International Conference on Power Systems Transients – IPST 2003 in New Orleans, USA

A Coupling Capacitor Voltage Transformer Representation


for Electromagnetic Transient Studies

D. Fernandes Jr.1, W. L. A. Neves1, and J. C. A. Vasconcelos2

(1) Departamento de Engenharia Eletrica, Universidade Federal de Campina Grande, Av. Aprigio Velo-
so, 882, Bodocongo, 58.109-970, Campina Grande – PB – Brazil (e-mail: damasio@dee.ufcg.edu.br,
waneves@dee.ufcg.edu.br), (2) Companhia Hidro Eletrica do Sao Francisco, Rua Delmiro Gouveia, 333,
Bongi, 50.761-901, Recife – PE – Brazil (e-mail: jcrabreu@chesf.gov.br)

Abstract – In this work, a coupling capacitor voltage trans- need to access its internal components. Saturation effects of
former (CCVT) model to be used in connection with the the magnetic core were not taken into account.
EMTP (Electromagnetic Transients Program) is presented. A In this work, a coupling capacitor voltage transformer
support routine was developed to compute the linear 230 kV
model to be used in connection with the EMTP (Electro-
CCVT parameters (resistances, inductances and capacitances)
from the magnitude and phase of the CCVT voltage ratio magnetic Transients Program) is presented. The potential
measured in laboratory, from 10 Hz to 10 kHz. The errors transformer multiple windings and the silicon carbide surge
were fairly small in the whole frequency range. The potential arrester nonlinear characteristic were included in the
transformer (PT) multiple windings, its magnetic core and the CCVT model in order to improve the transient response to
silicon carbide surge arrester nonlinear characteristics were overvoltages. Preliminary results were presented at the
taken into account in the model in order to improve transient IPST 2001 [7].
responses due to overvoltages. The surge arrester gap spark-
CHESF (Companhia Hidro Elétrica do São Francisco)
over voltage was measured and the silicon carbide nonlinear
characteristic was estimated. It is shown that careful attention
made available a 230 kV CCVT unit. Frequency response
must be taken when computing the ferroresonance suppres- measurements of magnitude and phase, in the range from
sion circuit (FSC) parameters to avoid numerical instabilities 10 Hz to 10 kHz, were carried out for this unit and used as
in time-domain simulations. The protection circuit is very input data to a fitting routine based on Newton’s method [8,
effective in damping out transient voltages when a short cir- 9] to compute the linear CCVT parameters R, L, C.
cuit is cleared at the CCVT secondary side. Digital simulations of ferroresonance were carried out
Keywords – CCVT model, EMTP, system protection, data ap- using this model. The results show that careful attention
proximations. must be taken when computing the ferroresonance suppres-
sion circuit (FSC) parameters to avoid numerical instabili-
ties in time-domain simulations. The protection circuit is
I. INTRODUCTION very effective in damping out transient voltages when a
For many years, electric utilities have used coupling ca- short circuit is cleared at the CCVT secondary side.
pacitor voltage transformers (CCVT) connected to protec-
tive relays and measuring instruments. However, problems II. BASIC PRINCIPLES
have yet been traced to incorrect inputs. This has affected
the reliability of the power system and caused failure in The basic electrical diagram for a typical CCVT is
many CCVT. In Brazil, some electrical energy companies shown in Fig. 1. The primary side consists of two capaci-
have reported unexpected overvoltage protective device tive elements C1 and C2 connected in series. The PT pro-
operations in several CCVT leading to failures of some vides a secondary voltage vo for protective relays and
units. The reported overvoltages occurred during normal measuring instruments. The inductance Lc is chosen to
switching conditions [1]. avoid phase shifts between vi and vo at power frequency.
Many works including field measurements, laboratory However, small errors may occur due to the exciting cur-
tests and digital simulations, have been conducted to study rent and the CCVT burden (Zb) [2].
the performance of the CCVT. Some studies have been con- LINE
centrated on nonlinear behavior of the potential trans-
former (PT) magnetic core to accurately simulate the tran-
sient response of CCVT [2, 3, 4]. C1
Other works have considered the effect of stray capaci-
tances in some CCVT elements to explain the measured vi Lc
frequency responses in the linear region of operation [5, 6]. PT
There are some problems in obtaining the CCVT parame-
C2 FSC Zb vo
ters. In [5], the used measurement techniques need disas-
sembling the CCVT and in [6], a method was developed to
estimate the CCVT linear parameters from frequency re-
sponse measurements at the secondary side without the Fig. 1 Electrical diagram for a typical CCVT.

