Sunteți pe pagina 1din 14

federal register

Thursday
November 12, 1998

Part II

Department of
Energy
Office of Energy Efficiency and
Renewable Energy

10 CFR Part 432


Energy Conservation Program: Test
Procedures for Distribution Transformers;
Proposed Rule
63360 Federal Register / Vol. 63, No. 218 / Thursday, November 12, 1998 / Proposed Rules

DEPARTMENT OF ENERGY (WordPerfectTM 6.1) of each statement SUPPLEMENTARY INFORMATION:


also be provided at that time. I. Introduction
Office of Energy Efficiency and ADDRESSES: Requests to make A. Authority
Renewable Energy statements at the public hearing and B. Background
copies of such statements should be C. Summary of the Proposed Test
10 CFR Part 432 addressed to Ms. Brenda Edwards-Jones, Procedures
II. Discussion
[Docket No. EE–TP–98–550] and written comments should be A. Standards to be Incorporated by
addressed to Ms. Kathi Epping, each at Reference
RIN 1904–AA85
the following address: U.S. Department B. Distribution transformers not subject to
Energy Conservation Program: Test of Energy, Office of Energy Efficiency the test procedures
Procedures for Distribution and Renewable Energy, EE–43, 1000 C. Reference Conditions
Independence Avenue, SW, D. Measures of Energy Consumption
Transformers E. Basic Model
Washington, DC 20585–0121. All such
AGENCY: Office of Energy Efficiency and documents should be identified both on F. Number of Units to be Tested
Renewable Energy, Department of G. New Part 432
the envelope and on the documents as
III. Procedural Requirements
Energy. ‘‘Energy Conservation Program for A. Review Under the National
ACTION: Notice of Proposed Rulemaking Commercial Products: Test Procedures Environmental Policy Act of 1969
and public hearing. for Distribution Transformers, Docket B. Review Under Executive Order 12866,
No. EE–TP–98–550.’’ The hearing will ‘‘Regulatory Planning and Review’’
SUMMARY: Pursuant to Section 346(a) of begin at 9:00 a.m., on January 6, 1999, C. Review Under the Regulatory Flexibility
the Energy Policy and Conservation Act and will be held in Room 1E–245 at the Act
as amended (EPCA), 42 U.S.C. 6317(a), U.S. Department of Energy, Forrestal D. Review Under Executive Order 12612,
the Department of Energy (DOE or the Building, 1000 Independence Avenue, ‘‘Federalism’’
Department) proposes to adopt test E. Review Under Executive Order 12630,
SW, Washington, DC. For more
procedures for measuring the energy ‘‘Governmental Actions and Interference
information concerning public with Constitutionally Protected Property
efficiency of distribution transformers. participation in this rulemaking Rights’’
The Department proposes to use these proceeding, see section IV, ‘‘Public F. Review Under the Paperwork Reduction
test procedures in the process of Comment,’’ of this notice. Act
evaluating whether and what efficiency Copies of the transcript of the public G. Review Under Executive Order 12988,
standards are appropriate for workshop and public comments ‘‘Civil Justice Reform’’
distribution transformers. If standards received may be read in the Freedom of H. Review Under Section 32 of the Federal
are promulgated, then use of these test Information Reading Room (Room No. Energy Administration Act of 1974
procedures would be required to 1E–190) at the U.S. Department of I. Review Under Unfunded Mandates
determine compliance and as a basis for Reform Act of 1995
Energy, Forrestal Building, 1000 IV. Public Comment
representations. The proposed rule Independence Avenue, SW, A. Written Comment Procedures
would incorporate by reference clauses Washington, DC between the hours of B. Public Hearing
from test procedures contained in 9:00 a.m. and 4:00 p.m., Monday 1. Procedures for submitting requests to
commercial standards. The Department through Friday, except Federal holidays. speak
is proposing to use one of two Copies of the standards to be 2. Conduct of hearing
alternative sets of standards as the incorporated by reference may be C. Issues Requested for Comment
primary references: alternative (A) is viewed at the Department of Energy’s I. Introduction
primarily based on American National Freedom of Information Reading Room
Standards Institute (ANSI)/Institute of at the address stated above. Copies of A. Authority
Electrical and Electronics Engineers the referenced standards may be The National Energy Conservation
(IEEE) standards C57.12.90–1993 and obtained by request from Global Policy Act of 1978, Pub. L. 95–619,
C57.12.91–1995, and alternative (B) is Engineering Documents World amended the Energy Policy and
based on National Electrical Headquarters (for NEMA Standards TP Conservation Act (EPCA) to add a Part
Manufacturers Association (NEMA) 1–1996 and TP 2–1998), 15 Iverness C of Title III, which established an
standard TP 2–1998, pending its Way East, Inglewood, CO 80112–5776 or energy conservation program for certain
approval by ANSI. the American National Standards industrial equipment. The most recent
DATES: The Department will accept Institute (for ISO Standard 9001–1993 amendments to EPCA, in the Energy
comments, data, and information and ANSI standards C57.12.90–1993, Policy Act of 1992 (EPAct), Public Law
regarding the proposed rule no later C57.12.91–1995, C57.12.00–1993, and 102–486, included amendments that
than February 5, 1999. Ten (10) copies C57.12.01–1989), 11 West 42nd Street, expanded Title III of EPCA to include
must be submitted. In addition, the New York, N.Y. 10036. certain commercial water heaters and
Department requests that an electronic FOR FURTHER INFORMATION CONTACT: heating and air-conditioning equipment,
copy (31⁄2′′ diskette) of the comments on Kathi Epping, U.S. Department of incandescent and fluorescent lamps,
WordPerfectTM 6.1 be provided. Energy, Office of Energy Efficiency and electric motors, and electric distribution
A public hearing will be held on Renewable Energy, EE–43, 1000 transformers.
January 6, 1999, in Washington, DC. Independence Avenue, S.W., Among these amendments is Section
Requests to speak at the hearing must be Washington, D.C. 20585–0121, (202) 124(a) of EPACT, which amended
received by the Department no later 586–7425, e-mail: Section 346 of EPCA, 42 U.S.C. 6317, to
than 4:00 p.m., December 23, 1998. Ten Kathi.Epping@ee.doe.gov, or Edward provide that the Secretary of Energy
(10) copies of statements to be given at Levy, Esq., U.S. Department of Energy, must prescribe testing requirements and
the public hearing must be received by Office of General Counsel, GC–72, 1000 energy conservation standards for those
the Department no later than 4:00 p.m., Independence Avenue, S.W., distribution transformers for which the
December 23, 1998, and the Department Washington, D.C. 20585, (202) 586– Secretary determines that standards
requests that a computer diskette 9507, e-mail: Edward.Levy@hq.doe.gov. ‘‘would be technologically feasible and
Federal Register / Vol. 63, No. 218 / Thursday, November 12, 1998 / Proposed Rules 63361

