Electrical equipment for gases, vapours, mists (G) Electrical equipment for combustible dusts (D) Zone classification example – petrol station US 'TYPE' into 'IP' Code destinations Documents issued by the manufacturer (ATEX)
SYMBOL TYPE OF PROTECTION CATEGORY CENELEC BASIC CONCEPT OF PROTECTION TYPE OF PROTECTION SYMBOL CENELEC BASIC CONCEPT OF PROTECTION TYPE NUMBER IP DESIGNATION DESCRIPTION DOCUMENTATION
e Increased safety M2 & 2 EN 50019 No arcs, sparks or hot surfaces Protection by enclosure tD EN 50281-1-1 Keep the combustible dust out and avoid hot surfaces DIRECT ENVIRONMENT 3 IP54 Attestation of Conformity (1) Declaration by the manufacturer that the components confirm with the provisions of Directive
nA Non-sparking 3 EN 50021 (IEC 61241-1*) 94/9/EC and includes detail on how to be incorporated into equipment or protective systems
Pressurisation pD IEC61241-4 3R IP14
d Flameproof M2 & 2 EN 50018 Contain the explosion, prevent flame Encapsulation mD IEC 61241-18* EC Declaration of Conformity (1) Declaration by the manufacturer that the equipment complies with the EHSR’s of Directive 94/9/EC
nC Enclosed break 3 EN 50021 propagation 3S IP54 and any other relevant directives that apply
q Quartz/sand filled 2 EN 50017 Intrinsic safety iD IEC 61241-11 Limit the energy of the spark and the surface BREATHER
temperature 4 and 4X IP56 Instructions (2) • Detailed information for safe use, installation, commissioning, maintenance, etc…
ZONE 0
ia Intrinsic safety M1 & 1 EN 50020/39 Limit the energy of the spark and the surface • Drawn up in one of the community languages
ib Intrinsic safety M2 & 2 EN 50020/39 temperature Non-electrical equipment and machinery GASOLINE PUMP ZONE 1 6 and 6P IP67 • On putting into service, translation of the instructions in the language of the country in which
nL Energy limitation 3 EN 50021
the equipment or protective system is to be used
ZONE 2
p Pressurised 2 EN 50016 Keep the flammable gas out TYPE OF PROTECTION SYMBOL CENELEC BASIC CONCEPT OF PROTECTION DOME SHAFT
nR Restricted breathing 3 EN 50021 (1) Declaration to accompany information given with each single product or each batch of identical products
nP Simple pressurisation 3 EN 50021 Constructionally safety c EN 13463-5* Ignition sources cannot arise
m Encapsulation 2 EN 50028 Inherent safety g EN 13463-4* Definition of protection classes (2) Instructions to accompany each piece of equipment or protective system
PIPING
o Oil immersion 2 EN 50015 according to NEMA
Flow restriction fr EN 13463-2* Keep the explosive atmosphere out
p TANK
Pressurisation EN 13463-7*
Liquid immersion k EN 13463-8* TYPE NEMA
Flameproof d EN 13463-3* Contain the explosion, prevent flame propagation Type 1 Enclosure predominately for indoor use. ATEX 95 ATEX 137
Protection against penetration by solid Directive 94/9/EC Directive 1999/92/EC
Control of ignition sources b EN 13463-6* Ignition source cannot become active foreign bodies.
Sira 04ATEX0000 Tamb = -40 °C to +60 °C KEMA NL 0344 2 x against penetration by water during 4. Hazardous Area classification
immersion; protection damage due to ice-
SIRA UK 0518 formation on the outside of the enclosure. 5. Mark explosive atmospheres with sign at point of entry (where necessary)
3 Protected against solid 3
Type designation
3 G Gas, vapour, mist ZONE 2 A place in which an explosive atmosphere is not likely to occur G Weidmüller Interface, 32760 Detmold, Germany
Normal Suitable for normal operation in normal operation but, if it does occur, will persist for a short
D Dust ZONE 22 period only. D 7 IP Rating
Name and address of
15cm manufacturer
min.
1m
Equipment groups Gases, vapours and mists for group II are grouped by...
Equipment group I applies to equipment intended ...spontaneous ignition temperature ...and by spark ignition energy
for use in underground parts of mines, and to those
parts of surface installations of such mines, liable
to be endangered by firedamp and/or combustible TEMPERATURE CLASS MAX. SURFACE TEMPERATURE II A (180 mJ) II B (60 mJ) II C (20 mJ) 8
dust. m
T1 450 °C Acetone Town gas Hydrogen
Equipment group II applies to equipment intended
for use in other places liable to be endangered by T2 300 °C Butane Ethyls Acetylene
explosive atmospheres. Further subdivisions into
IIA, IIB and IIC. T3 200 °C Fuel oil Hydrogen- –
sulphide
T4 135 °C Acetaldehyd Ethylether –
T5 100 °C – – –
T6 85 °C – – Carbon-
disulfide