1
International Conference on Power Systems Transients – IPST 2003 in New Orleans, USA

Ferroresonance oscillations may take place if the circuit included in time-domain simulations to improve the repre-
capacitances resonate with the iron core nonlinear induc- sentation of the transient effects in CCVT. The circuit
tance. These oscillations cause undesired information trans- shown in Fig. 2 is considered with specific impedances Z1,
ferred to the relays and measuring instruments. Therefore, Z2, Z3, Z4, Z5 and with all the elements referred to the PT
a ferroresonance suppression circuit (FSC) is normally secondary side, according to Fig. 4.
included in one of the CCVT windings. LINE
Circuits tuned at power frequency (L in parallel with C)
and a resistance to ground have been often used as ferrore- r2C1
sonance suppression circuits [4, 6] because they damp out 1 Z1 2 Z2 3
transient oscillations and require small amount of energy
during steady-state. vi/r Z4
r2C2 r2Cp Z3 4 Zb vo
Z5
III. DEVELOPED ANALYTICAL METHOD
The diagram shown in Fig. 1 is valid only near power
frequency. A model to be applicable for frequencies up to a Fig. 4 CCVT model with specific impedances.
few kilohertz needs to take into account the PT primary
winding and compensating inductor stray capacitances at The expressions for the impedances in the s domain,
least [3 − 6]. with s = jω, are:
In this work, the circuit shown in Fig. 2 was used to rep-
resent the CCVT. It comprises of a capacitive column (C1,
[ ](
Z 1 = (R c + sLc ) r 2 // 1 r 2 sC c ; )
C2), a compensating inductor (Rc, Lc, Cc), a potential trans- (
Z 2 = R p + sL p )r 2
;
former (Rp , Lp , Cp , Lm , Rm) and a ferroresonance suppres-
sion circuit (Rf , Lf1 , Lf2 , −M , Cf) [5, 6].
( )(
Z 3 = R m r 2 // sL m r 2 ; ) (1)

The FSC configuration is shown in Fig. 3(a). A non- ( ) (


Z 4 = sL f 1 + 1 sC f // sL f 2 ; )
saturable iron core inductor Lf is connected in parallel with Z 5 = R f − sM .
a capacitor Cf so that the circuit is tuned to the fundamental
frequency with a high Q factor [4]. The FSC digital model Where, r is the PT ratio and the symbol // means that
is shown in Fig. 3(b). The damping resistor Rf is used to elements are in parallel.
attenuate oscillations caused by the ferroresonance phe- The CCVT model parameters R, L, C should reproduce
nomenon. the transfer functions of magnitude and phase represented
by vo/vi. They are calculated using the technique described
LINE below for the minimization of nonlinear functions.
C1 Cc B. Minimization Technique of Nonlinear Functions
Lc Rc Lp Rp
Here, the used iterative technique for minimizing nonlin-
Cf Lf2 ear functions is based on Newton’s method which uses a
C2 Cp Lm Rm Lf1 −M Zb quadratic approximation to the function F(x) derived from
the second-order Taylor series expansion about the point xi.
Rf In two dimensions, the second-order Taylor series ap-
proximation can be written in the form:

Fig. 2 CCVT model for calculation of parameters.  ∂F ( x1 , x 2 ) 


 ∂x1 
F ( x1 + p1 , x 2 + p 2 ) ≈ F ( x1 , x 2 ) + [ p1 p 2 ] 
Cf  ∂F ( x1 , x 2 ) 
Cf  ∂x 2 
Lf Lf1 Lf2  
(2)
 ∂ 2 F ( x1 , x 2 ) ∂ 2 F ( x1 , x 2 ) 
−M  
1  ∂x12 ∂x1 ∂x 2   p1 
Rf Rf + [ p1 p 2 ]  
2 2
 ∂ F ( x1 , x 2 ) ∂ 2 F ( x1 , x 2 )   p 2 
(a) (b)  ∂x 2 ∂x1 ∂x 22 
 