economically justified, and would result B. Background concerning issues relating to today’s
in significant energy savings.’’ 42 U.S.C. The Secretary’s Determination notice notice were submitted to DOE prior to
6317(a). On October 22, 1997, the was based, in part, on analyses the public workshop. The Department
Department issued a notice setting forth conducted by the Oak Ridge National will consider these two letters as part of
its determination (‘‘Determination Laboratory (ORNL). In July 1996, ORNL the public comment received. The
notice’’) that, based on the best published a report, entitled comments made at the workshop as well
information currently available, energy ‘‘Determination Analysis of Energy as the written comments were
conservation standards for electric Conservation Standards for Distribution considered in preparing the test
distribution transformers are Transformers, ORNL–6847’’ which procedure presented in today’s
technologically feasible and assessed several options for setting proposed rule, and recommendations
economically justified and would result efficiency standards. The report was were incorporated where appropriate.
in significant energy savings. 62 FR based on information from annual sales The reasons for not incorporating any
significant recommendations are
54809. Consequently, the Department is data, average load data, and surveys of
explained in section II of today’s
now proceeding to establish, by notice existing and potential transformer
proposed rule.
and comment rulemaking, test efficiencies that were obtained from
procedures for distribution several organizations. In September C. Summary of the Proposed Test
transformers. 1997, ORNL published a second report, Procedures
entitled ‘‘Supplement to the The Department will use the test
In the Determination notice, the
‘‘Determination Analysis’’ (ORNL–6847) procedures in today’s proposed rule in
Department construed the term
and Analysis of the NEMA Efficiency the process of evaluating whether and
‘‘distribution transformer’’ in section
Standard for Distribution Transformers, what efficiency standard levels are
346 of EPCA to mean ‘‘all transformers ORNL–6925’’. The purpose of this
with a primary voltage of 480 V to 35 appropriate for distribution
report was to assess NEMA TP 1 along transformers. If efficiency standards are
kV, a secondary voltage of 120 V to 480 with the options considered in the
V, and a capacity of either 10 to 2500 promulgated, then manufacturers would
determination study, using the more be required to use these test procedures
kVA for liquid-immersed transformers accurate analysis model and transformer to determine compliance with the
or 0.25 kVA to 2500 kVA for dry-type market and loading data developed standards and as a basis for
transformers,’’ except for transformers subsequent to the publication of the representations they make as to the
which are not continuously connected original ORNL report. efficiency levels of the transformers they
to a power distribution system as a On February 10, 1998, the Department produce.
distribution transformer. The held a public workshop with The Department is proposing that a
Department believes this exception representatives from the National uniform set of test procedures be
would include regulating transformers, Electrical Manufacturers Association applied to all distribution transformers
machine tool transformers, welding (NEMA), manufacturers, utilities, for which standards will be considered,
transformers, grounding transformers, Federal and state agencies, foreign and to all for which standards are
testing transformers, and other government, and other interested parties ultimately adopted. This does not
transformers which are not designed to in Washington, DC. Draft Test necessarily mean, however, that a single
transfer electrical energy from a primary Procedures were presented as a basis for standard or set of labeling requirements
distribution circuit to a secondary discussion. In addition, the following will be adopted for all transformers. In
distribution circuit, or within a issues were discussed: (a) adoption of possible future rulemakings addressing
secondary distribution circuit, or to a national and international consensus standards and labeling, distribution
consumer’s service circuit. The standards in the test procedures for transformers will be divided into
Department indicated that all products determining energy efficiency of classes, if appropriate. A separate class
included in this definition of distribution transformers, (b) burden and an appropriate standard will be
‘‘distribution transformer’’ would be imposed on industry, especially on created for each group of products
addressed in its rulemakings on energy manufacturers, by additional testing and where the record indicates the product
efficiency test procedures and standards data processing, (c) the definition of includes a utility or performance-related
for transformers. ‘‘basic model’’ for distribution feature that affects energy efficiency.
transformers, (d) sampling plan for units Moreover, in evaluating an efficiency
Subsequently, the Department has to be tested, (e) selection of a measure standard in a future rulemaking, the
learned that industry typically classifies of energy consumption for distribution Department will consider whether the
transformers with a secondary voltage transformers, (f) selection of reference standard would result in any lessening
up to 600 V as distribution transformers. temperatures, (g) requirement for of the utility or performance of the
These transformers are included, for applying corrections to measurement transformer(s) that would be covered by
example, in the scope of NEMA data of both liquid-immersed and dry- the standard. Finally, even if standards
standard TP 1. In light of industry usage types of transformers, (h) requirements are promulgated for distribution
and practice, the Department has for quality assurance in testing, and (i) transformers, some classes of
decided that the term ‘‘distribution defining the transformers which are to transformers may be excluded from
transformer’’, in the statute, includes be covered by the test procedures. A standards.
transformers with a secondary voltage transcript of the public workshop is The Department proposes today to
480 V to 600 V, in addition to those available at the Freedom of Information incorporate by reference clauses from
transformers in the above-mentioned Reading Room. industry standards for measuring the
definition. These additional NEMA submitted a written statement energy efficiency of distribution
transformers are covered by today’s at the workshop, and 5 comments were transformers. The proposed rule
proposed test procedures, and will be received subsequent to the public contains two alternative sets of
included in the Department’s workshop. A letter from Don Ballard standards for testing transformers for
consideration of efficiency standards for (industry consultant) and a letter from energy consumption and efficiency, and
transformers. the US Department of Agriculture the Department intends to select one of
63362 Federal Register / Vol. 63, No. 218 / Thursday, November 12, 1998 / Proposed Rules

these alternatives for inclusion in the by the IEEE and approved by ANSI: (1) tolerances. DOE will examine these
final rule. Alternative (A) is primarily ANSI/IEEE C57.12.90–1993, ‘‘IEEE documents for possible incorporation by
based on American National Standards Standard Test Code for Liquid- reference in the final DOE test
Institute (ANSI)/Institute of Electrical Immersed Distribution, Power and procedures, if they have been approved
and Electronics Engineers (IEEE) Regulating Transformers and IEEE by IEEE, their sponsoring organization
standards C57.12.90–1993 and Guide for Short Circuit Testing of (and preferably by ANSI as well), prior
C57.12.91–1995, and alternative (B) is Distribution and Power Transformers,’’ to adoption of the final rule. After the
based on National Electrical (2) ANSI/IEEE C57.12.91–1995, ‘‘IEEE final rule is published, however, any
Manufacturers Association (NEMA) Standard Test Code for Dry-Type subsequent amendments to any of the
standard TP 2–1998. The two reference Distribution and Power Transformers,’’ referenced standards by the standard-
test standards under alternative (A) are and (3) ANSI/IEEE C57.12.00–1993, setting organizations (ANSI, IEEE,
well established within the industry and ‘‘IEEE Standard General requirements NEMA, ISO) would become part of the
have been used for over two decades. for Liquid-Immersed Distribution, DOE test procedure only if DOE amends
Limited additional reference is made Power and Regulating Transformers.’’ the test procedure to incorporate them.
under alternative (A) to ANSI/IEEE ANSI/IEEE C57.12.90–1993 and ANSI/ In comments on workshop issues,
C57.12.00–1993 regarding reference IEEE C57.12.91–1995 are considered NEMA recommends TP 2–1998 as the
temperatures, loss tolerances, and primary references as they address tests sole primary reference to be
measurement tolerances. With respect to and measurements leading to the energy incorporated in the DOE test procedure,
actual tests and measurements for consumption and efficiency values. because it combines in one document
power losses leading to energy ANSI/IEEE C57.12.00–1993 the subject matter that is now available
consumption and efficiency, the complements the previous two ANSI/ in several documents. DOE recognizes
material in the C57 series standards and IEEE standards by specifying the the advantages of having all relevant
TP 2 is nearly identical. The NEMA reference temperatures and testing requirements in a single primary
standard TP 2–1998, referenced in measurement tolerances, which are reference because it enhances the
alternative (B), combines all information essential in fully defining the convenience for users and will facilitate
applicable to tests, measurements for measurement data. The three future harmonization. However, DOE
energy consumption, and calculation of aforementioned standards contain more also desires to incorporate consensus
efficiency in a single document material than the information that is standards that have the broadest
applicable to both liquid-immersed and applicable to loss or efficiency testing. acceptance by the stakeholders, such as
dry-type transformers. Hence, only the applicable sections and the cited ANSI standards.
The test procedure involves the clauses are incorporated by reference in The Department is concerned over
measurement of electric power today’s proposed rulemaking. whether TP 2 has undergone broad-
consumed by the transformer in the The Department is considering based scrutiny. In order for DOE to
form of no-load and load losses, as well referencing a single clause, 4.11.1, of accept TP 2, the Department would
as the determination of certain other International Standards Organization need to have sufficient evidence that all
quantities needed to establish the test (ISO) Standard 9001–1993, ‘‘Quality users and stakeholders have had an
conditions: temperature of the windings Systems—Model for quality assurance opportunity to review TP 2. The
and the core; current; voltage; frequency in design, development, production, Department would like comments from
installation, and servicing,’’ for stakeholders, such as utilities and
and waveform of voltage; and direct
guidance purposes only, concerning contractors who specify transformers for
current resistance of the windings.
compliance with requirements for commercial and industrial applications
Today’s proposed rule also proposes a
quality assurance of the test and (e.g., retail, industrial, and office
sampling plan for testing a basic model
measuring equipment. buildings), on the adequacy of TP 2 to
to establish its compliance with
The remaining reference standard measure transformer efficiency. The
standards and to provide a basis for
being considered by the Department was Department also is concerned that
efficiency representations.
prepared by NEMA: TP 2–1998, ‘‘Test portions of the current version of TP 2
In addition to discussing the
Method for Measuring the Energy have been abbreviated from the ANSI/
standards to be incorporated by
Consumption of Distribution IEEE standards, and certain portions are
reference, the following issues are
Transformers.’’ It is also considered a ambiguous and should be made more
discussed below: distribution
primary reference standard. This NEMA explicit. There are also instances in
transformers not subject to the test
publication is planned for submission to which the terminology should be
procedures, the reference conditions in
the ANSI C57 committee for review and changed. In addition, certain portions
the test procedure, measures of energy
possible approval as a national do not read as if the current version of
consumption, the definition of a ‘‘basic
standard, thus including in the approval TP 2 is a final document. If these
model’’ to permit grouping of models for
process a broader constituency, such as concerns with TP 2 are addressed
testing purposes, and the sampling plan. the electric utility industry, which is the during the ANSI approval process as the
II. Discussion principal user group of distribution Department believes is likely, and if TP
transformers. 2 receives approval from ANSI, the
A. Standards to be Incorporated by In addition, IEEE PC57.123, ‘‘Draft Department would be inclined to adopt
Reference Guide for Transformer Loss alternative B.
The Department is proposing to Measurement’’ is nearing completion
incorporate by reference specific and provides additional guidance on B. Distribution Transformers Not
portions of either three widely used how to conduct transformer loss Subject to the Test Procedures
commercial standards, or of a standard measurements. The Department is also The commercial standards on which
being developed by the National aware that a revised version of ANSI/ today’s proposed test procedures are
Electrical Manufacturers Association IEEE C57.12.01 is currently being based are intended to test 60 Hz
(NEMA), as a test procedure in balloted. If adopted, this revision would transformers, although the standards
Appendix A of 10 CFR part 432. The make C57.12.01 more consistent with allow for minor variations in frequency.
three national standards were prepared C57.12.00 in specifying measurement Many manufacturers would need to
Federal Register / Vol. 63, No. 218 / Thursday, November 12, 1998 / Proposed Rules 63363

