ABU HAORIYAH - 380/115kV BSP GIS

CUSTOMER: SAUDI ELECTRICITY COMPANY. SEC. EOA.


EXPANSION PROJECT.
CONTRACT NO. : 30733178/00 NATIONAL CONTRACTING COMPANY
SUBSTATION: 380/115kV BSP ABU HADRIYAH LTO. AL KHOBAR.
TYPE FORM: 420kV GIS
BAYNo. C4. BUS 1 VOLTAGE TRANSFORMER

Type VZR-AM400CFS3
Standard IEC 60044-2
Rated primary voltage 380143 kV
Rated secondary voltage 110-110/43 1110-110143 V
Rated output 100 1100 VA
Accuracy class O.2&3P 1 0.2&3P
Highest system voltage 420
Rated insulation level 630/1425
Rated voltage factor 1.5 130 s
Rated frequency 60
Rated SF6 gas pressure 600 kPa-abs at 20'C
Construction No. 3387061-4

Serial No. Phase


10910015 A
10910016 B
10910017 C
ABU HADRIYAH • 380/115kV BSP GIS
CUSTOMER: SAUDI ELECTRICITY COMPANY. SEC. EOA.
EXPANSION PROJECT.
CONTRACT NO. : 30733178/00 NATIONAL CONTRACTING COMPANY
SUBSTATION: 380/115kV BSP ABU HADRIYAH LTD. AL KHOBAR.
TYPE FORM : 420kV GIS
BAYNo. C4. BUS 1 VOLTAGE TRANSFORMER

MANUFACTURER : TOSHIBA JAPAN.

TYPE : VZR - AM400CFS3

: 380kV
"3
110 - 110V 110 - 110V
F 73

CRITERIA OF
SERIAL. No. CHECKS TO BE PERFORMED RESULT
ACCEPTANCE
1 INSPECT PHYSICAL DAMAGE I DEFECTS NO DAMAGE I DEFECTS OK

2 CHECK NAME PLATE CORRECTNESS AS PER APPROWED DWGS. OK

3 CHECK TIGHTNESS OF ALL BOLTED CONNECTIONS SATISFACTORY OK

CHECK ALL GROUNDING CONNECTIONS


4 AS PER APPROWED DWGS. OK
ARE SECURL Y CONNECTED
CHECK ALL SECONDARY WIRING IS CORRECTLY
5 AS PER APPROWED DWGS. OK
COLOUR CODED AND SIZE OF WIRE AS SPECIFIED
CHECK VT. LOCATION AND SECONDARY TERMINAL
6 AS PER APPROWED DWGS. OK
LABELING AS PER DRAWING.

WITNESSED BY
Name: MUHAMMAD KASHIF

Signature: Signature: / / /;)

Date: VI
TOSHIBA CORPORATION
Date: BIll mo v~1t·
SAUDI ELECTRICTY COMPANY. CSD. EOA

TOSHIBA CORPORATION
FIELD TEST PROCEDURE & RECORD
ABU HAORIYAH • 380/115kV BSP GIS
CUSTOMER: SAUDI ELECTRICITY COMPANY. SEC. EOA.
EXPANSION PROJECT.
CONTRACT NO. : 30733178/00 CONTRACTOR: NATIONAL CONTRACTING COMPANY
SUBSTATION: 380/115kV BSP ABU HADRIYAH LTD. AL KHOBAR.
TYPE FORM : 420kVGIS
BAYNo. C4. BUS 1 VOLTAGE TRANSFORMER

VOLTAGE TRANSFORMER.
Insulation resistance measurement.

VTNo. PHASE SERIAL No.