Fig. 3 (a) FSC configuration. (b) FSC digital model. And for n dimension, the expression above in ma-
trix/vector form is:
A. Calculation of the CCVT Model Parameters
1 T 2
In order to develop the analytical expressions of CCVT F ( x + p ) ≈ F ( x ) + p T ∇F ( x ) + p ∇ F ( x) p . (3)
model, it was considered only the linear region of the PT 2
magnetic core because the core was not saturated during In order to obtain the step p, the function F is minimized
the frequency response measurements. The nonlinearity is by forming its gradient with respect to p and setting it equal

2
International Conference on Power Systems Transients – IPST 2003 in New Orleans, USA

to zero. Therefore,
Signal
∇2F(x)p = −∇F(x). (4) Generator
C1
The approximate solution xk+1 is given by: ∼ vi

[
x k +1 = x k + p = x k − ∇ 2 F ( x k ) ]
−1
∇F ( x k ) . (5)
Power
Amplifier
C2
Inductive
Tank
vo Filter
2 -1
Newton’s method will converge if [∇ F(x)] is positive
definite in each iterative step, that is, zT[∇2F(x)]-1z > 0 for
all z ≠ 0. This technique is known as the full Newton-type
method [8, 9]. It is a modification of Newton’s method for Oscilloscope
that iteration in which [∇2F(x)]-1 is not positive definite. In
the procedure, ∇2F(x) is replaced by a “nearby” positive
Fig. 5 Frequency response measurements for the 230 kV CCVT.
definite matrix ∇ 2 F ( x ) and p is computed solving
∇ 2 F ( x ) p = −∇F ( x ) . B. PT Nonlinear Characteristic Measurements
The function to be minimized is called merit function A sinusoidal voltage supplied by an autotransformer was
χ2(x) and it is given by expression below: applied across terminals X1 − X3 and gradually increased
2
from zero up to 251.3 V rms, according to Fig. 6. The rms
n
 yi − y (ω i ; x ) 
χ 2 ( x) = ∑ 
i =1 
σi
 .

(6) V – I data points were obtained. The data were converted
into the peak λ − i data using a routine from [11].
In order to estimate the PT magnetic core saturation, the
Where ωi is the i-th measured frequency value and yi is air core inductance was calculated by the expression:
the i-th measured frequency response value of the n data
points. σi is the standard deviation for each yi. x is the vec- N 2µ 0 S
L sat ≅ . (7)
tor which contains the parameters R, L, C to be determined l
and y(ωi; x) is the analytical model function. Where, N = 81 is the number of coils of the secondary
A FORTRAN routine was developed to minimize the winding, µ0 = 4π.10-7 H/m is the magnetic permeability in
merit function χ2(x) using the method described above. vacuum, S = 91.5 cm2 is the core crossection area and l =
Besides the function y(ωi; x), it is necessary to know its 71.28 m is the average length of the secondary winding. It
first and second derivatives with respect to each parameter was considered that saturation occurs with a flux density of
of the vector x. The algorithm is based on the following 2.1 T, which corresponds to λknee = 1.556415 V.s. The
steps [7]: value of iknee was calculated from [11] after a logarithmic
1. Supply the CCVT frequency response values yi for each extrapolation of the previous points in the rms V – I curve.
frequency ωi and enter with a guess for the parameters R, This corresponds to the previous to the last point of the λ−i
L, C (vector x); data points shown in Table I. The last segment slope is Lsat.
2. Determine χ2(x) and evaluate χ2(x + p);
X1
3. Save the value of χ2(x + p) and for a user defined num- A
H1
ber of iterations m, compare the actual value of the merit X2
V
function to its old value m iterations before:
4. If the difference is greater than a user defined tolerance,
X3 220 V ~
go back to step 2. Otherwise, stop the iterative process. Y1
2 Y2
IV. LABORATORY MEASUREMENTS H2
Autotransformer
1 Y3
Frequency response measurements of magnitude and
phase were carried out for the 230 kV CCVT. The rms Fig. 6 Measurement of the PT saturation curve.
v − i nonlinear curve for the PT magnetic core was meas-
ured as well. The surge arrester nonlinear characteristic Table I Nonlinear characteristic of the PT magnetic core.
was estimated from measurements of its gap sparkover Peak Current (A) Peak Flux (V.s)
voltage in our high voltage laboratory. 0. 076368 0.025772
A. Frequency Response Measurements 0.720881 0.189066
1.429369 0.396889
During the frequency response measurements, a low-
2.511675 0.748388
pass filter was required to attenuate high frequency noises.
3.662012 0.863553
A 3rd order RC active filter with a cut-off frequency of 15
4.587227 0.903317
kHz, was used [10]. A signal generator feeding an ampli-
fier whose maximum peak-to-peak voltage is 2 kV, was 5.712037 0.942706
connected across the high voltage terminal and the ground, 55.527018 1.556415
according to Fig. 5. 5552.7018 1.562242

