SAUDI ARAMCO ID/PID - 18-May-05 - REV 0 (Standards Cutoff - August 2004)

SAIC NUMBER DATE APPROVED QR NUMBER


SAUDI ARAMCO INSPECTION CHECKLIST
Prefab Buildings - Foundations and Pre-Installation
SAIC-M-1032 18-May-05 CIVIL-
Inspection
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

The foundation shall be verified against the IFC Drawings and the Shop
A1 Fabrication Drawings for the locations, size and orientations of the IFC Drawings
anchor bolts.

Foundation top of concrete shall be a minimum of 150mm above finished SAES-Q-005


A2
grade. Sec. 4.3.2.a

Concrete compressive strength shall be a minimum of 27.6 MPa


SAES-Q-005
A3 (4000psi) at 28 days; Concrete shall be cured before release for
Sec. 4.3.2.b
structure installation.

The minimum thickness of grout between the foundation and base plates SAES-Q-005
A4
shall be 25mm; Steel Shim and Packings to be provided. Sec. 4.3.2.c

Foundations constructed near slopes shall be built so that a line at 45 0


SAES-Q-005
A5 from the bottom of the footings nearest the slope shall not project out of
Sec. 4.3.2.e
the ground at any point along the slope.

Foundations shall be located in such a manner as to avoid existing SAES-Q-005


A6
underground items or those items shall be relocated. Sec. 4.3.2.f

All building materials shall be new and free of defects; Structural steel
12-SAMSS-014
A7 shapes, pipes, plates, sheets, wire strands, crane rails, cold formed
Sec. 6
sheets, sandwich panels and shapes shall conform to the IFC Drawings.

The anchor bolt layouts, base plate and bolt sizes, locations, elevations,
12-SAMSS-014
A8 unfactored column reactions and required foundation recesses shall
Sec. 9 & 11.1.4
match with IFC Drawings.

The minimum anchor bolt size shall be 20mm, come with double nuts 12-SAMSS-014
A9
and have adequate projection for two nuts and any required washers. Sec. 11.1.4

All primary bolted connections, as shown on drawings, shall be furnished


with high-strength bolts conforming to ASTM A325 or ASTM A325M,
12-SAMSS-014
A10 Type-1, galvanized. All high-strength bolts are to be tightened by the
Sec. 6.2.1
procedures outlined in AISC – "Specification for Structural Joints Using
ASTM A325 or ASTM A490 Bolts".

All high-strength bolts shall be furnished with nuts and washers. Nuts for
high-strength bolts shall conform to either ASTM A194/A194M or ASTM 12-SAMSS-014
A11
A563 or ASTM A563M. Washers shall conform to ASTM F436 or ASTM Sec. 6.2.2
F436M.

When high-strength bolts are required in sizes less than ½" diameter, the 12-SAMSS-014
A12
bolts shall conform to ASTM A449, Type 1, galvanized. Sec. 6.2.3

12-SAMSS-014
A13 All primary bolted connections shall contain at least two bolts.
Sec. 6.2.4

Page 1 of 3
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - August 2004)
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Prefab Buildings - Foundations and Pre-Installation
SAIC-M-1032 18-May-05 Civil
Inspection
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

All machine bolts shall conform to ASTM A307 and shall be galvanized
to either ASTM A153 or ASTM B695. ASTM A307 bolts are only allowed
for the attachment of secondary members such as girts and purlins, and
12-SAMSS-014
A14 items such as stair treads, handrail, ladders, etc. When ASTM A307
Sec. 6.2.5
bolts are used, the sizes used should not be the same diameter as any
A325 or A449 bolts used for the same Purchase Order. ASTM A307
bolts are to be limited to sizes 5/8" diameter and smaller.

ASTM A307 bolts shall be furnished with nuts that conform to ASTM
12-SAMSS-014
A15 A563 and washers conforming to ASTM F436, ASTM F436M or ASTM
Sec. 6.2.6
F844.

Eyebolts used to attach cable bracing shall be forged steel, load rated
12-SAMSS-014
A16 eyebolts and shall be galvanized to ASTM A153. The ultimate load for
Sec. 6.2.7
the eyebolt shall be 5 times the safe working load limit.

Unless indicated in the Purchase Order, the vendor shall provide either
single sheet or sandwich type roof and wall panels based on the required
12-SAMSS-014
A17 maximum heat transmission coefficient and required internal design
Sec. 6.5
temperature. The choice of panels is subject to prior written approval
from Saudi Aramco as shown on the IFC Drawings.

The use of fiberglass insulation shall meet the following conditions:


flexible; resilient; odorless; shall not contribute to corrosion of steel or
aluminum; flame spread rating of 25 or less; facing shall cover the width
12-SAMSS-014
A18 of the fiberglass blanket plus two flanges each 50 mm wide; vapor barrier
Sec. 6.5.1.h
to be aluminum foil or equal placed on the outside. Interior exposed
insulation shall receive a quilted covering (preferably a fiberglass scrim)
on the interior surface to protect the insulation.

Roof and Wall panels shall be attached to secondary framing members


by means of self-drilling or self-tapping screws. The screws shall be hex
head carbon steel screws assembled with an EPDM washer and
12-SAMSS-014
A19 mechanically zinc coating in accordance with ASTM B695, Class 50.
Sec. 6.6
However, in coastal areas, as defined in paragraph 4.3.3(b), an
austenitic (300 series) stainless steel fasteners shall be used. Fastener
heads shall be coated the same color as the panels.

Roof panels shall be made of a minimum 0.5 mm (26 gage) thick


galvanized or aluminum-zinc alloy-coated steel sheet. Roof panels for 12-SAMSS-014
A20
buildings in coastal areas, or as specified in the purchase order shall be Sec. 6.5.1.a
made of a minimum 0.8 mm thickness aluminum sheet.

Wall panels shall have nominal covering width not less than 900 mm (3 ft
nominal) unless approved otherwise by Saudi Aramco; The panel shall
12-SAMSS-014
A21 be made of a minimum 0.5 mm (26 gage) thick galvanized or aluminum-
Sec. 6.5.3.a & b
zinc alloy-coated steel sheet, or aluminum as applicable, formed
architecturally consistent with the ribbing of the roof.

REMARKS:

REFERENCE DOCUMENTS:
1- SAES-Q-005 -- Concrete Foundations, 29 January 2003
2- 12-SAMSS-014 -- Pre-Engineered Metal Buildings, 30 June 2002

Contractor / Third-Party Saudi Aramco

Page 2 of 3
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - August 2004)
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Prefab Buildings - Foundations and Pre-Installation
SAIC-M-1032 18-May-05 Civil
Inspection
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Inspector PID Representative


Performed Inspection Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Supervisor Proponent and Others


Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified
Name, Organization,
Name, Sign and Date:
Initials and Date:
*Person Responsible for Completion of Quality Work / Test Y = YES N = NO F = FAILED

Page 3 of 3