softstarter range
HPS2 D75 840
HPS2 DH30 720
Contents Page
2. Mounting 7
3. Installation 8
3.2 HPS2 D75 840/HPS2 DH30 720with built-in electronic overload protection 10
4. Description,settings,signals 11
5.2 HPS2 D75 840/HPS2 DH30 720 with built-in electronic overload protection 16
6. Trouble shooting 18
7. Technical data 28
8. Circuit Diagrams 30
9. Dimensions 31
2
The softstarter rated marking plate
PROSTAR Electric
P R O S T A R I N T E R N A T I O N A L E L E C T R I C C O. , LT D
Type
Supply voltage
Data according to CE and UL
! WARN
Do operation by regulation.
3
1A. Brief instructions Contents
(For installations that repuire CE-standard see chapter1B)
HPS2 D75 840 and HPS2 DH30 720 with and without overload protection
Identify your softstarter by checking the rating plate.See enclosed information(page 3)how to read the marking plat. Then select the appropriate
column.
Connections
Protective earth Connect the earth cable Connect the earth cable
Control circuit Apply control voltage to terminals Apply control voltage to terminals
1and 2 on top of the softstarter. 1and2 on top of the softstarter.See
See page3Make sure that you have page3Make sure that you have ordered
ordered corret control voltage. corret control voltage.
220 240V or 110 127V. 220 240V or 110 127V.
Can not be changed after delivery Can not be changed after delivery
Start and stop Connect the cables for start and stop Connect the cables for start and stop
signals to terminal 8and 9.Connect also signals to terminal 8and 9.Connect also
with a short wire terminals7and 10(for with a short wire terminals7and 10(for
PLC look at circuit diagram on page 30) PLC look at circuit diagram on page 30)
Settongs Potentiometers
Ir Set to rated motor current Set to rated motor current See
See lable on the Softstarters front. lable on the Softstarters front.
This also sets the rated current
for the electronic overload.
I LIM Set to actual need.Too low of a value, Set to actual need.Too low of a value,
and the motor may not accelerate. and the motor may not accelerate.
Switches
Kick Voltage kick during start.(Yes orNo). Voltage kick during start.(Yes orNo).
SC High current switch off.(Yes orNo). High current switch off.(Yes orNo).
TPF Reaction time for energy saving function. Reaction time for energy saving function.
Normal is standard.(Normal or slow) Normal is standard.(Normal or slow)
Ready for start
4
1B . Brief instructions for installation that require CE-standard
5
HPS2 D75 840 and HPS2 DH30 720 with and without overload protection
Identif softstarter by checking the rating plate.See enclosed information(page 3)how to read the marking plat. Then select
the appropriate column.
Mounting Softstarter unit Vertical mounting for adequate cooling Vertical mounting for adequate cooling
Protective earth Connect the earth cable Connect the earth cable
Main circuit Connect supply side to Connect supply side to terminals/busbars 1,3and 5
terminals/busbars 1,3 and 5
Connect motor side to Connect motor side to terminals/busbars 2,4 and 6
terminals/busbars 2,4 and 6
Control circuit Apply control voltage to terminals Apply control voltage to terminals
1and 2 on top of the softstarter. 1and 2 on top of the softstarter. See
See page3Make sure that you have page3 Make sure that you have ordered
ordered corret control voltage. corret control voltage.
220 240V or 110 127V. 220 240V or 110 127V.
Can not be changed after delivery Can not be changed after deliver y
Start and stop Connect the cables for start and stop Connect the cables for start and stop
signals to terminal 8and 9.Connect also signals to terminal 8and 9.Connect also
with a short wire terminals7and 10(for with a short wire terminals7and 10(for
PLC look at circuit diagram on page 30) PLC look at circuit diagram on page 30)
Settongs Potentiometers
Ir Set to rated motor current Set to rated motor current See lable on the
See lable on the Softstarters front. Softstarters front.This also sets the rated
current for the electronic overload.
