Sunteți pe pagina 1din 4

FOR

AUTOMATIC VOLTAGE REGULATOR


AVC63-12 AND AVC125-10

INTRODUCTION Frequency Compensation Storage: –40 to 70°C (–40 to 158°F)


The AVC63-12 and AVC125-10 regulate the One or two jumper-selectable V/Hz curves Max. Humidity: 95%, non-condensing
level of excitation supplied to the field of a with knee frequency adjustable from 45 to Weight: approx. 1.1 kg (2.5 lb)
conventional, brushless, synchronous gen- 65 Hz (50/60 Hz units) or 300 to 430 Hz
INSTALLATION
erator. (400 Hz units). Refer to Figure 1 (60 Hz) and
Figure 2 (400 Hz) for sensing models. Regulators are contained in an encapsu-
Regulation is achieved by sensing the gen- lated plastic case and may be mounted in
erator output voltage, converting it to a dc EMI Suppression any convenient position. A regulator may be
signal, and comparing the signal to a refer- Internal filter. (See CE Conformity) mounted directly on a genset using UNF ¼-
ence voltage. An error signal is developed 20 or equivalent hardware. Hardware selec-
and used to control the dc field power in Voltage Buildup
Automatic voltage buildup occurs from re- tion should be based on any expected ship-
order to maintain a constant generator out- ping/transportation and operating conditions.
put. sidual generator voltage as low as 6 Vac
(AVC63-12) or 12 Vac (AVC125-10). The torque applied to the mounting hard-
Each regulator includes frequency compen- ware should not exceed 65 in-lb (7.34 N•m).
sation with selectable slope, inverse-time Overexcitation Shutdown See Figure 5 for regulator dimensions.
overexcitation shutdown, buildup circuitry, Overexcitation shutdown protection reduces
single- or three-phase voltage sensing, sin- the output voltage to zero in the times CONNECTIONS
gle- or three-phase shunt or permanent shown below for the listed voltages. Other Before connecting the voltage regulator into
magnet generator (PMG) power input, paral- voltages and times are based on the inverse your system, review the terminal descrip-
lel droop compensation, and an accessory time characteristic curves of Figures 3 and 4 tions listed in Table 1 and the connection
input. The accessory input provides com- AVC63-12 diagrams in Figures 6 through 8.
patibility with devices such as var/power 125 Vdc, ±10% in approximately 10 s Table 1. Terminal Descriptions
factor controllers or excitation limiters. 210 Vdc, ±10% in approximately 1 s or less Term # Description
SPECIFICATIONS AVC125-10 CH GND Chassis ground connection
Power Input ∗ 250 Vdc, ±10% in approximately 10 s 2 Auxiliary input from SCP250
Configuration: 1-phase or 3-phase 370 Vdc, ±10% in approximately 1 s or less and/or EL 200 (See Fig. 7)
3
Frequency: 50 to 400 Hz Droop/Line Drop Compensation
4 Internal voltage adjust: con-
Voltage Range <10 VA adjustable from 0 to 10% of rated nect to 7. External voltage
AVC63-12: 90 TO 153 Vac input current at 0.8 power factor. (LDC com- adjust: no connection

Upper Terminal Strip


AVC125-10: 180 to 264 Vac pensates only for voltage drop due to line
reactance and reactive components of the 5 1 A current transformer (CT)
Maximum Continuous Burden
load current.) 5a 5 A CT
AVC63-12: 1,092 VA
AVC125-10: 1,750 VA Agency Approvals 6 CT common connection
∗ See Options for Inrush Current Reduction UL Recognition 6a Common connection for
Module information. Standard 508, File E97035 selectable features
Sensing Input CSA Certification 7 Internal voltage adjust: con-
Configuration: 1-phase or 3-phase Standard CAN/CSA-C22.2 No. 14-95, nect to 4. External voltage
Burden: <1 VA per phase File LR 23131 adjust: connect to 6a
Voltage Range CE Conformity 8 Connect to 6a to select 1
Option A: 90 to 139 Vac Radiated Emissions V/Hz underfrequency slope
Option B: 180 to 264 Vac EN50081-2 9 Connect to 6a to select
Nominal Frequency Conducted Emissions 3-phase sensing
EN50081-2 (EN55011, Class A) 20 C-phase sensing input
Option 1: 50 or 60 Hz
Conducted Emissions
Option 2: 400 Hz 22 A-phase sensing input
Lower Term. Strip