3
International Conference on Power Systems Transients – IPST 2003 in New Orleans, USA

C. Surge Arrester Nonlinear Characteristic Estimation Table IV 230 kV CCVT calculated parameters.
The 230 kV CCVT protection circuit comprises by a Rc = 0.39 Ω Lp = 4.92 mH Lf2 = 47.39 mH
silicon carbide (SiC) surge arrester connected in parallel Lc = 3.71 mH Rm = 50.6 Ω Rf = 4.99 Ω
with the capacitance C2. Cc = 11486.1 µF Lm = 700.0 mH M = 9.31 mH
In order to estimate the surge arrester v − i characteristic, Cp = 216.3 nF Lf1 = 10.87 mH −
its sparkover voltage was measured at power frequency.
Rp = 0.0395 Ω Cf = 166.39 µF −
The voltage supplied by a high voltage transformer, rated
100 kV and 10 kVA, was applied gradually across the 5.0
Laboratory measurements
Fitted curve
surge arrester terminals until gap sparkover was reached.
For 7 measurements, the sparkover voltage average value 0.0
was 58.5 kV rms. -5.0

Gain (dB)
According to ANSI/IEEE C62.1-1989 Standard [12], for
a completely assembled gapped silicon carbide arrester the -10.0
power frequency sparkover voltage should not be smaller -15.0
than 1.5 times the rated voltage. Therefore, the tested surge
arrester was rated as a 39 kV rms unit. -20.0
A 39 kV rms surge arrester has an arrester discharge -25.0
voltage (V10) at 10 kA for 8/20 equal to 89.7 kV. This 1.0E+1 1.0E+2 1.0E+3 1.0E+4
value of V10 was taken from ANSI/IEEE C62.2-1987 Stan- Frequency (Hz)
dard [13]. Fig. 7 Magnitude curves for the measured and fitted 230 kV
The surge arrester v − i characteristic is obtained as per- CCVT voltage ratios.
cent of discharge voltage at 10 kA for 8/20 µs. This charac- 90.0 Laboratory measurements
teristic depends also on the waveform applied to the ar- 60.0 Fitted curve
rester. In this work was considered a wavefront of 2 ms 30.0
Phase (degrees)