I LIM Set to actual need.Too low of a value, Set to actual need.Too low of a value,and
and the motor may not accelerate. the motor may not accelerate.
Switches
Kick Voltage kick during start.(Yes orNo). Voltage kick during start.(Yes orNo).
SC High current switch off.(Yes orNo). High current switch off.(Yes orNo).
TPF Reaction time for energy saving function. Reaction time for energy saving function.
Normal is standard.(Normal or slow) Normal is standard.(Normal or slow)
6
2. Mounting
Softstarter unit:
The softstarter must be mounted so that the cooling air passesvertically
over the heat sink.It must also be placed so that the cooling capacity
Is not decreased due to pollution or similar.
3
HPS2 D75 145 AE1376 600 760 350 105m /h/90CFM
Semiconductor fuses
The semiconductor fuses are not delivered built in the starter unit.
Use the recommended fuses given in the technical data.The combination
fuse size and softstater allows the maximum useof starting time and
current given for each softstarter without tripping.
Overload relays
The HPS2D verdion is possible to buy without built-in electronic overload
relay.This relay will protect both the motor and the softstarter from
over-heating during start and continuous run.
Recommended relay,see technical data,section 7.
7
3. Installation
Protective earth
Connect the protective earth at terminal marker The terminal is placed
on the right hand side on smaller units and directly on the mounting plate
for medium and large sizes.
Main circuits
The supply side of the softstarter has terminals marked 1,3,5.
The motor side is marked 2,4,6.
Note:Softstart HPS2 D is not phase sequence sensitive.
1 3 5
Softstart
2 4 6
Control circuit
Apply control voltage at terminals marked 1 and 2.See below,"Power
Supply" .Make sure that the ordered version corresponds to your rat-
ed voltage.
It is not possible to change the control voltage of the softstarter.
1 3 5
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
2 4 6
Power supply
110-127V 50-60Hz Connect terminals no.3 with no.4 and no. 5 with
no. 6 Supply at terminals no.1 and no.2
8
Start/Stop signa: 24V 10mA differential optocoupler input
Relay outputs
Switch over contacts for Run,TOR and Fault(terminals no.11-19).
If the softstarter shall be by-passed the"TOR" signal shall be used
for this purpose.
L1
L2 110-127V
L3 X2 1 3 4 5 6
N
QF
FU4
Soft Starter X2 1 3 4 5 6 13 16 19
L11 X2 7
8
1 3 5 K4 K5 K6
1 11 K7 T5
9
2 12 10
3 13 X2 2 12 11 15 14 18 17
4 14
5 HPS2D 15 KM
(HPS2DH)
KM
6 16
7 17
8 18
9 19
10 L11
2 4 6 HL1
FU8
Q 18 19
KH
KA HPS2D
KH
KA
14 16
K1 K2
HPS2D KM
A
HL2
KM
KM KA HL3
M
9
3.2HPS2 D75 840/ HPS2 DH30 720 with built-in
electronic overload protection.
To comply with the EMC-directive 89/336/ECC see instructions on page 5:
Protective earth
Connect the protective earth at terminal marker
The terminal is placed on the right hand side on smaller units and
directly on the mounting plate for medium and larger sizes.
Main circuits
The supply side of the softstarter has terminals marked 1,3,5.
1 3 5
The motor side is marked 2,4,6.
Note:Softstart HPS2 D and HPS2DH is not phase sequence sensitive. Softstart
Control circuit 2 4 6
1 3 5
20 21 22 23 24 25
OVERLOAD RESET
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
2 4 6
Power supply
110-127V 50-60Hz Connect terminals no.3 with no.4 and no.
5 with no. 6
Supply at terminals no.1 and no.2
220-240V 50-60Hz Connect terminals no.4 with no.5
Supply at terminals no.1 and no.2
Relay outputs
Swtich over contacts for Run, TOR, Fault and Overload (terminals no. 11-
22).If the softstarter shall be by-passed the signal"TOR"shall be used for
this purpose.
