PMCC Total Nos Spare Qty Spare section Dimensions Unit Rate Total Cost
O/G to ASB MCCB - 400Amp 1 1 2 600 1200 0
I/C - 1600Amp 1 0 1 1800 1800 0
B/C - 1600Amp 1 0 1 1800 1800 0
DG SET - 1600Amp( 4 POLE BR 1 0 1 1800 1800 0
DOL upto 5.5KW 80 16 96 300 28800 0
9.3KW 3 1 4 400 1600 0
15KW 5 1 6 400 2400 0
18.5KW 2 1 3 400 1200 0
30KW 12 3 15 500 7500 0
37KW 2 1 3 500 1500 0
45KW 1 1 2 500 1000 0
63 SFU Unit 8 2 10 300 3000 0
125 SFU 2 1 3 300 900 0
CONTROL TXF 1 0 1 600 600 0
MLDB 2 1 3 800 2400 0

TOTAL COL 57500


O/G COL 31.94
COLUMNS 32
ACB Column 5 0
MCCB Panel (Double Front) 14 0
Depth 1200 0
Double Front Panel Size - 17 mtr x 1.2 mtr x 1.8 mtr 16200
WxDxH

3.3KV SwitchGear Panel - 600A


I/C - 11/3.3KV TXF 1000KVA 1 0 1
450KW Soft Starter 4 1 5 900 4500
BUS PT 1 0 1

TOTAL 7
Panel Size - 5.6 Mtr 5600

11 KV Switchgear Panel -
I/C FOR 11KV 1 0 1
O/G - 11/3.3KV TXF 1000KVA 1 1 2
O/G - 11/0.433KV TXF 3000KVA 1 0 1
APFC - 300KVA 1 1 2
BUS PT 1 0 1

TOTAL 7
Panel Size - 5.6 Mtr 5600
HINDUSTAN DORR-OLIVER LTD.
MUMBAI. ENGINEERING DIVISION DATE 18/10/2010
CLIENT ONGC ASSAM PROJ. NO. BYE IT00900
PLANT ETP + WIP (GELKI) CAL. NO.
CONSULTANT REVISION P0
TITLE TRANSFORMER SIZING CACULATION SHT. NO.

TOTAL LOAD : 352.06 BKW


:
TOTAL AUX LOAD ON ASB : 100.00 BKW
10% MARGIN : 45.21
:
TOTAL LOAD : 497.27 BKW

CONSIDERING THE P.F. COS F = 0.8


SO, SIN F = 0.6

497.27
HENCE, KVA = = 621.58 KVA
0.8

TOTAL LOAD IN KVA AT 0.8 P.F. LAG = (KVA X COS F) + j (KVA X SIN F)
= 497.27 + j 372.95 KVA ………….[1]

THE HIGHTEST MOTOR LOAD = 45 KW


FULL LOAD CURRENT OF 45 KW MOTOR = 74 AMP
THE P.F. OF 45 KW MOTOR = 0.86 (i.e. COS F)
HENCE, SIN F = 0.51
SO, THE MOTOR KVA RATING = 52.3 KVA

TOTAL MOTOR LOAD IN KVA AT 0.8 P.F. LA = (KVA X COS F) + j (KVA X SIN F)
= 45 + j 26.70 KVA ………….[2]

SUBTRACTING [2] FROM [1] = 452.27 + j 346.25 KVA ………….[3]

STARTING METHOD OF THE MOTOR [I st.] = DOL


SO THE STARTING CURRENT OF MOTOR = 444 AMP NOTE NO. 1
STARTING P.F. OF MOTOR CONSIDERED AS = 0.2 (i.e. COS F)
HENCE, SIN F = 0.98

STARTING CURRENT AT 0.2 P.F. = (I st. X COS F) + j (I st. X SIN F)


= 88.80 + j 435.03 AMP
STARTING KVA AT 0.2 P.F. = 1.732 X 0.415 (I st. X COS F) + j (I st. X SIN F)
= 63.83 + j 312.69 KVA ………….[4]

ADDING [3] AND [4] = 516.09 + j 658.94 KVA ………….[5]


= 836.99 KVA ………….[6]

SO, THE TRANSFORMER OF RATING 1000 KVA IS RECOMMENDED.


