Sunteți pe pagina 1din 8

6.

Internal lightning protection


6.1 Equipotential bonding for metal According to IEC 60364-4-41, equipotential bond-
ing consists of the
installations main equipotential bonding (in future: protective
equipotential bonding)
Equipotential bonding according to IEC 60364-4- and the
41 and IEC 60364-5-54 supplementary equipotential bonding (in future:
supplementary protective equipotential bonding)
Equipotential bonding is required for all newly Every building must be given a main equipotential
installed electrical power consumer’s installations. bonding in accordance with the standards stated
Equipotential bonding according to IEC 60364 above (Figure 6.1.1).
series removes potential differences, i.e. prevents The supplementary equipotential bonding is
hazardous touch voltages between the protective intended for those cases where the conditions for
conductor of the low voltage electrical power con- disconnection from supply cannot be met, or for
sumer’s installations and metal, water, gas and special areas which conform to the IEC 60364 series
heating pipes, for example. Part 7.
equipotential bonding of bathroom
metal element going
through the building
buried installation, operation-

protected tank installation)


ally isolated (e.g. cathodic

230/400 V
(e.g. lift rails)

remote signalling system

5 1 Equipotential bonding bar


(main equipotential bonding,
antenna

in future: main earthing


terminal)
kWh

8 2 Foundation earth electrode

6 3 Connector
4
1 4 Lightning current arrester
5 Terminal
6
6 Pipe clamp
7 Terminal lug
to PEN 8 Isolating spark gap

heating SEB
distribution

6 6
network
insulating element

Z
IT system

gas waste 7
water water 4

Z terminal lug for external


lightning protection
foundation earth electrode / 3 3
2
lightning protection earth electrode

Fig. 6.1.1 Principle of lightning equipotential bonding consisting of lightning and main equipotential bonding (in future: protective equipoten-
tial bonding)

www.dehn.de LIGHTNING PROTECTION GUIDE 147


Main equipotential bonding ⇒ earth-termination systems of high-voltage cur-
The following extraneous conductive parts have to rent installations above 1 kV in accordance
be directly integrated into the main equipotential with HD 637 S1, if intolerably high earthing
bonding: potentials can be transferred
⇒ main equipotential bonding conductor in ⇒ railway earth for electric a.c. and d.c. railways
accordance with IEC 60364-4-41 (in future: in accordance with EN 50122-1 (railway lines of
earthing conductor) the Deutsche Bahn may only be connected
⇒ foundation earth electrodes or lightning pro- upon written approval)
tection earth electrodes ⇒ measuring earth for laboratories, if they are
⇒ central heating system separate from the protective conductors
⇒ metal water supply pipe
⇒ conductive parts of the building structure (e.g. Figure 6.1.1 shows the terminals and the respective
lift rails, steel skeleton, ventilation and air con- components of the main equipotential bonding.
ditioning ducting)
Design of the earth-termination system for
⇒ metal drain pipe
equipotential bonding
⇒ internal gas pipe The electrical low-voltage consumer’s installation
⇒ earthing conductor for antennas (in Germany requiring certain earthing resistances (disconnec-
in DIN VDE 0855-300) tion conditions of the protective elements) and the
⇒ earthing conductor for telecommunication foundation earth electrode providing good earth-
systems (in Germany in DIN VDE 0800-2) ing resistances at cost-effective installation, the
⇒ protective conductors of the electrical installa- foundation earth electrode is an optimal and
tion in accordance with IEC 60364 series (PEN effective complement of the equipotential bond-
conductor for TN systems and PE conductors ing. The design of a foundation earth electrode is
for TT systems or IT systems) governed in Germany by DIN 18014, which, for
example requires terminal lugs for the earthing
⇒ metal shields of electrical and electronic con- busbar. More exact descriptions and designs of the
ductors foundation earth electrode can be found in Chap-
⇒ metal cable sheaths of high-voltage current ter 5.5.
cables up to 1000 V
⇒ earth termination systems for high-voltage If a foundation earth electrode is used as lightning
current installations above 1 kV according to protection earth electrode, additional require-
HD 637 S1, if no intolerably high earthing volt- ments may have to be considered; they can be tak-
age can be dragged. en from Chapter 5.5.