NOTE:If the softstarter is by-passed during continues running a separate
overload relay must be used for HPS2D75 145 and HPS2DH30 110.For
the other the current transformers can be moved outside the by-pass
circuit.
10
4. Description,settings,signals
General
HPS2 D75 840 are made for normal starting conditions for starting pumps,
short conveyor belts,compressors,etc.It is possible to buy this version
with a built-in electronic overload with tripping class 10.See technical
data for starting capacity.
Kick=Y(On)
U PF=Y(On)
60sec.
U SD
60%
U INI 30%
= set U INI
10%
Rated Current
Selection of the motors rated current can be done from Knob=Ir
70-100% of the softstarters rated current.
This will also set the tripping level for the electronic ov
erload when enclosed.
Soft Start
Separately adjustable linear ramp with adjustable initia
l voltage.
Time: Adjustable from 0.5-60 sec. Knob=START
Initial voltage Adjustable from 10-60% of of full voltag- Knob=U INI
e.(If the current limit will alwa-ys overri-
de the initial voltage)
Kick start 90% of full voltage during 0.5 sec, selec- Switch=Kick
table yes/no
Soft Stop
Separately adjustable linear ramp with adjustable ste
p-down voltage.End voltage=Initial voltage(UINI ).
Time: Adjustable from 0 till 4 min (240 sec) Knob=STOP
Step-down Adjustable from 30-100% of full voltage. Knob=U SD
Current Limit
Adjustable from 200-500% of the motors rated current Knob=I LIM
Energy Saving
To comply with the EMC-directive 89/336/EEC see in- Swich=PF
structions on page 5.
Selectadle yes/no,it isactivated 60sec after the start
ramps end
11
Signal lamps indicating
OVL Overload
OVL
Buttons-
Reset Reset button for overload
Reset Settings
Ir The rated motor current is set via
potentiometer Ir
5 F1 Fault
2 10 F2 Fault
1 20 On Supply voltage
F1 F2 START
40 R Running
0,5 60s
20 T Completed start ramp
On R 5 50 P Active energy saving function
STOP 100
T P 0,5 240s
30 40 Potentiometers for setting-
START Ramp time during start
N Y U INI 50
STOP Ramp time during stop
PF
10 60% U INI Initial voltage
Kick 70 U SD Step down voltage
SC 50
I LIM Current limit at start
TPF U SD 90 Rated current of motor in % ofIe
norm slow Ir
30 100%
80 90 3 4
Switches for selection of-
Ir I LIM Energy saving function, Yes/No
PF
70 100% 2 5 * Ir Kick Kick start,Yes/No
SC High current switch-off,Yes/No
TPF Reaction time for energy
saving function,Normal/Slow
12
4.1 HPS2D75 840 Without built-in electronic
overload protection
LED'S
F1:(red) Fault signal for Phase loss,Thyristor fault ,
High current switch off.
F2:(red) Fault signal for Over temperature, Fault on
circuit board,Thyristor fault
On:(green) Supply voltage,Illuminates when softstarter
has control power.
R:(yellow) Motor is running.Illuminates when the motor
is energised from the softstarter.
T:(yesllow) Top of ramp .Start ramp is finished and stop
ramp hasn't begun.
P:(yesllow) Energy saving is active
Fault codes
F1 Phase loss,High current switch off.
F2 Over temperature,Fault on circuit board.
F1+F2 Thyristor fault (short circuit or open circuit)
Relay Signals
Run/K4 Motor is running.The motor is energised from
the softstarter
TOR/K5 Top of ramp . Start ramp is finished and stop
ramp hasn't begun. Can be used as a by-pa-
ss signal.
Fault/K6 Phase loss,Thyristor fault,Over temperature,
High current switch off,Fault on circuit board.
Input
Start/Stop Start when closed,stop when open,24V,20-
mA optocoupler differential input.+24V and
0V can be supplied from the board if no ext-
ernal supply is used.
U 60sec.
Run relay/K4
500 ms
TOP relay/K5
13
4.2 HPS2D75 840/ HPS2 DH30 720With built-in
LED'S
F1: (red) Fault signal for Phase loss,Thyristor fault .