modify test equipment in order to in a possible future standards the following reference conditions for
accurately conduct tests for transformers rulemaking. distribution transformers:
that operate at frequencies that deviate For the purposes of these test
substantially from 60 Hz. Because such procedures, the Department proposes to No-load Load
distribution transformers comprise a define the term ‘‘distribution losses losses
small segment of the market, they have transformer’’ to mean all transformers
with a primary voltage of 480 V to 35 Liquid-immersed
little potential for resulting in (50% of rated load) 20° C 85° C
significant energy savings. In addition, kV, a secondary voltage of 120 V to 600
V, a frequency of 55–65 Hz, and a Medium-voltage dry-
transformers with frequencies other type (50% of the
than 60 Hz were not included in the capacity of either 10 kVA to 2500 kVA
rated load) ............. 20° C 75° C
ORNL Determination analyses. for liquid-immersed transformers or
Low-voltage dry-type
Consequently, the Department is 0.25 kVA to 2500 kVA for dry-type (35% of the rated
proposing that the test procedures in transformers, except for transformers load) ....................... 20° C 75° C
which are not designed to be connected
today’s proposed rule cover only 55 to
to a power distribution system as a
65 Hz transformers, and the Department In order to address the inconsistencies
distribution transformer. These
intends to evaluate only 60 Hz in the reference conditions among the
exceptions would include regulating
transformers in a possible future transformers, machine tool transformers, industry standards, the proposed rule
standards rulemaking. The Department welding transformers, grounding specifies the following: (1) Use a
does not believe this will cause transformers, testing transformers, and consistent reference temperature of 20°
‘‘loopholes’’ because it would not be other transformers which are not C for reporting the no-load losses of
beneficial to the manufacturers to designed to transfer electrical energy both liquid-immersed and dry-type
substitute transformers at substantially from a primary distribution circuit to a transformers, and correct the measured
different frequencies for 60 Hz secondary distribution circuit, or within no-load loss data of dry-type
applications. a secondary distribution circuit, or to a transformers to 20° C as required in
In addition, the Department consumer’s service circuit. Converter ANSI standards for liquid-immersed
recognizes that the efficiency of and rectifier transformers with more transformers, if such a correction is
distribution transformers connected to than two windings per phase also would significant relative to required
rectifier and converter circuits cannot be not be included. measurement accuracy; (2) correct the
readily tested or accurately measured by C. Reference Conditions measured load loss data of dry-type
the conventional loss measurement test transformers for phase angle errors in
procedures outlined in today’s proposed There is considerable diversity in the
reference conditions specified in the the measuring equipment as required in
rule. The nameplates of these ANSI standards for liquid-immersed
transformers contain a rating for the existing commercial standards. Under
the current industrial practice, the load transformers, if such errors are
fundamental-frequency apparent output significant relative to required
losses of liquid-immersed transformers
power and a rating for the apparent measurement accuracy; (3) use an
are reported at the rated load and the
output power with non sinusoidal efficiency selected at lower than the
reference temperature of 85° C, as
current produced by the converter. The rated loading and using a reference
specified by ANSI/IEEE C57.12.00. This
latter is inherently smaller than the temperature for load losses that
reference temperature is based on an
former, because harmonic currents ambient temperature of 20° C and the approximates the temperature rise at
produce losses in addition to those of temperature rise of 65° C. The load new loading conditions, as opposed to
the fundamental-frequency current. As a losses of dry-type transformers are using temperature rises, as in ANSI/
result of additional physical and reported at the rated load and, IEEE standards, for rated nameplate
electrical requirements in the design of depending on the insulation system loading; and (4) measure losses of dry-
converter and rectifier transformers, used, at one of five specified type transformers to the same accuracy
their performance is optimized for the temperature rises in addition to an
output power rating with non sinusoidal as specified for liquid-immersed
ambient temperature of 20° C, as transformers.
current, yielding less than the optimal specified by ANSI C57.12.01. The
performance at fundamental resulting reference temperatures are: 80, These reference conditions enhance
frequencies, as would be required in a 100, 135, 150, and 170° C. ANSI uniformity in requirements and
general purpose distribution standards C57.12.90 and C57.12.91 facilitate comparison of products using
transformer. Conversely, optimally provide an identical algorithm for both liquid-immersed and dry-type
designed distribution transformers of converting the measured load loss insulations. Therefore the proposed rule
other types will not meet the optimal values to specified reference requires that test results be reported at
requirements of a converter and rectifier temperatures. the following loads and reference
transformer. These transformers also For no-load losses of liquid-immersed temperatures: 1
were not included in the ORNL transformers, ANSI C57.12.00 specifies
Determination analyses. In addition, the reference temperature of 20° C, thus 1 Establishing specific loading levels is properly
rectifier and converter transformers approximating ambient conditions. part of the energy conservation standard, but
generally have more than two windings Additionally, ANSI C57.12.90 provides correction of measurement data to new reference
per phase, requiring more magnetic an algorithm for converting a no-load conditions (including loading levels) must be
material and resulting in higher no-load included in the test procedure. Today’s proposed
loss value measured at another test procedures use the loading levels in NEMA TP
losses. For these reasons, the test temperature to that at the reference 1, because they appear to be widely used in the
procedures in today’s proposed rule will temperature. No reference temperature industry and are reasonable for testing that is
not apply to converter and rectifier is specified for the no-load losses of the conducted to consider and develop standards. Any
standards that are prescribed for transformers will
transformers with more than 2 windings dry-type transformers. include specific loading levels, which the
per phase, and the Department is not Finally, NEMA TP 1–1996 Department will incorporate into the applicable test
inclined to evaluated these transformers recommends minimum efficiencies and procedures.
63364 Federal Register / Vol. 63, No. 218 / Thursday, November 12, 1998 / Proposed Rules

No-load Load differences between liquid-immersed equivalent load losses at a different


losses losses and dry-type transformers. The reference temperature. For load losses of
proposed reference temperature to dry-type transformers, TP 1
Liquid-immersed which no-load losses would be adjusted recommends a single reference
(50% of rated load) 20 °C 55 °C for both types of transformers is 20 °C, temperature of 75 °C, as a substitute for
Medium-voltage 2 dry-
type (50% of the
which is consistent with C57.12.00 and the five temperatures at the rated load
rated load) ............. 20 °C 75 °C TP 1, but not with C57.12.01 which corresponding to the five insulation
Low-voltage 3 dry-type does not specify the reference classes. To assess the adequacy of this
(35% of the rated temperature for no-load losses of dry- adjustment, reduced operating
load) ....................... 20 °C 75 °C type transformers. The 20 °C reference temperatures were calculated at 50%
temperature is close to the ambient and 35% of rated load for all five
Under the proposed rule, the measured temperature; therefore losses can be temperature classes of dry-type
no-load and load losses used in the easily measured when the transformer is insulation and for liquid-immersed
efficiency computation would be cold, but this reference temperature insulation. The relationship whereby
adjusted to the stated reference does not represent operating conditions. the temperature rise (∆T) is proportional
conditions, the total uncertainty However, because the changes in the to the 0.8th power of the dissipated
(including measurement inaccuracy and core losses due to temperature are small power (W) was used for this calculation.
uncertainty resulting from lack of (quoted in C57.12.90 as 6.5 × 10¥4 per Thus, ∆T = kW0.8, where k is a constant.
reference condition adjustments) unit per °C), these differences will have The assumption was made that, at the
exceeds 3 percent. only a small effect on the resulting rated load, 75% of dissipated power is
These reference temperatures were calculated efficiency. the load loss and the remainder is no-
selected with the objectives of obtaining If a transformer is being tested for load (core) loss.
uniformity in reference conditions, efficiency at less than full-rated or The results are summarized in Table
having reference conditions that best nameplate loading (as may be the case 1 for both 50% and 35% of the rated
reflect the actual operating conditions, for a possible future efficiency loads. Note that for dry-type
and maintaining consistency with the standard), it is proper to adjust the transformers, out of 10 estimated
practices of the current commercial reference temperature for load losses. A reference temperatures, five are below
standards as much as possible. Fully well established algorithm published in 75 °C, four are above, and one is exactly
satisfying all three criteria, however, ANSI C57.12.90 and ANSI C57.12.91 is on. Thus, the selected value in TP 1
was not practical or even possible, due used to perform the computational represents a reasonable compromise,
to the previously mentioned diversity in operation to convert load losses especially if each of the 10 groups were
the existing practice and the inherent measured at a given temperature to to have similar installed kVA capacity.

TABLE 1.—CALCULATED TEMPERATURE RISES FOR TRANSFORMERS OPERATED AT LOWER THAN THE RATED
(NAMEPLATE) LOAD
Estm. ref- Estm. ref-
Temperature Temperature erence tem- Temperature erence tem-
Reference
Insulation system temperature rating rise at rated rise at 50% of perature at rise at 35% of perature at
temperature
°C load rated load 50% of rated rated load 35% of rated
°C
°C °C load °C Load
°C °C

Liquid-Immersed

85 .............................................................. 65 85 35 55 ........................ ........................

DryType

130 ............................................................ 60 80 30 50 25 45
150 ............................................................ 80 100 40 60 35 55
185 ............................................................ 115 135 60 80 50 70
200 ............................................................ 130 150 65 85 55 75
220 ............................................................ 150 170 75 95 65 85
Assumptions:
No-load losses 25%; load losses 75%.
Algorithm: >T=kW0.8.
>T—temperature rise.
W—dissipated power.
k—constant.
>T rounded off to the nearest 5 °C.