because the measurements were made at power frequency. 0.0


The estimation of percent was based on a typical character- -30.0
istic for 6 kV silicon carbide arrester, supplied by the -60.0
manufacturer [14]. The 39 kV surge arrester nonlinear -90.0
characteristic is shown in Table II. -120.0
-150.0
Table II Silicon carbide surge arrester nonlinear characteristic.
-180.0
Peak Current (A) Peak Voltage (kV) 1.0E+1 1.0E+2 1.0E+3 1.0E+4
100 20.8 Frequency (Hz)
200 27.9 Fig. 8 Phase curves for the measured and fitted 230 kV CCVT
500 39.0 voltage ratios.
1000 42.9 The average errors of magnitude and phase for initial
2000 45.5 guesses parameters are, respectively, 23.3 % and 16.0o.
After the fitting, the average errors of magnitude and phase
V. ANALYSIS AND DISCUSSION OF THE RESULTS are, respectively, 5.5 % and 8.9o. According to figures 7
and 8, the errors are fairly small for frequencies up to 2
kHz. Near 60 Hz the magnitude and phase errors are very
A. 230 kV CCVT Parameters small. This is the region in which the CCVT operates most
The 230 kV CCVT parameters were obtained from fre- of the time.
quency response data points of magnitude and phase meas- There are some CCVT parameters known at 60 Hz with
ured in the high voltage laboratory of our university. The reasonable accuracy, which are the cases of Lc and Rp. In
initial guesses and fitted parameters, referred to the poten- the fitting process, constraints were used to perform a fine
tial transformer secondary side, are shown in Table III and adjustment of these previously known parameters. Here
Table IV, respectively. The magnitude and phase curves they were allowed to vary within 20 %. This procedure
for the measured and fitted voltage ratios are shown in fig- imposes limitations for the fitting technique, but it gives
ures 7 and 8, respectively. more realistic results.
If Cc and Cp are neglected in the model, the frequency
Table III 230 kV CCVT initial guesses parameters.
response of CCVT does not follow the frequency response
Rc = 1.0 Ω Lp = 3.0 mH Lf2 = 95.0 mH curve of the entire model. In order to verify this, a sensitiv-
Lc = 2.0 mH Rm = 90.0 Ω Rf = 4.0 Ω ity analysis was carried out for the voltage ratio magnitude
curve, considering the entire model (parameters from Table
Cc = 1100.0 µF Lm = 300.0 mH M = 10.0 mH
IV) and the model using Table IV values with Cc and Cp set
Cp = 1.0 µF Lf1 = 10.0 mH − to zero. The results are shown in Fig. 9. It can be seen a
Rp = 3.0 Ω Cf = 140.0 µF − large difference between the curves from 100 Hz onwards.

4
International Conference on Power Systems Transients – IPST 2003 in New Orleans, USA

5.0
1 + A1 s 2
0.0 Y f (s) = . (8)
B0 + B1 s + B 2 s 2 + B3 s 3
-5.0
Where, A1 = Cf(Lf1 + Lf2), B0 = Rf, B1 = Lf2 − M, B2 =
Gain (dB)

-10.0
RfCf(Lf1 + Lf2) and B3 = Lf1Lf2Cf − MCf(Lf1 + Lf2). Replacing
-15.0 the FSC parameters by their calculated values (Table IV),
-20.0 it is obtained two imaginary zeroes, z1 = j321.18 and z2 =
-25.0 With Cc and Cp −j321.18, and three real poles, p1 = 11404.0, p2 = −577.0
Without Cc and Cp and p3 = −167.0.
-30.0
1.0E+1 1.0E+2 1.0E+3 1.0E+4 The numerical instability takes place due to the pole
Frequency (Hz) p1 = 11404.0 located on the right half-plane of the s plane.
Fig. 9 Sensitivity analysis for the CCVT magnitude curve.
In order to eliminate the instability it is necessary to make
B3 in equation (8) greater than or equal to zero, assuring
B. Ferroresonance Simulations that all poles are located on the left half-plane of the s
plane. This condition is satisfied by assuming values for
To perform the 230 kV CCVT ferroresonance simula- inductance M smaller or equal to 8.84 mH. In fact, the fit-
tions, MICROTRAN [15] was used. The CCVT model is ting procedure gave a non-realizable model for the ferrore-
shown in Fig. 10. The magnetizing inductance Lm was re- sonance suppression circuit. This problem is solved if the
placed by a nonlinear inductance connected across the coil Lf is divided into Lf1 and Lf2 and modeled as L1 + M
CCVT secondary terminals whose λ − i data points are and L2 + M, respectively, where L1 and L2 are leakage in-
shown in Table I. The potential transformer was repre- ductances. The fitting routine was modified to take this
sented by the three winding single-phase transformer model. assumption into account. The error for the amplitude curve
The protection circuit composed by a silicon carbide surge is about the same as the fitted curve shown in Fig. 7. How-
arrester was included as well. Its v − i nonlinear character- ever, for phase curve, the fitting was not so accurate for
istic is shown in Table II. At point A the system was repre- frequencies beyond 200 Hz. Further investigations are
sented by its Thévenin equivalent. needed regarding the CCVT equivalent circuit in order to
The ferroresonance simulations were based on tests rec- improve the fitting for the phase curve.
ommended by IEC 186 Standard [16]. The first test estab- For ferroresonance analysis, the value of M equal to
lishes that the equipment must be energized at 1.2 p.u. of 8.84 mH does not affect the simulation results, because the
rated voltage. One of the secondary terminals is short cir- ferroresonance takes place in low frequencies, normally
cuited and its burden has to be nearly zero. The short cir- between 1/3 sub harmonic and the 3rd harmonic. In this
cuit must be sustained during three cycles at least. frequency range the magnitude and phase curves for the
In order to analyze the importance of the FSC in tran- CCVT voltage ratio are very similar for both values of M,
sient damping, two simulations were performed: one case 8.84 mH and the estimated value, 9.31 mH.
with the FSC included in the CCVT model and another Fig. 12 shows the CCVT secondary voltage waveform
case when the FSC is removed. In both cases, the simula- when the FSC is removed. The oscillations remain up to
tions consist of a close-open operation of a switch SW con- 500 ms, when the steady-state is reached. Fig. 13 shows the
nected across the CCVT secondary terminals, as shown in same case with the FSC included in the CCVT model. The
Fig. 10. The switch closes at t = 125 ms and remains closed oscillations are damped in a time smaller than 100 ms, in
during 6 cycles, when the short circuit is cleared. conformity with ferroresonance standard tests.
In the simulation that takes into account the FSC, it was Fig. 14 shows the CCVT secondary voltage when the
observed numerical instabilities taking place in the CCVT FSC is included in the model, but considering the failure of
secondary voltage waveform, according to Fig. 11. This the protection circuit. Comparing Fig. 14 with Fig. 13, one
problem can be explained by writing the FSC admittance, can see that the protection circuit is very effective in limit-
Yf(s), based on its model shown in Fig 3(a). ing peak transient voltages at the CCVT secondary side.