F2: (red) Fault signal for Over temperature, Fault on
circuit board,Thyristor fault Fault on ciriuit
board,Thyr-istor fault,High current switch
off
On: (green ) Supply voltage,Illuminates when so
ftstarter has co-ntrol power.
R: (yellow) Motor is running.Illuminates when the motor
is ene-rgised from the softstarter.
T: (yellow) Top of ramp .Start ramp is finished and stop
ramp hasn't begun.
P: (yellow ) Energy saving is active.
OVL:(yellow) Overload
Fault codes
F1 Phase loss.
F2 Over temperature,Fault on circuit board,High
current switch off
F1+F2 Thyristor fault (short circuit or open circuit)
OVL Overload
Relay Signals
Run/K4 Motor is running.The motor is energised from
the soft-starter
TOR/K5 Top of ramp.Start ramp is finished and stop
ramp hasn't begun.Can be used as a by-pass
signal.
Fault/K6 Phase loss, Thyristor fault, Over temperature,
High current switch off,Fault on circuit board.
U 60sec.
Run relay/K4
500 ms
TOP relay/K5
14
5. Operation and function
Stop
When the start signal is removed from the start/stop input the soft st-
op routine is executed and a decreasing linear time-voltage ramp is
applied to the motor.Start and stop voltages are selectable(endvo-
ltage=initial voltage for start ramp).
LED"T"and relay"TOR"are switched off when the stop begins.
LED"R"and relay"RUN" are switched off when the stop ramp isfinish-
ed.
Current limit
(Start sequence)If the motor current reaches the level of the current
limit, no higher voltage is applied to the motor unless the current
decreases below the limit.
During a start sequence the softstarter can't limit the current for mo-
re than 240sec.
When the start routine is finished(ramp time+max.240 sec)the follo-
wing will occur if the current hasn't decreased below thelimit.
1. Switch "SC"is in position Yes: The softstarter turns off
2. Switch"SC" is in position No: Full voltage is applied to the motor
Energy saving
If the function is selected (switch "PF")a power factor optimisation
commences 60 sec after the start-ramps end,this is indicated with the
LED"P".If a slower reaction on decreased load
is requested ,the switch "TPF"shall be put at position"slow"
.To comply with the EMC-directive 89/336/EEC see instructions o-
n page 5.
High current switch off
If the current limit is overridden for more than 200 ms after"top
of ramp",the softstarter turns off.
Reset via a stop signal.
The function is selectable with swich"SC",yes/no
Note:This is not complete short circuit protection,normal fusesfor pr-
otecting the equipment from short circuit are always required.
Over temperature
If the heat sink becomes overheated a temperature sensor will turn
off the softstarter.Reset via a stop signal.
Thyristor fault
If a thyristor is damaged(short circuit or open circuit)the softstarter
will indicate this.
If a thyristor is shorted a statrt can be accomplished if the energy sa-
ving function is not selected.
Phase loss
If one or more of the phases are missing when a start signal is applied,
the softstarter will turn off and indicate a fault.Reset viaa stop signal.
15
5.2 HPS2D75...840 / HPS2DH30...720 with built-in
electronic over load protection
Power on
When the softstarter is supplied with power the green LED "On"
is illuminated and the board executes a self check routine.If th-
ere are faults,the LED's "F1"and"F2", indicate these.
Start
When the start/stop input is supplied with 24V (switch is closed)the
soft start routine is executed and an increasing linear time-voltage
ramp is applied to the motor,Start voltage is selectable while the e-
nd voltage is always full voltage.
LED " R" and relay"Run" will indicate that a start has begun.
LED "T" and relay"TOR" will indicate that the start ramp has finished.
A 0.25 sec. pulse with voltage up to the current limit setting is appli-
ed to the motor at the beginning of the ramp if the switch 'kick' is in
position "YES".
A soft start can be done with a shorted thyristor if the switch"PF" is
in position "No" (LED's F1 and F2will be illuminated,and relay "Fa-
ult" will be activated).