A 10910015
BUS 1.VT. B 10910016
C 10910017

Primary Circuit : > 1000 MO


Secondary Circuit: > 2 MO (Toshiba standard)

Insulation resistance (GO) Ambient


Measurement circuit Result
Phase A Phase B Phase C Temp. 0 C
PRIMARY - GROUND 100 GO 100 GO 100 GO 23.1 OK

SECONDARY1-GROUND 40GO 30 GO 25 GO 23.1 OK

SECONDARY 2- GROUND 40GO 40 GO 30 GO 23.1 OK

SECONDARY 1- PRIMARY 40 GO 40 GO 30 GO 23.1 OK

SECONDARY 2 - PRIMARY 40GO 40 GO 25GO 23.1 OK

SECONDARY1-SECONDARY2 16GO 15GO 17 GO 23.1 OK

WITNESSED BY
Name: MUHAMMAD KASHIF

Signature: Signature:

Date: 6f Date: eJ I
FIELD TEST PROCEDURE & RECORD
ABU HADRIYAH - 380/115kV BSP GIS
CUSTOMER: SAUDI ELECTRICITY COMPANY. SEC. EOA.
EXPANSION PROJECT.
CONTRACT NO. : 30733178/00 NATIONAL CONTRACTING COMPANY
SUBSTATION: 380/115kV BSP ABU HADRIYAH CONTRACTOR : LTD. AL KHOBAR.
TYPE FORM : 420kVGIS
BAYNo. C4. BUS 1 VOLTAGE TRANSFORMER

VOLTAGE TRANSFORMER.
Polarity check.
Check the polarity by inductive kick method for both taps.

Earthing
conductor
Removed

Primary Indication
Phase Terminal No. Result
Injection point ON OFF

A
1a1 -1n
1a2 - 1n
X2A:1-3
X2A:2-3 + - OK
2a1 - 2n
2a2 - 2n
X2B: 1 - 3
X2B: 2 - 3 + - OK

K835 B
1a1 -1n
1a2 - 1n
X2A:4-6
X2A:5-6 + - OK
2a1 - 2n
2a2 - 2n
X2B: 4-6
X2B: 5 - 6 + - OK
1a1 -1n
1a2 -1n
X2A:7-9
X2A:8-9 + - OK
C
2a1 - 2n
2a2 - 2n
X2B: 7 - 9
X2B: 8-9 + - OK

Criteria : Subtractive polarity [Toshiba standard]


At the moment of making the switch, voltmeter should be indicated positive.
At the moment of breaking the switch, voltmeter should be indicated negative.

Signature: Signature:

Date: 01 Date: 01 IJ/?-OID


TOSHIBA CORPORATION SAUDI ELECTRICTY COMPANY. CSD. EOA

TOSHIBA CORPORATION
ABU HAORIYAH· 380/115kV BSP GIS
CUSTOMER:

CONTRACT NO. :
I SAUDI ELECTRICITY
30733178/00
COMPANY. SEC. EOA. PROJECT:
EXPANSION PROJECT.
NATIONAL CONTRACTING COMPANY
CONTRACTOR:
SUBSTATION: 380/115kV BSP ABU HADRIYAH LTD. AL KHOBAR.
TYPE FORM : 420kVGIS
IBAY NO. IC4. BUS 1 vnl Tar-", RATING: ~RnI<V 3150A. 63kA 1S8C. 60Hz

VOLTAGE TRANSFORMER.
Winding resistance measurement.
Measurment of winding resistance by bridge method, and value will be corrected to 75° C.

•..•
nma v vvlnalna KeSIStance (ll)
Phase Measurea liorrectea Koutlne I est Error % Ambient Result
at Ul.. at (tJu l.. value at (tJu C Temo.o C
A 47900 57420 57770 0.61 23.6 OK

B 47850 57472 57940 -0.81 23.1 OK

C 48000 57585 58500 -1.6 23.4 OK

VT SECONDARY WINDING RESISTANCE MEASURED AT SECONDARY TERMINALS.

Secondary Winding Resistance(Q)


Phase Terminal No. Measured Corrected Routine Test Error % Result
atOC at 75° C Value at 75° C
1 a 1 - 1n 0.0850 23.6 0.1018 0.1020 -0.22 OK

