External Alarm Configuration Procedure

1 Introduction to Hardware Ports and Alarm Cables

1.1 Monitoring Ports on the BBU

The UPEU on the BBU has two Boolean input ports, as shown in the
following figure:

Boolean input ports on the UPEU in the upper part of the BBU:
− EXT-ALM0: port for Boolean inputs 0 to 3
− EXT-ALM1: port for Boolean inputs 4 to 7
The BBU supports a maximum of 16 Boolean inputs. Each UPEU
supports eight Boolean inputs. The BBU is configured with one UPEU in
the lower part by default.

2011-03-17 Huawei Confidential Page 1 of 5


External Alarm Configuration Procedure

1.2 Color Definitions for the Boolean Alarm Cables on the BBU

Recommends Cable Leading Sequence


RJ45 Pin/Color Twisted Pair
for the BBU

1 Orange white Boolean input 1+ 1 and 2 twisted

2 Orange Boolean input 1– (GND) 1 and 2 twisted

3 Green white Boolean input 2+ 3 and 6 twisted

4 Blue Boolean input 3- (GND) 4 and 5 twisted

5 Blue white Boolean input 3+ 4 and 5 twisted

6 Green Boolean input 2- (GND) 3 and 6 twisted

7 Brown white Boolean input 4+ 7 and 8 twisted

8 Brown Boolean input 4- (GND) 7 and 8 twisted

2011-03-17 Huawei Confidential Page 2 of 5


External Alarm Configuration Procedure

1.3 Hardware Connection of External Alarms

For the detailed information about port numbers and slots, see the
following table:
Name and BOM of Core
Monitoring Monitoring Frame Position - Slot Port
BTS Type the Monitoring Number of Cable color
Device Device Port Position Number
Cable the Cable

4 X1.1/X1.2 Orange white/orange

5 BBU Boolean X1.3/X1.6 Green white/green


UPEU (The EXT-ALM1
6 alarm cable X1.5/X1.4 Blue white/blue
Boolean alarms The UPEU is in slot 19 of
7 X1.7/X1.8 Brown white/white
BTS3900 of a UPEU are frame 0. The GTMU is in
0 X1.1/X1.2 Orange white/orange
reported on the slot 6 of frame 0.
1 BBU Boolean X1.3/X1.6 Green white/green
GTMU) EXT-ALM0
2 alarm cable X1.5/X1.4 Blue white/blue

3 X1.7/X1.8 Brown white/white

2011-03-17 Huawei Confidential Page 3 of 5


External Alarm Configuration Procedure

2 Setting the Boolean Alarm of the BBU

2.1 Setting the Boolean Alarm of the BBU on the BSC6900

Step 1: As shown in figure 1, set the alarm name, alarm level, and the
gateway categories on the MML. The command used on the MML is SET
ENVALMPARA. The alarm ID here is the alarm ID of the port to be set.

Figure 1

Step 2: In the MML input serial port, type the SET BTSENVALMPORT
command to set the high and low voltage levels of the dry contacts on the
UPEU.

Figure 2
Note: For the current BTS in the BSC6900, the numbers of the ports on the PEU in
both upper and lower parts of the PEU are in range of 0 to 7.

Step 3: Use the MML command (LST BTSENVALMPORT) to check


whether the numbers of the ports where dry contacts are set and the
alarm levels are correctly set.

2011-03-17 Huawei Confidential Page 4 of 5


External Alarm Configuration Procedure

2.2 Alarm ID of the Boolean Alarm

The alarm ID of Boolean alarm which can be defined by the user starts from
65033 to 65533.

2011-03-17 Huawei Confidential Page 5 of 5