Stop
When the start signal is removed from the start/stop input the s-
oft stop routine is executed and a decreasing linear time-voltage
ramp is applied to the motor.Start and stop voltages are select
able (end voltage = initial voltage for start ramp).
LED"T"and relay "TOR" are switched off when the stop begins.
LED"R" and rleay "RUN" are switched off when the stop ramp i-
sfinished
Current limit
(Start sequence)if the motor current reaches the level of the curr-
ent limit, no higher voltage is applied to the motor unless the cur-
rent decreases below the limit.
During a start sequence the softstarter can't limit the current for
more than 240 sec.
When the start routine is finished (ramp time + max. 240 sec)the
following will occur if the current hasn't decreased below the limit.
1. Switch"SC", is in position Yes: The softstarter turns off
2. Switch"SC", is in position No: Full voltage is applied to the mo-
tor
Energy saving
If the function is selected (switch "PF") a power factor optimisati-
on commences 60 sec after the start-ramps end, this is indicated
with the LED "P".
If a slower reaction on decreased load is requested,the switch"T-
PF" shall be put at position "slow".
To comply with the EMC-directive 89/336/EEC see instructions on
page 5.
Over temperature
If the heat sink becomes overheated a temperature sensor will tu-
rn off the softstarter.
Reset via a stop signal.
Thyristor fault
If a thyristor is damaged (short circuit or open circuit) the softstar-
ter will indicate this.
If a thyristor is shorted a start can be accomplished if the energy
saving function is not selected.
Phase loss
If one or more of the phases are missing when a start signal is ap-
plied, the softstarter will turn off and indicate a fault. Reset via a
stop signal.
16
Overload protection
The built in electronic overload function protects the motor and the
softstarter from damage due to overload. When an overload situation
occurs the softstarter stops immediately and indicates this with the
LED OVL and relay K3. After a certain delay (cooing time) the soft-
starter can be reset and a new start can be tried.Reset is done with
the push-button on the softstarter or by a short-circuit between
terminals no.24 and no.25. The start signal must always be opened
before a reset can be accomplished(security).
17
6. Trouble shooting
Signal relays
See next LED'S
page
RUN TOR Fault
ON R
T P
T P
18
The motor does not start
Check the status on LED's and signal relays and read the
explanation below.
See 6-1-1 forHPS2D without electronic overload protection and
See 6-2-1 forHPS2D(H) with electronic overload protectiOn.
Status signals
No control voltage
Check voltage on terminals 1 and 2.
Correct voltage level according to the rating plate?
Are the cooling fans running? (not HPS2 DH30)
If everything is OK-Internal fault on the PCB
19
6.1.2 Fault codes
Softstarter without O.L card mounted
Stand by x
Without
energy
saving After start signal
a)
x 1) x x x 3)
PF=No
Ramp up x x x x
Normal run x x x x x
Stopping x x x x x
Stand by x
With
energy
saving
After start signala) x x x x x x
PF=Yes
Ramp up x x x x x x
4) 4) 4) 4)
Dwell x x x x x x x
4) 4) 4) 4)
Optimise x x x x x x x
Stopping x x x x x x x
1) Detecting the fault and gives a fault signal but the softstarter is
able to run.
2) Open circuit means open circuit between softstarter and motor
3) Associated with an open circuit on the motor side with 2 or more
phases missing. Although the fault is detected if the fault was p-
resent when the start signal was activated the system will not trip,
i.e it is just an indication.
4) The F1+F2 fault signals are delayed when running with the func-
tion PF in position YES under 60 sec. from TOR is activated to
PF have been activated.
The fault have to be present longer than 5 sec. before tripping.
During this 5 sec the LED F1 flashes.Then the LED F2 flashes for
another 5 sec. If the fault remains or occur during these last five
sec . it will trip with a F1+F2 signal. If no fault it will go back to
normal run.
a) When the fault is present before the start signal is given (closing
between 8 and 9 ).