NOTES :
1] 45KW MOTOR WILL BE STARTED WITH DOL, SO THE St Current-6 times FL Current
1] THE MOTOR FULL LOAD CURRENT IS CONSIDERED FOR 4 POLES AS PER CROMPTON GREAVES CATALOGUE ATTACHED.
H. G. PATEL T N MERCHANT
PREPARED BY APPROVED BY
HINDUSTAN DORR-OLIVER LTD.
MUMBAI. ENGINEERING DIVISION DATE 18/10/2010
CLIENT ONGC ASSAM PROJ. NO. BYE IT00900
PLANT ETP + WIP (GELKI) CAL. NO.
CONSULTANT REVISION P0
TITLE INCOMER SIZING CALCULATION SHT. NO.

THE TRANSFORMER RATING CONSIDERED AS = 1000 KVA

NOW, AS PER THE FORMULA

KVA RATING OF TRANSFORMER = 1.732 X VOLTAGE X CURRENT

1000 = 0.72 X CURRENT

SO, CURRENT = 1391.25 AMP

SO, THE INCOMER AS WELL AS THE BUSDUCT RATING OF 1600 AMP IS RECOMMENDED.
H. G. PATEL T N MERCHANT
PREPARED BY APPROVED BY
HINDUSTAN DORR-OLIVER LTD.
MUMBAI. ENGINEERING DIVISION DATE 18/10/2010
CLIENT ONGC ASSAM PROJ. NO. BYE IT00900
PLANT ETP + WIP (GELKI) CAL. NO.
CONSULTANT REVISION P0
TITLE TRANSFORMER SIZING CACULATION SHT. NO.

TOTAL LOAD : 1240.00 BKW


:
TOTAL AUX LOAD ON ASB : 0.00 BKW
10% MARGIN : 124.00
:
TOTAL LOAD : 1364.00 BKW

CONSIDERING THE P.F. COS F = 0.8


SO, SIN F = 0.6

1364.00
HENCE, KVA = = 1705.00 KVA
0.8

TOTAL LOAD IN KVA AT 0.8 P.F. LAG = (KVA X COS F) + j (KVA X SIN F)
= 1364.00 + j 1023.00 KVA ………….[1]

THE HIGHTEST MOTOR LOAD = 450 KW


FULL LOAD CURRENT OF 450 KW MOTOR = 98 AMP
THE P.F. OF 450 KW MOTOR = 0.84 (i.e. COS F)
HENCE, SIN F = 0.54
SO, THE MOTOR KVA RATING = 535.7 KVA

TOTAL MOTOR LOAD IN KVA AT 0.8 P.F. LA = (KVA X COS F) + j (KVA X SIN F)
= 450 + j 290.67 KVA ………….[2]

SUBTRACTING [2] FROM [1] = 914.00 + j 732.33 KVA ………….[3]

STARTING METHOD OF THE MOTOR [I st.] = Soft Starter


SO THE STARTING CURRENT OF MOTOR = 294 AMP NOTE NO. 1
STARTING P.F. OF MOTOR CONSIDERED AS = 0.2 (i.e. COS F)
HENCE, SIN F = 0.98

STARTING CURRENT AT 0.2 P.F. = (I st. X COS F) + j (I st. X SIN F)


= 58.80 + j 288.06 AMP
STARTING KVA AT 0.2 P.F. = 1.732 X 3.3 (I st. X COS F) + j (I st. X SIN F)
= 336.08 + j 1646.44 KVA ………….[4]

ADDING [3] AND [4] = 1250.08 + j 2378.76 KVA ………….[5]


= 2687.23 KVA ………….[6]

SO, THE TRANSFORMER OF RATING 3000 KVA IS RECOMMENDED.


NOTES :
1] 450KW MOTOR WILL BE STARTED WITH Soft Starter, SO THE St Current-3 times FL Current
2] THE MOTOR FULL LOAD CURRENT IS CONSIDERED FOR 4 POLES AS PER CROMPTON GREAVES CATALOGUE ATTACHED.
H. G. PATEL T N MERCHANT
PREPARED BY APPROVED BY
HINDUSTAN DORR-OLIVER LTD.
MUMBAI. ENGINEERING DIVISION DATE 18/10/2010
CLIENT ONGC ASSAM PROJ. NO. BYE IT00900
PLANT ETP + WIP (GELKI) CAL. NO.
CONSULTANT REVISION P0
TITLE INCOMER SIZING CALCULATION SHT. NO.

THE TRANSFORMER RATING CONSIDERED AS = 3000 KVA

NOW, AS PER THE FORMULA

KVA RATING OF TRANSFORMER = 1.732 X VOLTAGE X CURRENT

3000 = 5.72 X CURRENT

SO, CURRENT = 524.88 AMP

SO, THE INCOMER AS WELL AS THE BUSDUCT RATING OF 600 AMP IS RECOMMENDED.