Magnetic Ferroresonance
493.2 nF Potential Transformer
Core Suppression
Ce = C1 + C2 A 86.29 H 9.1 kΩ 114.7 H 920 Ω Circuit
166.39 µF 47.39 mH
SW
λ−i 10.87 mH −8.84 mH vo
Gap 50.6 Ω
4.99 Ω
C1
~ vi′ = 1.2
C1 + C2
vi 9.29 pF
v−i
Thévenin
Equivalent

SiC
Surge Arrester
Fig. 10 230 kV CCVT model for electromagnetic transient studies.

5
International Conference on Power Systems Transients – IPST 2003 in New Orleans, USA

60
50
sults reveal the importance of the FSC and the protection
Secondary Voltage (kV) 40 circuit in damping out transient voltages when a short cir-
30 cuit is cleared at the CCVT secondary terminals, the au-
20 thors intend to perform ferroresonance tests in laboratory
10
0
for validation purposes.
-10
-20
ACKNOWLEDGMENTS
-30 The authors are grateful to CHESF for providing a 230
0 20 40 60 80 100 120 140
Time (ms) kV CCVT unit at our laboratory. The financial support of
Fig. 11 CCVT secondary voltage: numerical instability. Mr. Damasio Fernandes Jr. from the Brazilian National
300 Research Council (CNPq) is acknowledged. The authors
200 also wish to thank the reviewers for their suggestions.
Secondary Voltage (V)

100
0
-100
REFERENCES
-200 [1] H. M. Moraes and J. C. A. Vasconcelos, “Overvoltages in CCVT
-300
During Switching Operations”, (In Portuguese), Proceedings of
-400
-500
the XV SNPTEE, Foz do Iguaçu, October 17-22, 1999.
-600 [2] J. R. Lucas, P. G. McLaren, W. W. L. Keerthipala and R. P.
-700 Jayasinghe, “Improved Simulation Models for Current and Volt-
0 100 200 300 400 500 age Transformers in Relay Studies”, IEEE Trans. on Power De-
Time (ms)
livery, Vol. 7, No. 1, pp. 152-159, January 1992.
Fig. 12 Secondary voltage: CCVT without the FSC. [3] M. R. Iravani, X. Wang, I. Polishchuk, J. Ribeiro and A. Sarshar,
400 “Digital Time-Domain Investigation of Transient Behaviour of
300 Coupling Capacitor Voltage Transformer”, IEEE Trans. on
Secondary Voltage (V)