20
6.1.3 Fiow chart
Version HPS2D without a built in electronic overload
Fault code
F1
During cont.run
Yes
No
No fault
Check that the main contactor are closed all the time
Interuptions in the main supply
No Yes
No
Faulty P.C.B
21
VersionHPS2D without a built in electronic overload
During cont.run
During ramp down
Shorted thyristor
Is the switch PF on?
No Yes
No fault
Make a new start
Faulty P.C.B.
F2 Fault code
Over temp.heatsink
No overtemp.
Fault temp.sensor
(check by disconnecting the sensor from the main P.C.B.)
Still F2 signal
F a u l t y P. C . B
22
6.2 HPS2D(H) with electronic overload protection
6.1.1 Different status on LED's and signal relays
Signal relays
See next LED S
page
RUN TOR Fault Over
load
OVL
F1 F2 Continuous run with shorted thyristor
ON R (Switch PF must be in N-position, Off)
T P
OVL Tripped electronic over load
F1 F2 Reset:With the reset button or by closing
ON R between terminals x 2:24 25
T P The start signal has to be removed and t-
he LED OVL has to flash.
23
The motor does not start
Check the status on LED's and signal relays and read the explana-
tion below.
See 6-1-1 for HPS2D without electronic overload protection and
See 6-2-1 for HPS2D (H) with electronic overload protection.
Status signals
No control voltage
. Check voltage on terminals 1 and 2.
. Correct voltage level according to the rating plate?
. Are the cooling fans running? (not HPS2DH30)
. If everything is OK-internal fault on the PCB
24
6.2.2 Fault codes
Softstarter with O.L card mounted
Stand by
x x x x
Without
energy
saving After start signala)
x 1) x x x x x 3 x
PF=No
Ramp up
x x x x x x x
Normal run x x x x x x x x
Stopping x x x x x x x
Stand by x x x x
With
energy
saving After start signala) x x x x x x x x x
PF=Yes
Ramp up x x x x x x x x x
Dwell x x 4) x x x x 4) x x 4) x 4) x
Optimise x x 4) x x x x 4) x x 4) x 4) x
Stopping x x x x x x x x x
1) Detecting the fault and gives a fault signal but the softstarter is a-
ble to run.
2) Open circuit means open circuit between softstarter and motor
3) Associated with an open circuit on the motor side with 2 or more p-
hases missing. Although the fault is detected if the fault was prese
nt when the start signal was activated the system will not trip, i.e it
is just an indication.
4) The F1+F2 fault signals are delayed when running with the functi-
on PF in position YES under 60 sec. from TOR is activated to PF h
ave been activated. The fault have to be present longer then 5 sec.
before tripping. During this 5 sec the LED F1 flashes.Then the LED
F2 flashes for another 5 sec. If the fault remains or occur during
these last five sec. it will trip with a F1+F2 signal. If no fault,it will
go back to normal run.
a) The fault have to be present before the start signal is given (clo-
singbetween 8and 9 ).
25
6.2.3 Flow chart
Version HPS2D and HPS2DH with built in electronic over load
Fault code
F1
No
No
No
No fault
Check that the main contactor are closed all the time
Interuptions in the main supply
No No fault
The main contactor opens before end of ramp
Faulty P.C.B
26
Version HPS2D and HPS2DH with a built in electronic overload
During cont.run
During ramp down
Shorted thyristor
Is the switch PF on?
No Yes
High over current above8*set Ie
No fault
Make a new start
Faulty P.C.B.
F2 Fault code
Over temp.heatsink
No overtemp.
Fault temp.sensor
(check by disconnecting the sensor from the main P.C.B.)