For liquid immersed transformers, in the actual use of these transformers, and The written comments received in
the proposed test procedure the was arrived at using the same type of conjunction with the workshop on
reference temperature for the load losses approach that was used to calculate the February 10, 1998, support 20°C as the
is lowered from 85°C (in C57.12.00 and adjustment of the load loss reference reference temperature for no-load losses
C57.12.90) to 55°C. This adjustment temperature for dry-type transformers. of both types of transformers and 75°C
better approximates the conditions of as the reference temperature for load

2 Medium voltages are considered to be greater 3 Low voltages are considered to be no greater

than 1200 volts. than 1200 volts.


Federal Register / Vol. 63, No. 218 / Thursday, November 12, 1998 / Proposed Rules 63365

losses of dry-type transformers. For load energy conservation program, although burden of testing. It would apply an
losses of liquid-immersed transformers, not for distribution transformers, several approach to distribution transformers
stakeholders agreed with using a models often are essentially the same, that has proven effective in the
reference temperature lower than 85°C with each model having some residential appliance program, but with
but did not recommend a specific value. refinement that does not significantly appropriate modifications given the
affect the energy efficiency or nature of distribution transformers. The
D. Measures of Energy Consumption
performance. In order to lessen the factors outlined in this approach are the
The test procedure provides for three burden of test procedures, generally design variables that affect a
interrelated measures of energy appliance models having essentially transformer’s efficiency. Design
consumption: (a) total transformer identical electrical and mechanical considerations cause a transformer’s
losses, (b) transformer efficiency, and (c) characteristics are categorized into a
estimated annual energy consumption efficiency to increase as its power rating
family of models. The Department has
(EAEC). Under the test procedure, each increases. For dry type transformers,
used the term ‘‘basic model’’ to identify
measure is computed at the loading a family of such models, which consist efficiency decreases as voltage
parameters used in NEMA TP 1–1996: of products or items of equipment increases, when all other factors are
50% of the rated load for liquid- whose performance, design, mechanical, held constant. In addition, liquid-
immersed and medium-voltage dry-type and functional characteristics are immersed insulation is inherently more
transformers, and at 35% of the rated essentially the same. Components of efficient than dry-type insulation, and
load for low-voltage dry-type similar design may be substituted in a multiple phases slightly decrease
transformers. basic model without requiring efficiency. Consequently, the
Transformer losses consist of load additional testing if the represented Department believes the assignment of
losses and no load losses. Load losses measures of energy consumption minimum efficiencies will likely be
vary quadratically with the output continue to satisfy applicable provisions made in accordance with such
current and, hence, with output power. for sampling and testing. Only groupings. For example the Canadian
No load losses vary with excitation representative samples within each energy conservation standard for
volatge. The efficiency of a transformer ‘‘basic model’’ are tested. distribution transformers implements
varies with the output power as a result Thus, the term ‘‘basic model’’ has this approach. Therefore, the
of varying losses. been defined as follows: ‘‘Basic model Department is proposing the definition
The industry practice, as required by means all units of a given type of for ‘‘basic model’’ be based on NEMA’s
the cited ANSI standards, has been to covered product (or class thereof) approach.
measure and report transformer losses manufactured by one manufacturer
rather than energy efficiency. DOE and—* * *[as to dishwashers, for
believes that efficiency is the preferable example] which have electrical
TABLE 2.—PREFERRED STANDARD
KVA RATINGS LIQUID-IMMERSED
energy descriptor because it is a characteristics that are essentially
normalized measure and allows trade- identical, and which do not have any DISTRIBUTION TRANSFORMERS
offs between the two types of losses, differing physical or functional
load losses and no-load losses. characteristics which affect energy Single-Phase
Workshop participants supported consumption.’’ 10 CFR 430.2. Power Rating:
efficiency as a measure for energy At the February 1998 workshop, DOE 10
conservation in distribution presented a similar definition for 15
transformers. Consequently the transformers, but it was opposed by all 25
Department is inclined to use efficiency groups and individuals because 37.5
as the energy descriptor for any distribution transformers, unlike 50
standards that may be promulgated. consumer appliances, are not produced 75
Expressing energy consumption in in large numbers of virtually identical 100
terms of efficiency presents some units. However, NEMA presented an 167
difficulties in calculations and approach in which a basic model could 250
adjustment of test data (e.g. to reference be defined to include all transformers 333
conditions) because accuracy may be having the same nominal power (kVA) 500
lost in the rounding-off process to the rating, the same insulation type (liquid- 667
nearest tenth of one percent. To avoid immersed or dry-type), and the same 833
this loss of computational accuracy, number of phases (single or three), and Three-phase
under the proposed rule, the operating within the same voltage range.
Power Rating:
intermediate calculations would use Under NEMA’s definition, ‘‘rating’’
15
transformer losses (in watts) or would means a standard output power rating,
30
use percent efficiency with two digits as tabulated in NEMA TP 1–1996, tables
45
after the decimal point. Only the final 4–1 and 4–2 (reproduced herein as
75
efficiency percentage would be rounded tables 2 and 3), but will encompass
112.5
off to the nearest one tenth of one some ratings that are close but not equal
150
percent. to the standard ratings. These power
225
ratings are also the preferred ratings 300
E. Basic Model from ANSI/IEEE C57.12.00–1993 for 500
It is common for a manufacturer to liquid-immersed transformers and 750
make numerous models of a product ANSI/IEEE C57.12.01–1989 for dry-type 1000
covered by EPCA, and under the Act transformers. 1500
each model is potentially subject to The Department believes the 2000
testing for energy efficiency. Moreover, foregoing approach to defining ‘‘basic 2500
for appliances covered by the EPCA model’’ is a sound means to reduce the
63366 Federal Register / Vol. 63, No. 218 / Thursday, November 12, 1998 / Proposed Rules

TABLE 3.—PREFERRED STANDARD of possible efficiency standards, it recommended the enforcement


KVA RATINGS DRY-TYPE DISTRIBU- would become operative primarily if sampling test also be used for
TION TRANSFORMERS and when standards are promulgated. demonstration of compliance. However,
At that point, the efficiency of each after reviewing these approaches more
Low volt- Medium basic model of distribution transformer closely, the Department believes the
Power rating, age, > 1.2 voltage, ≤ would be established initially by sampling plan for compliance in Part
kVA kV 1.2 kV ‘‘compliance testing’’ for the purposes of 430 favors consumers by providing high
determining whether the transformer statistical probability that the mean
Single-Phase complies with the applicable efficiency performance of the basic model meets or
15 standard and of labeling the exceeds the performance level claimed
25 transformer. A sampling plan for by the manufacturer based on testing a
37.5 compliance is intended to provide a small number of models. Most of the
50 statistically meaningful sampling error introduced by estimating the
75 procedure for conducting tests, so as to performance of the basic model from a
100 reduce the testing burden while giving sample (rather than from testing all
167 sufficient assurance that the true mean units) is absorbed by the producer
250 energy efficiency of a basic model (i.e., (manufacturer). The probability of false
333 the average efficiency of all units
500 determination of compliance is low and
manufactured) meets or exceeds a given is quantifiable from the confidence limit
667
833 performance level. and the divisor. For example, for
For this purpose, one product under transformer losses, using a lower
Three-Phase 10 CFR Part 430, § 430.24, involves confidence limit of 95%, 0.97 as the
some similarities with distribution divisor, and assuming a standard
15 transformers. The required sampling deviation of 3% for a basic model and
30 plan for compliance testing of
45
a minimum sample size of five, possible
fluorescent lamp ballasts under § 430.24 errors and corresponding probabilities
75 (q)(1) states, ‘‘For each basic model of
112.5 for false determinations of compliance
fluorescent lamp ballasts, as defined in are:
150
225 paragraph (14) of § 430.2, a sample of
sufficient size, no less than four, shall Error in percent 1.5 2.0 2.9
300
be tested to insure that (i) any Probability in
500
represented value of estimated annual percent ........... 10 5 1
750
1000 operating costs, energy consumption, or Under these constraints there is a
1500 other measure of energy consumption of probability of less than 5% that the
2000 a basic model for which consumers estimated average losses of the entire
2500 would favor a lower value shall be no population exceed the true average by
less than the higher of (A) the mean of 2%.
The Department has some concern, the sample or (B) the upper 99 percent Conversely, the enforcement sampling
however, that this approach may allow confidence limit divided by 1.01, and approach in Part 430 is based on a
manufacturers who sell some high (ii) any represented value of the ballast Student’s t-test; it generally tests
efficiency models to deliberately under efficiency factor or other measure of whether there is a sufficiently high
design other transformers within that energy consumption of a basic model for probability to conclude that the average
basic model, while still meeting the which consumers would favor a higher performance of all units of the basic
standard for the average efficiency of the value shall be no greater than the lower model is below the standard to warrant
basic model. The Department is of (A) the mean of the sample or (B) the enforcement action. By selecting an
considering addressing this point by lower 99 percent confidence limit of the upper confidence limit and a minimum
imposing a maximum efficiency true mean divided by 0.99.’’ sample size, the probability of the
variation within a basic model, similar A sampling plan for enforcement, on populations not meeting the standard by
to what is now done in ANSI/IEEE the other hand, is intended to provide a certain amount can be established. For
C57.12.00 and C57.12.01, as well as a statistically meaningful sampling example, for transformer losses, using
NEMA TP 2. The Department would procedure for conducting tests, so as to the upper 95% confidence limit and a
like comments on this concern. reduce the testing burden while giving sample size of five, on a population
F. Number of Units to be Tested sufficient assurance that a distribution with standard deviation of 3%, the
transformer found to be in possible errors and corresponding
As discussed above, the classification noncompliance will actually be in probabilities for significant false
of transformers into ‘‘basic models’’ is noncompliance. The sampling plan for determinations of compliance are high
one step to reduce the burden of testing. enforcement testing under Part 430 is as shown in the table below:
The Department also proposes to permit provided in 10 CFR 430.70, Appendix
the use of a statistically meaningful B. This sampling plan is based on the Error in percent 0.8 2.9 5.7
sampling procedure for selecting test statistical t-test yielding 97.5 percent Probability in
specimens, so as to further reduce the probability of obtaining a determination percent ........... 90 50 5
testing burden on manufacturers while of compliance when the true mean Under these constraints there is a
giving sufficient assurance that the true efficiency is equal to the applicable probability of almost 50% that the
mean energy efficiency of a basic model standard. estimated average losses of the entire
meets or exceeds the efficiency level At the February 1998 workshop, DOE population exceed the true average by
claimed by the manufacturer. presented both sampling approaches for 3%.
Although the sampling plan presented consideration for compliance testing for Thus, after considerable review, the
in this test procedure rule might have distribution transformers. In the Department is proposing in today’s
some application during the evaluation comments on workshop issues, NEMA proposed rule to use Part 430’s sampling
Federal Register / Vol. 63, No. 218 / Thursday, November 12, 1998 / Proposed Rules 63367