Normative definition in IEC 60050-826 of an extra- Equipotential bonding conductors (in future: pro-
neous conductive component: tective bonding conductors)
A conductive unit not forming part of the electri- Equipotential bonding conductors should, as long
cal installation, but being able to introduce electric as they fulfil a protective function, be labelled the
potential including the earth potential. same as protective conductors, i.e. green/yellow.
Note: Extraneous conductive components also Equipotential bonding conductors do not carry
include conductive floors and walls, if an electric operating currents and can therefore be either
potential including the earth potential can be bare or insulated.
introduced via them. The decisive factor for the design of the main
The following installation components have to be equipotential bonding conductors in accordance
integrated indirectly into the main equipotential with IEC 60364-5-54 and HD 60364-5-54 is the cross
bonding via isolating spark gaps: section of the main protective conductor. The main
⇒ installations with cathodic corrosion protec- protective conductor is the one coming from the
tion and stray current protection measures in source of current or from the service entrance box
accordance with EN 50162 or the main distribution board.

148 LIGHTNING PROTECTION GUIDE www.dehn.de


Main equipotential bonding Supplementary equipotential bonding
Normal 0.5 x cross section of the between two bodies 1xcross section of the small-
largest protective conduc- er protective conductor
tor of the installation between a body and an 0.5 x cross section of the
extraneous conductive protective conductor
part
Minimum 6 mm2 with mechanical 2.5 mm2 Cu or equivalent
protection conductivity
without mechanical 4 mm2 Cu or equivalent
protection conductivity
Possible limit 25 mm2 Cu or equivalent − −
conductivity
Table 6.1.1 Cross sections for equipotential bonding conductors

In any case, the minimum cross section of the main This standard also includes the requirements for
equipotential bonding conductor is at least 6 mm2 the inspection of clamping units of cross sections
Cu. 25 mm2 Cu has been defined as a possible max- above 16 mm2 with regard to the lightning current
imum. ampacity. Reference is made therein to the testing
The supplementary equipotential bonding (Table of the lightning protection units in accordance
6.1.1) must have a minimum cross section of 2.5 with EN 50164-1.
mm2 Cu for a protected installation, and 4 mm2 Cu If the requirements in the previously mentioned
for an unprotected installation. standard are met, then this component can also be
used for lightning equipotential bonding in accor-
For earth conductors of antennas (according to IEC dance with IEC 62305-1 to 4 (EN 62305-1 to 4).
60728-11 (EN 60728-11)), the minimum cross sec-
tion is 16 mm2 Cu, 25 mm2 Al or 50 mm2 steel. Terminals for equipotential bonding
Terminals for equipotential bonding must provide
a good and permanent contact.
Equipotential bonding bars
Equipotential bonding bars are a central compo-
nent of equipotential bonding which must clamp
all the connecting conductors and cross sections
occurring in practice to have high contact stability;
it must be able to carry current safely and have suf-
ficient corrosion resistance.
DIN VDE 0618-1: 1989-08 (German standard) con-
tains details of the requirements on equipotential
bonding bars for the main equipotential bonding.
It defines the following connection possibilities as
a minimum:
⇒ 1 x flat conductor 4 x 30 mm or round conduc-
tor Ø 10 mm
⇒ 1 x 50 mm2
⇒ 6 x 6 mm2 to 25 mm2
⇒ 1 x 2.5 mm2 to 6 mm2

These requirements on an equipotential bonding


bar are met by K12 (Figure 6.1.2). Fig. 6.1.2 K12 Equipotential bonding bar, Part No. 563 200

www.dehn.de LIGHTNING PROTECTION GUIDE 149


Fig. 6.1.3 Pipe earthing clamp, Fig. 6.1.4 Pipe earthing clamp, Fig. 6.1.5 Pipe earthing clamp,
Part No. 408 014 Part No. 407 114 Part No. 540 910

Integrating pipes into the equipotential bonding Supplementary equipotential bonding


