The use of solar energy in spaces conditioning in
the form of passive and active systems was the object
of an important national research programme
coordinated by INCERC Bucharest and carried out
in the period 1972-1985. A combination of the
characteristics of two passive solutions experimented
on the support of the 2 solar houses: CS 1 Câmpina
(1974) and CS 3 Bucharest (1982) (modified Trombe
and unventilated solar space) is represented by the
Controlled ventilation solar space, which is the object
of this report. The solution was experimentally
validated on the support of the CE INCERC
Bucharest experimental building. The report aims to
present the calculation method proper for dimension-
ing and for assessing the energy performance of the
Ventilated solar space as a part of a new building
which is efficient in terms of energy performance. The
mathematical model is detailed and its validation on
the support of the experimental building in the season
September 2008 – March 2009 is presented as well. 2008 – martie 2009.
*
National Building Research Institute – INCERC, Bucharest, Romania; e-mail: dan.constantinescu@incerc2004.ro
– Nr. 1 / 2010 53
D. Constantinescu
54 – Nr. 1 / 2010
Assessment of the energy performance of the solar space system
– Nr. 1 / 2010 55
D. Constantinescu
56 – Nr. 1 / 2010
Assessment of the energy performance of the solar space system
30 90
Te Consum
Ta tmVE NT [°C] te ta med [°C] CONS [kWh]
de caldura
Tvent 25 80 [kWh/zi]
[ °C ]
Heat
20 70 consumption
[kWh/day]
15 60
10 50
5 40
0 30
-5 20
-10 10
-15 0
01.09 29.09 27.10 24.11 22.12 19.01 16.02 16.03
Day / Ziua
Fig. 1. Data recorded in the 2008-2009 cold season in the CE INCERC Bucharest experimental building
Fig. 2. Operation of the ventilated solar space on 05.01.2009 – CE INCERC Bucharest experimental building
– Nr. 1 / 2010 57
D. Constantinescu
Fig. 3. Operation of the ventilated solar space on 12.01.2009 – CE INCERC Bucharest experimental building
Direct sunlight percentage
Date /
Fig. 4. Direct sunlight coefficient of the collecting wall of the solar space attached to the CE INCERC Bucharest
experimental building
58 – Nr. 1 / 2010
Assessment of the energy performance of the solar space system
– Nr. 1 / 2010 59
D. Constantinescu
Control volume
60 – Nr. 1 / 2010
Assessment of the energy performance of the solar space system
∂ ϑ ( x, τ)
−λ⋅ ⋅ S p + (ατ& ) ⋅ [cs IT (τ) + (1 − cs ) ⋅ I d (τ)] ⋅ Sv = α cv S p ⋅ [ϑ p ( x = ∆, τ) − t (τ)] +
∂x x=∆
+ α r S p ⋅ [ϑ p ( x = ∆, τ) − tv (τ)] (6)
Sv Sv
= β is marked. = β.
Sp Sp
The processing of equation (6) generates the
following relation:
∂ ϑ p ( x, τ)
−λ⋅ = [α cv ⋅ (1 − C1 ) + α r ⋅ (1 − B1 )] ⋅ [ϑ p ( x = ∆, τ) − t Es (τ)] (7)
∂x x=∆
α cvC2 + α r B2 ατ& β
t Es (τ) = ⋅ ⋅ I (τ) + te (τ) (8)
α cv ⋅ (1 − C1 ) + α r ⋅ (1 − B1 ) α cvC2 + α r B2
where: cu:
I (τ) = cs I t (τ) + (1 − cs ) ⋅ I d (τ)
where coefficient cs was used according to the în care coeficientul cs s-a utilizat conform fig. 4.
diagram in fig. 4.
Relation (7) represents the III-rd rank boundary
condition at level x = ∆. a III-a la cota x = ∆.
∂ ϑ p ( x, τ)
−λ⋅ = α i ⋅ [ti (τ) − ϑ p ( x = 0, τ)] (9)
∂x x=0
– Nr. 1 / 2010 61
D. Constantinescu
where m – indicator for the layers forming the solar în care m este indice pentru straturile din com-
radiation collecting unit, characterized by a low
thermal capacity, others than the reinforced concrete caracterizate de capacitate termic redus , altele
collecting wall (the structural component made of decât per
BCA – autoclaved lightweight concrete – plus the (elementul structural din BCA la care
thermal insulation layer); the two boundary conditions se stratul de termic )
become as follows:
∂ ϑ p ( x, τ)
− λ ⋅ = α& i ⋅ [ti (τ) − ϑ p ( x = 0, τ)] (9)
∂x x =0
∂ ϑ p ( x, τ) (10)
− λ ⋅ = α& e ⋅ [ϑ p ( x = ∆, τ) − t Es (τ)]
∂x
x=∆
62 – Nr. 1 / 2010
Assessment of the energy performance of the solar space system
t E j − t E j −1
N1 = − M 2 ⋅ + M 3 ⋅ (ti 0 − t E j −1 )
∆τ
(15)
t E j − t E j −1
2
N = M 3 ⋅
∆τ
Relations (12) and (13) can be used by means
of the recurrence procedure in finite (hourly) time-
lags, ∆τ. Identifier j defines the current calculation (orare) ∆τ. Indicativul j tervalul de
interval and j – 1, the previous interval modified by calcul curent, iar j – 1 intervalul anterior decalat cu
∆τ. ∆τ.