approach for compliance testing. For Department proposed to create a new of the rule on small entities and
transformer losses, the proposed lower part 431 in the Code of Federal considers alternative ways of reducing
confidence limit is 95%, and the divisor Regulations (10 CFR part 431) to cover negative impacts.
is 0.97, with a minimum sample size of certain commercial and industrial Today’s proposed rule prescribes test
five. equipment 61 FR 60439 (November 27, procedures that will be used to
Some manufacturers, however, 1996). The Department is now determine what standards, if any, DOE
particularly small companies, have contemplating adding a new Part 432 would adopt, and that would likely
limited output of certain basic models; which would include products become generally applicable only upon
consequently, under today’s proposed addressed under 346 of EPCA. adoption of standards. Unless and until
sampling plan, a manufacturer would such standards are adopted, the
need to test a relatively high proportion III. Procedural Requirements Department anticipates that
of the units it manufactures of such a A. Review Under the National manufacturers will use the test
basic model. Moreover, although the Environmental Policy Act of 1969 procedures to voluntarily test their
Department could provide in its transformers and provide to DOE
In this rulemaking, the Department efficiency information about their
sampling plan that the minimum
proposes provisions to establish test products. No entities, small or large,
number of units tested of a low
procedures for electric distribution would be required to comply with these
production basic model be reduced from
transformers. These test procedures test procedures. Therefore DOE believes
five to two or three, any such basic
would be used initially only for the today’s proposed rule does not have a
model would be subject to increased
purpose of considering the adoption of ‘‘significant economic impact on a
risk of being determined to be in non-
energy conservation standards. During a substantial number of small entities,’’
compliance due to the statistical
subsequent rulemaking concerning such and the preparation of a regulatory
probabilities associated with testing a
standards, the Department will address flexibility analysis is not warranted.
small number of units. To allay these
the extent to which these test
concerns, the Department is considering D. Review Under Executive Order
procedures would become generally
three possible approaches for sampling 12612, ‘‘Federalism’’
applicable and binding for determining
limited production models:
(1) Combine two or more limited the energy efficiency of distribution Executive Order 12612, ‘‘Federalism,’’
production basic models of distribution transformers. 52 FR 41685 (October 30, 1987),
transformer into an aggregate ‘‘basic The Department has concluded that requires that regulations, rules,
model’’; this rule would not have a significant legislation, and any other policy actions
(2) Allow testing of a sample fewer effect on the human environment, and be reviewed for any substantial direct
than five units, and also permit the use is covered under the categorical effect on States, on the relationship
of a represented efficiency value that exclusion A.6 of appendix A to Subpart between the National Government and
exceeds, by a specified increment, the D, 10 CFR Part 1021, which applies to States, or in the distribution of power
average efficiency of the sample, so long procedural rulemakings. (10 CFR Part and responsibilities among various
as each tested unit exceeds a 1021 is a DOE regulation implementing levels of government. If there are
minimum level of efficiency 4; the National Environmental Policy Act substantial effects, then the Executive
(3) Allow compliance testing over a of 1969 (NEPA), and Appendix A to Order requires preparation of a
period of time. Subpart D sets forth DOE actions federalism assessment to be used in all
The third alternative would be similar excluded from NEPA review.) decisions involved in promulgating and
to the Department’s approach for lamps, Accordingly, neither an environmental implementing a policy action.
which permits lamp manufacturers to assessment nor an environmental The proposed rule published today
submit a certification report up to one impact statement is required. would not regulate the States. At this
year after the date the manufacture of a point, it primarily would affect the
B. Review Under Executive Order 12866,
new model commences, provided that manner in which DOE determines
‘‘Regulatory Planning and Review’’
prior to distribution the manufacturer whether standards should be adopted,
submits a statement describing how it Today’s proposed rule has been as prescribed under the Energy
determined the model meets the energy determined not to be a ‘‘significant Conservation and Policy Act. The
conservation standard. See section regulatory action,’’ as defined in section proposed rule published today would
430.62(c)(2) and 42 U.S.C. 6295(i)(7). 3(f) of Executive Order 12866, not alter the distribution of authority
The Department solicits comments on ‘‘Regulatory Planning and Review.’’ 58 and responsibility to regulate in this
these possible approaches. FR 51735 (October 4, 1993). area. Accordingly, DOE has determined
Accordingly, this action was not subject that preparation of a federalism
G. New Part 432 to review under the Executive Order by assessment is unnecessary.
10 CFR part 430 covers consumer the Office of Information and Regulatory
products as distinct from commercial Affairs. E. Review Under Executive Order 12630,
and industrial equipment. The ‘‘Governmental Actions and
C. Review Under the Regulatory Interference With Constitutionally
4 DOE is considering, as a method of
Flexibility Act Protected Property Rights’’
implementing this approach, the following: If fewer The Regulatory Flexibility Act, 5 It has been determined pursuant to
than 5 units of a basic model are manufactured in
a period of 180 days, all units manufactured within
U.S.C. 603, requires the preparation of Executive Order 12630, ‘‘Governmental
this period shall be tested, and the average an initial regulatory flexibility analysis Actions and Interference with
efficiency of the sample Ē shall satisfy the condition for every rule which by law must be Constitutionally Protected Property
Ē ≥ ES [1 ¥ 0.04 ÷ √n (1 ¥ ES ÷ 100)] proposed for public comment, unless Rights,’’ 52 FR 8859 (March 18, 1988),
where n is the number of units in the sample, and the agency certifies that the rule, if that this regulation would not result in
Es is the represented value of efficiency.
promulgated, will not have a significant any takings which might require
For sample sizes of two, three, or four
transformers, the lowest efficiency in the sample economic impact on a substantial compensation under the Fifth
Emin shall satisfy the condition number of small entities. A regulatory Amendment to the United States
Emin ≥ ES [1 ¥ 0.08 (1 ¥ ES ÷ 100)] flexibility analysis examines the impact Constitution.
63368 Federal Register / Vol. 63, No. 218 / Thursday, November 12, 1998 / Proposed Rules