EN50081-2 (EN55011, Class A)


(See Table 4 for style/option information.) ESD Immunity 24 B-phase sensing input
Accessory Input EN50082-2 (4 kV contact, 8 kV air) 26 1- or 3-phase power input
Voltage Range: ±3 Vdc EFT Immunity
28 3-phase power input
EN50082-2 (2 kV coupling clamp)
Power Output Magnetic Immunity 30 1- or 3-phase power input
Maximum Continuous Output EN50082-2 (30 Arms, 50 Hz) F1 Field + connection
AVC63-12: 12 Adc at 63 Vdc Safety
F2 Field – connection
AVC125-10: 10 Adc at 125 Vdc EN61010-1
10 Second Forcing Output Radiated Immunity ADJUSTMENTS
AVC63-12: 24 Adc at 125 Vdc Electric Field: EN61000-4-3 (10 V/m)
AVC63-12 and AVC125-10 adjustments are
AVC125-10: 20 Adc at 250 Vdc Conducted: EN61000-4-6 (10 Vrms)
described in the following paragraphs.
Minimum Field Resistance Type Tests
Field Flashing
AVC63-12: 5.25 Ω Shock
AVC125-10: 12.5 Ω When the regulator is operated with the
Withstands 20 G in each of 3 mutually per- generator for the first time, the residual
Regulation Accuracy pendicular planes. magnetism may not be of sufficient magni-
±0.5% of voltage setpoint, average response Vibration tude or the correct polarity. If the generator
Voltage Drift Withstands 4.5 G at18 to 2,000 Hz residual voltage is less than 6 Vac for the
±0.5% variation for a 40°C (104°F) change Physical AVC63-12 or 12 Vac for the AVC125-10 at
terminals 26, 28 and/or 30, shut down the
Response Time Temperature
prime mover and proceed with the following
<4 ms Operating: –40 to 70°C (–40 to 158°F) steps.