In order to integrate pipes into the equipotential If the disconnection conditions of the respective
bonding, earthing pipe clamps corresponding to system configuration can not be met for an instal-
the diameters of the pipes are used (Figures 6.1.3 lation or a part of it, a supplementary local equipo-
and 6.1.4). tential bonding is required. The reason behind is
Pipe earthing clamps made of stainless steel, which to interconnect all simultaneously accessible parts
can be universally adapted to the diameter of the as well as the stationary operating equipment and
pipe, offer enormous advantages for mounting also extraneous conductive parts. The aim is to
(Figure 6.1.5). keep any touch voltage which may occur as low as
These pipe earthing clamps can be used to clamp possible.
pipes that are made of different materials (e.g.
Moreover, the supplementary equipotential bond-
steel, copper and stainless steel). These compo-
ing must be used for installations or parts of instal-
nents allow also a straight-through connection.
lations of IT systems with insulation monitoring.
Figure 6.1.6 shows equipotential bonding of heat-
ing pipes with straight-through connection. The supplementary equipotential bonding is also
required if the environmental conditions in special
Test and inspection of the equipotential bonding installations or parts of installations mean a partic-
Before commissioning the electrical consumer’s ular risk.
installation, the connections must be inspected to The IEC 60364 series Part 7 draws attention to the
ensure their faultless condition and effectiveness. supplementary equipotential bonding for opera-
A low-impedance conductance to the various parts tional facilities, rooms and installations of a partic-
of the installation and to the equipotential bond- ular type.
ing is recommended. A guide value of < 1 Ω for the These are , for example,
connections at equipotential bonding is consid-
ered to be sufficient. ⇒ IEC 60364-7-701 Rooms with bathtub or show-
er
⇒ IEC 60364-7-702 Swimming pools and other
basins
⇒ IEC 60364-7-705 For agricultural and horticul-
tural premises

The difference to the main equipotential bonding


is the fact that the cross sections of the conductors
can be chosen to be smaller (Table 6.1.1), and also
this supplementary equipotential bonding can be
Fig. 6.1.6 Equipotential bonding with straight-through connection limited to a particular location.

150 LIGHTNING PROTECTION GUIDE www.dehn.de


6.2 Equipotential bonding for low
voltage consumer’s installations
Equipotential bonding for low voltage consumer’s
installations as part of the internal lightning pro-
tection, represents an extension of the main equi-
potential bonding (in future: protective equipo-
tential bonding) according to IEC 60364-4-41 (Fig-
ure 6.1.1).
In addition to all conductive systems, this also inte-
grates the supply conductors of the low voltage
consumer’s installation into the equipotential
bonding. The special feature of this equipotential
bonding is the fact that a tie-up to the equipoten-
tial bonding is only possible via suitable surge pro-
tective devices. The demands on such surge protec-
tive devices are described more detailed in Annex
E subclause 6.2.1.2 of IEC 62305-3 (EN 62305-3) as
well as in subclause 7 and Annexes C and D of IEC
62305-4 (EN 62305-4).
Analogous to the equipotential bonding with met-
al installations (see Chapter 6.1), the equipotential
bonding for the low voltage consumer’s installa-
tion shall also be carried out immediately at the
point of entry into the object. The requirements
Fig. 6.2.1 DEHNbloc NH lightning current arrester installed in a bus- governing the installation of the surge protective
bar terminal field of a meter installation (refer to Fig. 6.2.2) devices in the unmetered area of the low voltage
consumer’s installation (main distribution system)
are described in the directive of the VDN (Associa-
tion of German Network Operators) “Surge pro-
tective devices Type 1. Directive for the use of
surge protective equipment Type 1 (up to now
Class B) in main distribution systems” (see sub-
clauses 7.5.2 and 8.1) (Figures 6.2.1 and 6.2.2).