F. Review Under the Paperwork provides in essence that, where a consultation with elected
Reduction Act proposed rule contains or involves use representatives of state, local, and tribal
Today’s notice of proposed of commercial standards, the notice of governments and a summary and
rulemaking would not impose any proposed rulemaking must inform the evaluation of the comments and
compliance certification, labeling or public of the use and background of concerns presented.
such standards.
other reporting requirements. The Department has determined that
The rule proposed in this notice
Accordingly, no OMB clearance is the action proposed today does not
incorporates by reference commercial
required under the Paperwork standards NEMA TP 2. The Department include a Federal mandate that may
Reduction Act (44 U.S.C. 3501 et seq.). has evaluated these standards and result in estimated costs of $100 million
G. Review Under Executive Order concludes they were not developed in a or more to state, local or to tribal
12988, ‘‘Civil Justice Reform’’ manner which fully provides for public governments in the aggregate or to the
participation, comment, and review. private sector. Therefore, the
With respect to the review of existing
The rule proposed in this notice also requirements of Sections 203 and 204 of
regulations and the promulgation of
incorporates by reference commercial the Unfunded Mandates Act do not
new regulations, Section 3(a) of
standards IEEE/ANSI C57.12.90–1993, apply to this action.
Executive Order 12988, ‘‘Civil Justice
C57.12.91–1995, C57.12.00–1993, and
Reform,’’ 61 FR 4729 (February 7, 1996), IV. Public Comment
C57.12.01–1989, as well as ISO
imposes on executive agencies the Standard 9001–1993. The Department
general duty to adhere to the following A. Written Comment Procedures
has evaluated these standards and is
requirements: (1) eliminate drafting unable to conclude whether they were Interested persons are invited to
errors and ambiguity; (2) write developed in a manner which fully participate in the proposed rulemaking
regulations to minimize litigation; and provides for public participation, by submitting data, comments, or
(3) provide a clear legal standard for comment, and review. However, the information with respect to the
affected conduct rather than a general Department believes the IEEE/ANSI and
standard and promote simplification proposed issues set forth in today’s
ISO review processes provide for proposed rule to Ms. Kathi Epping, at
and burden reduction. With regard to participation from a larger group of
the review required by Section 3(a), the address indicated at the beginning of
entities than the NEMA standards the notice. All submittals received by
Section 3(b) of the Executive Order review process.
specifically requires that Executive the date specified at the beginning of
As required by Section 32(c) of the
agencies make every reasonable effort to this notice will be considered by the
Federal Energy Administration Act, the
ensure that the regulation: (1) clearly Department will consult with the Department in developing the final rule.
specifies the preemptive effect, if any; Attorney General and the Chairman of Pursuant to the provisions of 10 CFR
(2) clearly specifies any effect on the Federal Trade Commission 1004.11, any person submitting
existing Federal law or regulation; (3) concerning the impact of these information which he or she believes to
provide a clear legal standard for standards on competition, prior to be confidential and exempt by law from
affected conduct while promoting prescribing a final rule. public disclosure should submit one
simplification and burden reduction; (4) complete copy of the document and ten
specifies the retroactive effect, if any; (5) I. Review Under Unfunded Mandates
Reform Act of 1995 (10) copies, if possible, from which the
adequately defines key terms; and (6) information believed to be confidential
addresses other important issues Section 202 of the Unfunded
has been deleted. The Department of
affecting clarity and general Mandates Reform Act of 1995
Energy will make its own determination
draftsmanship under any guidelines (‘‘Unfunded Mandates Act’’) requires
that the Department prepare a budgetary with regard to the confidential status of
issued by the Attorney General. Section
3(c) of the Executive Order requires impact statement before promulgating a the information and treat it according to
Executive agencies to review regulations rule that includes a Federal mandate its determination.
in light of applicable standards Section that may result in expenditure by state, Factors of interest to the Department
3(a) and Section 3(b) to determine local, and tribal governments, in the when evaluating requests to treat as
whether they are met or it is aggregate, or by the private sector, of confidential information that has been
unreasonable to meet one or more of $100 million or more in any one year. submitted include: (1) a description of
them. DOE reviewed today’s proposed The budgetary impact statement must the items; (2) an indication as to
regulation under the standards of include: (i) identification of the Federal whether and why such items are
Section 3 of the Executive Order and law under which the rule is customarily treated as confidential
determined that, to the extent permitted promulgated; (ii) a qualitative and within the industry; (3) whether the
by law, it meets the requirements of quantitative assessment of anticipated information is generally known by or
those standards. costs and benefits of the Federal available from other sources; (4)
mandate and an analysis of the extent to whether the information has previously
H. Review Under Section 32 of the which such costs to state, local, and
Federal Energy Administration Act of been made available to others without
tribal governments may be paid with
1974 obligation concerning its
Federal financial assistance; (iii) if
Pursuant to Section 301 of the feasible, estimates of the future confidentiality; (5) an explanation of the
Department of Energy Organization Act compliance costs and of any competitive injury to the submitting
(Pub. L. 95–91), the Department of disproportionate budgetary effects the person which would result from public
Energy is required to comply with mandate has on particular regions, disclosure; (6) an indication as to when
Section 32 of the Federal Energy communities, non-Federal units of such information might lose its
Authorization Act (FEAA), as amended government, or sectors of the economy; confidential character due to the
by Section 9 of the Federal Energy (iv) if feasible, estimates of the effect on passage of time; and (7) why disclosure
Administration Authorization Act of the national economy; and (v) a of the information would be contrary to
1977 (Pub. L. 95–70). Section 32 description of the Department’s prior the public interest.
Federal Register / Vol. 63, No. 218 / Thursday, November 12, 1998 / Proposed Rules 63369

B. Public Hearing topics covered by this notice, as follows: • The adequacy of TP 2 to meet the
(1) proposed test procedures; (2) requirements of non-NEMA
1. Procedures for Submitting Requests
adequacy of TP 2 to meet the manufacturers and users, such as
To Speak
requirements of users; (3) distribution utilities and contractors who specify
The time and place of the public transformers not subject to the test transformers for commercial and
hearing are indicated at the beginning of procedures; (4) grouping of transformers industrial applications (e.g., retail,
this notice of proposed rulemaking. The for testing purposes, as manifested by industrial, and office buildings);
Department invites any person who has the definition of a basic model; (5) • Distribution transformers not
an interest in today’s notice of proposed sampling plan for compliance; and (6) subject to the test procedures;
rulemaking, or who is a representative general statutory requirements. Any • Grouping of transformers for testing
of a group or class of persons that has issue concerning a definition in the purposes, as manifested by the
an interest in these proposed issues, to proposed rule should be addressed definition of a basic model; and
make a request for an opportunity to during the discussion of the topic(s) to
make an oral presentation. If you would • The sampling plan for compliance
which that issue pertains. (The Department is particularly
like to attend the public hearing, please The Department will introduce each
notify Ms. Brenda Edwards-Jones at interested in discussing how small
topic with a brief summary of the
(202) 586–2945. Requests to speak may populations should be handled.)
relevant provisions of the proposed rule,
be hand delivered to the address and the significant issues involved. List of Subjects in 10 CFR Part 432
indicated at the beginning of the notice Participants in the hearing will then be
between the hours of 8:00 a.m. and 4:00 Administrative practice and
permitted to make a prepared statement
p.m., Monday through Friday, except procedure, Energy conservation,
limited to five (5) minutes on that topic.
Federal holidays. Household appliances. Incorporation by
At the end of all prepared statements on
The person making the request should reference.
a topic, each participant will be
briefly describe the interest concerned permitted to briefly clarify his or her Issued in Washington, DC., on October 2,
and state why he or she, either statement and comment on statements 1998.
individually or as a representative of a made by others. The Department is Dan W. Reicher,
group or class of persons that has such particularly interested in having Assistant Secretary, Energy Efficiency and
an interest, is an appropriate participants address in their statements Renewable Energy.
spokesperson, and give a telephone the specific issues set forth below in For the reasons set forth in the
number where he or she may be Section IV–C, ‘‘Issues for Public preamble, Chapter II of Title 10, Code of
contacted. Comment,’’ and participants should be Federal Regulations, is proposed to be
Each person selected to be heard is prepared to answer questions by the amended by adding a new Part 432 to
requested to submit an advance copy of Department concerning these issues. read as follows.
his or her statement prior to the hearing Representatives of the Department may
as indicated at the beginning of this also ask questions of participants PART 432—ENERGY CONSERVATION
notice. Any person wishing to testify concerning other matters relevant to the PROGRAM FOR DISTRIBUTION
who cannot meet this requirement, may hearing. The total cumulative amount of TRANSFORMERS
at the Department’s discretion be time allowed for each participant to
permitted to testify if that person has make prepared statements shall be 20 Sec.
made alternative arrangements with the minutes. 432.1 Purpose and scope [Reserved].
Office of Codes and Standards in The official conducting the hearing 432.2 Definitions.
432.22 Reference Sources.
advance. The letter making a request to will accept additional comments or
432.24 Units to be tested.
give an oral presentation shall ask that questions from those attending, as time Appendix A to Part 432—Uniform Test
such alternative arrangements be made. permits. Any further procedural rules, Method for Measuring the Energy
or modification of the above procedures, Consumption of Distribution
2. Conduct of Hearing
needed for the proper conduct of the Transformers.
A DOE official will be designated to hearing will be announced by the Authority: 42 U.S.C. 6317.
preside at the hearing. The hearing will presiding official.
not be a judicial or an evidentiary-type A transcript of the hearing will be § 432.1 Purpose and scope [Reserved].
hearing, but will be conducted in made, and the entire record of this § 432.2 Definitions.
accordance with 5 U.S.C. 553 and rulemaking, including the transcript,
Section 336 of the Act. The Department will be retained by the Department of Basic model means all units of a given
of Energy reserves the right to select the Energy and made available for type of distribution transformer
persons to be heard at the hearing, to inspection in the Department’s Freedom manufactured by a single manufacturer
schedule the respective presentations, of Information Reading Room. Any and which have a comparable nominal
and to establish the procedures person may purchase a copy of the output power (kVA) rating, operate
governing the conduct of the hearing. transcript from the transcribing reporter. within the same voltage range, have the
Each participant will be permitted to same insulation type (liquid-immersed
make a prepared general statement, C. Issues Requested for Comment or dry type), and have the same number
limited to five (5) minutes, prior to the The Department of Energy is of phases (single or three).
discussion of specific topics. The interested in receiving comments and/or Converter transformer means a
general statement should not address data concerning the feasibility, transformer designed for the dedicated
these specific topics, but may cover any workability and appropriateness of the applications of converting direct current
other issues pertinent to this test procedures proposed in today’s (dc) to alternating current (ac), or
rulemaking. Other participants will be proposed rulemaking. Also, DOE converting alternating current to direct
permitted to briefly comment on any welcomes discussion on improvements current. Its nameplate contains a rating
general statements. The hearing will or alternatives to these approaches. In for the fundamental-frequency apparent
then be divided into segments, with particular, the Department is interested output power and a rating for the
each segment consisting of one or more in gathering comments on the following: apparent output power with non
63370 Federal Register / Vol. 63, No. 218 / Thursday, November 12, 1998 / Proposed Rules