Still F2 signal
F a u l t y P. C . B
27
7. Technical data
General data
HPS2D HPS2DH
Motor output Pe
220-230V kW 22-250 7,5-200
380-415V kW 37-450 15-400
500V kW 45-560 18,5-500
UL
208V HP 10-250 5-200
230V HP 10-300 5-250
480V HP 25-600 10-500
Degree of protection IP 00 IP 00
Harmonic contents
During start
% 5 5
During operation % 2 2
Settings
Initial voltage during start UINI % 10-60 10-60
Ramp time during start START s 0.5-60 0.5-60
Ramp time during stop STOP s 0.5-240 0.5-240
Current limit at start ILIM 2-5xIe 2-5xIe
Rated motor current Ir % 70-100 70-100
Step down voltage USD % 100-30 100-30
Signal relay
Rated operational voltage Ue V 250 250
Rated thermal current I th A 5 5
Rated operational current Ie
at AC 11( Ue=250V) A 1.5 1.5
Main circuit
Connection clamp
Cu-cable mm 2 6 35 - - - -
Al-cable mm 2 6 35 - - - -
Connection bar
Width thickness mm - - 15 4 25 6 40 6 50 6
Hole diameter mm - - 6.8 11 11 11
Control circuit
Connection clamp mm 2 2.5 2.5 2.5 2.5 2.5 2.5
Signal relay
Connection clamp mm 2 2.5 2.5 2.5 2.5 2.5 2.5
UL info:
Power connection AWG 18-2 18-2 8-3/0 (2) (2) (3)
4-500kcmil 4-500kcmil 4-500kcmil
Control connection AWG 22-12 22-12 22-12 22-12 22-12 22-12
28
Size related data
4)
Size Starting caprcity Type Current range Max.power Max.fusing rating main circuit Power requirements
loss at max.Ie Bussmann fuses Ferraz fuses of control circuits
A W VA
HPS2D
3) 5)
75 4,5 Ie for 14s T75 DU 22 80 250A 170M1371 315A 6,6 URD 30 D08 A 0315 40
3)
110 4,5 Ie for 14s T135 DU 65 135 315A 170M2619
5)
400A 6,6 URD 30 D08 A 0400 40
3)
145 4,5 Ie for 14s T200 DU 100 150 400A 170M2621 5)
500A 6,6 URD 30 D08 A 0500 40
2)
300 5 Ie for 7s T450 DU 165 310 700A 170M40176) 630A 6,6 URD 31 D08 A 0630 65
2)
370 5 Ie for 7s T900 DU 265 500 900A 170M50156) 900A 6,6 URD 32 D11 A 0900 90
2)
470 5 Ie for 7s T900 DU 265 500
1250A 170M50186) 1250A 6,6 URD 33 D11 A 1250 90
HPS2DH
3)
30 5 Ie for 25s 1) 125A 170M13685) 160A 6,6 URD 30 D08 A 0160 40
3)
45 5 Ie for 25s 1) 200A 170M2617 5) 200A 6,6 URD 30 D08 A 0200 40
3)
60 5 Ie for 25s 1) 250A 170M1371 5) 250A6,6 URD 30 D08 A 0250 40
3)
75 5 Ie for 25s 1) 315A 170M26195) 315A 6,6 URD 30 D08 A 0315 40
3)
110 5 Ie for 25s 1) 400A 170M26215) 450A 6,6 URD 30 D08 A 0450 40
3)
145 5 Ie for 25s 1) 450A 170M30206) 500A 6,6 URD 30 D08 A 0500 65
3)
175 5 Ie for 25s 1) 500A 170M30216) 550A 6,6 URD 30 D08 A 0550 65
2)
2)
300 5 Ie for 25s 1) 2) 900A 170M50156) 900A 6,6 URD 32 D08 A 0900 90
370 5 Ie for 25s 1) 2) 1000A 170M5016 6)
1000A 6,6 URD 33 D08 A 1000 90
470 5 Ie for 25s 1) 1250A 170M50186) 1250A 6,6 URD 33 D08 A 1250 90
2)