6.3 Equipotential bonding for infor-


mation technology installations
Lightning equipotential bonding requires that all
metal conductive components such as cable lines
and shields at the entrance to the building shall be
incorporated into the equipotential bonding so as
to cause as little impedance as possible. Examples
of such components include antenna lines, (Figure
6.3.1) telecommunication lines with metal conduc-
tors, and also fibre optic systems with metal ele-
ments. The lines are connected with the help of
elements capable of carrying lightning current
Fig. 6.2.2 DEHNventil ZP combined arrester directly snapped on the (arresters and shielding terminals). A convenient
busbars in the terminal field of the meter cabinet installation site is the point where cabling going

www.dehn.de LIGHTNING PROTECTION GUIDE 151


α α

feeding point
α α
air termination tip

sealing unit
range
isolated air-termination system
(DEHNconductor)
connection
equipotential bonding insulating pipe

isolated down conductor


230 V~ (HVI-conductor)
DATA
s^= 0.75 m in air
230 V~ antenna
s^= 1.5 m in brickwork
s = separation distance

equipotential bonding earth-termination


to BTS system

Fig. 6.3.1 Lightning equipotential bonding with isolated air-termina- Fig. 6.3.2 Isolated construction of a lightning protection system at a
tion system, type DEHNconductor, for professional anten- cell site
na systems according to IEC 62305-3 (EN 62305-3)

outside the building transfers to cabling inside the ed into the equipotential bonding in accordance
building. Both the arresters and the shielding ter- with DIN VDE 0855 Part 300 (German standard)
minals must be chosen to be appropriate to the and must reduce the risk of being affected
lightning current parameters to be expected. through their design, (cable structure, connectors
In order to minimise induction loops within build- and fittings) or suitable additional measures.
ings, the following additional steps are recom- Antenna elements that are connected to an anten-
mended: na feeder and cannot be connected directly to the
⇒ cables and metal pipes shall enter the building equipotential bonding, as this would affect their
at the same point functioning, should be protected by arresters.
⇒ power lines and data lines shall be laid spatial- Expressed simply, it can be assumed that 50 % of
ly close but shielded the direct lightning current flows away via the
⇒ avoiding of unnecessarily long cables by laying shields of all antenna lines. If an antenna installa-
lines directly tion is dimensioned for lightning currents up to
100 kA (10/350 μs) (Lightning Protection Level III
Antenna installations: (LPL III)), the lightning current splits so that 50 kA
For reasons connected with radio engineering, flow through the earth conductor and 50 kA via
antenna installations are generally mounted in an the shields of all antenna cables. Antenna installa-
exposed location. Therefore they are more affect- tions not capable of carrying lightning currents
ed by surges, especially in the event of a direct must therefore be equipped with air-termination
lightning strike. In Germany they must be integrat- systems in whose protection area the antennas are