sinusoidal current produced by the contains a rating for the fundamental- (iii) All standards incorporated by
converter. frequency apparent output power and a reference are available for inspection at the
Distribution transformer means a rating for the apparent output power Office of the Federal Register Information
transformer with a primary voltage of Center, 800 North Capitol Street, N.W.,
with non sinusoidal current produced Washington, DC.
480 V to 35 kV, a secondary voltage of by the converter.
120 V to 600 V, a frequency of 55–65 Total losses mean, for a distribution Option One for Paragraph (a)(3)
Hz, and a capacity of either 10 to 2500 transformer, the total of the no-load and (3) List of standards incorporated by
kVA for liquid-immersed transformers load losses. It does not include losses reference. (i) ANSI/IEEE Standard C57.12.90–
or 0.25 kVA to 2500 kVA for dry-type due to accessories, such as cooling fans. 1993, ‘‘IEEE Standard Test Code for Liquid-
transformers, except for: Transformer means a static Immersed Distribution, Power, and
(1) Converter and rectifier Regulating Transformers and IEEE Guide for
electromagnetic device consisting of a Short-Circuit Testing of Distribution and
transformers with more than two winding, or two or more coupled Power Transformers’’, sections 5 through
windings per phase, and windings, with a magnetic core for 5.3.2, sections 8 through 8.4, and sections 9
(2) Transformers which are not introducing inductive coupling between through 9.4.1.
designed to be continuously connected electric circuits, designed to transfer (ii) ANSI/IEEE Standard C57.12.00–1993,
to a power distribution system as a power by electromagnetic induction IEEE Standard General Requirements for
distribution transformer. This second between circuits at the same frequency. Liquid-Immersed Distribution, Power, and
exception includes regulating Regulating Transformers’’ clause 9.4.
transformers, machine tool transformers, § 432.22 Reference Sources. (iii) ANSI/IEEE Standard C57.12.91–1995,
welding transformers, grounding ‘‘IEEE Standard Test Code for Dry-Type
(a) Materials Incorporated by
Distribution and Power Transformers’’
transformers, testing transformers, and Reference. (1) General. The following clauses 5 through 5.4.2.3, clauses 8 through
other transformers which are not standards which are not otherwise set 8.3, and clauses 9 through 9.4.2.
designed to transfer electrical energy forth in this part 432 are incorporated
from a primary distribution circuit to a by reference. The material listed in Option Two for Paragraph (a)(3)
secondary distribution circuit, or within paragraph (a)(2) of this section has been (3) Standard incorporated by reference.
a secondary distribution circuit, or to a approved for incorporation by reference NEMA Standards Publication TP 2–1998,
consumer’s service circuit. by the Director of the Federal Register ‘‘Standard Test Method for Measuring the
Dry-type distribution transformer Energy Consumption of Distribution
in accordance with 5 U.S.C. 552(a) and Transformers’’ sections 1, 2, 3, 4, 5, and 6.
means a distribution transformer in 1 CFR Part 51. Any subsequent Deviations from these sections are set forth
which the core and coils are immersed amendment to a standard by the at Appendix A to Part 432 section 3.2(ii).
in a gaseous or dry-compound standard-setting organization will not
insulating medium. Option One for Paragraph (b)
affect the DOE test procedures unless
Efficiency means, for a distribution and until amended by DOE. Material is (b) Reference Standard. The following
transformer, the ratio of the useful incorporated as it exists on the date of standard is referred to in the DOE test
output power to the total input power. procedure and elsewhere in 10 CFR part 432
the approval and a notice of any change but is not incorporated by reference and is
Liquid-immersed distribution in the material will be published in the provided here for guidance: ISO Standard
transformer means a distribution Federal Register. 9001–1993, ‘‘Quality Systems—Model for
transformer in which the core and coils (2) Availability of Standards. quality assurance in design, development,
are immersed in an insulating liquid. production, installation, and servicing’’
Load losses mean, for a distribution Option One for Paragraph (a)(2)(i) 5
clause 4.11.1.
transformer, those losses which are (i) Copies of ANSI standards C57.12.90–
1993, C57.12.91–1995, and C57.12.00–1993 Option Two Omits Paragraph (b)
incident to the carrying of a specified
load. Load losses consist of ohmic (I2R) can be obtained from the American National
§ 432.23 Test procedures for measures of
loss in the windings due to load and Standards Institute, 11 West 42nd Street,
energy consumption.
New York, N.Y., 10036;
eddy currents; the loss due to
Option One for Paragraph (a)
circulating currents in parallel windings Option Two for Paragraph (a)(2)(i)
or in parallel winding strands; and stray (a) Total losses, expressed in kilowatts, of
(i) Copies of NEMA Standards Publication
a liquid-immersed distribution transformer
losses due to leakage fluxes in the TP 2–1998 can be obtained from Global
operated at 50% of the rated load shall be
windings, core clamps, and other parts. Engineering Documents World Headquarters,
determined in accordance with clause 3.1.2
Low-voltage dry-type transformer 15 Iverness Way East, Inglewood, CO 80112– of Appendix A to this part. Total losses of a
means a distribution transformer with a 5776; dry-type distribution transformer operated at
primary voltage rated at 1.2 kV and (ii) All standards incorporated by reference either 50% or 35% of the rated load, as
are available for inspection at the U.S.
below. appropriate, shall be determined in
Department of Energy, Office of Energy accordance with clause 3.2.3 of Appendix A
Medium-voltage dry-type transformer
Efficiency and Renewable Energy, Hearings to this part.
means a distribution transformer with a and Dockets, Forrestal Building, 1000
primary voltage rated above 1.2 kV. Independence Ave, SW, Washington, DC Option Two for Paragraph (a)
No-load losses mean, for a 20585. (a) Total losses, expressed in kilowatts, of
distribution transformer, those losses a liquid-immersed distribution transformer
which are incident to the excitation of 5 In the preamble to this proposed rule, the operated at 50% of the rated load shall be
the transformer. No-load losses consist Department states its intention to adopt as the test determined in accordance with clause 3.3 of
of core loss, dielectric loss, conductor procedure for distribution transformers either Appendix A to this part. Total losses of a dry-
loss in the windings due to exciting portions of standards prepared by IEEE and type distribution transformer operated at
approved by ANSI, or portions of a standard being either 50% or 35% of the rated load, as
current, and conductor loss due to the developed by NEMA. In the proposed rule
circulating currents in parallel appropriate, shall be determined in
lll
language, passages introduced by the phrase
accordance with clause 3.4 of Appendix A to
windings. ‘‘OPTION ONE FOR PARAGRAPH ’’
constitute the language DOE proposes to use if it this part.
Rectifier transformer means a
lll
decides to adopt the ANSI/IEEE standards, and the Option One for Paragraph (b)
transformer designed for the dedicated phrase ‘‘OPTION TWO FOR PARAGRAPH ’’
application of converting alternating introduces the regulatory language proposes in the (b) Efficiency, expressed in percent, of a
current to direct current. Its nameplate event the NEMA standard is adopted. liquid-immersed distribution transformer
Federal Register / Vol. 63, No. 218 / Thursday, November 12, 1998 / Proposed Rules 63371

