Sunteți pe pagina 1din 4

BUTTERFLY VALVES FOR AIR

MK
Product Brochure
T-Product 2002 November

US

For continuous duty, intermittent high-low control of combustion air flow


Individually adjustable high and low flow positions
Designed for continuous on-off cycling
Life expectancy of 2 million cycles
DC system prevents overheating of solenoid coil and no inrush current
Damper for speed control
Visual position indication of butterfly disc
Wafer-type valve body fits between standard ANSI flanges
Low maintenance
CE certified models available

Application
MK solenoid butterfly air valves are designed for high-low control of air flow for
combustion systems. The high-capacity butterfly valves have adjustable high and
low flow stops to simplify system setup. The continuous duty capability of the
solenoid operators makes them ideally suited for the continuous cycling of frequency
firing control systems.
MK

Specifications
Operating Limits
Ambient temperature range: -4° F to 104° F (-20° C to 40° C)
Maximum inlet pressure: 2 psig (130 mbar)
M..N, without dampening unit: opening time: less than 0.5 seconds
closing time: less than 0.5 seconds
M..R, with dampening unit: opening time: 2 – 4 seconds
closing time: 2 – 4 seconds
Switching frequency: arbitrary
Operating life: 2 million cycles
Adjustable high and low flow rates: standard
Available pipe sizes in inches: 11⁄2" to 4"

Electrical Data
Supply voltage: 120 Vac; +10/-15%; 50/60 Hz
Duty cycle: Continuous
Type of enclosure: NEMA 3 (IP 54)
Solenoid coil insulation: Class F
Solenoid coil power factor: cos ϕ = 1
Short-circuit protection: use 6.3 A fast-blow fuse
Power consumption at 120 Vac: M 5: 73 VA or watts
M 6: 85 VA or watts
A full wave rectifier located in the terminal box converts incoming AC current to DC.
Power consumption is the same on start-up and during continuous operation.

Materials of Construction
MK solenoid butterfly valves have pressure die-cast aluminium alloy solenoid hous-
ings, class 40 gray cast iron butterfly bodies and discs, and stainless steel shafts
with graphite packing rings. Electrical terminal boxes have two 1⁄2" NPT connections
and two grounding screws. Terminals will accept a maximum wire gauge of #14.

Special Features
Adjustable maximum and minimum flow: Individually adjustable stops in the
valve drive unit permit precise field adjustment of high and low flows.
Normally open or normally closed operation: Valves are solenoid-operated
with spring return and can be configured in the field to either open or close on
actuation of the solenoid.
Preheated air: Special models for preheated air are available.
Contact Kromschroder for details.

2/4
MK

Sizing
Maximum Flow Capacity, SCFH (m3/h) at 10" WC (25 mbar) pressure drop through valve
Type K 40 K 50 K 65 K 80 K 100
SCFH m /h
3 SCFH m /h
3 SCFH m /h
3 SCFH m3/h SCFH m3/h
Air Flow 5,600 160 10,500 300 21,000 590 42,000 1,190 75,000 2,100
Bypass Orifice Flow Capacity, SCFH (m3/h) at 10" WC (25 mbar) pressure drop through valve
Type K 40 K 50 K 65 K 80 K 100
SCFH m3/h SCFH m3/h SCFH m3/h SCFH m3/h SCFH m3/h
Air Flow 270 7.6 270 7.6 420 11.9 480 13.6 620 17.6
The above charts are accurate at sea level altitude, 1 psig (69 mbar), line pressure and 60° F (16° C).
Mass flows will decrease at higher temperatures, line pressures and altitudes.

To estimate flows at other pressure drops across the valve, multiply figures in the table by the following factors.
Pressure Drop, "WC 1 2 5 20 30 40 50
Flow Multiplication Factor 0.32 0.45 0.71 1.41 1.73 2.00 2.24

Dimensions and Weights

1/2 NPT
11.2"
(285)
8.66" øF
(220) D
DN

3.43"
(87)

E
L

Type DN L D E F Actuator Weight


IN mm IN mm IN mm IN mm IN mm LBS kg
MK 40 11⁄2" 40 1.38 35 3.62 92 8.07 205 3.54 90 M5 19.8 9
MK 50 2" 50 1.38 35 4.21 107 8.62 219 3.54 90 M5 22 10
MK 65 21⁄2" 65 1.38 35 5.00 127 8.78 223 5.00 127 M6 33 15
MK 80 3" 80 1.57 40 5.59 142 9.06 230 5.00 127 M6 35 16
MK 100 4" 100 1.57 40 6.73 171 9.49 241 5.00 127 M6 36.4 16.5

3/4
MK

Order Information
Solenoid actuators M and butterfly valves K are shipped seperately for field as-
sembly and are ordered as seperate items.

Actuators M
M valve actuator
5 actuator size 5 for valve sizes 11⁄2" up to 2"
6 actuator size 6 for valve sizes 21⁄2" up to 4"
T T-product
N fast opening, fast closing
R slow opening, slow closing
Q 120 Vac, 50/60 Hz
9 metal terminal connection box

Butterfly valves K
K butterfly valve
11⁄2" to 4 " (DN 40 to 100) nominal diameter
T T-product
W for fitting between two ANSI flanges

For pre-heated air applications, the M 6 actuator must be used on all valve se-
ries.

Warning:
Situations dangerous to personnel and property can result from the misapplication and incorrect operation of combustion equipment.
Kromschroder advises compliance with the National Fire Protection Association standards that apply for related equipment and Insurance Underwriters
recommendation, and care of operation.
03250319 11.02 F.T 1.000

We reserve the right to make technical changes designed to improve our products without prior notice.
For current product information, visit our website at www.kromschroder.com.

G. Kromschröder AG KROMSCHRODER INC.


Postfach 2809, D-49018 Osnabrück 1595-H Georgetown Rd., Hudson, OH 44236,
Ph. ++49 (0) 541/1214-0, Fax ++49 (0) 541/1214-370 Ph. 330-342-0595, Fax 330-342-0596,
info@kromschroeder.com, www.kromschroeder.com info@kromschroder.com, www.kromschroder.com