152 LIGHTNING PROTECTION GUIDE www.dehn.de


located. Choosing a suitable cable, the respective ⇒ Metal core: termination by means of earthing
partial lightning current share must be determined clamp e.g. SLK, near splice box
for each antenna line involved in down conduct- ⇒ Prevention of potential equalising currents:
ing. The required cable dielectric strength can be connect indirectly via spark gap e.g. DEHNgap
determined from the coupling resistance, the CS, base part BLITZDUCTOR CT, rather than
length of the antenna line and the amplitude of directly
the lightning current.
Telecommunication lines:
According to the current standard IEC 62305-3 (EN Telecommunication lines with metal conductors
62305-3), antenna installations mounted on build- normally consist of cables with balanced or coaxial
ings can be protected by means of cabling elements of the following types:
⇒ air-termination rods ⇒ cables with no additional metal elements
⇒ elevated wires ⇒ cables with metal sheath (e.g. metal damp-
⇒ or spanned cables proofing) and / or metal supporting elements
⇒ cables with metal sheath and additional light-
In each case the separation distance s must be ning protection reinforcement
maintained in the areas protected against light-
ning strikes. The splitting of the partial lightning current
The electrical isolation of the lightning protection between IT lines can be determined using the pro-
system from conductive components of the build- cedures in Annex E of IEC 62305-1 (EN 62305-1).
ing structure (metal structural parts, reinforce- The individual cables must be integrated into the
ment etc.), and the isolation from electric lines in equipotential bonding as follows:
the building, prevent partial lightning currents
a) Unshielded cables must be connected by SPDs
from penetrating into control and supply lines and
which are capable of carrying partial lightning
hence protect sensitive electrical and electronic
currents. Partial lightning current of the line
devices from being affected or destroyed (Figure
divided by the number of individual wires =
6.3.1 and Figure 6.3.2).
partial lightning current per wire.
Fibre optic installations: b) If the cable shield is capable of carrying light-
Fibre optic installations with metal elements can ning currents, the lightning current flows via
normally be divided into the following types: the shield. However, capacitive/inductive inter-
ferences can reach the wires and make it nec-
⇒ cables with metal-free core but with metal essary to use surge arresters. Requirements:
sheath (e.g. metal vapour barrier) or metal
supporting elements ⇒ The shield at both ends must be connected to
the main equipotential bonding to be capable
⇒ cables with metal elements in the core and of carrying lightning currents (Figure 6.3.3).
with metal sheath or metal supporting ele-
ments
⇒ cables with metal elements in the core, but
without metal sheath.
For all types of cable with metal elements, the min-
imum peak value of the lightning current, which
adversely affects the transmission characteristics of
the optical fibre, must be determined. Cables capa-
ble of carrying lightning currents must be chosen,
and the metal elements must be connected to the
equipotential bonding bar either directly or via an
SPD.
⇒ Metal sheath: termination by means of shield
terminals e.g. SAK, at the entrance of the Fig. 6.3.3 SAK shield connection system capable of carrying light-
building ning currents

www.dehn.de LIGHTNING PROTECTION GUIDE 153


Telekom customer c) If the cable shield is not capable of carrying
lightning currents, then:
⇒ for the terminal connected at both ends, the
TAE procedure is the same as for a signal wire in an
IT installation
unshielded cable. Partial lightning current of
the cable divided by the number of individual
wires + 1 shield = partial lightning current per
3 OUT 4 wire
⇒ if the shield is not connected at both ends, it
has to be treated as if it were not there; partial
BLITZDUCTOR
BCT MLC BD 110

lightning current of the line divided by the


No.919 347

number of individual wires = partial lightning


BLITZDUCTOR CT current per wire
1 IN 2
BCT MLC BD 110
5 kA (10/350 μs)
If it is not possible to determine the exact wire
load, it is recommendable to take the threat
parameters from IEC 61643-22. For a telecommuni-
cations line hence results a maximum load per wire
APL
of 2.5 kA (10/350 μs).
Fig. 6.3.4 Lightning equipotential bonding for connection of a
telecommunications device BLITZDUCTOR CT (application Of course not only the used SPD must be capable
permitted by Deutsche Telekom) of withstanding the expected lightning current
load, but also the discharge path to the equipoten-
tial bonding.
By means of a multi-core telecommunications line
for example this can be demonstrated:
⇒ A telecommunications cable with 100 double
wires coming from LPZ 0A is connected in an
LSA building distribution case and shall be pro-
tected by arresters.
⇒ The lightning current load of the cable was
assumed to be 30 kA (10/350 μs)
⇒ The resulting symmetrical splitting of light-
Fig. 6.3.5 DEHN equipotential bonding enclosures (DPG LSA) for ning current to the individual wire is 30 kA /
LSA-2/10 technology, capable to carry lightning current 200 wires = 150 A / wire.

At first this means no special requirements to the


⇒ In both buildings where the cable ends, the discharge capacity of the protective elements to be
lightning protection zone concept must be used. After the discharge elements have flown
applied, and the active wires must be connect- through, the partial currents of all wires add up to
ed in the same lightning protection zone (usu- 30 kA again to load in the downstream discharge
ally LPZ 1) path, for example clamping frames, earthing
⇒ If an unshielded cable is laid in a metal pipe, clamps or equipotential conductors. To be safe
this must be treated like a cable with a cable from any damage in the discharge path lightning
shield which is capable of carrying lightning current tested enclosure systems can be used (Fig-
currents. ure 6.3.5).

154 LIGHTNING PROTECTION GUIDE www.dehn.de

S-ar putea să vă placă și