operated at 50% of the rated load shall be 1.7 Reference temperature means the of liquid-immersed distribution transformers.
determined in accordance with clause 3.1.2 temperature, specified in a standard, to Perform waveform correction on the
of Appendix A to this part. Efficiency of a which the transformer losses shall be measured no-load losses and perform phase
dry-type distribution transformer, expressed corrected and reported. angle correction for the load losses.
in percent, operated at either 50% or 35% of 1.8 Temperature correction means the 3.1.1 Perform temperature corrections for
the rated load shall be determined in adjustment (correction) of measurements of the loss data of § 3.1 by converting the no-
accordance with clause 3.2.3 of Appendix A no load losses and load losses, obtained with load losses to 20°C and converting the load
to this part. the distribution transformer under test at a losses to 55°C with the loading at 50% of the
temperature that is different from the rated load. To perform these temperature
Option Two for Paragraph (b) corrections, the provisions in sections 8.4
reference temperature, to values that would
(b) Efficiency, expressed in percent, of a have been obtained with the distribution and 9.4.2 of ANSI/IEEE standard C57.12.90–
liquid-immersed distribution transformer transformer at the reference temperature. 1993 are applicable. For the conversion to the
operated at 50% of the rated load shall be 1.9 Test voltage means the voltage of the 50% loading the quadratic relationship
determined in accordance with clause 3.5 of electric power supplied to the distribution P(L50)=P(LM) (50/M)2 applies, where P(L50) is
Appendix A to this part. Efficiency of a dry- transformer under test. the load loss power at 50% loading, P(LM) is
type distribution transformer, expressed in 1.10 Waveform correction means the the load loss power at M% loading, and (50/
percent, operated at either 50% or 35% of the adjustment (correction) of measurement data M) is the ratio of the loading at the 50%
rated load shall be determined in accordance obtained with a test voltage that is non- reference condition to the loading during the
with clause 3.5 of Appendix A to this part. sinusoidal (distorted) to values that would measurement (near 100% loading).
(c) The estimated annual energy have been obtained with sinusoidal voltage. 3.1.2 Calculate the total losses (P50) at 50
consumption (EAEC), expressed in kilowatt- % loading by adding the no-load losses and
hours per year, for a distribution transformer Option One for Paragraph 2 the load losses as computed in § 3.1.1, and
operating continuously at 50% or 35% of the 2. References. calculate the efficiency at 50 % loading
rated output power, as appropriate, shall be 2.1 ANSI/IEEE Standard C57.12.90–1993, according to the equation:
the product of: ‘‘IEEE Standard Test Code for Liquid- E50=100 [P0(50)/(P0(50)+PL(20))],
(1) The total losses in kilowatts as Immersed Distribution, Power, and where E50 is the efficiency at 50% loading,
determined in paragraph (a) of this section; Regulating Transformers and IEEE Guide for and P0(50) and PL(50) are the output power and
and Short-Circuit Testing of Distribution and total loss power, respectively, at 50%
(2) The representative use cycle of 8766 Power Transformers’’ (ANSI/IEEE C57.12.90). loading.
hours per year. 2.2 ANSI/IEEE Standard C57.12.00–1993, 3.2 Dry-Type Transformers.
IEEE Standard General Requirements for Using the methods specified in ANSI/IEEE
§ 432.24 Units to be tested.
Liquid-Immersed Distribution, Power, and standard C57.12.91–1995, sections 5, 8, and
For each basic model of distribution Regulating Transformers’’ (ANSI/IEEE 9, measure the resistance of transformer
transformers, a random sample of C57.12.00). windings, the no-load losses and load losses
sufficient size, but no fewer than five 2.3 ANSI/IEEE Standard C57.12.91–1995, of dry-type distribution transformers.
production units, shall be tested to ‘‘IEEE Standard Test Code for Dry-Type Perform waveform correction on the
insure that any represented value of Distribution and Power Transformers’’ measured no-load losses and perform phase
efficiency shall be no greater than the (ANSI/IEEE C57.12.91). angle correction for the load losses.
2.4 ISO Standard 9001–1993, ‘‘Quality 3.2.1 In addition to the requirements of
lower of the: ANSI/IEEE standard C57.12.91–1995, the
Systems—Model for quality assurance in
(a) Mean of the sample; or design, development, production, following two additional requirements apply
(b) The lower 95% confidence limit of installation, and servicing.’’ to the measurements in section 3.2 of this
the estimated true mean divided by a appendix:
number equal to [1¥0.03(1¥Es/100)], Option Two for Paragraph 2 (i) Perform phase angle correction for the
where Es is the represented value of 2. References. measured load losses as specified in ANSI/
efficiency claimed for that particular NEMA Standards Publication TP 2–1998, IEEE standard C57.12.90–1993, clause 9.4.1
basic model. ‘‘Standard Test Method for Measuring the and Table 1;
Energy Consumption of Distribution (ii) Measure the no-load losses with the
Appendix A to Part 432—Uniform Test Transformers’’ (NEMA TP 2). transformer at the reference temperature of
Method for Measuring the Energy 20°C; a temperature tolerance of ±10°C is
Consumption of Distribution Transformers Option One for Paragraph 3 permissible; if no-load loss measurements are
1. Definitions. Use the definitions in 10 3. Test Procedures’ Measurements and conducted outside this temperature
CFR 432.21 and the following: Instrumentation, Reference Conditions, tolerance, perform the appropriate
1.1 ANSI Standard means a standard Calculations. temperature correction such as that specified
approved by a committee accredited by the The resistance of transformer windings, the in ANSI/IEEE standard C57.12.90–1993,
American National Standards Institute. no-load losses, and the load losses of clause 8.4.
1.2 IEEE Standard means a standard transformers shall be measured, and the total 3.2.2 Perform temperature corrections for
developed and approved by the Institute of losses and efficiency shall be computed at the loss data by converting the load losses of
Electrical and Electronics Engineers. All IEEE the specified loading levels and reference medium-voltage dry-type transformers to
standards referenced in Appendix A have temperatures, using the methods described in 75°C, at 50% of the rated load, and
been approved or recognized by ANSI. the following industry standards (with converting the load losses of low-voltage dry-
1.3 ISO Standard means a standard certain specified modifications and type transformers to 75°C, at 35% of the rated
developed and approved by the International exceptions): ANSI/IEEE standards C57.12.90– load. To perform these temperature
Standards Organization. 1993 and C57.12.91–1995 (primary corrections, the provisions of ANSI/IEEE
1.4 NEMA Standards Publication means a references); ANSI/IEEE standard C57.12.00– standard C57.12.91-1995, clause 9.4.1 shall
standard developed and approved by 1993 (supplemental reference). The methods apply. For the conversions to the 50% and
National Electrical Manufacturers to be used, including applicable sections and 35% loading levels the algorithm of § 3.1.1
Association. clauses in the referenced standards, as well applies.
1.5 Phase angle error means an error as exceptions and modifications to such 3.2.3 Calculate the total losses, PL(50)(35),
introduced in the phase angle displacement sections and clauses, are listed in this at either 50% or 35% loading, as appropriate,
between voltage and current phasors by the appendix: §§ 3.1–3.3 and their subclauses. by adding the no-load losses and load losses
test equipment. Phase angle error, if 3.1 Liquid-Immersed Distribution as computed in § 3.2.2, and calculate the
significant, can introduce errors in measured Transformers. efficiency of the transformer at either 50% or
transformer losses. Using the methods specified in ANSI/IEEE 35% loadings according to the equation:
1.6 Phase angle correction means the standard C57.12.90–1993 sections 5, 8, and 9, E(50)(30)=100 [P0(50)(30)/(P0(50)(30)+PL(50)(30))],
adjustment (correction) of measurement data measure the resistance of transformer where E(50)(30) is the efficiency in percent,
to negate the effects of phase angle error. windings, the no-load losses and load losses P0(50)(30) is the output power in kilowatts, and
63372 Federal Register / Vol. 63, No. 218 / Thursday, November 12, 1998 / Proposed Rules

PL(50)(30) is the loss power in kilowatts. The Option Two for Paragraph 3 (i) Section 7 of TP 2, Demonstration of
subscripts, (50) or (35), denote the loading 3. Test Procedures—Measurements and Compliance, shall not be a part of the DOE
levels, either 50% or 35%. Instrumentation, Reference Conditions, test procedure.
3.3 Quality Assurance in Testing. Calculations. (ii) The reference conditions for reporting
Accuracies required for measuring the The resistance of transformer windings, the the data under the DOE test procedure shall
winding resistances, the no-load and load no-load losses, and the load losses of be: 20 °C ± 10 °C for no-load losses of liquid-
losses, and the temperature of distribution transformers shall be measured, and the total immersed distribution transformers and dry-
transformers shall be those specified in ANSI losses and efficiency shall be computed at type distribution transformers; 55 °C for load
the specified loading levels and reference losses of liquid-immersed distribution
Standard C57.12.00–1993, Section 9.4.
temperatures, using the methods described in transformers operated at 50% of the rated
Test equipment and measuring instruments
the following industry standards (with load; 75 °C for load losses of medium-voltage
shall be calibrated and maintained in their dry-type transformers operated at 50% of the
certain specified modifications and
normal operating condition. Calibration exceptions): NEMA standard TP 2. The rated load; and 75 °C for load losses of low-
records shall be maintained to demonstrate methods to be used, including applicable voltage dry-type transformers operated at
compliance with the required measurement sections and clauses in the referenced 35% of the rated load.
accuracies. General guidance as to standards, as well as exceptions and (iii) The exceptions listed in item 4 of the
procedures that will aid in meeting these modifications to such sections and clauses, Scope of TP 2 do not apply to the DOE test
objectives is provided by the following are listed in this appendix: sections 3.1–3.5 procedure.
Clause 4.11.1 of ISO Standard 9001–1993, and their subclauses. 3.3 The total losses of liquid-immersed
‘‘Quality Systems—Model for quality 3.1 Liquid-Immersed and Dry-Type distribution transformers, at the specified
assurance in design, development, Distribution Transformers. reference conditions, shall be computed
production, installation, and servicing.’’: In accordance with NEMA TP 2, sections according to clause 5.2.3 of TP 2.
‘‘The supplier shall establish and maintain 1, 2, 3, 4, 5, and 6, do the following: measure 3.4 The total losses of the dry-type
documented procedures to control, calibrate the resistance of transformer windings, the distribution transformers, at the specified
no-load losses, and the load losses of liquid- reference conditions, shall be computed data
and maintain inspection, measuring and test
immersed and dry-type transformers; apply according to clause 5.3.3 of TP 2.
equipment (including test software) used by
waveform corrections, phase angle 3.5 Compute the efficiency values of
the supplier to demonstrate the conformance corrections, and temperature corrections to liquid-immersed distribution transformers
of product to the specified requirements. the measured data for no-load losses and load and dry-type distribution transformers at the
Inspection, measuring and test equipment losses; and ensure the quality assurance specified reference conditions using the
shall be used in a manner which ensures that measures for testing operations. algorithm provided in clause 5.4 of TP 2.
measurement uncertainty is known and is 3.2 Deviations from NEMA TP 2. For the
consistent with the required measurement purpose of this DOE test procedure the [FR Doc. 98–30140 Filed 11–10–98; 8:45 am]
capability.’’ following deviations from TP 2 shall apply: BILLING CODE 6450–01–P

S-ar putea să vă placă și