Publication Revision First Printing: 06/01 Copyright


9337200991 D Revised: 03/06 2006
CAUTION To allow operation of an external voltage 5. Check regulation under normal operat-
Do not flash the field when the genera- adjust control, remove the jumper between ing conditions.
tor is in motion. Regulator damage may terminals 4 and 7 and connect a 10 kΩ, If the regulation is poor:
result. external potentiometer across terminals 6a a. Check that the prime mover is up
and 7. The front-panel VLT ADJ control to rated speed.
1. With the prime mover at rest, apply an should be set fully clockwise for proper op-
ungrounded dc source of not more than eration of the external adjustment. Note that b. Check that the voltmeter is con-
24 Vdc to terminals F1 (+) and F2 (–) in as the external potentiometer resistance nected at the same point as the
series with a limiting resistor. Use 1 Ω increases, generator voltage also increases. regulator sensing.
of resistance for each volt applied. The c. Use an average-sensing voltmeter
power source should have a rating of at Factory Calibration (FAC CAL)
(not an rms-sensing voltmeter).
least 1 W/Ω. CAUTION 6. Reduce the generator frequency. The
EXAMPLE: If using a 24 Vdc source, The FAC CAL control is intended for use generator output should decrease from
use a 24 Ω, 24 W resistor. during factory calibration only. The fol- this point.
2. Allow the field to be flashed for ap- lowing procedure can be used if the fac- If the generator output voltage does not
proximately 10 seconds before remov- tory calibration has been disturbed. decrease at the desired frequency:
ing the dc source. 1. With the regulator operating on a gen- a. Check that all wiring is in accor-
3. If voltage buildup does not occur after erator, adjust the FAC CAL control fully dance with the connection dia-
performing steps 1 and 2, verify the po- counterclockwise and the external volt- grams provided in this instruction
larity of the dc source and repeat steps age adjust control fully clockwise. sheet.
1 and 2. 2. Adjust the FAC CAL control clockwise b. Adjust the UF KNEE control.
Frequency Roll-Off (UF KNEE) until the generator voltage reaches the
OPTIONS
The underfrequency knee (roll-off) is typi- desired maximum voltage setting. The
regulator is calibrated and the FAC The AVC63-12 and AVC125-10 may be
cally set below the nominal system fre- equipped with the following options to en-
quency. When the generator speed falls CAL control can be sealed.
hance operation.
below the knee setpoint of the regulator, Parallel Droop Compensation
generator voltage is reduced proportionally Variable parallel droop compensation levels Remote Voltage Adjust
to the speed of the machine. To adjust the can be obtained by adjusting the DRP con- Connect a 10 kΩ, 2 W potentiometer across
underfrequency knee, perform the following trol. Clockwise rotation increases the terminals 6a and 7, remove the jumper from
steps. amount of droop for a given condition. terminals 4 and 7, and adjust the front panel
1. Adjust the generator frequency at the VLT ADJ control fully clockwise to enable
Line Drop Compensation remote adjustment of the voltage setpoint.
nominal level (50, 60, or 400 Hz).
When the sensing input CT connections are
2. Adjust the UF KNEE control counter- reversed to provide line drop compensation, Inrush Current Reduction Module
clockwise. the droop adjustment become the line drop A Basler ICRM-15 is required when energiz-
3. Adjust the VLT ADJ control for nominal compensation adjustment. ing the AVC63-12 or AVC125-10 from a
generator voltage. source that is already at the regulator input
4. Adjust the UF KNEE control clockwise STARTUP power rating. The ICRM-15 minimizes the
until the voltage begins to decrease. Startup and troubleshooting procedures for amount of inrush current that could be seen
the AVC63-12 and AVC125-10 are listed in when power is applied.
5. Adjust the UF KNEE counterclockwise
until the voltage just returns to the the following procedure. Symptoms of Excitation Disable
value set in step 3. startup problems stemming from improper This option disables excitation by removing
regulator adjustments and certain generator power from the regulator. A switch removing
The underfrequency knee is now set just system problems that resemble faulty regu-
below the nominal operating frequency. voltage from terminals 26, 28 and/or 30 will
lation are listed with possible solutions. Sim- remove regulator power.
Further rotation in the counterclockwise plifying the system by eliminating compo-
direction will lower the knee frequency set- nents, such as remote adjustment potenti- Excitation Limiter
point at which underfrequency compensa- ometers and other nonessential items, can The Basler EL 200 provides an initial, fast-
tion just begins. be helpful in the troubleshooting process. acting limit of the field current at a user-
Connecting a jumper from terminal 8 to 6a Adjustments, options, and an operational defined level. Once the field current has
will provide an underfrequency slope of test are included in the paragraphs following changed to the selected level, the EL 200
1 PU V/Hz. No connection to terminal 8 will the procedure. provides a signal to the regulator to change
result in an underfrequency slope of 2 PU 1. Ensure that the regulator has been the excitation level.
V/Hz. The slope can also be selected on the installed in accordance with the Instal-
400 Hz models. However, the actual V/Hz Var/Power Factor Control
lation and Connections paragraphs be- This option enables the AVC63-12 and
curve is approximately 1 PU or 2 PU, de- fore proceeding with system startup.
pending if terminal 8 is jumpered to 6a. AVC125-10 to regulate the var and power
2. Start the prime mover and bring it up to factor while the generator is connected to an
Stability (STB) rated speed. infinite or utility bus. The Basler SCP 250
An oscilloscope or other voltage recording If the voltage does not build up: supplies a dc signal into terminals 2 and 3 of
device should be used in an optimal stability a. Flash the field. the regulator to correct for vars or power
setting is desired. Adjust the stability setting factor. Figure 7 illustrates regulator and SCP
with the generator at no load. b. Remove power for one minute to
reset the overexcitation circuit. 250 interconnection.
Clockwise rotation of the STB control will Current Boost System
slow response time. Counterclockwise rota- 3. Slowly adjust the VOLT potentiometer
tion will speed response time. If rotated too or external, voltage adjust rheostat until With the CBS 212 option, if the generator
far counterclockwise, the generator voltage the voltage reaches nominal. output voltage decreases below the preset
may oscillate (hunt). If the voltage will not build up to rated: operating point due to a short or large motor
starting, the CBS 212 provides full current
To obtain good response, rotate the STB Check the generator output for a
boost to the generator exciter until the volt-
control counterclockwise until the system shorted or excessive load.
age returns to a level just above the operat-
just begins to oscillate. Then, rotate the 4. Apply and remove the generator load ing point.
control clockwise just past the point where to check stability.
oscillation occurred. Apply various amounts Manual Voltage Control
If the generator response is too slow or
of load to determine proper stability per- is hunting (oscillating): The Basler MVC-112 provides a method for
formance. manually controlling the generator output
a. Check the generator output for a
Voltage (VLT ADJ) during generator startup and commissioning
shorted or excessive load. Adjust
or in the unlikely event of a regulator failure.
Installation of a jumper across terminals 4 the STB potentiometer with no
Model MVC-112 is suitable for use with
and 7 allows the front-panel VLT ADJ con- load applied.
either the AVC63-12 or AVC125-10 voltage
trol to vary the generator nominal voltage b. Check stability of the governor. regulator.
over the operating range.
OPERATIONAL TEST To test regulator operation, perform the MAINTENANCE
This test verifies the operation of all eight following steps. A periodic inspection of the regulator should
models of the AVC63-12 and AVC125-10. 1. Connect the regulator according to be made to ensure that it is clean and free
Table 3 lists each regulator model and the Figure 9 and apply the appropriate volt- from accumulations of dust and moisture.
corresponding test voltage and frequency. ages. Ensure that all connections are clean and
Table 3. Testing Parameters 2. Adjust the VLT ADJ control fully coun- tight.
Input terclockwise. TROUBLESHOOTING
Observe that the lamp is off. In case of regulator failure or defective op-
Sensing
Model Power 3. Adjust the VLT ADJ control clockwise. eration, simplifying the system by eliminating
Vac Hz
Observe that the lamp turns on. components such as remote adjust potenti-
AVC63-12A1 120 120 50/60 ometers and other non-essential items can
4. Adjust the VLT ADJ control until the
AVC63-12A2 120 120 400 lamp just turns off. be helpful in the troubleshooting process.
AVC63-12B1 120 240 50/60 Regulator operation is satisfactory if the
AVC63-12B2 120 240 400 above results are obtained. However, stabil-
AVC125-10A1 240 120 50/60 ity must be tested with the generator and
regulator in operation.
AVC125-10A2 240 120 400
AVC125-10B1 240 240 50/60
AVC125-10B2 240 240 400

