CIRCUIT : K01 11 KV FEEDER OCEF PROTECTION:

1. General Relay Data

Manufacturer : AREVA Type : P122


Rated Voltage : 130-250 V DC Rated Current In : 0.01 TO 8 In
Serial No. : Model Number : P122B00M211
Frequency : 50 Cde. : 27928/001

2. Commissioning Preliminaries tick

Serial number on , module and settings checked : √

CT shorting switch in case checked : √

Earth connection to case checked : √

Test block connections checked : √

Insulation checked : √

Auxiliary supply voltage checked term. : √

3. Auxiliary Supply Checked

Watchdog Contact Check Checked (tick)


Aux. Supply Off Terminal 35 & 36 (closed) √
Aux. Supply On Terminal 35 & 36 (open) √

4 Metering Checks

Terminal Actual Value Injected Relay Metered Value


RED PHASE CURRENT 0.5 A
YELLOW PHASE CURRENT 0.5 A
BLUE PHASE CURRENT 0.5 A
NEUTRAL CURRENT 0.5 A

Hardware Configuration

Hardware Check
Performed At Result Details
Not yet performed
Analog Outputs
Test Equipment Test Object
Display Connection
Device Connector
Name Terminal
CMC256plus 1
VA 2
?????? 3
N
CMC256plus 1
VB N
??????
CMC256plus I 1 I L1
A 2 I L2
?????? 3 I L3
N
CMC256plus I 1
B 2
?????? 3
N

Binary/Analog Inputs
Test Equipment Test Object
Display Connection
Device Connector
Name Terminal
CMC256plus 1+ TRIP1
?????? 1-
2+
2- Start L1
3+ Start
3-
4+
4-
5+
5-
6+
6-
7+
7-
8+
8-
9+
9-
10+
10-
1
2
N
Binary Outputs
Test Equipment Test Object
Display Connection
Device Connector
Name Terminal
CMC256plus 1+ TRIP 11 KV
?????? 1-
2+ TRIP 66 KV
2-
3+ Bin. Out 3
3-
4+ Bin. Out 4
4-
11 Bin. Out 5
12 Bin. Out 6
13 Bin. Out 7
14 Bin. Out 8
N

Analog DC Inputs
Test Equipment Test Object
Display Connection
Device Connector
Name Terminal
CMC256plus V+ V1
?????? V-
I+ I1
I-

Test Object - Device Settings

Substation/Bay:
Substation: ALI SABIEH 63/20 kV Substation address:
Bay: =J02, 20 KV FEEDER Bay address:

Device:
Name/description: ALI SABIEH 63/20 kV Manufacturer: SIEMENS
Device type: 7SJ6321 Device address:
Serial/model number: ______________________
Additional info 1:
Additional info 2:

Nominal Values:
f nom: 50,00 Hz Number of phases: 3
V nom (secondary): 100,0 V V primary: 20,00 V
I nom (secondary): 1,000 A I primary: 300,0 A

Residual Voltage/Current Factors:


VLN / VN: 1,732 IN / I nom: 1,000

Limits:
V max: 200,0 V I max: 50,00 A

Debounce/Deglitch Filters:
Debounce time: 3,000 ms Deglitch time: 0,000 s

Overload Detection:
Suppression time: 50,00 ms

Test Object - Overcurrent Parameters


Overcurrent protection
Abs. Time Tolerance: 0,200 s Rel. Time Tolerance: 10,00 %
Abs. Current Tolerance: 0,10 In Rel. Current Tolerance: 10,00 %
PT connection: On Line
CT Starpoint Towards Line
Connection:
Directional: No
Apply Auto Reset: No

Group: Line-Neutral

Reset Ratio: 0,95


Setting Active Pick-up Current Time Characteristic
I> Yes 0,100 In (0,100 A) 0,500 s Definite time
I>> No 1,000 In (1,000 A) 0,000 s
I>>> No 10,000 In (10,000 A) 0,050 s

Group: Line-Line

Reset Ratio: 0,95


Setting Active Pick-up Current Time Characteristic
I> Yes 1,000 In (1,000 A) 1,000 Siemens VI
I>> Yes 2,000 In (2,000 A) 0,700 s
I>>> No 10,000 In (10,000 A) 0,050 s

Group: Negative sequence

Reset Ratio: 0,95


Setting Active Pick-up Current Time Characteristic
I> Yes 0,200 In (0,200 A) 8,000 s Definite time
I>> No 4,000 In (4,000 A) 0,100 s
I>>> No 10,000 In (10,000 A) 0,050 s

Group: Zero sequence

Reset Ratio: 0,95


Setting Active Pick-up Current Time Characteristic
I> No 1,000 In (1,000 A) 1,000 IEC Normal Inverse
I>> No 4,000 In (4,000 A) 0,100 s
I>>> No 10,000 In (10,000 A) 0,050 s

Test Object - Distance Settings


System parameters:
Line length: 1,000 Ω Line angle: 75,00 °
PT connection: at line CT starpoint: Dir. line
Impedance correction no
1A/I nom:
Impedances in primary no
values:

Tolerances:
Tol. T rel.: 5,000 %
Tol. T abs. +: 50,00 ms Tol. T abs. -: 0,000 s
Tol. Z rel.: 5,000 % Tol. Z abs.: 50,00 mΩ

Grounding factor:
kL mag.: 1,000000 kL angle: 0,000000°
Separate arc no
resistance:

Zone Settings:

50N-1 Neutral Overcurrent:


Test Object - Overcurrent Parameters

Overcurrent protection
Abs. Time Tolerance: 0,200 s Rel. Time Tolerance: 10,00 %
Abs. Current Tolerance: 0,10 In Rel. Current Tolerance: 10,00 %
PT connection: On Line
CT Starpoint Connection: Towards Line
Directional: No
Reset Ratio: 0,95
Apply Auto Reset: No
Threshold Active Pick-up Current Time Characteristic
I> Yes 0,100 In (0,100 A) 0,500 s Definite time
I>> No 1,000 In (1,000 A) 0,000 s
I>>> No 10,000 In (10,000 A) 0,050 s

Test Settings for Fault Type L1-E

Fault Model
Prefault time: 0,000 s
Postfault time: 500,0 ms
Max. fault time abs.: 240,0 s Max. fault time rel.: 100,00 %
Fault voltage: 1,000 Vn
Load Current: 0,000 In
Angle: -75,00 °
Th. Reset Enabled: No
Th. Reset Method: Manual

Pick-up Test
Test Type: Do not perform test
Trip Value: n/a
Resolution: 100,0 ms
Evaluate: No
Max.
Relative I [A] Direction tnom tmin tmax Fault
Time
0,90 I> 0,09 n/a N/T 300,0 ms N/T 240,0 s
0,95 I> 0,10 n/a N/T 300,0 ms N/T 240,0 s
1,00 I> 0,10 n/a 500,0 ms 300,0 ms N/T 240,0 s
1,05 I> 0,11 n/a 500,0 ms 300,0 ms N/T 240,0 s
1,10 I> 0,11 n/a 500,0 ms 300,0 ms N/T 240,0 s

Binary Outputs
TRIP 11 KV: 0
TRIP 66 KV: 0
Bin. Out 3: 0
Bin. Out 4: 0
Trigger condition
Trigger Logic: OR
TRIP1: 1
Start: X

Test Module
Name: OMICRON Overcurrent Version: 2.22
Test Start: 13-ožu-2011 21:10:07 Test End: 13-ožu-2011 21:10:12
User Name: Manager:
Company:

Test Results for Fault Type L1-E


Relative I [A] Direction tnom tact Deviation [%] State Overload Result
0,90 I> 0,09 n/a N/T N/T Tested Passed
0,95 I> 0,10 n/a N/T N/T Tested Passed
1,00 I> 0,10 n/a 500,0 ms 542,8 ms 8,55 Tested Passed
1,05 I> 0,11 n/a 500,0 ms 531,3 ms 6,26 Tested Passed
1,10 I> 0,11 n/a 500,0 ms 519,6 ms 3,92 Tested Passed
Pick-up Test Results
Test Status: No results available!

Pick-up value:
Dropout value:
Reset ratio:
Ratio error (Relative):
Assessment:

Overcurrent Characteristic Diagram


10,00

7,00

5,00

3,00

2,00

1,00

0,70
t [s]

0,50

0,30

0,20

0,10

0,07

0,05
0,90 2,00 3,00 4,00 5,00
L1-E - I /( In *0,100)

State:
5 out of 5 points tested.
5 points passed.
0 points failed.

Test performed offline: Test results are simulated!


General Assessment: Test passed
51 and 50-1 Phase Overcurrent:
Test Object - Overcurrent Parameters

Overcurrent protection
Abs. Time Tolerance: 0,200 s Rel. Time Tolerance: 10,00 %
Abs. Current Tolerance: 0,10 In Rel. Current Tolerance: 10,00 %
PT connection: On Line
CT Starpoint Connection: Towards Line
Directional: No
Reset Ratio: 0,95
Apply Auto Reset: No
Threshold Active Pick-up Current Time Characteristic
I> Yes 1,000 In (1,000 A) 1,000 Siemens VI
I>> Yes 2,000 In (2,000 A) 0,700 s
I>>> No 10,000 In (10,000 A) 0,050 s

Test Settings for Fault Type L1-L2-L3

Fault Model
Prefault time: 0,000 s
Postfault time: 500,0 ms
Max. fault time abs.: 50,00 s Max. fault time rel.: 100,00 %
Fault voltage: 0,933 Vn
Load Current: 0,000 In
Angle: -75,00 °
Th. Reset Enabled: No
Th. Reset Method: Manual

Pick-up Test
Test Type: Do not perform test
Trip Value: n/a
Resolution: 100,0 ms
Evaluate: No
Max.
Relative I [A] Direction tnom tmin tmax Fault
Time
1,40 I> 1,40 n/a 33,75 s 22,50 s 57,12 s 50,00 s
1,60 I> 1,60 n/a 22,50 s 15,99 s 33,75 s 50,00 s
1,80 I> 1,80 n/a 16,88 s 12,40 s 23,95 s 47,90 s
2,00 I> 2,00 n/a 700,0 ms 500,0 ms 18,56 s 37,13 s
2,20 I> 2,20 n/a 700,0 ms 500,0 ms 15,15 s 30,31 s