The average temperature of the control volume Temperatura medie a aerului din volumul de
air is determined by relation (5) according to value contro
ϑp (x = ∆, τ), determined by relation (13) and by valoarea ϑp (x = ∆, τ
the outdoor temperature te (τ). The air temperature t e (τ
variation along the control volume height (of the
collecting greenhouse) may be expressed by the
following relation:
t ( y, τ) = te (τ) + [ϑ p ( x = ∆, τ) − te (τ)] ⋅ [1 − exp (−ay )] (16)
The expression of the greenhouse height ,
average temperature, t (τ) allows the identification t (τ), permite identificarea coeficientului a:
of coefficient a:
t (τ) − te (τ) 1 − exp (−aH ) 1)
=1− (17)
ϑ p ( x = ∆, τ) − te (τ) aH
where t (τ) is determined at each moment τ by în care t (τ τ cu
relation (5). 5).
The consistency condition of this method is that
value a = ct. at any τ moment. odei este ca
Thus is determined the temperature value of valoarea a = ct. la orice moment τ.
the air exhausted in the occupied space at each
moment τ: τ:
tas − t (τ) = t ( y = H , τ) = te (τ) + aH ⋅ [ϑ p ( x = ∆, τ) − t (τ)] (18)
Another item used in identifying the verifying Un alt element de identificare i de consisten
the consistency of solution (12) of the heat integral a (12) a integrale a c ldurii îl
equation is the value of the numerical coefficient n coeficientul numeric n al spline
of the spline function which represents the care temperaturii în grosimea
temperature variation in the collecting wall thickness, peretelui captator, ϑ(x, τ) ) . Valoarea acestuia
ϑ (x, )). Its values should be constant and trebuie s fie constant i independent de momentul
independent of moment τ . Values a and n are τ. Determinarea valorilor a i n se face pe cale
experimentally determined by the procedure of experimental prin aplicarea procedurii de validare
validating the mathematical model presented, a modelului matematic prezentat, particularizat
particularized for the constructive solution of the pentru constructiv a serei captatoare din
collecting greenhouse belonging to the solar space. componen a solar.
ϑ p ( x = ∆, τ) − t ( τ)
1)
Φ= , Φ = 1 − exp (−aH )
ϑ p ( x = ∆, τ) − te ( τ) aH
– Nr. 1 / 2010 63
D. Constantinescu
64 – Nr. 1 / 2010
Assessment of the energy performance of the solar space system
0,006625
square standard deviation/theoretical average temp
0,0065
ab.med.patratica/temp.medie.teor. [ - ]
0,006375
0,00625
0,006125
0,006
0,005875
0,00575
0,2 0,25 0,3 0,35 0,4 0,45 0,5 0,55 0,6 0,65 0,7 0,75 0,8 0,85 0,9 0,95 1
n
4.2. The second time-lag, 14.11.-25.12.2008 4.2. Cel de al doilea interval cuprins între
confirms the preservation of value a ⋅ H = 3.106 14.11.2008-
and the reaching of value n = 0.60. The diagrame in aH n = 0,60. În graficul
Fig. 8 presents the variation of function f (n) (20), din fig. 8 se prezin f (n) (20), din
which provides n = 0.60. n = 0,60.
– Nr. 1 / 2010 65
D. Constantinescu
46
te
42 t-vent.m [°C]
t-vent.t [°C]
38
34
t.vent.m, t.vent.t, te [°C]
30
26
22
18
14
10
6
0 10 20 30 40 50 60 70 80 90 100 110 1 20 13 0 140 150 160 1 70 180 190 200 2 10 22 0 230
momentul [h]
Fig. 7. Temperatures specific to the operation of the ventilated solar space – 01.10.2008-10.10.2008
(232 hours) CE INCERC Bucharest
0,00536
0,00535
0,00534
ab.med.patratica./temp.medie.teor.[ - ]
0,00533
0,00532
0,00531
0,0053
0,00529
0,00528
0,00527
0,2 0,25 0,3 0,35 0,4 0,45 0,5 0,55 0,6 0,65 0,7 0,75 0,8 0,85 0,9 0,95 1
n
66 – Nr. 1 / 2010
Assessment of the energy performance of the solar space system
tas − m = 12.2°C also attest the very good estimation tas − m = 12,2°C
by the theoretical model.
The diagram in Fig. 10 presents f (n) and the În graficul din fig. 10 f (n), iar în
diagram in Fig. 11 values tas-t (τ), tas-m (τ), te (τ). graficul din fig. 11 valorile tas-t (τ), tas-m (τ), te (τ).
This analysis shows that the hourly calculation
model used for the temperature of the air exhausted
in the occupied space provides results allowing their
inclusion in the calculation algorithm of the thermal
response of the entire building, if the average value
n = 0.62 isFig.VI.5
usedTemperaturi
(an average rated with
caracteristice n solar ventilat 15.11.2008 - 25.12.2008
the spatiului
functionarii
(976 ore) CE INCERC Bucuresti.