Time In Seconds
250
Terminal Voltage

200
150 Ideal 1 PU/Hz

100
Ideal 2 PU/Hz
50
0
20 25 30 35 40 45 50 55 60 65 Figure 4. AVC12510 Overexcitation Shutdown Characteristics
Frequency In Hertz

Figure 1. 60 Hz Frequency Compensation

250
Terminal Voltage in Volts

200
Ideal 1 PU/Hz
150

100
Ideal 2 PU/Hz

50

0
150 200 250 300 350 400 450
Frequency in Hertz

Figure 2. 400 Hz Frequency Compensation

100

Shutdown Region
10

1
70 90 110 130 150 170 190 210 230
DC Output Voltage

Figure 3. AVC63-12 Overexcitation Shutdown Characteristics Figure 5. Outline Drawing


Part of 3 L
AVC63-12 Part of
2 C
or P0009-25 EL200
AVC125-10 08-15-05

AVC units may be connected to either the


EL 200 or the SCP 250 using the
A
terminals as shown in place of this series
interconnection. See the unit instruction C Part of
manuals for more information. SCP250
When the AVC receives a positive voltage
(terminal 2 positive, terminal 3 negative)
at the Accessory input, the setpoint
decreases. A negative voltage (terminal 2
negative, terminal 3 positive) at the
Accessory input increases the setpoint.

Figure 7. AVC Interconnection Diagram


CT
GEN 1
52 1

0.1
6
AVC 52b 1
5 or 5A
CCC
0.1 ENABLE
6
CONTACT
AVC 52b 2
5 or 5A
LOAD

GEN 2
CT 52 2
0.1
6
AVC 52b 3

P0009-26.vsd
5 or 5A

08-10-01
52 3
GEN 3
CT

Figure 8. Cross-Current Compensation

100 W
Lamp
Input Sensing
Power Voltage
10 20
ohms ohms

F1 F2 26 28 30 20 22 24

AVC63-12 or AVC125-10
D2590-33
03-24-06

CH
GND
2 3 4 5 5a 6 6a 7 8 9
Figure 6. Typical Interconnection Diagram

1 A wire-wound resistor with a minimum


power rating of 15 W should be used.

Figure 9. Operational Test Setup

S-ar putea să vă placă și