1 a 2 -1n 0.0572 23.9 0.0685 0.0668 2.52 OK


A
2 a 1 - 2n 0.0810 23.9 0.0969 0.0995 -2.52 OK

2 a 2 - 2n 0.0600 23.9 0.0718 0.0733 -2 OK

1 a 1 - 1n 0.0832 23.3 0.0999 0.1020 -2.1 OK

1 a 2 - 1n 0.0575 23.1 0.0691 0.0677 2 OK


B
2 a 1 - 2n 0.0840 23.1 0.1008 0.1030 -2 OK

2 a 2 - 2n 0.0590 23.1 0.0709 0.0707 0.23 OK

1 a 1 - 1n 0.0821 23.1 0.0986 0.1010 -2.37 OK

1 a 2· 1n 0.0546 23.3 0.0655 0.0668 -1.9 OK


C
2 a 1 - 2n 0.0810 23.4 0.0972 0.0994 -2.34 OK

2 a 2 - 2n 0.0545 23.4 0.0654 0.0668 -2.12 OK

Criteria: ±5% of routine test value at factory and less than the specified value. [Toshiba standard]
RfT75: Routine test value at factory (at GIS in 75°C)
RsTs : Site test value which contained a measurement cable(at GIS)
RsT75: Site test value (at LCP in 75°C ;Calculated value)
RST75 = RSlC(235+75)/(235+ Ts)
Ts: Ambient temperature

TEST EQUIPMENT USED: YOKOGAWA.PORTABLE DOUBLE BRIDGE.

TESTED BY WITNESSED BY
Name: BENNY JACOB Name: MUHAMMAD KASHIF

Signature
Date:
ii, J
01 ,,/ 20' 0
TOSHIBA CORPORATION
~
::t:a:tur~I/II/;,bID ddf}
SAUDI ELECTRICTY COMPANY. CSD. EOA
ABU HAORIYAH • 380/115kVBSP GIS
CUSTOMER: SAUDI ELECTRICITY COMPANY. SEC. EOA. PROJECT:
EXPANSION PROJECT.
CONTRACT NO. : 30733178/00 NATIONAL CONTRACTING COMPANY
CONTRACTOR:
SUBSTATION: 380/115kV BSP ABU HADRIYAH LTO. AL KHOBAR.
TYPE FORM : 420kV GIS
BAYNo. C4. BUS 1 VOLTAGE TRANSFORMER RATING: I380kV, 3150A. 63kA 1sec. 60Hz

VOLTAGE TRANSFORMER.
Ratio test.
-
Voltage
Earthing
conductor Source
Removed - - - ~

f=:TT
- -E---"

~(§):
ES VT
Cloee

B
C

Primary Voltage Secondan Voltaae (mV )


Phase Rated Ratio Terminal No. Result
{V} Calculated Meassured
380kV
..J3 110V VT1.JB:X2A : 1 - 3 2000 V 1002.77 V 999.40 OK
380k'l/ 110V VT1.JB:X2A : 2 - 3 2000 V 578.95 V 577.70 OK
..J3 ..J3
A
380kV
..J3 110V VT1.JB:X2B: 1 - 3 2000 V 1002.77 V 999.40 OK
380kY 110V VT1.JB:X2B : 2 - 3 2000 V 578.95 V 578.20 OK
..J3 ..J3
380kY 110V VT1.JB:X2A : 4 - 6 2000 V 1002.77 V 1000.10 OK
..J3
380k'l/ ..11ll VT1.JB:X2A : 5 - 6 2000 V 578.95 V 578.20 OK
..J3 ..J3
B
380kV
..J3 110V VT1.JB:X2B : 4 - 6 2000 V 1002.77 V 1000.10 OK
380kY 110V VT.JB:X2B : 5 - 6 2000 V 578.95 V 577.90 OK
..J3 ..J3
380kV
..J3 110V VT1.JB:X2A : 7 - 9 2000 V 1002.77 V 1000.40 OK
380kV 110V VT1.JB:X2A : 8 • 9 2000 V 578.95 V 578.50 OK
..J3 ..J3
C
380k'l/ 110V VT1.JB:X2B : 7 - 9 2000 V 1002.77 V 1000.80 OK
..J3
380kV 110V VT1.JB:X2B : 8 - 9 2000 V 578.95 V 578.10 OK
..J3 ..J3

Criteria: Rated ratio ±O.5%

TEST EQUIPMENT USED: FLUKE 187 MULTI METER & MAGNUS.

TESTED BY WITNESSED BY
Name: BENNY JACOB Name: MUHAMMAD KASHIF

Signature: Signature:

Date: Or! (I / <]0(0 ~ Date: 0//1// '){)/D ~