Services Technical data for auxiliary

Practical advice
contacts and releases
For i DPN (DPN), C60, C120, ID, I-NA

MN, MNs, MX + OF, MX, MNx releases


Releases MN MNs
Cat. no. 26960 26961 26959 26963
Nominal line voltage (V) (+10, -20 %) 220 to 240 48 48 115 220 to 240
alternating current (AC) b b - b b
direct current (DC) - - b - -
Operating frequency 50/60 Hz b b - - b
400 Hz - - - b -
Min. cut-in voltage (V) 187 40.8 40.8 98 187
Min. tripping voltage (V) between 0.35 and 0.70 Un between 0.35 and 0.70 Un
Holding current (A) 0.014 0.034 0.022 0.017 0.015
Power consumption (VA) 3.3 1.6 1.1 2 3.4
Min. voltage dip time (ms) 30 8 8 30 > 300

Releases MX + OF
Cat. no. 26946 26947 26948
Nominal line voltage (V) (+10, -20 %) 100 230 415 100 130 48 48 12 12 24 24
alternating current (AC) b b b - - b - b - b -
direct current (DC) - - - b b - b - b - b
Operating frequency 50/60 Hz b b b - - b - b - b -
Min. cut-out voltage (V) 77 77 77 77 77 33.6 33.6 8.4 8.4 8.4 8.4
Inrush current (A) 0.4 0.8 1.5 0.3 0.3 1 0.7 4 2.5 7.7 5.6
Inrush power (VA) 44 184 625 38 45 48 33.6 48 30 185 135
Min. control impulse duration (ms) 8 8 8
Power circuit breaking time (ms) 18 18 18
OF contact rated operational current Ie (A) see the auxiliary contact table on the next page

Releases MX
Cat. no. 26476 26477 26478
Nominal line voltage (V) (+10, -20 %) 100 230 415 100 130 48 48 12 12 24 24
alternating current (AC) b b b - - b - b - b -
direct current (DC) - - - b b - b - b - b
Operating frequency 50/60 Hz b b b - - b - b - b -
Min. cut-out voltage (V) 77 77 77 77 77 33.6 33.6 8.4 8.4 8.4 8.4
Inrush current (A) 0.4 0.8 1.5 0.3 0.3 1 0.7 4 2.5 7.7 5.6
Inrush power (VA) 44 184 625 38 45 48 33.6 48 30 185 135
Min. control impulse duration (ms) 8 8 8
Power circuit breaking time (ms) 18 18 18

Releases MNx MNx C60 MNx MNx C60


Cat. no. 26969 26977 26971 26991
Nominal line voltage (V) (+10, -20 %) 230 230 400 400
alternating current (AC) b b b b
direct current (DC) - - - -
Operating frequency 50/60 Hz b b b b
Min. tripping voltage (V) 100 100 280 280
Holding current (A) 0.014 0.014 0.014 0.014
Power consumption (VA) 3.3 3.3 5.6 5.6
Breaking time (ms) 20 20 20 20
Min. control circuit opening time (ms) 30 30 30 30

 version: 7.1 92605E.indd


Services Technical data for auxiliary
Practical advice
contacts and releases
For i DPN (DPN), C60, C120, ID, I-NA

MSU releases
Releases M&SU
Cat. no. 26479 26979
Nominal line voltage (V) (+10, -20 %) 230 230
alternating current (AC) b b
direct current (DC) - -
Operating frequency 50/60 Hz b b
Operating threshold (V) 255 (-0, +5 %) 275 (-0, +5 %)
Holding current (A) 0,002 0,002
Inrush power (VA) 128 128
Power consumption (VA) 0,046 0,046
Breaking time (ms) according to the curve

OF, SD, OF + SD/OF, OF.S, OFsp auxiliary contacts


b Conform to EN 62019 for C60, C120 and i DPN (DPN).
b Degree of protection: IP20.
b Rating of auxiliary contact short-circuit protection device:
v circuit breaker: C60 / i DPN - 2P - C curve - 6 A - limitation class 3
v fuse: 6 A, 500 V, type Gg, 10.3 x 38 mm.

Contact rated operational current le (A) to CEI 60947-5 :


Contacts auxiliary OF, SD, OFsp
OF + SD/OF, OF.S
Cat.no. 26924/26927/26929/26923 16940
Rated operational cat. AC12 380...415 V AC 3 -
Voltage Ue (V) 220...240 V AC 6 -
cat. AC15 220...240 V AC - 6
cat. DC12 24 V DC 6 -
48 V DC 2 -
60 V DC 1,5 -
130 V DC 1 -
cat. DC13 230 V DC - 1

Common technical data of auxiliary contacts and


releases
Common technical data
Operating temperature when live (°C) -25 °C à +50 °C
Storage temperature -40 °C à +85 °C