tremendous amount of fossil sustainability point of view, efforts should focus on to show scien-
fuels if renewable energy source like ground coupled heat pumps tific evidence to the knowledge body of the society. Thermodynamic
(GCHPs) substituted them. The use of GCHPs is growing significantly analysis of the system would produce scientific results that help
in commercial and residential sectors and has numerous advantages convince scientific knowledge body to propel the system at large.
over air source heat pumps as described by [11]. The increase in Thermal analysis of a system focuses on first law and second law
interest to the heat pumps is due to their high utilization efficiency of thermodynamics. First law deals with energy balance of a system
over conventional heating and cooling systems. More or less whereas second law address energy and entropy of a system, it
constant temperature over the year is an important feature of the gives in depth of the system operations. Combining first law and
second law of thermodynamics is necessary for exergy analysis of
* Corresponding author. Tel.: þ4791004758. the system that gives detail know how of the performance evalu-
E-mail address: splohani@daad-alumni.de (S.P. Lohani). ation and optimization of the system. Exergy analysis is the basis
0960-1481/$ – see front matter Ó 2009 Elsevier Ltd. All rights reserved.
doi:10.1016/j.renene.2009.10.002
1276 S.P. Lohani, D. Schmidt / Renewable Energy 35 (2010) 1275–1282
Indices
in Inlet
for identifying irreversibility of the system and is helpful to The environment or system surrounding is considered as large
minimize entropy generation in a process where heat and work thermal reservoir and has no influence of local activity of
interaction takes place [1]. Exergy analysis is an important tool to source or sink.
determine how efficient thermal systems can be designed or in Reference temperature is taken as dynamic environment
other words it can reveal unavoidable thermal inefficiencies of the temperature and atmospheric pressure.
system [4].
Few numbers of experimental investigations of ground coupled
heat pumps in building application based on exergetic analysis has
been published [5–8,13]. However, all analysis has been performed 2.1. Balance equation for building system
with steady state condition.
Theoretical investigation of similar system has not yet been When the abovementioned assumption is observed, the exergy
published to the knowledge of the author. This study intends to is basically divided into four different subcomponents, physical
carry out dynamic energy analysis and quasi static exergy analysis exergy ExPH, chemical exergy ExCH, kinetic exergy ExKN and potential
of the system on theoretical basis. exergy ExPT [1]. However, physical exergy is considered as impor-
tant while dealing with heat and mass interactions of the systems.
Total exergy of a system can be written as following equations.
1 3 4 5
zfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflffl
ffl}|fflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflffl{
zfflfflfflffl}|fflfflfflffl{ 2 zfflfflfflfflfflfflfflfflffl
ffl}|fflfflfflfflfflfflfflfflffl
ffl{ zfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflffl}|fflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflffl{
zfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflffl
ffl}|fflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflffl
ffl{
Ti _ T0 Tret Tin
_
m,c, ðTi T0 Þ T0 ,ln Sgen ,T0 ¼ Qh , 1 _
þm,c, ðTret TÞ T0 ,ln _
þ m,c,ð1 hF Þ ðTin Tret Þ T0 ,ln
T0 Th T0 Tret
(4)
S.P. Lohani, D. Schmidt / Renewable Energy 35 (2010) 1275–1282 1277
about 20%, hence the average of both could be of best representa- Table 1
tive figure to evaluate the energy demand of the system [15]. Overview of the most important parameters defining the base case building model.
The reference zone has two outer walls with length of 8 m each Parameters Value
and the zone area of 64 m2 (8 m 8 m). Height of the zone is 2.6 m External Wall, U Value 0.48 (W/m2 K)
is at height of 5.2 m and the total height of the building is consid- Internal Wall, U Value 1.072 (W/m2 K)
ered as 13 m so that no ground and roof influence has occurred in Floor and Ceiling, U Value 0.41 (W/m2 K)
Windows U-glass: 2 W/m2 K,
the zone model.