200 Power Delivery, Vol. 13, No. 2, pp. 622-629, April 1998.
100 [4] D. A. Tziouvaras, P. McLaren, G. Alexander, D. Dawson, J.
0 Ezstergalyos, C. Fromen, M. Glinkowski, I. Hasenwinkle, M.
-100 Kezunovic, Lj. Kojovic, B. Kotheimer, R. Kuffel, J. Nordstrom,
-200 and S. Zocholl, “Mathematical Models for Current, Voltage and
-300
Coupling Capacitor Voltage Transformers”, IEEE Trans. on
-400
Power Delivery, Vol. 15, No. 1, pp. 62-72, January 2000.
0 100 200 300 400 500 [5] M. Kezunovic, Lj. Kojovic, V. Skendzic, C. W. Fromen, D. R.
Time (ms) Sevcik and S. L. Nilsson, “Digital Models of Coupling Capacitor
Fig. 13 Secondary voltage: CCVT with the FSC. Voltage Transformers for Protective Relay Transient Studies”,
IEEE Trans. on Power Delivery, Vol. 7, No. 4, pp. 1927-1935,
3.0
2.5 October 1992.
Secondary Voltage (kV)

2.0 [6] Lj. Kojovic, M. Kezunovic, V. Skendzic, C. W. Fromen and D. R.


1.5
1.0 Sevcik, “A New Method for the CCVT Performance Analysis
0.5 Using Field Measurements, Signal Processing and EMTP Model-
0.0
-0.5
ing”, IEEE Trans. on Power Delivery, Vol. 9, No. 4, pp. 1907-
-1.0 1915, October 1994.
-1.5 [7] D. Fernandes Jr., W. L. A. Neves and J. C. A. Vasconcelos,
-2.0
-2.5 “Identification of Parameters for Coupling Capacitor Voltage
-3.0 Transformers”, Proceedings of the IPST 2001, pp. 463-468, Rio
0 100 200 300 400 500
Time (ms)
de Janeiro, June 24-28, 2001.
[8] D. Kahaner, C. Moler and S. Nash, Numerical Methods and
Fig. 14 CCVT secondary voltage: failure in the protection circuit. Software, Prentice Hall PTR, New Jersey, 1989.
Although the results shown in figures 11-14 are interest- [9] W. H. Press, S. A. Teukolsky, W. T. Vetterling and B. P.
ing, it is not certain at this stage whether they are accurate. Flannery, Numerical Recipes in Fortran - The Art of Scientific
Computing, Second Edition, Cambridge University Press, 1992.
Laboratory measurements will be carried out in the near [10] D. Fernandes Jr., Estimation of Coupling Capacitor Voltage
future for validation purposes. Transformer Parameters, M. Sc. Dissertation (In Portuguese),
UFPB, September 1999.
VI. CONCLUSIONS [11] W. L. A. Neves and H. W. Dommel, “On Modeling Iron Core
In this work, a CCVT model for electromagnetic tran- Nonlinearities”, IEEE Trans. on Power Systems, Vol. 8, No. 2,
pp. 417-423, May 1993.
sient studies was presented. The model comprises linear [12]ANSI/IEEE Std C62.1-1989, IEEE Standard for Gapped Sili-
parameters R, L, C obtained from the fitting routine based con-Carbide Surge Arresters for AC Power Circuits, 1989.
on Newton’s method that uses as input data the frequency [13]ANSI/IEEE Std C62.2-1987, IEEE Guide for the Application of
response measurements of magnitude and phase, in the Gapped Silicon-Carbide Surge Arresters for AC Systems, 1987.
range from 10 Hz to 10 kHz. The model includes the PT [14] IEEE Surge Protective Devices Committee, “Modeling of Cur-
magnetic core and SiC surge arrester nonlinear characteris- rent-Limiting Surge Arresters”, IEEE Trans. on Power Apparatus
and Systems, Vol. PAS-100, No. 8, pp. 4033-4040, August 1981.
tics and may be used in connection with the EMTP. [15] Microtran Power System Analysis Corporation, Electromag-
The results show that careful attention must be taken netic Transients Analysis Program, Vancouver, 1999.
when calculating the FSC parameters to avoid numerical [16]IEC 186 (1969), Voltage Transformers, First Supplement (1970),
instabilities in time-domain simulations. Although the re- Amendment No. 1, 1978.