ABU HADRIYAH - 380/115kV BSP GIS

CUSTOMER:

CONTRACT NO. :
I SAUDI ELECTRICITY
30733178/00
COMPANY. SEC. EOA. PROJECT:
EXPANSION PROJECT.
NATIONAL CONTRACTING COMPANY
CONTRACTOR:
SUBSTATION: 380/115kV BSP ABU HADRIYAH LTO. AL KHOBAR.
TYPE FORM : 420kVGIS
BAYNo. C4.A812 RATING: 380kV 3150A. 63kA 1sec. 60Hz

CURRENT TRANSFORMER INSULATION RESISTANCE MEASUREMENT.

Insulation resistance measurement.


Circuits to ground by means of 1000V megger. Duration : 60 Sec.

INSULATION RESISTANCE (MO) AMBIENT


CT.No. PHASE CT.RATIO RESULT
S-G TEMPRATURE
750/1500/20001
A 56GO 24.3 OK
2500/3000 : 1A
750/1500/20001
A812. F. C1 B 56GO 24.3 OK
2500/3000 : 1A
750/1500/20001
C 66GO 24.3 OK
2500/3000 : 1A
750/1500/20001
A 56GO 24.3 OK
2500/3000 : 1A
750/1500/20001
A812. F. C2 B 86GO 24.3 OK
2500/3000 : 1A
750/1500/20001
C 66GO 24.3 OK
2500/3000: 1A
750/1500/20001
A 67GO 24.3 OK
2500/3000 : 1A
750/1500/20001
A812. F. C3 8 60GO 24.3 OK
2500/3000 : 1A
750/1500/20001
C 77GO 24.3 OK
2500/3000 : 1A
750/1500/20001
A 49GO 24.3 OK
2500/3000 : 1A
750/1500/20001
A812. B2. C1 B 37G 0 24.3 OK
2500/3000: 1A
750/1500/20001
C 47GO 24.3 OK
2500/3000: 1A
750/1500/20001
A 57G 0 24.3 OK
2500/3000: 1A
750/1500/20001
A812. B2. C2 B 36GO 24.3 OK
2500/3000 : 1A
750/1500/20001
C 79G 0 24.3 OK
2500/3000 : 1A
750/1500/20001
A > 102 G 0 24.3 OK
2500/3000 : 1A
750/1500/20001
A812. B2. C3 B > 102 G 0 24.3 OK
2500/3000 : 1A
750/1500/20001
C > 102 G 0 24.3 OK
2500/3000: 1A
750/1500/20001
A > 102 G 0 24.3 OK
2500/3000: 1A
750/1500/20001
A812. 82. C4 8 > 102 G 0 24.3 OK
2500/3000: 1A
750/1500/20001
C > 102 G 0 24.3 OK
2500/3000 : 1A

Criteria: More than 2MO (Toshiba Standard)


Note: S: Secondary G: Ground

TEST EQUIPMENT USED: AVO MEGGER. BM11D.


N~ .,~ -test co.."I'f)cd ot¢- -r'YOI'"f") Le.-p ~ CT.

TESTED BY WITNESSED BY
Name: BENNY JACOB Name: MUHAMMAD KASHIF

Signature:

Date:
, /2010
~/11
TOSHIBA CORPORATION
~
Signature:

Date: )...811f /'Mo


SAUDI ELECTRICTY
dtJ1
COMPANY. CSD. EOA
A CORPO~. __IUN
ABU HADRIYAH • 3801115kV BSP GIS
CUSTOMER:

CONTRACT NO. :
I SAUDI ELECTRICITY
30733178100
COMPANY. SEC. EOA. PROJECT:
EXPANSION PROJECT.
NATIONAL CONTRACTING COMPANY
CONTRACTOR:
SUBSTATION: 380/115kV BSP ABU HADRIYAH LTO. AL KHOBAR.
TYPE FORM : 420kVGIS
BAYNo. C4.A810 RATING: 380kV 3150A. 63kA 1sec. 60Hz

CURRENT TRANSFORMER POLARITY TEST.

Check polarity by inductive kick method for all taps.

INDICATION
CT. No. PHASE CT.RATIO TAP TERMINAL No. RESULT
ON OFF
75011A 1S3A - 1S4A X21A: 3.4
+ - OK

150011A 1S2A - 1S4A X21A: 2,4


+ - OK

A810. 81. C1 A 200011A 1S2A - 1S5A X21A: 2,5


+ - OK

250011A 1S1A - 1S4A X21A: 1 ,4


+ - OK

300011A 1S1A - 1S5A X21A: 1 .5


+ - OK

75011A 1S38 - 1S48 X21A: 8,9


+ - OK

150011A 1S28 - 1S48 X21A: 7,9


+ - OK

A810. 81. C1 8 200011A 1S28-1S58 X21A: 7 ,10


+ - OK

250011A 1S18 - 1S48 X21A: 6.9 +- - OK

300011A 1S18 -1S58 X21A: 6,10


+ - OK

75011A 1S3C - 1S4C X21A:13,14


+ - OK

150011A 1S2C - 1S4C X21A: 12 , 14


+ - OK

A810. 81. C1 C 200011A 1S2C - 1S5C X21A: 12,15


+ - OK

250011A 1S1C - 1S4C X21A: 11,14


+ - OK

300011A 1S1C - 1S5C X21A:11,15


+ - OK

Criteria : Subtractive polarity [Toshiba standard]


At the moment of making the switch, voltmeter should be indicated positive.
At the moment of breaking the switch, voltmeter should be indicated negative.
Note : Polarity test carried out from LCP to CT

Equipment Used : Galvano Meter & 8attery pack

TESTED BY WITNESSED BY
Name: 8ENNYJAC08 Name: MUHAMMAD KASHIF

Signature:r/, 1/ 20ft:> Signature: fA QLA .


Date: 2f, J) ~ Date: VI, 'II/"J;1. ~ .
TOSHIBA CORPORATION !AVIDI E OijCTY COMPANY. CSD. EOA
I BA CDRPDJ ~~II