U-frame: 1.5 W/m2 K
The zone model is shown in Fig. 1. The Fig. 1a shows that the Frame fraction to the total window: 20%
whole surface of the building, the size, and the location of the zone Solar heat gain coefficient: 0.76
under investigation. Fig. 1b depicts the exterior walls and windows Internal emissivity: 0.9
placed on them. Solar Transmittance: 0.6764
Set Point Temperature 21 C–23 C (Heating Mode)
In the figure it has been seen that there is two interior walls that Maximum supply inlet temperature 40 C
is considered as adiabatic meaning no heat and work transfer for floor heating system
through the walls between zone and the surroundings. The floor Infiltration rate 0.6 h1
and ceiling of the zone are adjacent to each other, which are No Ventilation System
Boiler with proportional controller Tsupp (30 C)–45 C
involved in heat interaction between zone and the surroundings
Tsupp (20 C)–22 C
along with two exterior walls. Floor heating system is incorporated Weather data ASHRAE IWEC Weather File
here in the simulation of the zone model of the building. The
mechanical ventilation system is not considered and the air
exchange rate with infiltration is taken as 0.6 h1 that is supposed
energy source via building to the sink. However, this analysis has
to represent a typical modern tight German building. The value is
been carried out taking consideration of high grade energy sources,
taken as representing figure for all European buildings analysis. The
fossil fuels as a source of primary energy. Here, primary energy
internal loads of a building including equipments, occupants are
source is taken as renewable energy (ground source heat pump,
taken as 5 W/m2 year around value according to German standard
and air source heat pump), therefore, the model is slightly changed
[3]. The climate data for the analysis of a building is taken from
to incorporate the modification. Moreover, the model from distri-
ASHRAE IWEC Weather file for Hamburg, since analysis is being
bution to building envelope system is used in accordance with
done for heating in this study. The various inputs of the construc-
Schmidt [14], Fig. 2.
tion details of the building are given in the Table 1.
The energy flow in a system is divided into thermal energy and
The reference zone model is an inbuilt function of IDA-ICE
auxiliary energy flow. Thermal energy flow at each subsystem
building simulation and has been modeled in detail using the
provides an information of energy demand at each modules
CEDETZONE model. In this model the long wave and short wave
whereas auxiliary energy flow is an amount of electricity required
heat interaction are taken in to account using the net radiation
to operate the system. In this analysis, however, primary and
method [2].
generation energy is substituted by ground and/or air source heat
IDA-ICE has also provision for two different zone models,
pump.
Climate model and Energy model. The climate model is in detail
Since there was not a typical simulation module developed for
and calculates vertical temperature gradient, includes long wave
a heat pump integrating heating or cooling system, an earlier
radiation calculations, mean radiant and operative temperatures,
studies of representative heat pumps characteristic curves (COP
and comfort index and daylight level. The energy model is simple
curves) are used for the purpose of analysis and in this approach of
and has a more conventional precision level and based on a mean
evaluation heat pumps are usually deemed as black box that is to
radiant temperature. Both models evaluate CO2, air mass, humidity
say no detail analysis of component basis has been done, but input
and energy of the system. Selecting climate model in the simulation
and output from the heat pumps are obtained. Output of the heat
does not complicate and lengthen the simulation process and time
pump is generation energy which then flows through distribution
instead it assures better accuracy and precision of the results.
subsystem to finally envelope subsystem. Storage is not considered
Therefore, this study takes in to account of climate model for the
in this analysis. A characteristics curve from Ito [10] is used in this
simulation of the building system. Table 2 shows different cases
study. Brief descriptions of these curves are presented herein. Fig. 3
that have been studied.
shows the COP curve that is used in this analysis.
The relation between COP and the temperature of the heat
4. Model analysis and simulation procedure sources is shown in Fig. 3. Generally, a water source heat pump
gives a higher COP than an air source heat pump if both tempera-
Energy analysis model developed by Schmidt [14] is quite tures are the same, which in above figure can also be seen. While
explicit and has detail investigation of energy chain from primary obtaining the typical characteristics curves, few operating
Table 2
Describes the different cases that have been studied during analysis.
Cases Description
Case 1: Conventional system Building with condensation boiler
(base case) (hboiler ¼ 0.95) and floor heating system.
Infiltration rate 0.6 h–1.
Case 2: Ground coupled heat Building system same as base case and ground
pump integration system coupled heat pump with constant
condensation temperature 30 C with varying
inlet evaporator temperature.
Case 3: Ground coupled heat Building system same as base case and ground
pump integration system coupled heat pump with constant
condensation temperature 40 C with varying
inlet evaporator temperature.
Case 4: Air source heat pump Building system same as base case and Air
integration system source heat pump with constant condensation
temperature 30 C with varying ambient
temperature.
Case 5: Air source heat pump Building system same as base case and Air
integration system source heat pump with constant condensation
temperature 40 C with varying ambient
temperature.
Fig. 3. Relation between COP and the temperature at the evaporator using air or water
conditions were imposed during experimentation, condenser inlet
as a heat source (Ito et al., 2000).