570 5 Ie for 25s 1) 2) 1500A 170M60186) 250A 6,6 URD 33 TTF A 1600 90
720 5 Ie for 25s 1) 1800A 170M60206) 250A 6,6 URD 233 PLAF 2000 90
29
8. Circuit Diagrams
L1
L2
L3
START/STOP HPS2 D75 840 E1 Circuit board
1
3
5
+
X2
E3-5 Fan
9
PLC
-
10
F6 Temperature
monitor
START/STOP
X2
J1-J3 Contact blocks
7 F6
t
10
SOFT STOP Relay,actuated in
X1 X3 T2 K4
8
1 3 operational position
E1
9 2 4
X2
START/STOP 7 K5 Relay,actuated at
X2 t START
8
7 9
full voltage
J1
10
10
4 (Ue=100%)
L N K4 V1
3
11 2 V2
SOFT STOP 12
1 K6 Relay,fault signal
X2 13
K5
8
14 Ue=
15 100% J2 T2 Current
9
4
16
K6 V3 transformer
3
17 V4
Only for 2
HPS2 D175 300 18 m 3 1
E3 E4 19 T5 Control
T5
M M Only for transformer
HPS2 D75 145
J3
X1 E3 4
1 M 3
V5 V1-V6 Thyristor
2 V6
2 X1
1
1
Only for X1-X3 Terminal block
HPS2D370 840 2
X2
1
2
3
4
5
6
E3 E4 E5
2
4
6
M M M
L N Uc=230V
W
U
V
X1
X2
1
2
3
4
5
6
1
M
2
Uc=115V
L N
E2
X2
+ X2 K3
PLC
9
20 X3 T2 E2 Circuit board OVL
OVL 1
- External reset 21
10 2 T3
of OVL 22
X2 23 3 E3-5 Fan
24 24 4
START/STOP
13 14 25 25
X2 F6 Temperature
7 F6
monitor
t
10
SOFT STOP
X1 X3 T2
8
1 3 J1-J3 Contact blocks
E1
2 4
9
X2
START/STOP 7
K3 Relay,overload
X2 t START
8
7 9
10
J1 K4 Relay,actuated in
10 4
L N K4 3
V1 operational position
11 2 V2
SOFT STOP 12
1
X2 13
K5
K5 Relay,actuated at
8
14 Ue= full voltage
15 100% J2
9 4 (Ue=100%)
16
K6 V3
3
Only for 17 V4
HPS2 D175 300 2
18
HPS2DH145 175 m 3 1 K6 Relay,fault signal
E3 E4 19
T5
Only for
M M HPS2 D75 145
HPS2 DH30 110 J3 T2 Current
E3 4
X1
V5 transformer
1 M 3
2 V6
2 X1
1
Only for 1 T3 Current
HPS2D370 840 2
HPS2 DH210 720 transformer
X2
1
2
3
4
5
6
E3 E4 E5
2
4
6
M M M
L N Uc=230V T5 Control
W
U
V
X1 transformer
X2
1
2
3
4
5
6
1
M
2
Uc=115V
L N V1-V6 Thyristor
30
9. Dimensions
4
218
218
125
280
265 7.5
280 45 45
15
265 7.5
7(4x)
7(4x)
Max400
260
313
260
313
360
26.5
7
26.5
HPS2D175 300 HPS2 DH145 250 HPS2 D370 570 HPS2 DH300 470
25
6
6
310
310
235
183
205
237
66
382 540
117 210 210
117 6 Hole 9X7
R3.5 25
13
R5.5
572
600
380
402
444
27
65
14
11 7 11
173.5 173.5 34
41 300
6
310
310
205
237
205
237
66
66
540 540
210 210 210 210
6 Hole 9X7 6 Hole 9X7
572
600
572
600
62.5
27
27
62.5
14
14
31
HPS2 D and HPS2 DH softstarters
Suggestions for basic setting of ramp times,current limit etc. For different applications:
Type of load
Ramp time Ramp time Initial voltage, Step down voltage, Current limit
for start for stop U IN (start) U SD (start)
I LIM (xIe)
Please note that these settings are only suggestions.Every application has to be looked at individually.
P R O S T A R I N T E R N A T I O N A L E L E C T R I C C O . , LT D
Email: prostar@prostarele.com;
URL: http://www.chinainverter.com