30
28 t-vent.m [°C]
26 t-vent.t [°C]
te [°C]
24
22
20
t.vent.m, t.vent.t, te [°C]
18
16
14
12
10
8
0
-2
-4
0 48 96 144 192 240 288 336 384 432 480 528 576 624 672 720 768 816 864 912 960
momentul [h]
Fig. 9. Temperatures specific to the operation of the ventilated solar space – 15.11.2008-25.12.2008
(976 hours) CE INCERC Bucharest
– Nr. 1 / 2010 67
D. Constantinescu
0,00778
0,00777
square standard deviation/theoretical average temp
0,00776
ab.med.patratica/temp.med.teoretica [ - ]
0,00775
0,00774
0,00773
0,00772
0,00771
0,0077
0,00769
0,00768
0,1 0,15 0,2 0,25 0,3 0,35 0,4 0,45 0,5 0,55 0,6 0,65 0,7 0,75 0,8 0,85 0,9 0,95 1
n
36
te
32 t-vent.m [°C]
t-vent.t [°C]
28
24
t.vent.m, t.vent.t, te [°C]
20
16
12
-4
-8
0 100 200 300 400 500 600 700 800 900 1000 1100 1200
momentul [h]
Fig. 11. Temperatures specific to the operation of the ventilated solar space –
13.01.2009-04.03.2009 (1217 hours), CE INCERC Bucharest
68 – Nr. 1 / 2010
Assessment of the energy performance of the solar space system
5. METHODOLOGICAL SYNTHESIS 5. S
It requires considering the solar radiation
collecting unit as a homogeneous flat plate with
material geometrical and thermo-physical
characteristics which are determined as follows:
Table 1.
3
Material Thickness [m] λ [W / mK] ρ [kg / m ] c [J / kgK] a [m 3 / s]
Mat. 1 δ1 λ1 ρ1 C1 a1
Mat. 2 δ2 λ2 ρ2 C2 a2
Mat. 2 δ2 λ3 ρ3 C3 a3
... ... ... ... ... ...
Mat. n – 1 δn – 1 λn–1 ρn – 1 Cn – 1 an – 1
Mat. n δn λn ρn Cn an
– Nr. 1 / 2010 69
D. Constantinescu
ατ& β
C1 = A1 + A2 B1 ; C2 = A3 + A2 B2 ; D1 = ;
α cvC2 + α r B2
δM δM
Bii = α i ⋅ ; Bi e = α& e ⋅ ;
λM λM
n = 0.62 (for the solution of the CE INCERC n
Bucharest solar space)
M1, M2, M3, Num, according to relation (14). M1, M2, M3, 14).
70 – Nr. 1 / 2010
Assessment of the energy performance of the solar space system
5.5. N1, N2 are determined (according to 15) 5.5. N1, N2 (conform (15))
The calculation relations necessary in deter-
mining the thermal flows and the temperatures
required by the dynamic simulation are: dinamice sunt:
qi (x = 0, τ) according to (12) qi (x = 0, τ) conform (12)
ϑp (x = δM, τ) according to (13) ϑp (x = δ M , τ) conform (13)
t (τ) according to (5) t (τ) conform (5)
tas (τ) according to (18) tas (τ) conform (18)
Of these, q i (x = 0, τ) and t as (τ) are the Dintre acestea qi (x = 0, τ tas (τ) sunt para-
parameters required by the dynamic simulation of
the main zone of the building, which is equipped with
a ventilated solar space.
6. CONCLUZII
6. CONCLUSIONS
1.
1. Taking into account the ventilated solar solar ventilat s-a elaborat un model propriu regimului
space of CE INCERC, a model specific to the hourly variabil de transfe având ca
pace heat transfer transient conditions was carried
out, the object of which is the modeling of the
dynamic process of pre-heating the air exhausted in .
the building. 2.
2. The experimental validation tests covered
three periods of time totalizing 104 days, a number suficient pentru a valida statistic rezultatele.
sufficient for statistically validating the results.
3.
3. The parallel analysis was focused on the
temperature variation of the hot air exhausted in the
heated space and on the thermal flow supplied to
the ventilated solar space by a convective effect. 4.
4. The errors between the measured and the
calculated values range between 3-8 % which con-
firms the satisfactory accuracy of the mathematical
model specific to the ventilated solar space.
BIBLIOGRAPHY BIBLIOGRAFIE
[1] *** Impact of the modern solutions of the energy [1] * * *
upgrading of the existing buildings on their energy
and economic performance, in the context of the
European Directive 2002/91/EEC, Contract 6B02
contextul prevederilor directivei europene 2002/
Amtrans, Phases 3 and 4 / 2004
91/EEC
[2] Constantinescu, D., Heat Engineering Treatise –
Heat Engineering in Construction, Vol. 1, Ed. AGIR, [2] Constantinescu, D. – .
Bucharest, 2008 , Vol. 1 – Fundamentare