temperature was maintained constant at 30 C and 40 C respec-
tively, while varying the evaporator source temperatures. Working
fluid of the heat pump in all cases was R22. This operating condition 4.1. Simulation procedure
of the heat pump with air and water source temperature resembles
with our analysis for the heat pump integrated building heating As the aim of this study is to compare energy and exergy flow of
system. As the building heating system is low temperature floor a system supplied with fossil fuel plant and ground and air source
heating system, Working fluid R22 is quite applicable for low and heat pump for the same building zone model. Hence there is no
medium temperature floor heating system that has been used in need of changing anything in the IDA-ICE building zone model for
getting the above curves. Similarly, from the simulation result of both systems. The self developed exergy analysis module that uses
conventional heating systems, we obtained inlet temperature of dynamic values from IDA-ICE is implemented on each system and
the generation plant lies in the range of 26–32 C ensuing starts simulation of the system. The simulation is performed
condenser inlet temperatures constant at 30 C is quite reasonable dynamically with periodic start up for 1st January, 2007 a repre-
for our investigations. However, condenser inlet temperature 40 C sentative day for winter climate using ASHRE IWEC climate file for
is also rational to be examined because in many other cases this Hamburg. The self developed exergy model with steady state
situation might occur for low/medium floor heating systems. The exergy equations has used dynamic values of energy from the
source temperature was varying in air source heat pump as simulation and calculates quasi steady state exergy for the each
ambient temperature fluctuates with day and time, but in case of subsystem. While in the case of heat pumps dynamic values of
ground source heat pump we consider a system with vertical heat energy from IDA-ICE is taken from distribution subsystems to
exchanger of 50 m depth and took constant temperature of 10 C, envelope subsystems. For the primary energy transformation and
thus inlet water to evaporator approximates around 8 C. COP in generation part, COP curves of earlier studies has taken and fit into
ground source heat pump is, therefore, constant in this analysis. the analysis of this study. Energy and exergy input output of the
heat pump are calculated with the help of spread sheet using Table 4
similar steady state equations of the exergy. Overall primary exergy efficiencies for the building in all cases.
Table 3
Energy and exergy demands for the different subsystems of all cases.
Energy Exergy Energy Exergy Energy Exergy Energy Exergy Energy Exergy Energy Exergy
[kWh/a] [kWh/a] [kWh/a] [kWh/a] [kWh/a] [kWh/a] [kWh/a] [kWh/a] [kWh/a] [kWh/a] [kWh/a] [kWh/a]
Case 1 Th. 3365 3028 3059 2753 2896.7 265 2503 227 2292 200 7147 450
Elec. 51 51 15 15 2 2 0 0 0 0 0 0
Total 3415 3078 3074 2768 2899 267 2503 227 2292 200 7147 450
Case 2 Th. 2175 44 2899 267 2896.7 264.7 2503 227 2292 200 7174 450
Elec. 2166 2166 0 0 2.3 2.3 0 0 0 0 0 0
Total 4341 2210 2899 267 2899 267 2503 227 2292 200 7174 450
Case 3 Th. 1952 33 2899 267 2896.7 264.7 2503 227 2292 200 7174 450
Elec. 2832 2832 0 0 2.3 2.3 0 0 0 0 0 0
Total 4784 2865 2899 267 2899 123.6 2503 227 2292 200 7174 450
Case 4 Th. 1521 6 2899 267 2896.7 264.7 2503 227 2292 200 7174 450
Elec. 4127 4127 0 0 2.3 2.3 0 0 0 0 0 0
Total 5648 4133 2899 267 2899 267 2503 227 2292 200 7174 450
Case 5 Th. 1418 5 2899 267 2896.7 264.7 2503 227 2292 200 7174 450
Elec. 4436 4436 0 0 2.3 2.3 0 0 0 0 0 0
Total 5854 4441 2899 267 2899 267 2503 227 2292 200 7174 450
The exergy curve gives completely different picture from the less than that of case 1, but for cases 4 and 5 exergy demand is
energy curve; exergy demand of envelope sub system is very low 34% and 44% higher as compared to case 1. While generation
down despite having the highest energy demand for the same. exergy demand is 91% less for all heat pumps. This clearly
The discrepancy between two analyses substantiates the need of substantiate that ground coupled heat pump building heating
exergy analysis in getting more insight of source energy system is far more sustainable approach than conventional
requirement. Since the energy dissipates from the envelope sub building heating system. It needs less absolute energy and exergy
system to the environment is at low temperature between 21 C supply at primary level and it also make clear that high grade
and 23 C, the exergy content of these massive energy flows is energy is not a requirement for the building heating energy
then very small and in principle could be supplied through low supply.
quality energy sources say low exergy energy. As it is evident
from the curve that in the fossil plant system (case 1) biggest 6. Prioritizing the systems from energetic/exergetic
exergy losses take place at primary and generation sub systems, viewpoint
which is the point of high quality energy in the form of fuels or
electricity is being fed to the building system. The exergy flow fed The performance of the different cases has been presented
to the building envelope is zero when it finally gets to the outside mostly with energetic/exergetic standpoint. The reason behind
air (reference). Thus, all exergy provided to the building envelope a typical results for cases, pro and cons of it with regard of
is at last consumed. While in cases 2, and 3, the absolute amount sustainability issue that is utmost important in days to come to
of primary exergy needed for maintaining the same temperature keep up balance between energy supply and climate change have
level of the zone 21–23 C in the heating mode, are 30%, and 8% been unveiled. A final conclusion of the system, ranking of the cases
Table 5 analysis gives case 2 is one of the most realistic systems that have
Ranking of all cases from best to worst with energetic and exergetic perspective. around 50% high overall primary coefficient of performance and
Cases Energetic Exergetic overall primary exergy efficiency and about 25% less primary energy
perspective perspective and exergy demand than the base case ‘‘case 1’’.