Binary Outputs
TRIP 11 KV: 0
TRIP 66 KV: 0
Bin. Out 3: 0
Bin. Out 4: 0
Trigger condition
Trigger Logic: OR
TRIP1: 1
Start: X

Test Module
Name: OMICRON Overcurrent Version: 2.22
Test Start: 13-ožu-2011 21:10:16 Test End: 13-ožu-2011 21:10:21
User Name: Manager:
Company:

Test Results for Fault Type L1-L2-L3


Relative I [A] Direction tnom tact Deviation [%] State Overload Result
1,40 I> 1,40 n/a 33,75 s T out of rng.
1,60 I> 1,60 n/a 22,50 s 23,08 s 2,56 Tested Passed
1,80 I> 1,80 n/a 16,88 s 16,82 s -0,35 Tested Passed
2,00 I> 2,00 n/a 700,0 ms 704,7 ms 0,68 Tested Passed
2,20 I> 2,20 n/a 700,0 ms 734,5 ms 4,93 Tested Passed

Pick-up Test Results


Test Status: No results available!

Pick-up value:
Dropout value:
Reset ratio:
Ratio error (Relative):
Assessment:

Overcurrent Characteristic Diagram


500,0000

100,0000
50,0000

10,0000
5,0000

1,0000
0,5000
t [s]

0,1000
0,0500

0,0100
0,0050

0,0010
0,0005

1,0 2,0 3,0 5,0 7,0 10,0


L1-L2-L3 - I /( In *1,000)

State:
5 out of 5 points tested.
5 points passed.
0 points failed.

Warning(s):
Some points were out of time range and could not be tested.

Test performed offline: Test results are simulated!


General Assessment: Test passed
46-1 Negative Phase Sequence:
Test Object - Overcurrent Parameters

Overcurrent protection
Abs. Time Tolerance: 0,200 s Rel. Time Tolerance: 10,00 %
Abs. Current Tolerance: 0,10 In Rel. Current Tolerance: 10,00 %
PT connection: On Line
CT Starpoint Connection: Towards Line
Directional: No
Reset Ratio: 0,95
Apply Auto Reset: No
Threshold Active Pick-up Current Time Characteristic
I> Yes 0,200 In (0,200 A) 8,000 s Definite time
I>> No 4,000 In (4,000 A) 0,100 s
I>>> No 10,000 In (10,000 A) 0,050 s

Test Settings for Fault Type I2

Fault Model
Prefault time: 0,000 s
Postfault time: 500,0 ms
Max. fault time abs.: 240,0 s Max. fault time rel.: 100,00 %
Fault voltage: 1,000 Vn
Load Current: 0,000 In
Angle: -75,00 °
Th. Reset Enabled: No
Th. Reset Method: Manual

Pick-up Test
Test Type: Do not perform test
Trip Value: n/a
Resolution: 100,0 ms
Evaluate: No
Max.
Relative I [A] Direction tnom tmin tmax Fault
Time
0,90 I> 0,18 n/a N/T 7,200 s N/T 240,0 s
0,95 I> 0,19 n/a N/T 7,200 s N/T 240,0 s
1,00 I> 0,20 n/a 8,000 s 7,200 s N/T 240,0 s
1,05 I> 0,21 n/a 8,000 s 7,200 s N/T 240,0 s
1,10 I> 0,22 n/a 8,000 s 7,200 s N/T 240,0 s

Binary Outputs
TRIP 11 KV: 0
TRIP 66 KV: 0
Bin. Out 3: 0
Bin. Out 4: 0
Trigger condition
Trigger Logic: OR
TRIP1: 1
Start: X

Test Module
Name: OMICRON Overcurrent Version: 2.22
Test Start: 13-ožu-2011 21:10:25 Test End: 13-ožu-2011 21:10:30
User Name: Manager:
Company:

Test Results for Fault Type I2


Relative I [A] Direction tnom tact Deviation [%] State Overload Result
0,90 I> 0,18 n/a N/T N/T Tested Passed
0,95 I> 0,19 n/a N/T N/T Tested Passed
1,00 I> 0,20 n/a 8,000 s 8,226 s 2,82 Tested Passed
1,05 I> 0,21 n/a 8,000 s 7,927 s -0,92 Tested Passed
1,10 I> 0,22 n/a 8,000 s 7,632 s -4,60 Tested Passed
Pick-up Test Results
Test Status: No results available!

Pick-up value:
Dropout value:
Reset ratio:
Ratio error (Relative):
Assessment:

Overcurrent Characteristic Diagram


1000,00

500,00

100,00

50,00

10,00
t [s]

5,00

1,00

0,50

0,10

0,05
0,90 2,00 3,00 4,00 5,00
I2 - I /( In *0,200)

State:
5 out of 5 points tested.
5 points passed.
0 points failed.

Test performed offline: Test results are simulated!


General Assessment: Test passed