Case1 – Base case Reference case Reference case
Case 2 – GSHP @ condenser Better Better
inlet temperature 30 C
Case 3 – GSHP @ condenser Good Good References
inlet temperature 40 C
Case 4 – ASHP @ condenser Worse Worse [1] Bejan A. Advanced engineering thermodynamics. New York: Wiley Inter-
inlet temperature 30 C science; 1998. pp. 501–14.
Case 5 – ASHP @ condenser Worst Worst [2] Bring A, Sahlin P, Vuolle M. Models for building indoor climate and energy
inlet temperature 40 C simulation. Report of IEA SHC Task 22, Subtask B (1999).
[3] DIN 4108-6: 2003–06. Wärmeschutz und Energie-Einsparung in Gebäuden –
Teil 6: Berechnung des Jahresheizwärme- und des Jahresheizenergiebedarfs.
studied have been presented primarily based on sustainability German National Standard. Berlin: Deutsches Institut für Normung e.V.
[4] Dincer I, Rosen MA. Exergy as a driver for achieving sustainability. Interna-
viewpoint in Table 5 below. tional Journal of Green Energy 2004:1–19.
[5] Hikmet E, Mustafa I, Mehmet E, Kazim P. Energy and exergy analysis of
7. Conclusion a ground coupled heat pump with two horizontal ground heat exchangers.
International Journal of Building and Environment 2007:3606–15.
[6] Hikmet E, Mustafa I, Mehmet E. Numerical and experimental analysis of
The analysis of the several cases under investigations has a horizontal ground–coupled heat pump system. Building and Environment
revealed that exergy analysis is very important to get more insight of 2007:1126–34.
the processes than that of sheer energy analysis. The discrepancy [7] Hepbasli A, Tolga Balta M. A study of modeling and performance assessment of
a heat pumps system for utilizing low temperature geothermal resources in
over overall primary energy and exergy efficiencies has divulged the buildings. Building and Environment 2006:3747–56.
fact that exergy demand of a building heating system is very low, [8] Hepbasli A, Akdemir O. Energy and exergy analysis of a ground source
however energy demand is not. Exergy efficiency is in the range of (geothermal) heat pump system. Energy Conversion and Management
2004:737–53.
0.035–0.09 whereas energy efficiency is from 0.5 to 1.06. The energy [9] Hauser G. Vereinfachte Behandlung des Wärmeverhaltens großer Gebäude
efficiency exceeds over 1 just because extraction of evaporator durch thermische Systeme. Betonwerk und Fertigteil-Technik 1978:266–71.
energy (which is free) is ignored in the calculation of the efficiency [10] Ito S, Miura N. Studies of a heat pump using water and air heat sources in
parallel. Heat Transfer Asian Research 2000:473–90.
but is monitored. The efficiencies alone do not reveal more insight of [11] Lund, JW & Freeston, DH, World-wide direct uses of geothermal energy,
the absolute demand, though overall losses proportion in the system Proceedings world geothermal congress, Kyushu-Tohoku, Japan, (2000) 1–21.
can be determined, hence absolute energy and exergy demands are [12] Lund, JW, Ground-source (geothermal) heat pumps, course on heating with
geothermal energy: conventional and new schemes. World Geothermal
crucial to determine heat generation plant. The biggest exergy losses
Congress 2000 Short Courses, Kazuno, Tohuko District, Japan, (2000) p.
occur in all cases studied, by far in the energy conversion process 209–36.
namely: in conventional heating system at generation subsystem [13] Ozgener L, Hepbasli A, Dincer I. Performance investigation of two geothermal
district heating systems for building applications: energy analysis. Energy and
and in heat pumps at primary subsystems. Nevertheless, energy
Building 2006:286–92.
losses are negligible in conventional system. The exergy losses in [14] Schmidt D. Design of low exergy building and a pre–design tool. The Inter-
generation subsystem is in the range of 90% while in heat pumps national Journal of Low Exergy and Sustainable Buildings 2004:1–47.
exergy losses in primary subsystems is in the range of 85–95%. [15] Weitzmann P. Modelling building integrated heating and cooling systems. PhD
thesis, DTU–Technical University of Denmark, Copenhagen (2004).
Exergy losses in each subsystem are basically due to intrinsic ther- [16] Energy conservation in buildings and community systems (ECBCS) [viewed
modynamic irreversibility in the processes. The comparison of the 27/10/2007], http://www.ecbcs.org/home.htm.